Doc.

No
Rev. No.
Excess Flow Valves
Sheet No.
Date
Note
Line

Rev

Description Parameters

1 General Data
2 Item Excess Flow Valves
3 Service Liquid Petroleum Gas (LPG)
4 Equipment Number
5 Quantity
6 Valve
7 Model VTS
8 Size of Valves 3"
9 End Connections (Threaded , Double Flange , Wafer) Flanged (Note 1)
10 Class of Service 300#
11 Manufacturer
12 Service Condition
13 Media Liquid
14 Specific gravity of Media 0.53 - 0.57
15 Desired Closing Flow rate (GPM/SCFM) VTS
16 Normal Operating Flow Rate 500 GPM
17 Minimum Flow Rate
18 Inlet Pressre (PSIG) 154
19 Inlet Temperature Amb.
20 Direction of Valve Vertical
21 Line
22 Pipe Line Size 3"
23 Pipe Sch. Sch 40
24 Materilas
25 Body Carbon Steel
26 Internals Stainless Steel
27
Excess flow valve are protective devices to prevent the uncontrolled
28
Application of Valve release of hazardous materials from storage vessels. EFVs are designed to
29 close when the flow rate exceeds from the normal operating condition.
30

31 Notes
32 Note
33 1 Vendor may suggest any alternate details for installation / mounting of excess flow valves inside LPG bullets, suitable for its safe operation.
34 2 Vendor Should provide GA drawing and Thread details.
35