COMPONENTS:
IF THE POWER PRODUCED BY THE RENEWABLE SOURCES IS HIGHER THAN LOAD: CHARGE
If the spare power from renewable is lower than Plim_charge = 30 kW the Batteries are charged. Otherwise the
Electrolyzer generates H2
IF THE POWER PRODUCED BY THE RENEWABLE SOURCES IS LESS THAN LOAD: DISCHARGE
If the power not supplied to meet the load is lower than P1FC = 11,2 kW, it will be supplied by the Batteries. If the
Batteries cannot supply the whole and the rest is lower than P2 = 39,6 kW, the rest will be supplied by the Fuel Cell,
otherwise the rest will be supplied by the AC Generator.
If the power not supplied to meet the load is higher than P1FC = 11,2 kW, and lower than P2 = 39,6 kW, it will be
supplied by the Fuel Cell. If the FC cannot supply the whole and the rest is lower than P1gen = INF kW, the rest will be
supplied by the Batteries, otherwise the rest will be supplied by the AC Generator.
If the power not supplied to meet the load is higher than P2 = 39,6 kW, it will be supplied by the AC Generator. If the
AC Generator cannot supply the whole and the rest is lower than P1FC = 11,2 kW, the rest will be supplied by the
Batteries, otherwise the rest will be supplied by the Fuel Cell.
COSTS:
Initial Investment: 221,25 k$. Loan: 100 %, int. 5% in 25 years, annual quota: 15,698 k$. Cost AC gen. fuel, 1st. year:
2,583 k$
NPC OF THE SYSTEM (25 years lifetime): (comparing to only AC grid, 86MWh/yr, NPC=324,87 k$)
Total System Costs (NPC): 174,395 k$. Levelized cost of energy: 0,18 $/kWh
Distribution of NPC:
PV Generator Costs (NPC): 111,103 k$
Battery bank Costs (NPC): 49,098 k$
AC Generator Costs (NPC): 16,54 k$
Fuel Cell Costs (NPC): 4 k$
Electrolyzer+H2Tank Costs (NPC): 19,134 k$
Inverter Costs (NPC): 19,227 k$
AC Generator Fuel Costs (NPC): 22,683 k$
Installation+financing (NPC): -67,39k$
1 of 3
NPC / NPV (k$)
PV
AC GEN. FUEL
BATTERIES
AC GENERATOR
INV.+AUX. FC ELYZER.+H2_TANK
OTHER RESULTS:
100
80
60
40
20
2 of 3
NO MULTI-PERIOD SIMULATION -> ALL THE YEARS SAME ENERGY VALUES (MWh/yr).
100
50
50
0 0
12 34 567 89 11 13 15 17 19 21 23 25 1 2 3 4 5 6 7 8 9 11 13 15 17 19 21 23 25
0 0
1 23 45 6 78 9 11 13 15 17 19 21 23 25 1 23 45 6 78 9 11 13 15 17 19 21 23 25
AC GENERATOR: EXPORT:
4 8
3 6
2 4
1 2
0 0
1 23 45 6 78 9 11 13 15 17 19 21 23 25 1 23 45 6 78 9 11 13 15 17 19 21 23 25
4
0
2
0
1 23 45 6 78 9 11 13 15 17 19 21 23 25 1 23 45 6 78 9 11 13 15 17 19 21 23 25
80
60 60
40 40
20 20
0 0
12 34 567 89 11 13 15 17 19 21 23 25 12 34 567 89 11 13 15 17 19 21 23 25
0,08
0,06
0,04 0
0,02
0
123456789 11 13 15 17 19 21 23 25 1 23 45 6 78 9 11 13 15 17 19 21 23 25
0 0
1 23 45 6 78 9 11 13 15 17 19 21 23 25 1 23 45 6 78 9 11 13 15 17 19 21 23 25
3 of 3