PAXT-C
Drawing No. LP0406
Revised 3/01
Tel +1 (717) 767-6511
Fax +1 (717) 764-6587
www.redlion-controls.com
GENERAL DESCRIPTION
The PAXT (PAX Temperature Meter) offers many features and performance A linear DC output signal is available as a Plug-in card. The card provides
capabilities to suit a wide range of industrial applications. The meter employs either 20 mA or 10 V signals. The output can be scaled independent of the input
advanced technology for stable, drift free readout, while incorporating features range. The features of the linear output cards are:
that provide flexibility now and in the future with plug-in option cards. The - Output tracks either input, totalizer, max or min readings
plug-in card options allow the opportunity to configure the meter for present - Programmable output update times
applications, while providing easy upgrades for future needs. Once the meter has been initially configured, the parameter list may be
The PAXT Temperature meter accepts inputs from a variety of thermocouple locked out from further modification in its entirety or only the setpoint values
and RTD inputs, including 10 ohm copper and 120 ohm nickel, while can be made accessible.
conforming to the standards of ITS-90. The meter can be programmed to accept The meter has been specifically designed for harsh industrial environments.
custom and non-standard thermocouple and RTD elements, via a 16-point With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
custom scaling feature. requirements, the meter provides a tough yet reliable application solution.
The meter provides a Max and Min reading memory with programmable
capture time. The capture time is used to prevent detection of false max and min SAFETY SUMMARY
readings which may occur during start-up or unusual process events. All safety related regulations, local codes and instructions that appear in this
The signal totalizer (integrator) can be used to compute a time-temperature literature or on equipment must be observed to ensure personal safety and to
product. This can be used to provide a readout of temperature integration, useful prevent damage to either the instrument or equipment connected to it. If
in curing and sterilization applications. equipment is used in a manner not specified by the manufacturer, the protection
The meter has four setpoint outputs, implemented on Plug-in cards. The provided by the equipment may be impaired.
Plug-in cards provide dual FORM-C relays (5 A), quad FORM-A relays (3 A) Do not use this unit to directly command motors, valves, or other actuators
or either quad sinking or quad sourcing open collector logic outputs. The not equipped with safeguards. To do so can be potentially harmful to persons or
setpoint alarms can be configured in modes to suit a variety of control and alarm equipment in the event of a fault to the unit.
requirements.
Plug-in cards also facilitate bus communications. These include RS232,
RS485 and MODBUS. Readout values and setpoint alarm values can be
controlled through the bus. Additionally, the meter has features that allow a
remote computer to directly control the outputs of the meter. With a
CAUTION: Read complete CAUTION: Risk of electric shock.
communication card installed, it is possible to configure the meter using a instructions prior to installation
Windows based program. The configuration data can be saved to a file for later and operation of the unit.
recall.
1
SPECIFICATIONS ** The accuracy over the interval -270 to -200°C is a function of temperature,
1. DISPLAY: 5 digit, 0.56" (14.2 mm) red LED, (-19999 to 99999) ranging from 1°C at -200°C and degrading to 7°C at -270°C. Accuracy may be
2. POWER: improved by field calibrating the meter readout at the temperature of interest.
AC Versions (PAXT0000): *** These curves have been corrected to ITS-90.
AC Power: 85 to 250 VAC, 50/60 Hz, 15 VA 10. RTD INPUTS:
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working) Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
DC Versions (PAXT0010): Excitation current: 100 ohm range: 165 µA
DC Power: 11 to 36 VDC, 11 W 10 ohm range: 2.6 mA
(derate operating temperature to 40° C if operating <15 VDC and three Lead resistance: 100 ohm range: 10 ohm/lead max.
plug-in cards are installed) 10 ohm range: 3 ohms/lead max.
AC Power: 24 VAC,± 10%, 50/60 Hz, 15 VA Max. continuous overload: 30 V
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working). Accuracy* Accuracy* Standard
Input Type Range
3. ANNUNCIATORS: (18 to 28°°C) (0 to 50°°C) ***
2
MODBUS Card: Rating: Internal supply: 24 VDC ± 10% , 30 mA max. total
Type: RS485; RTU and ASCII MODBUS Modules External supply: 30 VDC max., 100 mA max. each output
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. Response Time: 200 msec. typ., 700 msec. max. to within 99% of final output
Working Voltage: 50 V. Not Isolated from all other commons. value (digital filter disabled)
Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200 and 38400. 19. MEMORY: Nonvolatile E2Prom retains all programmable parameters and
Addresses: 1-247. display values.
Format: 7/8 bits, odd, even, and no parity 20. ENVIRONMENTAL CONDITIONS:
Transmit Delay: Programmable Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
17. ANALOG OUTPUT CARD: Field installable plug-in card cards installed)
Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 VDC Storage Temperature Range: -40 to 60°C
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. Operating and Storage Humidity: 0 to 85% max. non-condensing
Working Voltage: 50 V. Not Isolated from all other commons. Altitude: Up to 2000 meters
Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C) 21. CERTIFICATIONS AND COMPLIANCES:
Resolution: 1/3500 UL Recognized Component, File #E179259
Compliance: 10 VDC: 10 KΩ load min., 20 mA: 500 Ω load max. Recognized to U.S. and Canadian requirements under the Component
Response Time: 200 msec. typ., 700 msec. max. to within 99% of final output Recognition Program of Underwriters Laboratories, Inc.
value (digital filter disabled) SAFETY
18. SETPOINT OUTPUT CARD: Four types of field installable plug-in cards EN 61010-1, IEC 1010-1
Dual Relay Card: Safety requirements for electrical equipment for measurement, control,
Type: Two FORM-C relays and laboratory use, Part I
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min. ELECTROMAGNETIC COMPATIBILITY
Working Voltage: 240 Vrms Immunity to EN 50082-2
Contact Rating:
Electrostatic discharge EN 61000-4-2 Level 3; 8 Kv air
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 1
load), 1/8 HP @120 VAC, inductive load
80 MHz - 1 GHz
Total current with both relays energized not to exceed 5 amps
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Life Expectancy: 100 K cycles min. at full load rating. External RC
Level 3; 2 Kv power
snubber extends relay life for operation with inductive loads
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
Response Time: 200 msec. typ., 700 msec. max. to within 99% of final output
value (digital filter disabled) 150 KHz - 80 MHz
Quad Relay Card: Simulation of cordless telephones ENV 50204 Level 3; 10 V/m
Type: Four FORM-A relays 900 MHz ±5 MHz
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min. 200 Hz, 50% duty cycle
Working Voltage: 250 Vrms Emissions to EN 50081-2
Contact Rating: RF interference EN 55011 Enclosure class A
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load), Power mains class A
1/10 HP @120 VAC, inductive load Notes:
Total current with all four relays energized not to exceed 4 amps 1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Life Expectancy: 100K cycles min. at full load rating. External RC Measurement error less than 2% of full scale.
snubber extends relay life for operation with inductive loads For operation without loss of performance:
Response Time: 200 msec. typ., 700 msec. max. to within 99% of final output Mount unit in a metal enclosure (Buckeye SM7013-0 or equivalent)
value (digital filter disabled) Route power and I/O cables in metal conduit connected to earth
Quad Sinking Open Collector Card: ground.
Type: Four isolated sinking NPN transistors. 22. CONNECTIONS: High compression cage-clamp terminal block
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. Wire Strip Length: 0.3" (7.5 mm)
Working Voltage: 50 V. Not Isolated from all other commons. Wire Gauge Capacity: One 14 AWG (2.55 mm) solid, two 18 AWG (1.02
Rating: 100 mA max @ VSAT = 0.7 V max. VMAX = 30 V mm), or four 20 AWG (0.61 mm).
Response Time: 200 msec. typ., 700 msec. max. to within 99% of final output 23. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 indoor use.
value (digital filter disabled) IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
Quad Sourcing Open Collector Card: bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
Type: Four isolated sourcing PNP transistors. mounting clip included.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. 24. WEIGHT: 10.4 oz. (295 g)
Working Voltage: 50 V. Not Isolated from all other commons.
ORDERING INFORMATION
TYPE MODEL NO. DESCRIPTION PART NUMBERS
3
OPTIONAL PLUG-IN CARDS AND ACCESSORIES
The PAX series meters can be fitted with up to three optional plug-in cards.
However, only one card from each function type can be installed at a time. The
function types include Setpoint Alarms (PAXCDS), Communications
MODBUS PLUG-IN CARD (PAXCDC)
A MODBUS communication port can be installed with the MODBUS plug-
(PAXCDC), and Analog Output (PAXCDL). The cards can be installed initially
in card. The MODBUS card uses standard MODBUS protocol, which allows
or at a later date. Each optional plug-in card is shipped with complete
the integration of devices of different types and manufacturers within a common
installation and programming instructions.
communication framework.
SETPOINT ALARMS PLUG-IN CARDS (PAXCDS) ANALOG OUTPUT PLUG-IN CARD (PAXCDL)
The PAX series has four setpoint alarm output plug-in cards. Only one of
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available
these cards can be installed at a time. (Logic state of the outputs can be reversed
from the analog output plug-in card. The programmable output low and high
in the programming.) These plug-in cards include:
scaling can be based on the input max, min, or total display value. Reverse
Dual relay, FORM-C, Normally open & closed
acting output is possible by reversing the scaling point positions.
Quad relay, FORM-A, Normally open only
Isolated quad sinking NPN open collector
Isolated quad sourcing PNP open collector UNITS LABEL KIT (PAXLBK)
Each meter comes with °F and °C overlay labels which can be installed into
the meter’s bezel display assembly. The backlight for the labels is controlled in
SERIAL RS485 PLUG-IN CARD (PAXCDC) the programming. Additional custom units are available in the Units Label Kit.
An RS485 communication port can be installed with the serial RS485 plug-
in card. The RS485 option allows the connection of up to 32 meters or other
devices (such as a printer, PLC, HMI, or a host computer) on a single pair of PC SOFTWARE (SFPAX)
wires not longer than 4,000 feet. The address number of each meter on the line The SFPAX is a Windows based program that allows configuring of the PAX
can be programmed from 0-99. Data from the meter(s) can be interrogated or meter from a PC. Using SFPAX makes it easier to program the PAX meter and
changed and alarm outputs can be reset by sending the proper command string. allows saving the PAX program in a PC file for future use. On-line help is
The function keys and user inputs can be programmed to send data to a printer available within the software. A PAX serial plug-in card is required to program
or other device via serial communications. the meter using the software.
PANEL CUT-OUT
4
2.0 SETTING THE JUMPERS
The meter has two jumpers that must be checked and / or changed prior to
applying power. The two jumpers are: RTD Input and User Input Logic. The
figure on the right is an enlargement of the jumper area below. RTD Input Jumper
To access the jumpers, remove the meter base from the meter case by firmly One jumper is used for RTD input ranges. Select the proper range to match
squeezing and pulling back on the side rear finger tabs. This should lower the the RTD probe being used. It is not necessary to remove this jumper when not
latch below the case slot (which is located just in front of the finger tabs). It is using RTD probes.
recommended to release the latch on one side, then start the other side latch.
Main
Circuit
Board JUMPER SELECTIONS
The indicates factory setting.
JUMPER JUMPER
LOCATION LOCATION
REAR TERMINALS
5
3.1 POWER WIRING
AC Power DC Power
Terminal 1: VAC Terminal 1: +VDC
Terminal 2: VAC Terminal 2: -VDC
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application,
the sensor input common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective
earth ground potential. If not, hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate
considerations must then be given to the potential of the user input common with respect to earth common; and the common of the
isolated plug-in cards with respect to input common.
6
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
7
5.1 MODULE 1 - Signal Input Parameters (4)1%@)
PARAMETER MENU
'+!, " SELECTION TYPE SELECTION TYPE ;17'" " -0- to 2=0- seconds
! '()*
tc-t
'(),
T TC
E TC
'()(
Pt385
C TC
RTD platinum 385
! 40-
'()* J TC Pt392 RTD platinum 392 The input filter setting is a time constant expressed in tenths of a second. The
filter settles to 99% of the final display value within approximately 3 time
'()8 K TC ni672 RTD nickel 672
constants. This is an Adaptive Digital Filter which is designed to steady the
'()" R TC Cu427 RTD copper 10 Ω
Input Display reading. A value of ‘0’ disables filtering.
'()3 S TC /3)'( Custom TC
'()9 B TC CS-rH Custom RTD High
FILTER BAND*
'()6 N TC /3)"7 Cutom RTD Low
Select the input type that corresponds to the input sensor. For RTD types,
9<%. " - to 2=- degrees
check the RTD Input Jumper for matching selection. For custom types, the
Temperature Scale parameter is not available, the Display Decimal Point is
! 4-
expanded, and Custom Sensor Scaling must be completed. The digital filter will adapt to variations in the input signal. When the
variation exceeds the input filter band value, the digital filter disengages. When
the variation becomes less than the band value, the filter engages again. This
TEMPERATURE SCALE allows for a stable readout, but permits the display to settle rapidly after a large
3/<7, " °F °C
process change. The value of the band is in display units, independent of the
Display Decimal Point position. A band setting of ‘0’ keeps the digital filter
! :; permanently engaged.
Select the temperature scale. This selection applies to for Input, MAX, MIN,
and TOT displays. This does not change the user installed Custom Units The following parameters only apply to Custom Sensor Scaling.
Overlay display. If changed, those parameters that relate to the temperature
scale should be checked. This selection is not available for custom sensor types. ICE POINT SLOPE
1/, " - to >=-0-- µV/°C
DISPLAY DECIMAL POINT
! -0--
.,/!' " 0 0.0 0.00 0.000 0.0000 This parameter sets the slope value for ice point compensation for the
8
INPUT VALUE FOR SCALING POINT 1 DISPLAY VALUE FOR SCALING POINT 2
1%! 4 " )4???? to 4???? .3! 2 " )4???? to 4????
! 40--- Enter the known second Input Value by using the arrow
keys. ! 4--- Enter the second coordinating Display Value by using the
arrow keys. (Follow the same procedure, if using more than
Do not exceed the listed limits for the selected custom range. 2 scaling points.)
PARAMETER MENU
9
HOLD DISPLAY RESET, SELECT, ENABLE MAXIMUM DISPLAY
When activated (momentary action), the Maximum
B3")4 " The shown display is held but all other meter functions
continue as long as activated (maintained action).
B3")4 " value resets to the present Input Display value. The
! .)E7. ! ")E1 Maximum continues from that value while active
(maintained action). When the user input is released, the
Maximum stops and holds its value. This selection
HOLD ALL FUNCTIONS functions independent of the selected display. The DSP
key overrides the display activated by the user input, but
B3")4 " The meter disables processing the input, holds all display
contents, and locks the state of all outputs as long as
not the Maximum function.
The Input Display value is one time added (batched) to the Totalizer at RESET, SELECT, ENABLE MINIMUM DISPLAY
transition to activate (momentary action). The Totalizer retains a running sum
of each batch operation until the Totalizer is reset. When this function is
selected, the normal operation of the Totalizer is overridden.
B3")4 " When activated (momentary action), the Minimum value
resets to the present Input Display value. The Minimum
! ")7# continues from that value while active (maintained action).
When the user input is released, the Minimum stops and
SELECT TOTALIZER DISPLAY holds its value. This selection functions independent of the
B3")4 " The Totalizer display is selected as long as activated
(maintained action). When the user input is released, the
selected display. The DSP key overrides the display
activated by the user input, but not the Minimun function.
! .)'#' Input Display is returned. The DSP key overrides the active
user input. The Totalizer continues to function including RESET MAXIMUM AND MINIMUM
associated outputs independent of being displayed.
B3")4 " ;4 "
RESET TOTALIZER
! ")E7 ! ")E7
B3")4 " ;4 " When activated (momentary action), ",3,' flashes and the Maximum and
! "'#'4 ! ")'#' Minimum resets to the present Input Display value. The Maximum and
Minimum function then continues from that value. This selection functions
When activated (momentary action), ",3,' flashes and the Totalizer resets independent of the selected display.
to zero. The Totalizer then continues to operate as it is configured. This
selection functions independent of the selected display.
SETPOINT SELECTIONS
The following selections are accessible only with the Setpoint plug-in card
RESET AND ENABLE TOTALIZER installed. Refer to the Setpoint Card Bulletin shipped with the Setpoint Plug-in
card, for explanation of their operation.
B3")4 " When activated (momentary action), ",3,' flashes and
the Totalizer resets to zero. The Totalizer continues to 713' - Select main or alternate setpoints
! "'#'2 operate as it is configured while active (maintained action). ")4 - Reset Setpoint 1 (Alarm 1)
When the user input is released, the Totalizer stops and Setpoint ")2 - Reset Setpoint 2 (Alarm 2)
holds its value. This selection functions independent of the ")A - Reset Setpoint 3 (Alarm 3)
selected display. Card ")H - Reset Setpoint 4 (Alarm 4)
Only ")AH - Reset Setpoint 34 (Alarm 34)
ENABLE TOTALIZER ")2AH - Reset Setpoint 234 (Alarm 234)
")<77 - Reset Setpoint All (Alarm All)
B3")4 " The Totalizer continues to operate as long as activated
(maintained action). When the user input is released, the
! ,)'#' Totalizer stops and holds its value. This selection functions
independent of the selected display. PRINT REQUEST
SELECT MAXIMUM DISPLAY B3")4 " ;4 "
B3")4 " The Maximum display is selected as long as activated
(maintained action). When the user input is released, the ! !"G6' ! !"G6'
! .)E1 Input Display returns. The DSP key overrides the active
user input. The Maximum continues to function
The meter issues a block print through the serial port when activated. The
data transmitted during a print request is programmed in Module 7. If the user
independent of being displayed. input is still active after the transmission is complete (about 100 msec), an
additional transmission occurs. As long as the user input is held active,
RESET MAXIMUM continuous transmissions occur.
When activated (momentary action), ",3,' flashes
and the Maximum resets to the present Input Display ;4 "
value. The Maximum function then continues from that
value. This selection functions independent of the
! ")E1
selected display.
10
5.3 MODULE 3 - Display and Program Lock-out
Parameters (A)7&/)
PARAMETER MENU
These displays can be programmed for 7&/ or ",.. When programmed for PROGRAM MODE SECURITY CODE*
7&/, the display will not be shown when the DSP key is pressed regardless of
Program Lock-out status. It is suggested to lock-out the display if it is not
needed. The associated function will continue to operate even if its display is
/#., " - to 2=-
locked-out. ! -
SP-1 SP-2 SP-3 SP-4 SETPOINT ACCESS* By entering any non-zero value, the prompt /#., - will appear when trying
to access the Program Mode. Access will only be allowed after entering a
3!)4 " 3!)2 " 3!)A " 3!)H " matching security code or universal code of 222. With this lock-out, a user input
would not have to be configured for Program Lock-out. However, this lock-out
! 7&/ ! 7&/ ! 7&/ ! 7&/ is overridden by an inactive user input configured for Program Lock-out.
The setpoint displays can be programmed for 7&/, ",. or ,6' (See * Factory Setting can be used without affecting basic start-up.
following table). Accessible only with the Setpoint plug-in card installed.
PARAMETER MENU
11
5.5 MODULE 5 - Totalizer (Integrator) Parameters (=)'#')
PARAMETER MENU
The signal totalizer (integrator) can be used to compute a time-temperature TOTALIZER HIGH ORDER DISPLAY
product. This can be used to provide a readout of temperature integration, When the total exceeds 5 digits, the front panel annunicator TOT flashes. In
useful in curing and sterilization applications. The second is through a user this case, the meter continues to totalize up to a 9 digit value. The high order 4
input or function key programmed for Batch (one time add on demand). If the digits and the low order 5 digits of the total are displayed alternately. The letter
Totalizer is not needed, its display can be locked-out and this module can be “J” denotes the high order display.
skipped during programming.
TOTALIZER BATCHING
The Totalizer Time Base and scale factor are overridden when a user input or
TOTALIZER DECIMAL POINT* function key is programmed for store batch (9<'). In this mode, when the user
.,/!' " 0 0.0 0.00 0.000 0.0000
input or function key is activated, the Input Display reading is one time added
to the Totalizer (batch). The Totalizer retains a running sum of each batch
! -0-- operation until the Totalizer is reset. This is useful in weighting operations,
when the value to be added is not based on time but after a filling event.
For most applications, this matches the Input Display Decimal Point
(.,/!'). If a different location is desired, refer to Totalizer Scale Factor. TOTALIZER USING TIME BASE
Totalizer accumulates as defined by:
TOTALIZER TIME BASE
Input Display x Totalizer Scale Factor
'9KC, " C,/ - seconds (÷ 1) J#5" - hours (÷ 3600) Totalizer Time Base
! 40--- by the 4 hours in the controlled time frame to yield a Totalizer Scale Factor
of 0.250. By placing these values in the equation, the Totalizer will
For most applications, the Totalizer reflects the same decimal point location accumulate every second as follows:
and engineering units as the Input Display. In these cases, the Totalizer Scale
Factor is 1.000. The Totalizer Scale Factor can be used to scale the Totalizer to 10.0 x 0.250 =0.00069 accumulates each second
a different value than the Input Display. Common possibilities are: 3600
1. Changing decimal point location (example tenths to whole) This results in:
2. Average over a controlled time frame. 0.04167 accumulates each minute
Details on calculating the scale factor are shown later. 2.5 accumulates each hour
If the Totalizer is being accumulated through a user input programmed for 10.0 reached at the end of 4 hours
Batch, then this parameter does not apply.
TOTALIZER SCALE FACTOR CALCULATION EXAMPLES
1. When changing the Totalizer Decimal Point (.,/!') location from the
TOTALIZER LOW CUT VALUE*
Input Display Decimal Point (.,/!'), the required Totalizer Scale Factor is
7#(5' " )4???? to ?????
multiplied by a power of ten.
Example: Input (.,/!')=0.0 Input (.,/!')= 0.00
! )4??0?? Totalizer Scale Totalizer Scale
A low cut value disables Totalizer when the Input Display value falls below .,/!' Factor .,/!' Factor
12
Modules 6, 7, and 8 are accessible only with the appropriate plug-in cards installed. A quick overview of each Module is
listed below. Refer to the corresponding plug-in card bulletin for a more detailed explanation of each parameter selection.
3!3,7 - SELECT SETPOINT NO SP-1 SP-3 '&%)6 - ON TIME DELAY 0.0 to 3275.0 sec
SP-2 SP-4 '&;)6 - OFF TIME DELAY 0.0 to 3275.0 sec
<(')6 - SETPOINT ACTION OFF dE-HI #5')6 - OUTPUT LOGIC nor rEv
Ab-HI dE-LO "3')6 - RESET ACTION AUto LAtC2
Ab-LO bANd LAtC1
AU-HI totLo 3'9)6 - STANDBY OPERATION NO YES
AU-LO totHI 71')6 - SETPOINT ANNUNCIATORS OFF rEv
3!)6 - SETPOINT VALUE -19999 to 99999 nor FLASH
EF3)6 - SETPOINT HYSTERESIS 1 to 65000 9"6)6 - PROBE BURN-OUT ACTION ON OFF
'F!, - ANALOG TYPE 0-20 0-10 <%)7& - ANALOG LOW SCALE VALUE -19999 to 99999
4-20 K%)E1 - ANALOG HIGH SCALE VALUE -19999 to 99999
KC1% - ANALOG ASSIGNMENT INP LO 5.' - ANALOG UPDATE TIME 0.0 to 10.0 sec.
HI tot 95"6 - PROBE BURN-OUT ACTION HI LO
13
5.9 MODULE 9 - Factory Service Operations (?);/3)
PARAMETER MENU CALIBRATION
/#., " The meter has been fully calibrated at the factory. If
the meter appears to be indicating incorrectly or
! HM inaccurately, refer to Troubleshooting before attempting
to calibrate the meter. When recalibration is required
(generally every 2 years), it should only be performed
by qualified technicians using appropriate equipment.
Calibration may be aborted by disconnecting power to the meter before
exiting Module 9. In this case, the existing calibration settings remain in effect.
press PAR.
-0-L 0.00 Adjust if necessary, press PAR
2. At -0- L, apply a dead short or set calibrator to zero to input terminals 4 and 4-0-L 10.00 Adjust if necessary, press PAR
5. Wait 10 seconds, then press PAR. 4. When %& appears remove the external meters and press PAR twice.
3. At =-0- L, apply 50.000 mV input signal (with an accuracy of 0.01% or
better) to input terminals 4 and 5. Wait 10 seconds, then press PAR. RESTORE FACTORY DEFAULTS
4. Return to the Display Mode.
5. Continue with Ice Point Calibration. /#., " Use the arrow keys to display /#., >> and press PAR.
The meter will display ",3,' and then return to /#., =-.
! >> Press DSP key to return to Display Mode. This will
overwrite all user settings with the factory settings.
TROUBLESHOOTING
PROBLEM REMEDIES
NO DISPLAY CHECK: Power level, power connections
CHECK: Active (lock-out) user input
PROGRAM LOCKED-OUT
ENTER: Security code requested
MAX, MIN, TOT LOCKED-OUT CHECK: Module 3 programming
CHECK: Module 1 programming, RTD Input Jumper position, input connections, input signal level,
INCORRECT INPUT DISPLAY VALUE Display Offset is zero, DSP is on Input Display
PERFORM: Calibration (If the above does not correct the problem.)
“OLOL” in DISPLAY (SIGNAL LOW) CHECK: Module 1 programming, RTD Input Jumper position, input connections, input signal level
“ULUL” in DISPLAY (SIGNAL HIGH) CHECK: Module 1 programming, RTD Input Jumper position, input connections, input signal level
INCREASE: Module 1 filtering, rounding, input range
JITTERY DISPLAY
CHECK: Wiring is per EMC installation guidelines
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding plug-in card installation
ERROR CODE (Err 1-4) PRESS: Reset KEY (If can not clear contact factory.)
For further assistance, contact technical support at the appropriate company numbers listed.
14
PARAMETER VALUE CHART Programmer ________________ Date _________
PAXT RTD and Thermocouple meter Meter# __________ Security Code _________
1-INP Signal Input Parameters 3-LOC Display and Program Lockout Parameters
FACTORY FACTORY
DISPLAY PARAMETER USER SETTING DISPLAY PARAMETER USER SETTING
SETTING SETTING
tyPE INPUT TYPE tc-J HI MAX DISPLAY LOCKOUT rEd
SCALE TEMPERATURE SCALE °F LO MIN DISPLAY LOCKOUT rEd
dECPt DISPLAY RESOLUTION 0 tOt TOTAL DISPLAY LOCKOUT rEd
round DISPLAY ROUNDING INCREMENT 1 SP-1 SETPOINT 1 ACCESS LOC
oFFSt DISPLAY OFFSET 0 SP-2 SETPOINT 2 ACCESS LOC
FILtr FILTER SETTING 1.0 SP-3 SETPOINT 3 ACCESS LOC
bANd FILTER ENABLE BAND 10 SP-4 SETPOINT 4 ACCESS LOC
ICE ICE POINT SLOPE 0.00 CodE SECURITY CODE 0
PtS SCALING POINTS 2
INP 1 INPUT VALUE 1 0.000 4-SEC Secondary Function Parameters
dSP 1 DISPLAY VALUE 1 0
INP 2 INPUT VALUE 2 1.000 DISPLAY PARAMETER
FACTORY
SETTING
USER SETTING
dSP 2 DISPLAY VALUE 2 1000
INP 3 INPUT VALUE 3 0.000 HI-t MAX CAPTURE DELAY TIME 0.0
dSP 3 DISPLAY VALUE 3 0 LO-t MIN CAPTURE DELAY TIME 0.0
INP 4 INPUT VALUE 4 0.000 dSP-t DISPLAY UPDATE TIME 2
dSP 4 DISPLAY VALUE 4 0 b-LIt UNITS LABEL BACKLIGHT ON
INP 5 INPUT VALUE 5 0.000 ICE ICE POINT COMPENSATION ON
dSP 5 DISPLAY VALUE 5 0
INP 6 INPUT VALUE 6 0.000 5-tOt Totalizer (Integrator) Parameters
dSP 6 DISPLAY VALUE 6 0 FACTORY
INP 7 INPUT VALUE 7 0.000 DISPLAY PARAMETER
SETTING
USER SETTING
16