Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct
A R T I C LE I N FO A B S T R A C T
Keywords: Four full-scale specimens were constructed and tested under reversal cyclic loading to study the seismic per-
GFRP-RC formance of interior GFRP-RC beam-column joints. The main test parameters were joint shear stress ratio and
Seismic performance type of reinforcement (steel or GFRP). The performance of the specimens was evaluated in terms of hysteresis
Interior beam-column joints diagrams, mode of failure, strains in the reinforcement and energy dissipations. Test results indicated that the
Glass fibre reinforced
linear nature of GFRP materials resulted in lower residual damage in GFRP-RC beam-column joints compared to
Joint shear stress
Concrete moment-resisting frames
the corresponding steel-RC counterparts. Moreover, GFRP-RC joints withstood multiple cyclic loadings up to 8%
P-delta effect drift ratio without exhibiting brittle failure.
Hysteresis response
Column-to-beam flexural strength ratio
1. Introduction has been focused by few researchers. Fukuyama et al. [8] conducted
one of the early studies in investigating the seismic behaviour of FRP-
Fibre reinforced polymers (FRPs) have been established as an al- RC frames by experimentally testing a half-scale three-story FRP-RC
ternative for steel reinforcement in concrete structures mainly due to moment frame. It was concluded that FRP-RC moment-resisting frames
their superior performance in terms of corrosion resistance, magnetic can perform satisfactory under cyclic loadings, thus confirming the
non-conductivity and higher strength-to-weight ratio. The FRP material feasibility of using FRP-RC frames in seismic regions.
possess different mechanical and chemical characteristics compared to In contrary to steel, which possesses relatively consistent mechan-
conventional steel which can change the performance of reinforce ical properties, FRP materials can be manufactured with significantly
concrete (RC) elements when the reinforcing steel is replaced with FRP. different mechanical properties by making changes in the choice of fi-
This necessitates to re-investigate various aspects of the behaviour FRP- bers used in the products. Carbon-FRP (CFRP), Aramid-FRP (AFRP),
RC elements. Glass-FRP (GFRP) and recently Basalt-FRP (BFRP) are mainly the most
Performance of various FRP-RC elements under predominately dominant types of FRP materials considered for the construction in-
flexural [1–4] and axial [5–7] monotonic loading has been studied over dustry.
the last two decades. Although the study of individual FRP-RC elements Among these FRP materials available for the construction industry,
under monotonic loading showed promising results, seismic perfor- GFRP and BFRP possess a unique combination of low modulus of
mance of FRP-RC elements, in particular, still requires especial atten- elasticity and high tensile strength that can prevent brittle failure of
tion. The FRP materials in general exhibit linear elastic behaviour and FRP-RC elements during an earthquake. Due to relatively high tensile
brittle failure which significantly reduce ductility of FRP-RC structural strength and low modulus of elasticity of GFRP and BFRP, these ma-
elements compared to their counterparts reinforced with conventional terials can withstand high tensile strains prior to failure. This allows
steel. Ductility is a key feature required for structures in seismic re- concrete elements reinforced with GFRP and BFRP to be able to un-
gions. Lack of ductility can result in low energy dissipation and cata- dergo significantly large lateral displacements during an earthquake
strophic collapse of structures during an earthquake. without exhibiting brittle failure.
To evaluate the seismic performance of FRP-RC structures, the be- Furthermore, the feasibility of using GFRP-RC frames in seismic
haviour of moment-resisting frames, as one of the main lateral load regions has been investigated by Said and Nehdi [9] and Mady and El-
resisting systems used in the construction industry, under cyclic loading Salakawy [10] by investigating the seismic behaviour of GFRP-RC
⁎
Corresponding author.
E-mail address: ehab.el-salakawy@umanitoba.ca (E. El-Salakawy).
https://doi.org/10.1016/j.engstruct.2019.04.091
Received 22 January 2018; Received in revised form 30 August 2018; Accepted 29 April 2019
Available online 03 May 2019
0141-0296/ © 2019 Elsevier Ltd. All rights reserved.
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
584
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
(a) Beam of G-1.3 (b) Beam of G-1.5 (c) Beam of G-1.8 (d) Beam of S-1.5
(g) Lateral beam of GFRP-RC specimens (h) Lateral beam of steel-RC specimen
Fig. 3. Reinforcement detailing of test specimens.
Standard CSA grade G400 steel reinforcement was used in the manufacturer [17] and are presented in Table 2. The stress-strain re-
construction of Specimen S-1.5 (steel-RC beam-column joint). The yield lationships of the GFRP and steel longitudinal bars are compared in
stress and strain of the steel reinforcement were obtained through a Fig. 5.
traction test and are provided in Table 2.
Sand-coated GFRP bars and stirrups were used in the GFRP-RC
specimens. Properties of the GFRP reinforcement was provided by the
585
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
Table 1
Properties of test specimens.
Specimen Beam Reinforcement (Top and Beam Reinforcement Beam Flexural Column Flexural Shear Flexural Ratio Concrete Strength
Bottom) Ratio Capacity (kN m) Capacity (kN m) Ratio (MPa)
Table 2
Properties of GFRP reinforcement.
Reinforcement Nominal Cross-Sectional Area GFRP Tensile Strength, Steel Yield Strength Modulus of Elasticity (GPa) GFRP Ultimate Strain, Steel Yield Strain
(mm2 ) (MPa) (‰)
a
Straight portion of the stirrup.
586
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
2.4. Loading scheme least to their maximum design capacity (bending capacity of the
main beams) during the first loading phase. Ghomi and El-Salakawy
As mentioned earlier, the columns were under constant axial load [13] tested several GFRP-RC exterior beam-column joints under the
during the test while the actuator was applying reversal cyclic loading same loading scheme as the first phase in this program and observed
to simulate a seismic event. The magnitude of the axial load was set at that the specimens reach their design capacity at 4% or 5% drift
approximately 15% of the maximum concentric axial capacity of the ratio. Using that observation as a baseline, 5% drift ratio was chosen
columns. as the threshold for the first loading phase in this program to ensure
The main reversal cyclic loading was applied in a displacement- that the GFRP-RC specimens are loaded at least to their maximum
controlled mode. The ACI 374.1-05 [18] criteria was used as a guideline design capacity.
to proportion the cyclic loading scheme as shown in Fig. 7. The cyclic 2. Moreover, the objective was to satisfy the requirements of current
loading procedure consisted of several loading steps gradually in- building codes and guidelines for lateral displacements of moment-
creasing in lateral drift ratio, which is defined as the ratio between the resisting frames in seismic regions in the first loading phase. The
lateral displacement of tip of the column and the length of the column. maximum allowable lateral drift ratios set by the National Building
The length of the column is measured from the centre of the pin at the Code of Canada [11] is 2.5%. Moreover, the CSA/S806-12 [15] re-
bottom of the column to the point of load application on the column. quires a deformable moment-resisting frame to be able to withstand
Each loading step consisted of three identical cycles to ensure stable 4% drift ratio. The threshold of 5% drift ratio exceeds both re-
crack propagation in each loading step. As shown in Fig. 7, after 2% quirements.
drift ratio, one load-controlled cycle with the amplitude equal to service
load was applied after each loading step to measure the performance of
3. Test results and discussions
the beam-column joints after different stages of cyclic loads under
service condition. The service load was calculated as the horizontal load
3.1. Hysteresis diagram and mode of failure
at the tip of the column (actuator load) causing a stress in the main
beam reinforcement corresponding to 25% of the ultimate tensile
Lateral load-displacement relationship (hysteresis diagram) of the
strength of the GFRP bars, according to Canadian Highway Bridge
specimens are shown in Fig. 8. The graphs corresponding to the GFRP-
Design Code [19], and 60% of the yield strength of the steel bars [16].
RC specimens are indicating the behaviour of the GFRP-RC specimens
In this program, the GFRP-RC specimens were tested under two
in the first loading phase (up to 5% drift ratio) while the graph corre-
series of cyclic loadings, Phase I and Phase II. In Phase I, the specimens
sponding to the steel-RC specimen shows the response of the specimen
were tested from 0 to 5% lateral drift ratio. In phase II, the specimens
till failure. As mentioned earlier, the steel-RC specimen, as oppose to
were immediately re-tested by starting over the loading procedure from
the GFRP-RC specimens, was tested under one loading phase only (from
0% lateral drift ratio to failure. In the second loading phase the seismic
0% drift ratio till failure). Upon yielding of reinforcement in a steel-RC
performance of the GFRP-RC specimens was investigated while they
moment-resisting frame during a seismic event, the original condition
had been already damaged to some extend in the first loading phase.
of the frame cannot be restored and the building will not be able to stay
The 5% drift ratio was selected as the threshold for the first loading
in service. Therefore, re-testing the steel-RC specimen after yielding of
phase based on the following:
its reinforcement is not valid.
The dashed lines in the graphs indicate the design capacity of the
1. The authors attempt was to ensure that the specimens are loaded at
specimens. The design capacity was defined as the magnitude of the
587
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
lateral load at the tip of the column (applied by the horizontal actuator be interpreted as an indicator of the damage induced to their corre-
as shown in Fig. 6) that results in the maximum design bending moment sponding moment-resisting frame after an earthquake. Therefore, re-
in the main beams. It should be mentioned that 25% increase in the placing steel reinforcement with GFRP bars and stirrups can sig-
yield strength, as required by CSA/A23.3-14 [16], was assumed in nificantly reduce the damage induced to concrete moment-resisting
calculating moment capacity of Specimen S-1.5. frames due to a seismic event and hence can reduce post-disaster costs
Comparing the hysteresis diagram of Specimen S-1.5 with Specimen due to reduced structural repair needs.
G-1.5 (with identical joint shear stress and different reinforcement Moreover, a steel-RC moment-resisting frame might be able to
material) indicates lack of ductility in GFRP-RC beam-column joints. survive a severe seismic event without total collapse; however, once
The steel reinforcement in Specimen S-1.5 yielded at 1.0% drift ratio yielding of the reinforcement occurs the structure cannot restore its
which resulted in a plateau in lateral load-displacement response of the original condition. Therefore, in many cases the structure has to be
specimen. Specimen G-1.5, on the other hand, exhibited constant in- demolished due to lack of serviceability.
crease in lateral load carrying capacity due to the linear elastic nature The magnitude of equivalent stiffness of the specimens at different
of the GFRP reinforcement. loading stages is compared in Fig. 10, as another indicator of the level
However, the ductile behaviour of Specimen S-1.5 comes with the of damage after each drift ratio. The equivalent stiffness was defined as
cost of significant residual damage after yielding of the steel re- the slope of an imaginary straight line connecting the maximum posi-
inforcement. Fig. 9 compares the column residual displacement at zero tive and negative lateral load during each drift ratio in the graphs of
column load after each loading step. It is evident that the linear elastic Fig. 8.
behaviour of the GFRP reinforcement significantly reduced the mag- As expected, larger number of longitudinal bars in the main beams
nitude of residual damage in the concrete at zero load condition in of the GFRP-RC specimens resulted in higher equivalent stiffness.
Specimen G-1.5 compared to Specimen S-1.5 after steel yielding. Moreover, Specimen S-1.5 exhibited higher equivalent stiffness at 0.8%
The magnitude of residual displacement in beam-column joints can drift ratio compared to Specimen G-1.5, due to higher modulus
Fig. 9. Column residual displacement. Fig. 10. Equivalent stiffness of test specimens.
588
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
Fig. 11. Condition of test specimens after 5% drift ratio (after the first loading phase for GFRP-RC specimens).
elasticity of steel than that of GFRP (184.8 GPa vs 62.6 GPa). However, Fig. 11 shows condition of the GFRP-RC specimens after completion
the rate of stiffness deterioration was significantly higher in Specimen of the first loading phase (after 5% drift ratio). As expected, no sig-
S-1.5 than G-1.5, which indicates the higher level of damage in nificant concrete damage was observed in the GFRP-RC specimens after
Specimen S-1.5 due to yielding of the steel reinforcement. 5% drift ratio. However, comparing the condition of the specimens
589
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
indicates that the increase in joint shear stress ratio increases the da- Followed by achieving the maximum lateral load carrying capacity
mage induced to the specimens in the vicinity of the joint area. at 6% drift ratio, gradual decrease in lateral load was observed in
In addition, the effect of beam longitudinal reinforcement on the Specimen G-1.5 during the consecutive drift ratios. The test was
concrete damage of the GFRP-RC specimens has to be considered. stopped after 8% drift ratio due to failure of the specimen. As suggested
Increasing the number of beam longitudinal reinforcement increases by 374.1-05 [18], failure was defined as the point with more than 25%
bending moment capacity of the beams hence the column-to-beam decrease in lateral load compared to the maximum lateral load ex-
flexural strength ratio decreases. The column-to-beam flexural strength hibited by the specimens.
ratio is commonly used as an indicator of the location of the damage In contrary to Specimen G-1.5, Specimen G-1.3 was not able to
concentricity in beam-column joints. The lower the ratio, the closer the reach the maximum design capacity in the second loading phase. This
centre of the damage to the column (joint area). As shown in Table 1, observation contradicted the expected behaviour of the specimens.
column-to-beam flexural strength ratio of the GFRP-RC specimens de- Compared to Specimen G-1.5, Specimen G-1.3 with lower joint shear
creases as their joint shear ratio increases. stress was expected to exhibit less concrete damage in the joint area
As shown in Fig. 8, in contrary to Specimens G-1.3 and G-1.5, hence behaving in a more stable manner in the second loading phase.
Specimen G-1.8 was not able to reach its design capacity during the first However, the authors believe that the lack of strength of Specimen G-
loading phase. The reason can be explained by the lower column-to- 1.3 in the second loading phase (compared to Specimen G-1.5) was
beam flexural strength ratio in Specimen G-1.8 compared to the other because of the damage occurred in the main beams and not the joint.
GFRP-RC specimens. Building codes and design guidelines commonly As shown in Fig. 3, the beams in Specimen G-1.3 were reinforced
suggest column-to-beam flexural strength ratios more than unity to with one layer of bars while the beams in Specimen G-1.5 were re-
prevent failure of the columns prior to failure of the beams (strong inforced with two layers of bars. The higher number of reinforcement
column-weak beam concept). However, this ratio in Specimen G-1.8 layers resulted in more confinement of the concrete core in the main
was calculated as 0.83. Therefore, the column reached its design ca- beams in Specimen G-1.5. Therefore, less damage was induced to the
pacity prior to the beam as shown in Fig. 11 in forms of concrete cover main beams of Specimen G-1.5 compared to the beams of Specimen G-
spalling in the column adjacent to the main beams. This resulted in a 1.3 hence less reduction in its lateral strength was observed.
decrease in lateral stiffness of the specimen, therefore the design ca- Although early concrete spalling in the column prevented Specimen
pacity was not reached during the first loading phase. G-1.8 from gaining the design capacity during the first loading phase,
Fig. 12 compares the normalized lateral load envelop (ratio of the the specimen was able to reach the design capacity in the second
maximum lateral load to the design capacity) of the test specimens up loading phase at 6% drift ratio. As shown in Table 1, the joint shear
to the first 5% drift ratio. As shown in the graph, the steel-RC specimen stress ratio applied to the joint area of Specimen G-1.8 when the main
exhibited significantly higher initial stiffness compared to the GFRP-RC beams are loaded to their design bending capacity was calculated as
specimens. This is due to the higher modulus of elasticity of steel (200 1.8 f 'c . Based on this observation, it was concluded that the interior
GPa) compared to that of the GFRP reinforcement used in this program GFRP-RC beam-column joints tested in this program are able to with-
(62.5 GPa). stand joint shear stress ratio of 1.8 f 'c .
The lower initial stiffness of GFRP-RC beam-column joints can sig- The maximum lateral load observed during testing of the GFRP-RC
nificantly affect seismic behaviour of GFRP-RC moment-resisting specimens in each drift ratio is shown in Fig. 14. The solid lines and the
frames by increasing lateral displacement of the structure during an dashed lines in the graphs indicate the response in the first and the
earthquake. Excessive lateral deformation of the structure increases the second loading phase, respectively. As expected, all specimens showed
secondary moments induced to the column due to significant gaps be- linear behaviour up to 5% drift ratio during the second loading phase.
tween centre of gravity and centre of geometry of the structure (P-delta This is indicated in the figure by the straight portion of the graphs
effect) as will be explained in later sections. connecting the origin to the point corresponding to the maximum lat-
Fig. 13 shows lateral load-drift response of the GFRP-RC specimens eral load during the third cycle of loading at 5% drift ratio in the first
during the second loading phase. Specimen G-1.5 was able to reach the loading phase.
design capacity again during the second loading phase. This indicates Fig. 15 shows the condition of the specimens after the final loading
that it is possible to design GFRP-RC frames to withstand the ultimate step (failure). Comparing the condition of the GFRP-RC specimens in-
state loading multiple times. However, due to the damage induced to dicates that the increase in the joint shear stress ratio increases the
the specimen during the first loading phase, the lateral stiffness of the damage induced to the joint area. As explained earlier, lower column-
specimen decreases which resulted in reaching the design capacity at a to-beam flexural strength ratio of the specimens with higher joint shear
higher lateral drift ratio (6%) compared to the first loading phase (5%). stress also results in penetration of the damage further into the joint. In
As mentioned before, the GFRP-RC specimens were not repaired after all specimens, the damage is more severe at the lower part of the
the first loading phase and the second loading phase was applied to the column (below lateral beams) due to the lack of confinement by lateral
specimens immediately after the completion of the first loading phase. beams. As shown in Fig. 1, the top surface of lateral beams was flush
with the top surface of the main beams leaving the bottom 100-mm of
the joint area unconfined.
The GFRP-RC were designed as over-reinforced sections causing the
mode of failure to be concrete crushing prior to rupture of the re-
inforcing bars. Therefore, the failure in the GFRP-RC specimens was
initiated by crushing of concrete at the outermost fibre of the beam or
column sections. This was observed by losing concrete cover in the
beams or columns near the joint area. However, at that point, the da-
mage remained limited to the unconfined concrete cover. The concrete
core, due to the confinement provided by the stirrups and the long-
itudinal bars, exhibited higher compressive strength and the specimens
continued to maintain their maximum lateral load carrying capacity
after losing the concrete cover. However, as the lateral drift ratio was
further increased, the concrete damage gradually increased in both the
joint and the beams resulting in gradual softening of the beam-column
Fig. 12. Normalized lateral load envelops. joints and decrease in the maximum lateral load.
590
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
Fig. 13. Hysteresis diagram of GFRP-RC specimens in the second loading phase.
591
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
592
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
This gradual failure, as oppose to sudden rupture of the longitudinal maximum bending moment in the columns adjacent to the joint area
bars, is opposite of what is generally expected from GFRP-RC elements. corresponding to each lateral drift ratio was calculated based on test
Sudden and brittle failure of GFRP-RC elements was one of the main results of the specimens. In order to follow the same approach as the
concerns regarding constructing these types of structures in seismic CSA/A23.3-14 [16], the secondary moments due to P-delta effect are
regions. However, this observation indicates that GFRP-RC beam- also added to the bending moments of the columns.
column joints can be proportioned in a way that prevents brittle failure Since the column axial load was kept constant during the test, the
of moment-resisting frames. component corresponding to the P-delta effect can be calculated by
This behaviour was very similar to the behaviour observed from the multiplying the column axial load (approximately 650 kN) by the
steel-RC specimen, even though the steel-RC beams were designed as column tip displacement.
under-reinforced sections (yielding of the reinforcement occurring prior Fig. 16 compares the magnitude of bending moment in the columns
to concrete crushing). Followed by yielding of the reinforcement, above the joint area with and without the effect of secondary moments
elongation of the reinforcement continued until the outer most fibre of during the first loading phase (up to 5% drift ratio). The horizontal
the concrete section reached the compressive strength of the concrete dashed lines in the graphs indicate bending moment capacity of the
and the same sequence as described for the GFRP-RC specimen until columns. As shown in the graphs, in Specimens G-1.3 and G-1.5 the
failure occurred. maximum bending moment capacity (design capacity) of the columns
was reached at 5% drift ratio, which is the drift ratio that the specimens
3.2. Effect of secondary moments reached the lateral design capacity corresponding to the bending mo-
ment capacity of the main beams. This was due to the column-to-beam
As mentioned earlier, the test set-up used in this program was de- flexural strength ratios close to unity in Specimens G-1.3 and G-1.5. In
signed to prevent the effect of secondary moments (P-delta) on the Specimen G-1.8, on the other hand, the design capacity of the column
specimens during the loading procedure. However, due to lower lateral was reached prematurely at 4% drift ratio due to column-to-beam
stiffness of GFRP-RC beam-column joints compared to conventional flexural strength ratio less than unity (0.83), as explained earlier.
steel-RC counterparts, higher lateral displacements should be expected Since secondary moments increase the magnitude of bending mo-
for GFRP-RC moment-resisting frames during an earthquake. Large ments at the columns, failure of columns could occur prior to the
lateral deformation of structures can result in significant secondary beams. As shown in the graphs of Fig. 16, including the effect of sec-
moments in the columns. Therefore, it seems necessary to include the ondary moments results in reaching the maximum design capacity of
effect of probable secondary moments into the lateral load-drift re- the columns at 4% drift ratio in Specimens G-1.3 and G-1.5, which is
sponse of the test specimens. less than 5%, the drift ratio that the flexural capacity of the main beams
The Canadian standards CSA/A23.3-14 [16] require to magnify of the specimens were reached.
column end moments due to secondary moments for sway frames. The In Specimen S-1.5 with column-to-beam flexural strength ratio of
593
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
Fig. 17. Maximum strain in joint stirrups. Fig. 18. Maximum strain in beam longitudinal bar.
1.16; however, adding the effect of secondary moments did not result in strain), 18,900 micro-strain, indicates a significant margin. This is in
exceeding the bending moment design capacity in the column. agreement with what was observed as the mode of failure of the tested
Therefore, it is suggested to limit the minimum column-to-beam flex- GFRP-RC beam-column joints in forms of gradual softening without
ural strength ratio to 1.2 in the design of GFRP-RC beam-column joints. brittle failure due to rupture of the bars. Therefore, designers can cal-
The ratio of 1.2 is conservatively obtained by rounding up the column- culate the maximum strain at the point of failure (concrete crushing) in
to-beam flexural strength ratio of Specimen S-1.5, 1.16. the GFRP-RC beams and ensure that a safe margin between the max-
However, it should be mentioned that reaching the bending moment imum probable and the rupture point exists.
capacity of the columns does not necessarily result in total collapse of In the design process of the test specimens, the maximum expected
the beam-column joints. As explained earlier, reaching the design ca- strains in the outermost layer of the longitudinal bars of the beams at
pacity is corresponding to compressive failure of unconfined concrete of the point of concrete crushing were calculated as 14,400, 13,250 and
the cover, while the confined concrete core will continue to resist fur- 10,850 micro-strain for Specimens G-1.3, G-1.5 and G-1.8, respectively.
ther loadings. However, it is very important to take into account the effect of concrete
It should be mentioned that the graphs of Fig. 16 and the suggested damage on increasing the strains in the bars compared to the theore-
limit of column-to-beam flexural strength ratio, 1.2, are based on the tically calculated values. For example, even though the maximum strain
column axial load applied to the test specimens in this program (650 in bars of Specimen G-1.8 was calculated as 10,850 micro-strain, the
kN). However, columns in a real structure may be under various mag- maximum observed value during the test was 11,550 micro-strain. This
nitude of axial load depending on the ultimate load and their location in difference was due to significant damage in the concrete that increase
the structure. The magnitude of column axial load affects the amount of the stress applied to the beam longitudinal bars.
secondary moments. However, the same procedure as describe earlier In Specimen S-1.5, the steel bars reached the yielding strain (2000
may be used to set appropriate column-to-beam flexural strength ratio micro-strain) at 1.0%. Therefore, to prevent yielding of the reinforce-
based on the applicable axial loads. ment during an earthquake, the lateral displacement of the arbitrary
moment-resisting frame that the test beam-column joint has been ex-
3.3. Strain-drift relationship tracted from should be limited to 1.0% drift ratio. However, the extra
cost associated with that purpose may make the structure economically
For each specimen, a total of six strain gauges were installed on the unreasonable to construct.
stirrups located in the joint area. Fig. 17 shows the maximum strain The maximum strains in the longitudinal bars of the main beams
obtained from these strain gauges at different drift ratios. The CSA/ were also monitored during the second loading phase. The maximum
S806-12 [15] limits the maximum strain in FRP stirrups to 5000 micro- strains corresponding to the GFRP-RC specimens during the second
strain. This limit is indicated in the graph of Fig. 17 by a solid line. loading phase up to 5% drift ratio were very close to the values cap-
As expected, the increase in the joint shear stress ratio of the spe- tured during the first loading phase. This confirms the ability of GFRP-
cimens increased the maximum strain observed in the joint stirrups. RC beam-column joints to maintain their functionality after being
However, as shown in the graphs, in none of the specimens the max- loaded to their maximum design capacity.
imum strain limit was exceeded prior to 5% drift ratio (in either first or
second loading phase). 3.4. Energy dissipation
This observation along with the satisfactory performance of the
GFRP-RC specimens up to 5% drift ratio (no concrete damage in the Low energy dissipation of GFRP-RC structures compared to steel-RC
joint area) indicates the adequacy of the transverse reinforcement used counterparts is one of the main concerns regarding using FRP re-
in the joint area. The joint reinforcement of the GFRP-RC specimens inforcement in seismic regions. Ductile behavior of steel reinforcement
tested in this program was designed according to the requirements for provides significant energy absorption at higher drift ratios. Although
confinement of the columns in seismic regions suggested by the CSA/ the linear elastic nature of GFRP bars limits the residual damage after
S806-12 [15]. an earthquake (as discussed earlier) it comes with the cost of compro-
In Specimen S-1.5, on the other hand, the maximum strain captured mising energy dissipation of GFRP-RC frames.
in the joint stirrups exceeded 2000 micro-strain, yielding strain of steel, Energy dissipation can be related to damping feature of structures
at 2% drift ratio. As explained earlier, once the yielding of the internal which, if increased, can decrease the lateral deformation of structures
reinforcement occurs the building has to be demolished even if it does during an earthquake. This, in turn, can reduce damage induced to the
not totally collapse during an earthquake event. structure and secondary moments (due to P-delta) effect. Therefore,
Fig. 18 shows the maximum strain captured on the longitudinal bars lower energy dissipation of GFRP-RC beam-column joints compared to
of the main beams in the vicinity of the columns (maximum moment steel-RC counterparts increases their vulnerability to high deforma-
location). Comparing the maximum strain observed in the bars of the tions. It should be mentioned that the effect of low energy dissipation
beams with the ultimate strain capacity of the GFRP bars (rupture on lateral deformation will be added to the effect of low initial stiffness
594
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
Fig. 20. Relationship between joint shear stress ratio, concrete strength and reinforcement ratio of main beams.
595
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
relationship was observed from the analysis of the two types of joints. The authors wish to express their gratitude for the financial support
To better compare the response of steel-RC and GFRP-RC beam-column received from the Natural Science and Engineering Research Council of
joints, the relationship between reinforcement ratio of the main beam Canada (NSERC) and the University of Manitoba Graduate Fellowship
and the joint shear stress ratio at 40 MPa concrete strength and the (UMGF). Also, the authors would like to acknowledge the help received
relationship between the concrete strength and the joint shear stress from the technical staff at the McQuade Heavy Structures Laboratory at
ratio at reinforcement ratio of 1.5% are shown in Fig. 21a and Fig. 21b, the University of Manitoba.
respectively.
As shown in the graphs of Fig. 21, the joint shear stress in steel-RC References
joints show higher sensitivity to reinforcement ratio of the main beams
and concrete strength. Fig. 21a indicates that although at lower re- [1] Brown VL, Bartholomew CL. FRP reinforcing bars in reinforced concrete members.
inforcement ratios, GFRP-RC joints exhibit higher joint shear stresses ACI Mater J 1993;90(1):34–9.
[2] Vijay PV, GangaRao HVS. Bending behavior and deformability of glass fiber-re-
compared to their steel-RC counterparts, steel-RC beam-column joints inforced polymer reinforced concrete members. Mater Struct 2010;43:73–90.
surpass the GFRP-RC beam-column joints in terms of joint shear stress [3] Yost JR, Gross SP. Flexural design methodology for concrete beams reinforced with
at higher reinforcement ratios. fibre-reinforced polymers. ACI Struct J 2002;99(3):308–16.
[4] Soric Z, Kisicek T, Galic J. Deflections of concrete beams reinforced with FRP bars.
Moreover, as shown in Fig. 21b, with the increase in concrete ACI Struct J 2002;99(3):308–16.
compressive strength the joint shear stress ratio in a GFRP-RC beam- [5] Alsayed SH, Al-Salloum YA, Almusallam TH, Amjad MA. Concrete columns re-
column joint remains approximately constant while the joint shear inforced by glass fibre reinforced polymer rods. ACI Special Publ 1999:103–12. SP-
188.
stress ratio drops significantly in a steel-RC beam-column joint. [6] Choo CC, Harik IE, Gensund H. Strength of rectangular concrete columns reinforced
with fibre-reinforced polymer bars. ACI Struct J 2006;103(3):452–9.
4. Conclusions [7] Tobbi H, Farghaly AS, Benmokraine B. Concrete columns reinforced longitudinally
and transversally with glass fibre-reinforced polymer bars. ACI Struct J
2012;109(4):551–8.
Based on the results obtained from testing of 4 full-scale interior [8] Fukuyama H, Masuda Y, Sonobe Y, Tanigaki M. Structural performances of concrete
beam-column joints, the following conclusions can be made: frame reinforced with FRP reinforcement. Non-metallic (FRP) reinforcement for
596
S.K. Ghomi and E. El-Salakawy Engineering Structures 191 (2019) 583–597
597