DD6900 Fru Cru Replacement
DD6900 Fru Cru Replacement
August 2021
Rev. 07
Contents
Figures.......................................................................................................................................... 7
Tables..........................................................................................................................................10
2 Contents
Shut down and disconnect the system........................................................................................................................36
Extend the system from the cabinet............................................................................................................................36
Remove the system cover...............................................................................................................................................37
Removing the air shroud..................................................................................................................................................38
Remove expansion card riser 2...................................................................................................................................... 38
Remove the network daughter card.............................................................................................................................39
Install the network daughter card................................................................................................................................. 39
Install expansion card riser 2.......................................................................................................................................... 40
Installing the air shroud.....................................................................................................................................................41
Install the system cover....................................................................................................................................................41
Slide the system into the cabinet..................................................................................................................................42
Reconnect and power on the system...........................................................................................................................42
Verify the replacement network daughter card.........................................................................................................43
Restore the HA configuration........................................................................................................................................ 44
Contents 3
Remove the system cover............................................................................................................................................... 71
Remove the NVRAM module.......................................................................................................................................... 72
Install the NVRAM module.............................................................................................................................................. 73
Install the system cover................................................................................................................................................... 73
Slide the system into the cabinet.................................................................................................................................. 74
Reconnect and power on the system...........................................................................................................................75
Verify the new NVRAM module..................................................................................................................................... 75
Restore the HA configuration.........................................................................................................................................76
4 Contents
Install a processor and heat sink module................................................................................................................... 100
Installing the air shroud...................................................................................................................................................101
Install the system cover................................................................................................................................................. 102
Slide the system into the cabinet................................................................................................................................ 102
Reconnect and power on the system.........................................................................................................................103
Verify the replacement CPU......................................................................................................................................... 103
Restore the HA configuration.......................................................................................................................................104
Contents 5
Shut down and disconnect the system...................................................................................................................... 133
Extend the system from the cabinet.......................................................................................................................... 134
Identifying the rail kit components.............................................................................................................................. 134
Remove the system from the cabinet........................................................................................................................ 136
Removing the rails........................................................................................................................................................... 137
Remove the original CMA brackets.............................................................................................................................138
Attach the new CMA brackets.....................................................................................................................................138
Install the rails...................................................................................................................................................................140
Secure the rail assemblies to the cabinet...................................................................................................................141
Install the system in the cabinet.................................................................................................................................. 142
Install the front bezel......................................................................................................................................................144
Install the CMA arms.......................................................................................................................................................144
Slide the system into the cabinet................................................................................................................................ 148
Reconnect and power on the system......................................................................................................................... 148
Restore the HA configuration.......................................................................................................................................149
6 Contents
Figures
1 Maintenance connections.......................................................................................................................................14
2 Drive fault LED.......................................................................................................................................................... 18
3 Removing the front bezel....................................................................................................................................... 19
4 Removing a hard drive............................................................................................................................................ 19
5 Installing a hard drive.............................................................................................................................................. 20
6 Installing the front bezel......................................................................................................................................... 21
7 Drive fault LED.......................................................................................................................................................... 21
8 Remove the system cover.....................................................................................................................................26
9 Removing cooling fan............................................................................................................................................. 26
10 Installing cooling fan................................................................................................................................................ 27
11 Remove the system cover..................................................................................................................................... 37
12 Removing the air shroud........................................................................................................................................ 38
13 Removing expansion card riser 2......................................................................................................................... 39
14 Removing the network daughter card................................................................................................................39
15 Installing the network daughter card.................................................................................................................. 40
16 Installing expansion card riser 2........................................................................................................................... 40
17 Installing the air shroud........................................................................................................................................... 41
18 NIC LEDs....................................................................................................................................................................43
19 Remove the system cover.....................................................................................................................................49
20 Removing the air shroud........................................................................................................................................50
21 Removing a memory module..................................................................................................................................51
22 Installing a memory module................................................................................................................................... 52
23 Installing the air shroud.......................................................................................................................................... 52
24 Slot numbering......................................................................................................................................................... 57
25 Remove the system cover.....................................................................................................................................60
26 Removing the expansion card from expansion card riser 1............................................................................ 61
27 Removing the expansion card from expansion card riser 2........................................................................... 61
28 Removing the expansion card from expansion card riser 3...........................................................................62
29 Installing expansion card into expansion card riser 1.......................................................................................63
30 Installing expansion card into expansion card riser 2...................................................................................... 63
31 Installing expansion card into expansion card riser 3...................................................................................... 64
32 Remove the system cover......................................................................................................................................71
33 Removing the NVRAM module from expansion card riser 1..........................................................................72
34 NVRAM module........................................................................................................................................................ 72
35 Installing the NVRAM module in expansion card riser 1..................................................................................73
36 Remove the system cover..................................................................................................................................... 79
37 TPM location............................................................................................................................................................. 79
38 Installing the TPM....................................................................................................................................................80
39 Remove the system cover.....................................................................................................................................86
40 Removing expansion card riser 1.......................................................................................................................... 87
Figures 7
41 Removing the integrated storage controller cable.......................................................................................... 88
42 Installing the integrated storage controller card..............................................................................................89
43 Installing the integrated storage controller card cable...................................................................................89
44 Installing expansion card riser 1............................................................................................................................ 90
45 Remove the system cover.....................................................................................................................................96
46 Removing the air shroud........................................................................................................................................ 96
47 Installing the air shroud......................................................................................................................................... 101
48 Remove the system cover................................................................................................................................... 108
49 Removing the air shroud...................................................................................................................................... 109
50 Removing the cooling fan..................................................................................................................................... 110
51 Removing expansion card riser 1..........................................................................................................................111
52 Removing expansion card riser 2........................................................................................................................ 112
53 Removing expansion card riser 3........................................................................................................................ 112
54 Removing the integrated storage controller cable......................................................................................... 113
55 Removing the integrated storage controller card........................................................................................... 113
56 Removing a memory module................................................................................................................................ 114
57 Removing the system board................................................................................................................................ 115
58 Installing system board.......................................................................................................................................... 116
59 Installing a memory module.................................................................................................................................. 118
60 Installing the integrated storage controller card............................................................................................. 118
61 Installing the integrated storage controller card cable.................................................................................. 119
62 Installing expansion card riser 1........................................................................................................................... 119
63 Installing expansion card riser 2..........................................................................................................................120
64 Installing expansion card riser 3.......................................................................................................................... 121
65 Installing the cooling fan assembly.....................................................................................................................122
66 Installing the air shroud.........................................................................................................................................123
67 Removing the front bezel..................................................................................................................................... 131
68 Installing the front bezel.......................................................................................................................................132
69 Sliding rail assembly - 2U systems..................................................................................................................... 135
70 CMA brackets......................................................................................................................................................... 135
71 CMA arms and separators................................................................................................................................... 136
72 Release and extend system from cabinet........................................................................................................ 136
73 Removing system from rails.................................................................................................................................137
74 Remove the original CMA bracket..................................................................................................................... 138
75 Attach outer CMA bracket to the rails............................................................................................................. 139
76 Attach inner CMA bracket to the rails.............................................................................................................. 140
77 Installing the rear end of the rail......................................................................................................................... 141
78 Installing the front end of the rail....................................................................................................................... 141
79 Installing screws..................................................................................................................................................... 142
80 Pull the inner rails out of the cabinet................................................................................................................ 142
81 Install the system in the rails............................................................................................................................... 143
82 Slide the system into the cabinet.......................................................................................................................143
83 Installing the front bezel.......................................................................................................................................144
8 Figures
84 Install the first separator...................................................................................................................................... 145
85 Install the first arm.................................................................................................................................................145
86 Close the first arm................................................................................................................................................. 146
87 Install the second separator................................................................................................................................ 146
88 Install the second arm........................................................................................................................................... 147
89 Close the second arm............................................................................................................................................147
Figures 9
Tables
1 Communications settings....................................................................................................................................... 14
2 NIC LED states......................................................................................................................................................... 44
3 Memory mapping..................................................................................................................................................... 46
4 Slot assignments......................................................................................................................................................58
10 Tables
Notes, cautions, and warnings
NOTE: A NOTE indicates important information that helps you make better use of your product.
CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid
the problem.
WARNING: A WARNING indicates a potential for property damage, personal injury, or death.
© 2020 - 2020 Dell Inc. or its subsidiaries. All rights reserved. Dell, EMC, and other trademarks are trademarks of Dell Inc. or its subsidiaries.
Other trademarks may be trademarks of their respective owners.
1
FRU and Upgrade Overview
The tool, safety, and connection information in this chapter applies to all component replacement procedures for the
PowerProtect system. Verify that the required tools are available, review the safety information, and connect to the system
before proceeding.
This chapter contains the following information:
Topics:
• Tools and supplies needed
• Safety overview
• Establish a serial management connection to the PowerProtect system
• Component characteristics
• Prepare HA systems for component replacement
CAUTION: PowerProtect systems are heavy. Use at least two people or a mechanical lift to move any system.
● To comply with applicable safety, emission, and thermal requirements, covers must not be removed and all bays must be
fitted with plug-in modules.
● For ESD protection, Dell EMC recommends that you wear a suitable antistatic wrist or ankle strap. Observe all conventional
ESD precautions when handling plug-in modules and components.
Safety instructions
WARNING: Whenever you need to lift the system, get others to assist you. To avoid injury, do not attempt to lift
the system by yourself.
WARNING: Opening or removing the system cover while the system is powered on may expose you to a risk of
electric shock.
CAUTION: Do not operate the system without the cover for a duration exceeding five minutes. Operating the
system without the system cover can result in component damage.
CAUTION: Many repairs may only be done by a certified service technician. You should only perform
troubleshooting and simple repairs as authorized in your product documentation, or as directed by the online or
telephone service and support team. Damage due to servicing that is not authorized by Dell is not covered by
your warranty. Read and follow the safety instructions that are shipped with your product.Always use a static
mat and anti-static wristband while working on components inside the system.
NOTE: It is recommended that you always use an anti-static mat and an anti-static wristband while working on components
inside the system.
CAUTION: To ensure proper operation and cooling, all bays in the system and system fans must be always
populated with a component or a blank.
1. Ethernet port
2. Serial port (COM 1)
Steps
Verify with the customer whether the system uses a serial connection or SOL, and follow one of the procedures below as
required.
Steps
1. Open an SSH shell.
2. Run the following command to connect to iDRAC.
ssh <iDRAC-IP-address> -l <iDRAC-username>.
3. Log in with the credentials for the iDRAC username.
4. Run one of the following commands to initiate the SOL session.
● console com2
● connect
Component characteristics
The following table lists the replaceable components, whether the component is hot-swappable, and whether the procedure can
be completed by a customer (CRU) or a Dell EMC or partner technician (FRU):
DIMM N CRU
Network daughter card N CRU
PCIe HBA/PCIe HBA mini-card N CRU
NVRAM N FRU
HBA330 N CRU
TPM N FRU
System board N FRU
CPU/heatsink N FRU
Rail kit N CRU
Prerequisites
CAUTION: Do not initiate a failover as described in Step 3 without approval to do so, as the failover process can
disrupt in-progress backup jobs on some protocol types.
Steps
1. Enter the management IP address of the node containing the failed component into a web browser, and login as sysadmin.
2. Verify the node role and number in the upper right corner of the screen.
NOTE: This is an estimate, and the rebuild may take significantly longer depending on the amount of activity on the system.
Topics:
• Identify a failed OS disk
• Remove the front bezel to access front panel hard drives
• Remove a hard drive
• Install the hard drive
• Install the front bezel
• Verify the replacement drive
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is illuminated solid amber.
2. Run the alerts show current command to identify the location of the failed disk. Record the slot number of the failed
disk.
CAUTION: The physical labeling of the disks on the system chassis, and the disk numbering in do not match.
The physical labeling starts with Disk 0, and starts with Disk 1.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
3. Match the slot number of the failed disk from the alerts show current output to the physical location of the disk.
4. Run the disk beacon command on the failed disk to illuminate the LED.
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Prerequisites
Follow the safety guidelines listed in Safety instructions on page 13.
Steps
1. Press the release button to open the hard drive release handle.
2. Holding the handle, slide the hard drive out of the hard drive slot.
3. If you are not replacing the hard drive immediately, insert a hard drive blank in the empty hard drive slot to maintain proper
system cooling.
Prerequisites
Follow the safety guidelines listed in Safety instructions on page 13.
Steps
1. Press the release button on the front of the hard drive to open the release handle.
2. Insert the hard drive into the hard drive slot and slide until the hard drive connects with the backplane.
3. Close the hard drive release handle to lock the hard drive in place.
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is off.
5. Run the disk show state command to verify the disk rebuild status.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Use the alerts show current (or alerts show current-detailed) command that will include messages
indicating fan loss or fan failure.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
24 Replace a Fan
The following table shows the physical layout of the fans as seen from the front of the system.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Replace a Fan 25
Figure 8. Remove the system cover
Steps
Press the release tab and lift the cooling fan out of the cooling fan assembly.
Steps
Holding the release tab, align the connector at the base of the cooling fan with the connector on the system board.
26 Replace a Fan
Figure 10. Installing cooling fan
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Replace a Fan 27
Slide the system into the cabinet
Steps
1. At the front of the cabinet, push the system inward until the lock levers click into place.
2. Push the blue slide release lock tabs forward on both rails and slide the system into the cabinet. The slam latches will engage
to secure the system in the cabinet.
28 Replace a Fan
Verify the replacement fan
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Use the enclosure show fans command to check the status of each fan. Record the failed fan.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
Replace a Fan 29
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
30 Replace a Fan
5
Replace a Power Supply
The system contains two power supplies in the rear of the chassis.
Complete the following procedure to replace a failed power supply.
This CRU can be performed with the system powered on.
Topics:
• Identify a failed power supply
• Remove a power supply
• Install the power supply unit
• Verify the replacement power supply
• Restore the HA configuration
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Check the LED on the affected power supply unit. The power supply handle functions as the LED.
NOTE: If a power supply unit is found to be faulted, the LED blinks amber.
2. Enter the alerts show current command (or alerts show current-detailed) to display messages indicating
power supply failure. A sample output is shown.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
4. Map the number of the failed PSU to the physical location of that power supply.
As seen from the back of the system, both power supplies are on the right--hand side of the system. Power supply 1 is the
left-hand PSU, and power supply 2 is the right-hand PSU.
Steps
1. Disconnect the power cable from the power source and from the PSU you intend to remove, and then remove the cable
from the strap on the PSU handle.
2. Press the release latch and slide the PSU out of the system by using the PSU handle.
Steps
1. Verify that nothing has dropped into the empty PSU slot before installing the replacement PSU.
2. Slide the PSU into the system until the PSU is fully seated and the release latch snaps into place.
3. Connect the power cable to the PSU, and plug the cable into a power outlet.
CAUTION: When connecting the power cable to the PSU, secure the cable to the PSU with the strap.
NOTE: When installing, hot swapping, or hot adding a new PSU, wait for 15 seconds for the system to recognize the
PSU and determine its status. The PSU redundancy may not occur until discovery is complete. Wait until the new PSU is
discovered and enabled before you remove the other PSU. The PSU status indicator turns green to signify that the PSU
is functioning properly.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Enter the enclosure show powersupply command to check the status of each power supply.
2. Use the alerts show current (or alerts show current-detailed) command.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Use the enclosure show io-cards command to check the status of the network daughter card. If the card has failed,
it will not appear in the command output.
2. If the network daughter card is visible in the output of the enclosure show io-cards command, use the alerts
show current command to look for alerts relating to one or more network interfaces that indicate a failure of the network
daughter card.
3. Verify the link and activity LEDs on the impacted port are off.
The network daughter card is located at the rear of the chassis, at the bottom.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. To remove expansion card riser 2:
a. Using Phillips #2 screwdriver, loosen the screws that secure the riser to the system.
b. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Steps
To install expansion card riser 2:
a. Align the screw and tab on the riser with the screw hole and slot on the system.
b. Lower the riser into the system until the riser connector engages with the connector on the system board.
c. Using Phillips #2 screwdriver, tighten the screws to secure the riser to the system.
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Verify the link and activity LEDs on all ports are lit on the active ports.
The network daughter card is located at the rear of the chassis, at the bottom.
2. Use the enclosure show io-cards command to check the status of the network daughter card. Verify the network
daughter card appears in the list
3. Use the alerts show current (or alerts show current-detailed) command.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Topics:
• Identify a failed DIMM
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Removing the air shroud
• Remove the memory module
• Install the memory module
• Installing the air shroud
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Verify the replacement DIMM
• Restore the HA configuration
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Enter the alert show current command to display message indicating a DIMM failure. A sample output is shown.
46 Replace a DIMM
# alert show history
2. Enter the enclosure show memory command.
Replace a DIMM 47
Shut down and disconnect the system
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
48 Replace a DIMM
Remove the system cover
Steps
1. Using a flat or a Phillips head screwdriver, rotate the latch release lock counter clockwise to the unlocked position.
2. Lift the latch till the system cover slides back and the tabs on the system cover disengage from the guide slots on the
system.
3. Hold the cover on both sides, and lift the cover away from the system.
Replace a DIMM 49
Figure 20. Removing the air shroud
Prerequisites
WARNING: Allow the memory modules to cool after you power off the system. Handle the memory modules by
the card edges and avoid touching the components or metallic contacts on the memory module.
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
2. Push the ejectors outward on both ends of the memory module socket at the same time to release the memory module from
the socket.
3. Lift and remove the memory module from the system.
50 Replace a DIMM
Figure 21. Removing a memory module
Prerequisites
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
NOTE: 16 GB DIMMs go in slots with white ejectors, and 8 GB DIMMs go in slots with black ejectors.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
CAUTION: To prevent damage to the memory module or the memory module socket during installation, do
not bend or flex the memory module. You must insert both ends of the memory module simultaneously.
2. Open the ejectors on the memory module socket outward to allow the memory module to be inserted into the socket.
3. Align the edge connector of the memory module with the alignment key of the memory module socket, and insert the
memory module in the socket.
CAUTION: Do not apply pressure at the center of the memory module; apply pressure at both ends of the
memory module evenly.
NOTE: The memory module socket has an alignment key that enables you to install the memory module in the socket in
only one orientation.
4. Press the memory module with your thumbs until the socket levers firmly click into place.
Replace a DIMM 51
Figure 22. Installing a memory module
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
52 Replace a DIMM
Install the system cover
Prerequisites
Follow the safety guidelines.
Ensure that all internal cables are routed correctly and connected, and that no tools or extra parts are left inside the system.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Replace a DIMM 53
Reconnect and power on the system
Steps
1. Close the cable management arms.
2. Prepare the terminal session.
3. Reconnect the AC power cords to the power supplies.
NOTE: The system may not power on automatically after plugging in the AC power cords.
4. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Enter the system show meminfo command to see the top level summary. Confirm that the system reports the correct
amount of memory.
2. Enter the enclosure show memory command to verify all DIMMs are discovered.
54 Replace a DIMM
NOTE: The DIMM part numbers and serial numbers are displayed by the command, but truncated from the sample
output below for readability.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
Replace a DIMM 55
datadomain-ha3a-p1.emc.com 1 active online
-------------------------- --------- --------- --------
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
56 Replace a DIMM
8
Replace a PCIe HBA (SAS, FC, or NIC)
The system uses a variety of PCIe HBAs to provide network, FC, or storage connectivity. If a port fails, the whole card requires
replacement.
CAUTION: This procedure does not apply to replacing the NVRAM module.
Topics:
• Identify the failed PCIe HBA (SAS, FC, or NIC)
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Remove an expansion card from an expansion card riser
• Install expansion card into expansion card riser
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Verify the PCIe HBA replacement
• Restore the HA configuration
2. Enter the enclosure show io-cards command to check the status of each I/O. Record the failed I/O. A sample output
is shown.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
NOTE: When removing an expansion card from riser 2 or 3, ensure that the PCIe card holder latch is closed.
Steps
1. If applicable, disconnect the cables from the expansion card.
2. Hold the expansion card by its edges, and pull the card until the card edge connector disengages from the expansion card
connector on the riser.
Figure 27. Removing the expansion card from expansion card riser 2
NOTE: When installing a card into riser 2 or 3, open the PCIe card holder latch.
Steps
1. Pull the expansion card latch.
2. If installed, remove the filler bracket.
NOTE: Store the filler bracket for future use. Filler brackets must be installed in empty expansion card slots to maintain
Federal Communications Commission (FCC) certification of the system. The brackets also keep dust and dirt out of the
system and aid in proper cooling and airflow inside the system.
3. Hold the card by its edges, and align the card edge connector with the expansion card connector on the riser.
4. Insert the card edge connector firmly into the expansion card connector until the card is fully seated.
5. Push the expansion card latch.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
CAUTION: This procedure does not apply to replacing the PCIe NIC, FC, or SAS module.
Steps
1. Check the status of the file system and disable it if necessary.
CAUTION: If the file system is not shut down, you will not be able to erase the data from the NVRAM
and you will get a message such as **** This operation is not allowed when the filesystem
a. Run the filesys status command to verify the state of the file system.
b. If the file system is enabled, run the filesys disable command to disable it.
# filesys disable
This action will disable the file system.
Applications may experience interruptions
while the file system is disabled.
Are you sure? (yes|no) [no]: yes
ok, proceeding.
Please wait............
The filesystem is now disabled.
2. Run the system erase nvram-flash command to erase the data on the NVRAM.
CAUTION: This command must be run by a qualified Dell EMC user with SE permissions, otherwise the
system displays a message such as **** This command is not available for this user. The SE
user must also provide the sysadmin password to confirm the command.
ok, proceeding.
NOTE: If the command fails, skip it and continue with the NVRAM replacement.
CAUTION: After erasing the NVRAM data, the NVRAM module is unusable until it receives a new firmware
installation at the factory.
Steps
1. Run the system bash enter command to launch BASH mode.
CAUTION: This command requires a BASH token issued by Support.
CAUTION: After erasing the NVRAM data, the NVRAM module is unusable until it receives a new firmware
installation at the factory.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
NOTE: This procedure describes and illustrates NVRAM module removal from slot 2 in expansion card riser 1.
Steps
1. If applicable, disconnect the cables from the expansion card in slot 1 (the top slot in riser 1).
2. Hold the expansion card by its edges, pull the card until the card edge connector disengages from the expansion card
connector on the riser, and place it on an ESD-safe surface.
3. Remove the NVRAM module from slot 2 (the middle slot in riser 1)
Figure 33. Removing the NVRAM module from expansion card riser 1
NOTE: This procedure describes and illustrates NVRAM module installation in slot 2 in expansion card riser 1.
Steps
1. Pull the expansion card latch.
2. Hold the NVRAM module by its edges, and align the card edge connector with the expansion card connector in slot 2 on the
riser.
3. Insert the NVRAM module edge connector firmly into the expansion card connector until the card is fully seated.
4. If applicable, reinstall the expansion card removed from slot 1 on the riser.
5. If applicable, reconnect the cables from the expansion card in slot 1.
6. Push the expansion card latch.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Run the alerts show current command to verify the system has cleared the NVRAM failure alert.
NOTE: It may take one to two minutes for the system to clear the alert.
2. Run the system show nvram command to verify the NVRAM appears.
NOTE: This command shows the charge level of the NVRAM battery. The battery must be at least 80% charged for the
file system to start.
# filesys enable
4. Run the filesys status command to verify the file system is enabled.
# filesys status
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
Run the system show all command, and look for the line indicating the TPM. If it is not present, the TPM requires
replacement:
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
CAUTION: Once the TPM plug-in module is installed, it is cryptographically bound to that specific system board.
Any attempt to remove an installed TPM plug-in module breaks the cryptographic binding, the removed TPM
cannot be reinstalled or installed on another system board.
Next steps
1. Install the system board.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
Run the disk show hardware command, and if any of the following disks are not reported, the HBA 330 requires
replacement:
(enc/disk)
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Steps
1. If installed, remove the expansion cards from the riser.
2. Disconnect any cables connected to the riser.
3. Press the release latches, and lift the riser from the riser connector on the system board.
Steps
1. Using a Phillips #2 screwdriver, loosen the screws that secure the integrated storage controller cable to the connector on
the system board.
2. Lift the integrated storage controller cable away from the integrated storage controller.
3. Lift one end of the card and angle it to disengage the card from the integrated storage controller card holder on the system
board.
NOTE: Do not remove the interposer board.
Steps
1. Press the touch point on the interposer board until the interposer board connector is firmly seated on the system board
connector.
2. Angle the card to engage the card with the integrated storage controller card holder on the system board.
3. Lower the card into place until the card is fully seated in the integrated storage controller card holder.
4. Route the integrated storage controller card cable along the wall of the system.
5. Align the screws on the integrated storage controller card cable with the screw holes on the connector.
6. Using a Phillips #2 screwdriver, tighten the screws to secure the integrated storage controller card cable to the card
connector on the system board.
Steps
1. Align the guide rails on the riser with the standoffs on the side of the system.
2. Lower the riser into the system until the riser connector engages with the connector on the system board.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Use the alerts show current (or alerts show current-detailed) command.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
Use the enclosure show cpu command to verify a CPU failure.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
94 Replace a CPU
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Replace a CPU 95
Figure 45. Remove the system cover
96 Replace a CPU
Remove processor and heat sink module
Prerequisites
WARNING: The heat sink may be hot to touch for some time after the system has been powered down. Allow the
heat sink to cool before removing it.
Steps
1. Using a Torx #T30 screwdriver, loosen the screws on the heat sink.
NOTE: Ensure that you loosen one screw before moving on to the next screw.
2. Pushing both blue retention clips simultaneously, lift the processor and heat sink module (PHM) out of the system.
3. Set the PHM aside with the processor side facing up.
Steps
1. Place the heat sink with the processor side facing up.
2. Insert a flat blade screwdriver into the release slot marked with a yellow label. Twist (do not pry) the screwdriver to break
the thermal paste seal.
3. Push the retaining clips on the processor bracket to unlock the bracket from the heat sink.
Replace a CPU 97
4. Lift the bracket and the processor away from the heat sink, and place the processor connector side down on the processor
tray.
5. Flex the outer edges of the bracket to release the processor from the bracket.
NOTE: Ensure that the processor and the bracket are placed in the tray after you remove the heat sink.
2. Flex the outer edges of the bracket around the processor ensuring that the processor is locked into the clips on the bracket.
NOTE: Ensure that pin 1 indicator on the bracket is aligned with the pin 1 indicator on the processor before placing the
bracket on the processor.
98 Replace a CPU
NOTE: Ensure that the processor and the bracket are placed in the tray before you install the heat sink.
3. If you are using an existing heat sink, remove the thermal grease from the heat sink by using a clean lint-free cloth.
4. Use the thermal grease syringe included with your processor kit to apply the grease in a quadrilateral design on the top of
the processor.
CAUTION: Applying too much thermal grease can result in excess grease coming in contact with and
contaminating the processor socket.
NOTE: The thermal grease syringe is intended for single use only. Dispose the syringe after you use it.
5. Place the heat sink on the processor and push down until the bracket locks onto the heat sink.
NOTE:
● Ensure that the two guide pin holes on the bracket match the guide holes on the heat sink.
● Ensure that the pin 1 indicator on the heat sink is aligned with the pin 1 indicator on the bracket before placing the
heat sink onto the processor and bracket.
Replace a CPU 99
Install a processor and heat sink module
Prerequisites
CAUTION: Never remove the heat sink from a processor unless you intend to replace the processor. The heat
sink is necessary to maintain proper thermal conditions.
WARNING: The heat sink may be hot to touch for some time after the system has been powered down. Allow the
heat sink to cool before removing it.
Steps
1. Align the pin 1 indicator of the heat sink to the system board and then place the processor and heat sink module (PHM) on
the processor socket.
CAUTION: To avoid damaging the fins on the heat sink, do not press down on the heat sink fins.
NOTE: Ensure that the PHM is held parallel to the system board to prevent damaging the components.
2. Push the blue retention clips inward to allow the heat sink to drop into place.
3. Using the #Torx T30 screwdriver with adjustable torque, tighten one screw at a time.
NOTE: Ensure that the screw is tightened completely before moving onto the next screw.
NOTE: The processor and heat sink module retention screws should not be tightened to more than 0.13 kgf-m (1.35
N.m or 12 in-lbf).
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Steps
1. Close the cable management arms.
2. Prepare the terminal session.
3. Reconnect the AC power cords to the power supplies.
NOTE: The system may not power on automatically after plugging in the AC power cords.
4. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Use the enclosure show cpu command to verify the new CPU.
2. Use the alerts show current (or alerts show current-detailed) command.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Topics:
• Verify the status of the system board
• Shut down and disconnect the system
• Remove a power supply
• Extend the system from the cabinet
• Remove the system cover
• Removing the air shroud
• Remove the cooling fan assembly
• Remove expansion card risers
• Remove the integrated storage controller card
• Remove the memory module
• Remove processor and heat sink module
• Remove the system board
• Install the system board
• Install a processor and heat sink module
• Install the memory module
• Install the integrated storage controller card
• Install expansion card riser 1
• Install expansion card riser 2
• Install expansion card riser 3
• Install the cooling fan assembly
• Installing the air shroud
• Install the system cover
• Install the power supply unit
• Slide the system into the cabinet
• Reconnect and power on the system
• Restoring the Service Tag by using the Easy Restore feature
• Enter the system Service Tag by using System Setup
• Import server profile
• Upgrade the identity module firmware
• Bring up the existing file system
• Restore the HA configuration
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. Disconnect the power cable from the power source and from the PSU you intend to remove, and then remove the cable
from the strap on the PSU handle.
2. Press the release latch and slide the PSU out of the system by using the PSU handle.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Steps
1. If installed, remove the expansion cards from the riser.
2. Disconnect any cables connected to the riser.
3. Press the release latches, and lift the riser from the riser connector on the system board.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. To remove expansion card riser 2:
a. Using Phillips #2 screwdriver, loosen the screws that secure the riser to the system.
b. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. Using Phillips #2 screwdriver, loosen the screw that secures the riser to the system.
4. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Steps
1. Using a Phillips #2 screwdriver, loosen the screws that secure the integrated storage controller cable to the connector on
the system board.
2. Lift the integrated storage controller cable away from the integrated storage controller.
3. Lift one end of the card and angle it to disengage the card from the integrated storage controller card holder on the system
board.
4. Lift the card out of the system.
5. Hold the interposer board by its edges, and pull the board until the connector on the board disengages from the connector
on the system board.
Prerequisites
WARNING: Allow the memory modules to cool after you power off the system. Handle the memory modules by
the card edges and avoid touching the components or metallic contacts on the memory module.
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
2. Push the ejectors outward on both ends of the memory module socket at the same time to release the memory module from
the socket.
3. Lift and remove the memory module from the system.
Steps
1. Using a Torx #T30 screwdriver, loosen the screws on the heat sink.
NOTE: Ensure that you loosen one screw before moving on to the next screw.
2. Pushing both blue retention clips simultaneously, lift the processor and heat sink module (PHM) out of the system.
3. Set the PHM aside with the processor side facing up.
Steps
1. Disconnect all cables from the system board.
CAUTION: Take care not to damage the system identification button while removing the system board from
the chassis.
CAUTION: Do not lift the system board by holding a memory module, processor, or other components.
2. Holding the system board holder, pull the blue release pin, and slide the system board toward the front of the system to
disengage the connectors from the slots on the system.
3. Incline the system board at an angle, and lift the system board out of the system.
Steps
1. Unpack the replacement system board assembly.
CAUTION: Do not lift the system board by holding a memory module, processor, or other components.
CAUTION: Take care not to damage the system identification button while placing the system board into the
chassis.
2. Holding the system board holder and blue release pin, push the system board toward the back of the system until the release
pin clicks into place.
3. Reconnect all cables to the system board.
WARNING: The heat sink may be hot to touch for some time after the system has been powered down. Allow the
heat sink to cool before removing it.
Steps
1. Align the pin 1 indicator of the heat sink to the system board and then place the processor and heat sink module (PHM) on
the processor socket.
CAUTION: To avoid damaging the fins on the heat sink, do not press down on the heat sink fins.
NOTE: Ensure that the PHM is held parallel to the system board to prevent damaging the components.
2. Push the blue retention clips inward to allow the heat sink to drop into place.
3. Using the #Torx T30 screwdriver with adjustable torque, tighten one screw at a time.
NOTE: The processor and heat sink module retention screws should not be tightened to more than 0.13 kgf-m (1.35
N.m or 12 in-lbf).
Prerequisites
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
NOTE: 16 GB DIMMs go in slots with white ejectors, and 8 GB DIMMs go in slots with black ejectors.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
CAUTION: To prevent damage to the memory module or the memory module socket during installation, do
not bend or flex the memory module. You must insert both ends of the memory module simultaneously.
2. Open the ejectors on the memory module socket outward to allow the memory module to be inserted into the socket.
3. Align the edge connector of the memory module with the alignment key of the memory module socket, and insert the
memory module in the socket.
CAUTION: Do not apply pressure at the center of the memory module; apply pressure at both ends of the
memory module evenly.
NOTE: The memory module socket has an alignment key that enables you to install the memory module in the socket in
only one orientation.
4. Press the memory module with your thumbs until the socket levers firmly click into place.
Steps
1. Hold the interposer board by its edges and align the interposer board connector with the connector on the system board.
2. Press the touch point on the interposer board until the interposer board connector is firmly seated on the system board
connector.
3. Angle the card to engage the card with the integrated storage controller card holder on the system board.
4. Lower the card into place until the card is fully seated in the integrated storage controller card holder.
5. Route the integrated storage controller card cable along the wall of the system.
6. Align the screws on the integrated storage controller card cable with the screw holes on the connector.
Steps
1. Align the guide rails on the riser with the standoffs on the side of the system.
2. Lower the riser into the system until the riser connector engages with the connector on the system board.
Steps
To install expansion card riser 2:
a. Align the screw and tab on the riser with the screw hole and slot on the system.
b. Lower the riser into the system until the riser connector engages with the connector on the system board.
c. Using Phillips #2 screwdriver, tighten the screws to secure the riser to the system.
Steps
1. Align the tab on the riser with the slot on the system, and guide rails on the riser with the standoffs on the side of the
system.
2. Lower the riser into the system until the riser edge connector engages with the connector on the system board.
The riser card edge engages with the riser guide on the system.
3. Using a Phillips #2 screwdriver, tighten the screw to secure the riser to the system.
Steps
1. Align the guide rails on the cooling fan assembly with the standoffs on the system.
2. Lower the cooling fan assembly into the system until the cooling fan connectors engage with the connectors on the system
board.
3. Press the release levers to lock the cooling fan assembly into the system.
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Steps
1. Verify that nothing has dropped into the empty PSU slot before installing the replacement PSU.
2. Slide the PSU into the system until the PSU is fully seated and the release latch snaps into place.
3. Connect the power cable to the PSU, and plug the cable into a power outlet.
CAUTION: When connecting the power cable to the PSU, secure the cable to the PSU with the strap.
NOTE: When installing, hot swapping, or hot adding a new PSU, wait for 15 seconds for the system to recognize the
PSU and determine its status. The PSU redundancy may not occur until discovery is complete. Wait until the new PSU is
discovered and enabled before you remove the other PSU. The PSU status indicator turns green to signify that the PSU
is functioning properly.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Perform one of the following steps:
● Press Y to restore the Service Tag, license, and diagnostics information.
● Press N to navigate to the Dell Lifecycle Controller based restore options.
● Press F10 to restore data from a previously created Hardware Server Profile.
After the restore process is complete, the BIOS prompts to restore the system configuration data.
2. Perform one of the following steps:
● Press Y to restore the system configuration data.
● Press N to use the default configuration settings.
After the restore process is complete, the system restarts.
Steps
1. Press F2 to enter System Setup.
4. Click Ok.
5. Import your new or existing iDRAC Enterprise license.
For more information, see the Integrated Dell Remote Access Controller User's Guide for your version of iDRAC at https://
Dell.com/idracmanuals.
Prerequisites
The system must support iDRAC9, and you need to know the first two digits of the iDRAC firmware version.
Prerequisites
The .pm firmware file must be on the local system you are using to connect to iDRAC.
Steps
1. Using your laptop, connect a USB port on laptop to the console port on the front of the PowerProtect system. Use the
default IP address 192.168.0.120.
2. Login with the user name root and the password calvin.
3. Select Maintenance > System Update > Manual Update.
4. Select Local for the location type.
5. Click Choose File to browse for the firmware file on the local system. Note the version number in the file name.
6. Click Upload to upload the file to the PowerProtect DD system.
7. Select the firmware file in the Upgrade Details area and click Install.
The system displays a confirmation that it added the identity module firmware upgrade to the job queue. Click Job Queue to
check the status. The job will complete in approximately one minute.
8. Select Dashboard > Power Off System to shut the system down.
9. Remove the AC power cords from the back of the system and wait five seconds before reconnecting them.
10. Press the power button to power the system back on.
The life cycle controller will upgrade the identity module firmware during the system boot process.
11. After the system reboot, log back into iDRAC with the user name root and the password calvin.
Next steps
After a system board replacement, user-configured iDRAC settings and users are reset. Those settings must be reconfigured
manually.
2. After verifying that the disks are visible to the destination system as foreign devices, run the following command in bash
mode.
# system headswap
The system responds:
Success
deployment chassis replacement..........[start]
Reassemble external shelf...............[OK]
Save external storage UUID to Head .....[OK]
Save head serial to external storage ...[OK]
Mount management volume.................[OK]
deployment chassis replacement..........[done]
4. If the system headswap command fails , run the following command in bash mode.
# dd_voltool –-headswap
5. Run the disk show state command to verify the system has updated the disk status.
The output should indicate that the data storage is in the In Use state.
6. Run the filesys status command to verify the status of the file system.
The system displays the message The filesystem is locked: Use 'filesys encryption unlock' to
enter the passphrase. if the file system is encrypted and locked.
7. If necessary, run the filesys encryption unlock command to unlock the file system.
The security officer must enter the system passphrase to unlock the file system.
8. Run the system upgrade status to check the progress of the system upgrade and index rebuild.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system on
page 14.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
The CMA assembly consists of two articulated arms, and two separators.
3. Locate the lock levers on the sides of the inner rails (1). Unlock each lever by rotating it up to its release position (2). Grasp
the sides of the system (3) firmly and pull it forward until the standoffs are at the front of the J-slots in the rails. Lift the
system up and away from the rails.
4. Place the system on a suitable work surface. Ensure the work surface(s) is capable of supporting the weight.
Steps
1. Open the front latch and disengage the rail from the flange.
2. Pull the entire rail forward to release the rear end of the rail from the flange.
Steps
1. Remove the two screws holding the CMA bracket to the rail.
Steps
1. Use the included screws to install the outer bracket to the rail.
2. Align the hole of the inner bracket and push down to attach it to the rail.
NOTE: Some pressure is required to push the inner bracket down and secure it. The bracket clicks when it locks in
place.
3. Repeat the preceding steps to attach the outer and inner brackets to the other rail.
Steps
1. Determine where to mount the system, and use masking tape or a felt-tip pen to mark the location at the front and back of
the cabinet.
NOTE: Install the left rail assembly first.
5. For the front end piece, rotate the latch outward and pull the rail forward until the pins slide into the flange, and release the
latch to secure the rail in place.
Steps
1. Align the screws with the designated U spaces on the front and rear rack flanges.
Ensure that the screw holes on the tab of the system retention bracket are seated on the designated U spaces.
Steps
1. At front of the cabinet, pull the inner slide rails out of the cabinet until they lock into place.
2. Locate the rear rail standoff on each side of the system. Position the system above the rails and lower the rear rail standoffs
into the rear J-slots on the slide assemblies.
3. Rotate the system downward until all the rail standoffs are seated in the J-slots.
4. Push the system inward until the lock levers click into place.
5. Pull the blue slide release lock tabs forward on both rails and slide the system into the cabinet. The slam latches will engage
to secure the system in the cabinet.
NOTE: Ensure that the inner rail slides completely into the middle rail. The middle rail locks if the inner rail is not fully
engaged.
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
2. Install the first arm on the right side of the chassis, on top of the separator with the open side up.
NOTE: The arms are reversible.
5. Install the second arm on the left side of the chassis, on top of the separator with the open side up.
6. Close the first arm by connecting it to the bracket on the right side of the chassis.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Run the ha online command on the node where the maintenance was performed to bring the HA configuration back
online.
# ha online
The operation will reboot this node.
Do you want to proceed? (yes|no) [no]: yes
2. Run the ha status command to verify that the HA pair is back online, and can failover.
3. Optionally run the ha failover command on the current active node to fail the system back to the original active node.