PSYCHROMETRICS

J.ILANGUMARAN
ics
etr
om
hr
yc
Ps
The Psychrometric Chart
COMFORT
“We air condition buildings to provide a comfortable
environment for the occupants”
Relative Humidity:
A minimum RH of 35% is recommended to prevent dry eyes, nose and throat.
A maximum RH of 70% is recommended to prevent surface condensation and mould etc.
Electrostatic charges can be generated at RH less than 45%.

Temperature and Humidity:


24oC DB and 60% RH for summer and 21oC DB and 50% RH for winter is energy efficient.

Air Movement: The terminal velocity, at neck level, should be designed for approximately 0.2m/s.

Air Freshness: For body odour dilution of 8l/s of fresh air per person should be introduced.
If smokers are present 16l/s of fresh air is required.

Air Cleanliness: Selection of an adequate filtration system is very important and some types
of air conditioning system permit better air cleansing than others.

Noise Levels: Careful selection of equipment and consideration of both external and internal
noise pollution is important.
A certain level of noise is necessary to mask clarity of individual conversations etc.
DRY BULB TEMPERATURE

-5 0 5 10 15 20 25 30 35 40

Dry Bulb Temperature oC


MOISTURE CONTENT
(Specific Humidity)
The weight of water in the air

Moisture Content kg/kg (Dry Air)


21oC DB and 50% RH = 0.007857 kg/kg 0.02

0.007857kg/kg
= 0.66%
1.186kg/m3 (air density)
0.015

0.01

0.005
RELATIVE HUMIDITY

RH is actual vapour pressure


compared to the vapour pressure
at saturation for the same dry bulb
temperature.

100% Relative Humidty


(Saturation Curve)
90%
80%
70%
60%
50%
40%
30%
20%
10%
COOLING & HEATING

COOLING

HEATING
DEWPOINT
Dewpoint is the temperature where
moisture begins to condense.
• Cool to dewpoint (from A to B)
no change in moisture content.

• Further cooling (to C) water vapour condenses


lowering the moisture content.

Saturation Curve

B COOL A
Moisture A
Dewpoint Content
O OL 0.01kg/kg B
C
C
Moisture
Content C
0.075kg/kg

10oC 14oC 22oC


Dry Dry Dry
Bulb Bulb Bulb
WET BULB TEMPERATURE
The sling psychrometer is used to determine
the moisture content of the air.

Wet Bulb Handle


Thermometer

Dry Bulb
Thermometer

Wetted
Cotton wick If air is saturated none of the moisture on the wick will
evaporate and the WB temperature will be the same
as the DB.
If the air is less than saturated moisture will evaporate
from the wick cooling the WB thermometer.
The difference between the WB and DB is called the
WB depression.
WET BULB TEMPERATURE

On the saturation curve WB and DB


temperatures are the same 25

o
C
e
ur
20

r at
pe
m
15
Te
B
W

10
Saturation Curve
5
0
-5

15oC Dry Bulb


DENSITY (Specific Weight)
The inverse of density is the Specific Volume
m3 /kg
The volume increases with temperature increase.
The density decreases with temperature increase.

1.32 1.3 1.28 1.26 1.24 1.22 1.2 1.18 1.16 1.14 1.12

Density kg/m3
TOTAL HEAT CONTENT
(SPECIFIC ENTHALPY)

75
70
100

65
60
95

55
90

50
85

45
40 80
35
30

75
25
20

70
15

65
10
5

60
0

55

50

45
-10 -5 0 5 10 15 20 25 30 35 40

Total Heat Content kJ/kg


SPECIFIC ENTHALPY CORRECTION FACTOR
DUE TO ALTITUDE

1.0

0.9

Specific Enthalpy
Correction Factor

0.8

0.7
0 1000 2000 3000
Altitude Metres
PSYCHROMETRIC DATA
1 DB Temperature = 24oC
2 WB Temperature = 17oC
3 RH = 50%
7
4 Moisture Content = 0.0093kg/kg
5 Total Heat Content = 48kj/kg
6 Dewpoint = 13oC 5
7 Saturated Moisture 2
Content = 0.0188kg/kg
3

6 4

1
COOLING & HEATING

COOLING

HEATING
COOLING CURVES
Due to Cooling Coil inefficiency
the air loses moisture before it
reaches the saturation curve.
The cooling process of a Cooling
coil follows the Cooling Curves.
HUMIDIFYING
To add moisture

DEHUMIDIFYING
To remove moisture

DEHUMIDIFYING

HUMIDIFYING
SENSIBLE HEAT:
A change in DB temperature. No change in moisture content.

LATENT HEAT:
A change In moisture content . No change in DB temperature.

TOTAL HEAT (ENTHALPY):


Sensible Heat + Latent Heat
TOTAL HEAT

He tal
at
To
TOTAL COOLING

ota l
T at
He Latent
Heat
Sensible
Heat
Humidification
Evaporative Cooling Heating & Humidification

Sensible Cooling Sensible Heating

Cooling & Dehumidification

Dehumidification

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
THE COMFORT ZONE

Summer

Winter

Brian Fossey

Tech
Roof Solar & Conduction Sensible Gain to Ceiling Void

Occupants Gain Light


PERIMETER Sensible & Latent SensibleGain
ZONE Ceiling
CIRCULATION SensibleGain To Room
ZONE To Room
INTERIOR
Floor ZONE
Miscellaneous Equipment Sensible Gain
Sensible Gain To Room

Floor Conduction Sensible Gain


Wall Solar & Conduction Sensible Gain
to Ceiling Void
Glass Solar &Conduction Sensible Gain
to Room
PERIMETER CIRCULATION INTERIOR
Infiltration Gain - Sensible & Latent ZONE ZONE ZONE
to Room

Wall Solar & Conduction Sensible Gain


to Room
ROOM SENSIBLE HEAT FACTOR
=
SENSIBLE HEAT
SENSIBLE HEAT + LATENT HEAT
=
SENSIBLE HEAT
TOTAL HEAT
SENSIBLE HEAT FACTOR (ESHF, GSHF, RSHF) LINES

1.) Calculate SHF.

2.) Plot line through SHF ratio and plotting point.

3.) Plot line parallel to item 2.)


through point of room condition.

Room Condition

SHF

SHF Plotting Point


Room Condition A
Heat gain from fan

Condition of air Condition of air


C B
leaving cooling coil entering cooling coil

RSHF - Room Sensible Heat Factor


Room Sensible and Latent Heat Gains
C from Walls, windows, infiltration,
people, lights and miscellaneous
equipment
B
A

Brian Fossey

Tech FAN COIL UNITS


A
Outside Air Louvre

Filter

Heating Coil

B Cooling Coil

Humidifier
C

Supply Fan
D
AIR HANDLING UNIT SUPPLYING 100% OUTSIDE AIR
D
A
Outside Air Summer
and
B C A
Entering Cooling
Coil Condition
Fan Gain Supply Air
D
Condition

Leaving Cooling
C
Coil Condition

AIR HANDLING UNIT


SUPPLYING 100%
OUTSIDE AIR SUMMER

Brian Fossey

Tech
D
WINTER
A AIR HANDLING UNIT
B C
SUPPLYING 100%
OUTSIDE AIR

A Fan Gain Supply Air


Outside Air Winter D
Condition

Steam Humidifier
and
Entering Heating Sp
Coil Condition C ra
yH
um
idi
f ier

B
Preheater for Steam Humidifier
B
Preheater for Spray Humidifier
AIR HANDLING UNIT WITH RECIRCULATED AIR

Outside Air Damper


Outside Air Louvre

Cooling Coil
Heating Coil

Humidifier
Supply

Filter
Supply
Air
Air
Fan
Outside G
A D E F
Air
Return Air Conditioned
Recirculated Air
Air
Disharge Room
C
Air B
Discharge Damper
Discharge Louvre

Return
Air
Fan
Room B
Saturation Condition
Curve RSHF

Maximum
60% RH

B
Saturation
Curve Return Air
Fan Gain
B Recirculated Air
Condition C

C B
SUMMER COOLING
Saturation
Curve Return Air
Fan Gain
B Recirculated Air
Condition C

Outside Air
Condition
Summer
A A

C B
SUMMER COOLING
Saturation
Curve Return Air
Fan Gain
B Recirculated Air
Condition C
Outside Air and
Recirculated Air
Mixture Condition
D
% Outside Air
(minimum outside air)

% Recirculated Outside Air


Air Condition
Summer
A A
D

C B
SUMMER COOLING
Saturation
Curve

B C

Outside Air and


Cooling Coil Recirculated Air
Mixture Condition
D

A D

C B
SUMMER COOLING
Saturation
Curve
Apparatus
Dewpoint B C
(ADP)
Outside Air and
Cooling Coil Recirculated Air
Mixture Condition
Leaving Cooling
D
Coil Condition
Bypass Factor E
A
normally 10%
of total coil

E
A D

C B
SUMMER COOLING
Saturation
Curve
Supply Air Supply Air
Fan Gain Condition G B C

D
E Cooling Coil

E
A D G

C B
WINTER
Minimum
Saturation 40% RH
Curve
Supply Air Supply Air
Fan Gain Condition G B C

Outside Air and E


D Recirculated Air
% Outside Air
Mixture Condition
(minimum outside air)

% Recirculated
Air
A

A E
D G

C B
WINTER - SPRAY HUMIDIFIER
Saturation
Curve
Supply Air Supply Air
Fan Gain Condition G B C

F
Spray Humidifier
D

Wet bulb Line

More than minimum D


outside air is required
A
F
A D G
In this situation a Preheater is not required
for daytime operation but would be needed
for morning warm-up.
C B
WINTER - SPRAY HUMIDIFIER

Saturation
Curve
Supply Air Supply Air
Fan Gain Condition G B C

F
Spray Humidifier

D
E
Preheat
Wet bulb Line

A
F
A E
D G
Preheater required when
low temperature or high %
outside air C B
WINTER - STEAM HUMIDIFIER

Saturation
Curve
Supply Air Supply Air
Fan Gain Condition G B C

Steam Humidifier D

A More than minimum D


outside air is required
A F
D G
In this situation a Preheater is not required
for daytime operation but would be needed
for morning warm-up.
C B
AIR HANDLING UNIT WITH RECIRCULATED AIR
Outside Air Condition Summer 32oC DB, 19oC WB.

Supply Air Room


Fan Gain Condition Return Air
Fan Gain
RSHF
%R
etur
n Ai
r ting
Leaving RSHF plot
Cooling Coil line
Condition

Outside Air
Condition
Supply Air
Entering Summer
Condition
Cooling Coil
Condition

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
AIR HANDLING UNIT WITH RECIRCULATED AIR
Outside Air Summer 28oC DB, 19oC WB.
Outside Air
Condition
Supply Air Room Summer
Fan Gain Condition

ti ng
Leaving
RSHF
RSHF plot
Cooling Coil Return Air line
Condition Fan Gain

Supply Air Entering


Condition Cooling Coil
Condition

Brian Fossey

Tech
PSYCHROMETRIC TERMS AND FORMULEA

ROOM CONDITIONS
RSH = Room Sensible Heat (watts)

RLH = Room Latent Heat (watts)

RTH = Room Total Heat (watts) = RSH + RLH

RSHF = Room Sensible Heat Factor = RSH/RTH

OUTSIDE AIR CONDITIONS


Outside Air Volume m3/s = Number of occupants X 0.008 to 0.01m3/s

OATH = Outside Air Total Heat - kW


= OA volume m3/s X (OA enthalpy kj/kg - Room enthalpy kj/kg) X OA density kg/m3

OASH = Outside Air Sensible Heat - kW


= OA volume m3/s X specific heat 1.02kj/kg oC X (OADB oC - Room DB oC) X density kg/m3

OALH = Outside Air Latent Heat - kW


= OATH - OASH
TOTAL CONDITIONS
TSH = Total Sensible Heat = RSH + OASH + *Air conditioning system gains
* Includes supply air and return air fan gains, duct leakage sensible losses,
return air gains from lights.

TLH = Total Latent Heat = RLH + OALH + supply air duct leakage latent losses.

GTH = Grand Total Heat = TSH + TLH

GSHF = TSH/GTH
EFFECTIVE CONDITIONS
ERSH = Effective Room Sensible Heat
= RSH + (BF* X OASH) + **Air conditioning system gains
* BF = Cooling coil bypass factor (approximately 0.1)

** Includes supply air and return air fan gains, duct leakage sensible losses,
return air gains from lights.
ERLH = Effective Room Latent Heat
= RLH + (BF* X OALH) + **Air conditioning system gains
* BF = Cooling coil bypass factor (approximately 0.1)
** Includes supply air and return air fan gains, duct leakage latent losses,
return air gains from lights.

ERTH = Effective Room Total Heat


= ERSH + ERLH

ESHF = Effective Sensible Heat Factor = ERSH / ERTH


AIR VOLUME CALCULATIONS
Dehumidified Supply Air Volume m3/s
= ERSH / Specific Heat 1.02 kj/kgoC X (RoomoC DB - ADPoC DB) X Density kg/m3
Psychrometric
Calculation
Example
Roof Solar & Transmission Sensible Gain to Ceiling Void

Occupants Gain Light


PERIMETER Sensible & Latent SensibleGain
ZONE Ceiling
CIRCULATION SensibleGain To Room
ZONE To Room
INTERIOR
Floor ZONE
Miscellaneous Equipment Sensible Gain
Sensible Gain To Room

Floor Transmission Sensible Gain


Wall Solar & Transmission Sensible Gain
to Ceiling Void
Glass Solar & Transmission Sensible Gain
to Room
PERIMETER CIRCULATION INTERIOR
Infiltration Gain - Sensible & Latent ZONE ZONE ZONE
to Room

Wall Solar & Transmission Sensible Gain


to Room
BUILDING COOLING LOADS ASSOCIATED WITH AIR HANDLING UNIT No 1
Load peaks at 9am July when outside air condition is 21oC DB, 19oC WB

ROOM COOLING LOADS AIR CONDITIONING SYSTEM


SENSIBLE HEAT GAINS RSH SYSTEM SENSIBLE HEAT GAINS SSH
1. Conduction Heat Gains: 5. Supply air fan and motor. = 28.59kW
walls, roof, ceiling, floor. 6. Supply air duct gain. = 23.53kW
2. Solar Heat Gains- 7. Supply air duct leakage to areas
windows, Walls,Roof. other than the air conditioned space. = 0
3. Heat gains from lighting
load to space. 8. Heat gain from lights to the return air
4. Miscellaneous equipment: plenum via the ceiling void. = 27kW
computers, printers etc.
5. Occupants 9. Minimum Outside Air Volume =4.84m3/s
Total= 329.45kW Heat gain from minimum outside air OASH.
Infiltration Gain= -5.079kW To be calculated using Psychrometric data.
Total Space Gains= 325kW
10. Return air fan and motor. = 10kW
LATENT HEAT GAINS RLH
3. Occupants= 31.9kW Total = 89kW
4. Infiltration= 11.64kW
Total = 44kW SYSTEM LATENT HEAT GAINS SLH
10. Cooling required to offset supply air
duct leakage to areas other than the
air conditioned space. =0
11. Heat gain from minimum outside air OALH.
To be calculated using Psychrometric data.
SYSTEM DESIGN CONDITIONS

Outside Air Summer = 21oC DB, 19oC WB

Outside Air Winter = - 4oC DB, 50% RH

Room Summer = 23oC DB, 60% RH

Room Winter = 21oC DB, 50% RH

Night set back room temperature winter = 10oC DB


A SYSTEM DESIGN CONDITIONS

B
20

Outside Air
21oC DB, 19oC WB
A

C
o
re
tu
ra
pe
m
Te

15
B
W

B Room 23oC DB, 60% RH

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
MINIMUM OUTSIDE AIR
Minimum Outside Air = 4.84m3/s

Outside Air Total Heat (OATH)


= OA air volume X (OA enthalpy - Room enthalpy) X OA density
The data in blue italics can be derived from the Psychrometric chart or from tables

= OA m3/s X (OA kj/kg - Room kj/kg) X OA kg/m3


= 4.84 X (54 - 50) X 1.19 = 23kW

Outside Air Sensible Heat (OASH)


= OA air volume X specific heat X density X (OADB oC - Room DB oC)
= OA m3/s X kj/kg oC X kg/m3 X (OADB oC - Room DB oC)
= 4.84 X 1.02 X 1.16 X (21 - 23) = -11kW

Outside Air Latent Heat (OALH)


= OATH - OASH = 23 - -11 = 34kW
EFFECTIVE ROOM SENSIBLE HEAT FACTOR

Effective Room Sensible Heat (ERSH)


= RSH + (Bypass factor BF X OASH) + SSH
BF assume cooling coil is 10% efficient = 0.1
= 325 + (0.1 X -11) + 89 = 413kW

Effective Room Latent Heat (ERLH)


= RLH + (Bypass factor BF X OALH) + SLH
= 44 + (0.1 X 34) + 0 = 47kW

Effective Room Total Heat (ERTH)


= ERSH + ERLH = 413 + 47 = 460kW

Effective Room Sensible Heat Factor


= ERSH/ERTH = 413/460 = 0.9
SENSIBLE HEAT FACTOR (ESHF, GSHF, RSHF) LINES

1.) Calculate SHF.

2.) Plot line through SHF ratio and plotting point.

3.) Plot line parallel to item 2.)


through point of room condition.

Room Condition

SHF

SHF Plotting Point


A EFFECTIVE ROOM
SENSIBLE HEAT FACTOR
B
ERSHF
20

Outside Air
21oC DB, 19oC WB
A

C
o
re
tu
ra
pe
m
Te

15
B
B
W

ESHF = 0.9 Room 23oC DB, 60% RH

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
APPARATUS DEWPOINT ADP

The ADP is at the point where the ESHF


intersects the Saturation Curve.

ADP = 14.2oC DB and WB


A APPARATUS DEWPOINT ADP

B
20

Outside Air
21oC DB, 19oC WB
A

C
o
re
tu
ra
pe
m
Te

15
B
B
W

ESHF = 0.9 Room 23oC DB, 60% RH


ADP = 14.2oC DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
GRAND SENSIBLE HEAT FACTOR

Total Sensible Heat (TSH)


= RSH + OASH + SSH = 325 + (-11) + 89 = 403kW

Total Latent Heat (TLH)


= RLH + OALH + SLH = 44 + 33 + 0 = 77kW

Grand Total Heat (GTH)


= TSH + TLH = 403 + 77 = 480kW

Grand Sensible Heat Factor

= TSH/GTH = 403/480 = 0.84


A GRAND SENSIBLE HEAT FACTOR
GSHF
B
20

Outside Air
21oC DB, 19oC WB
A

C
o
re
tu
ra
pe
m
Te

15
B

GSHF = 0.84
W

ESHF = 0.9 B Room 23oC DB, 60% RH


o
ADP = 14.2 C DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
SUPPLY AIR VOLUME

Supply Air Volume m3/s

= ERSH/Specific Heat X (Room oC DB - ADP oC DB) X Supply Air Density*

= 413kW/ 1.02kj/kgoC X (23 - 14.2) x 1.215kg/m3

Supply Air Volume = 38 m3/s


RETURN AIR SYSTEM GAINS

Return Air System Heat Gain = (Return Air Fan + Lighting gain to return air)
= 10+27 = 37kW
Temperature rise due to return air system gain
= (Return air System gain) - divided by
Specific heat
X Supply Air Volume
X (1 - % pressurisation air remaining in the building)*
X Density of room air
= 37kW/ 1.02kj/kgoC X 38m3/s X (1- 0.1) X 1.19kg/m3 = 0.9oC

Recirculated Air = 23 + 0.9 = 24oC

* Assume that 10% of the total air remains in the space to pressurise the
building to offset some of the effects of infiltration and for makeup air to
toilet exhaust.
A D
F RETURN AIR SYSTEM GAIN
G

C B
20

Outside Air
21oC DB, 19oC WB
A

C
o
re
tu
ra
pe
m
Te

15
B

GSHF = 0.84
W

Recirculated Air Condition


ESHF = 0.9 B Room 23oC DB, 60% RH C
o
ADP = 14.2 C DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
A D
F MIXED AIR CONDITION
G

C B
20

Outside Air
21oC DB, 19oC WB
A

C
o
re
tu
ra
pe
m

Mixed Air Condition D


Te

15
GSHF = 0.84
B
W

Recirculated Air Condition


ESHF = 0.9 B Room 23oC DB, 60% RH C
o
ADP = 14.2 C DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
PERCENTAGE OUTSIDE AIR

The percentage of Minimum Outside Air to Supply Air Volume


= Minimum Outside Air Volume / Supply air Volume
= 4.84m3/s divided by 38m3/s

4.84/38 = 12.74%

Check the location of the mixed air condition


A D
F MIXED AIR CONDITION
G
CHECK
C B
20

Outside Air
21oC DB, 19oC WB
A

1 0 .2 6 %
o

87
re

0%
tu
ra
pe

Mixed Air Condition


m
Te

15
GSHF = 0.84 12.74%
B
W

Recirculated Air Condition


ESHF = 0.9
ADP = 14.2oC DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
BYPASS FACTOR BF

Due to the cooling coil inefficiency assume that


the air bypassing the coil is 10% of the total air
A D
F BYPASS FACTOR BF
G

C B
20

Outside Air
21oC DB, 19oC WB

o
C
re
tu
A

ra
pe
BF Bypass Factor
m
10% of length of GSHF Te
B
W

Mixed Air Condition D


15
F GSHF = 0.84
Recirculated Air Condition
ESHF = 0.9 B Room 23oC DB, 60% RH C
ADP = 14.2oC DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
COOLING COIL

D Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB

F Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB


ROOM SENSIBLE HEAT FACTOR RSHF

Room Sensible Heat RSH = 325kW

Room Latent Heat RLH = 44kW

Room Total Heat RTH = 325 + 44 = 369kW

Room Sensible Heat Factor = 325/369 = 0.88

RSHF = 0.88
A D
F ROOM SENSIBLE HEAT FACTOR
G
RSHF
C B
20

Outside Air A
21oC DB, 19oC WB

o
C
re
tu
ra
pe
BF Bypass Factor
m
10% of length of GSHF Te
B
W

Mixed Air Condition D


15
ESHF = 0.9 GSHF = 0.88
F Recirculated Air Condition
Room 23oC DB, 60% RH C
RSHF = 0.88 B
ADP = 14.2oC DB and WB

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System

Tech Brian Fossey 03/99


All rights Reserved
Copyright 1999 by York International Inc.
SUPPLY AIR SYSTEM GAINS
SYSTEM SENSIBLE HEAT GAINS SSH
Supply air fan and motor.
Supply air duct heat gain.
Cooling required to offset supply air
duct leakage to areas other than the
air conditioned space.
SSH = 28.59 + 23.53 = 52kW
Temperature rise due to SUPPLY air system gain

= Supply air System gain


divided by
Density of supply air X
Specific heat X Supply Air Volume

= 52kW
1.215kg/m3 X 1.02kj/kgoC X 38m3/s
= 1.1oC
Final Supply Air condition = 15.5 + 1.1 = 16.6oC DB
A D
F SUPPLY AIR HEAT GAIN
G

C B
20

Outside Air A
21oC DB, 19oC WB

o
C
re
tu
ra
Coil Leaving

pe
BF Bypass Factor
m
Condition
10% of length of GSHF Te
Mixed Air Condition
B
W

ESHF = 0.9
15 GSHF = 0.88 Mixed Air Condition D
(Coil Entering Condition)
B Recirculated Air Condition
ADP = 14.2oC DB and WB F RSHF = 0.89
Room 23oC DB, 60% RH
Supply Air Condition G

10

10 15 20 25 30
Dry Bulb Temperature oC

YORK Production System


All rights Reserved
Brian Fossey 03/99
Copyright 1999 by York International Inc.
SUMMARY - AIR HANDLING UNIT SUMMER CONDITIONS

FANS

Supply Fan Air Volume = 38m3/s

Return Air Fan Air Volume = 38 X 0.9* = 34.2m3/s


* 10% air remains in the air conditioned space to offset
toilet exhaust and for pressurisation against infiltration.

Supply Air condition = 16.6oC DB, 15.2oC WB

COOLING COIL

Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB

Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB


WINTER MIXED AIR CONDITION

Outside Air DB oC = - 4

Recirculated Air DB oC = 21 + 1(Return Air Gain) = 22

Minimum Outside Air = 12.74%

0.1274 X - 4 = -0.51
0.8726 X 22 = 19.2
Mixed Air DB oC = 18.69
A F STEAM HUMIDIFIER
D G

C 20
B

Increase Moisture Content by 15 Room Winter B


0.0025kg/kg 21oC DB, 50% RH
Recirculated
Air Condition C
oC RSHF = 0.89
tu re
ra 10 G
e
e mp F
T Mixed Air Condition
B Steam
W with minimum Outside Air
5 Humidifier
D
Increased Outside Air Volume D
0

-5

Outside Air Winter

-5 0 5 10 15 20 25
Dry Bulb Temperature oC
A F SPRAY HUMIDIFIER
D G

C 20
B

Increase Moisture Content by 15 Room Winter B


0.0015kg/kg 21oC DB, 50% RH
Recirculated
Air Condition C
oC RSHF = 0.89
tu re
ra 10 G
e
e mp F
T Mixed Air Condition
B Spray
W with minimum Outside Air
5 Humidifier
D
0 Increased Outside Air Volume D

-5

Outside Air Winter

-5 0 5 10 15 20 25
Dry Bulb Temperature oC
HUMIDIFIER SIZING

STEAM HUMIDIFIER

Increase moisture content by 0.0025kg/kg

Density = 1.24 kg/m3


Steam Volume = 38m3/s X 3600 (m3/hour) X 0.0025kg/kg X 1.24kg/m3
= 424kg/Hour

SPRAY HUMIDIFIER
Increase moisture content by 0.0015kg/kg

Density = 1.24 kg/m3


A F STEAM HUMIDIFIER
D G WITH PREHEAT
C 20
B

Increase Moisture Content by 15 Room Winter B


0.0025kg/kg 21oC DB, 50% RH
Recirculated
Air Condition C
oC RSHF = 0.89
tu re
ra 10 G
e
e mp F
T
B Steam
W
5 Humidifier
D Mixed Air Condition D
with high percentage
of minimum0 Outside Air

-5 Preheater

Outside Air Winter

-5 0 5 10 15 20 25
Dry Bulb Temperature oC
A F SPRAY HUMIDIFIER
D G WITH PREHEAT
C 20
B

Increase Moisture Content by 15 Room Winter B


0.0015kg/kg 21oC DB, 50% RH
Recirculated
Air Condition C
oC RSHF = 0.89
tu re
ra 10 G
e
e mp F
T
B Spray
W
5 Humidifier

0 Preheater
-5 Mixed Air Condition
with high percentage of D
Outside Air Winter minimum Outside Air

-5 0 5 10 15 20 25
Dry Bulb Temperature oC
A F G H REHEAT
D

C 20
B

Increase Moisture Content by 15 Room Winter B


0.0015kg/kg 21oC DB, 50% RH
Recirculated
Air Condition C
oC RSHF = 0.89
tu re
ra 10 G
e
e mp F
B
T Reheater
W Spray
5 Humidifier H

0 Preheater
-5 Mixed Air Condition
with minimum Outside Air D
Outside Air Winter

-5 0 5 10 15 20 25
Dry Bulb Temperature oC