⚫ 1. Product Description
IPF48100 is an intelligent energy storage module developed by Narada based on the new lithium battery energy storage
module technology and mainly used in communication base stations. It has a rated voltage of 48V and a capacity of 100Ah, and
can connect up to 32 groups in parallel. The battery can automatically adapt to different charging voltages, fast charging, and has
a long service life. It can be directly used in parallel with a lead-acid battery pack to realize the expansion of existing network
batteries.
The BMS of the IPF48100 is divided into two parts, BMU and BDC. BMU (Battery Management Unit) realizes the voltage
and temperature monitoring of single cells, SOH/SOC calculation, operation logic strategy control, parameter setting, external
communication and other functions. BDC (Bidirectional Direct Current) is a bidirectional DC conversion circuit between the battery
pack and the main circuit of the communication backup power supply. It is used to perform functions such as battery constant
current, constant voltage charging and discharging, standby, and protection.

www.naradapower.com
Product Introduction
⚫ 1. 1 Technical index
Model IPF48100 Max Number of Parallel 32
Nominal Voltage 48V Max Parallel Power 48kW
Nominal Capacity 100Ah@0.2C ,25℃ 1) Charge current limit;
2) Adaptive battery
characteristic discharge mode;
Operating Mode 3) Intelligent lithium battery
Charging Voltage 54V priority discharge mode;
4)Set constant voltage
discharge mode
Max Charger/ Dimensions (width * depth
100A/100A 444*401*131mm
Discharge Current * height)
Continuous Charge
50A/50A Terminals M5
/Discharge current
Output voltage range 30~60V weight 40Kg
BDC Efficiency 98% Installation method 19 inch cabinet
Communication RJ45,Contain
Design life 12 years
Interface RS485/CAN*2

www.naradapower.com
Product Introduction
⚫ 1.2 Panel and interface

1
2 9
3
4

5 6 7 8
Interface description:
NO. Silk-screen Definition Description
1 DO-1 / DO-2 Dry contact output Alarm output Dry contact, configurable (default closed)
2 HALL GND Grounding
3 COM_IN Communication interface 1.For reporting information and communication cascades;
2. Use RJ48 terminal,satisfy 1000A surge protection capability.
4 COM_OUT Communication interface
RUN Running light
ALM Warning light
5 Detailed functions are shown in Table 1
CHG Charging light
DCH Discharging light
6 SOC SOC light
7 / Buzzer Manual power on and off, maintenance, belong to the contact button.
8 MANUAL ON/OFF Manual ON and OFF button www.naradapower.com
Manual ON or OFF、maintain,belongs to touch switch.
9 +/- Positive /Negative terminal The positive and negative wiring ports are fixed with M5 bolts.
Product Introduction

Communication
Interface
RJ45 Female connector

Communication interface pin definition:


RJ45引脚 Definition Description
1/3 RS485-A Used for communication and data transmission
between groups when batteries are connected in
2/4 RS485-B parallel, as well as communication with external
monitoring units.
5 485-GND Grounding
6 NC Empty pin
7 CAN-H CAN communication + Used for communication and data transmission
between groups when batteries are connected in
8 CAN-L CAN communication -
parallel, as well as communication with external
monitoring units.

www.naradapower.com
Product Introduction
⚫ Product Features:
◆ Parallel expansion and power expansion: N groups of parallel support maximum power ≤48kW, N is recommended
not to be greater than 32;
◆ Intelligent software anti-theft: communication anti-theft design reduces the risk of site battery theft;
◆ Long life: 4500 Cycles@0.5C, 80%DOD, 25℃;
◆ Easy operation and maintenance: Integrated BMS design, battery support self-management, real-time online
monitoring of battery capacity, SOC/SOH, etc., to improve the reliability of site backup power;
◆ Maintenance-free: IPF can be maintenance-free during use, which saves battery operation and maintenance testing
costs and reduces the frequency of site visits;
◆ Digital, intelligent, monitorable, controllable, life cycle operation information can be obtained and reported;

www.naradapower.com
Product Introduction
⚫ IPF48100 Function
◆ Status monitoring: Support single cell voltage, temperature and the entire set of voltage and current detection;
◆ Alarm management: Support single over/under voltage, whole group over/voltage, over current, high and low
temperature and other abnormal alarms;
◆ Abnormal protection: Support single over/under voltage, whole group over/under voltage, over current, high
and low temperature, short circuit, reverse connection, battery cell failure, BMS hardware failure, etc.;
◆ Information reporting: Provide northbound CAN/RS485 interface, upload alarm and status data through
CAN/RS485 interface;
◆ Anti-theft function: Cooperate with the communication protocol provided by Narada to realize the anti-theft
function of communication;
◆ Activation function: Supports three activation functions, PWR activation, power port activation, MANUAL
ON/OFF activation;

www.naradapower.com
Operating Mode
Operating Mode: IPF48100 can realize three usage modes, which can cover all backup power
scenarios after communication;

1. Self-managed constant voltage discharge mode 2. Set constant voltage discharge mode
3. Battery characteristic discharge mode
IPF48100 can follow the system power bus voltage, The lithium battery module communicates with
the switching power supply system. The lithium The lithium battery module outputs according
intelligently self-manage the constant voltage
battery module can be set to the constant voltage to the characteristic discharge curve of the
discharge output, and the constant voltage
discharge mode through the switching power battery. Parallel with lead-acid battery supports
discharge output range is 44V ~ 54V. The lithium
supply. The range of constant voltage discharge synchronous discharge.
battery module works in this mode, and it can be
connected in parallel with lead-acid batteries and can be set from 48V to 57V, and the output is
lithium iron phosphate batteries (including cascade constant voltage at the set value of the power
batteries) to achieve priority discharge of lithium supply;
batteries;
www.naradapower.com
Application scenario
⚫ IPF48100 Application scenario DC power
AC power Rectifier
distribution cabinet distribution cabinet

IPF48100 is used to supply power to the power system. DC OutPut

IPF batteries can be used alone, or can be mixed with lead-


AC/DC

acid batteries or different brands of lithium batteries for AC Input


AC/DC
- 48V DC

common backup.
AC/DC
Inside the IPF, BMS monitors the status of
temperature, current, voltage, etc., and provides protection
functions such as overvoltage, undervoltage, overcurrent,
short circuit, high and low temperature, and the
communication interface (CAN/RS485) reports battery
operating status and alarm information.

IPF48100 Lead-acid
battery

AC
DC Monitoring unit
Signal

www.naradapower.com
Application scenario
⚫ Site renovation
Construction of 5G sites on stock sites and maintenance and reconstruction of stock sites;
◆ Mixed use with other types of batteries;
◆ Mixed use of new and old;
◆ Flexible expansion

www.naradapower.com
Application scenario
⚫ Edge computing data center
◆ Flexible deployment, quickly build base station
◆ Intelligent maintenance, reducing manpower

www.naradapower.com
Application scenario
⚫ New base station
◆ High-density base stations, energy-saving and consumption-reduction requirements;
◆ Up to 32 groups are directly connected in parallel;
◆ Empowering "dual-carbon" work, meeting the needs of new energy access and integration of backup and storage;
Satisfy remote power supply

www.naradapower.com
Application scenario
Case1– Two 50Ah old lithium batteries mixed with one IPF48100 lithium
⚫ Nantong XX outdoor base station ⚫ Case description:
Intelligent lithium and ordinary lithium battery are used in parallel. Intelligent lithium
access to original system and adaptively follow bus-bar voltage to avoid impact.

Outdoor base station


Intelligent lithium discharge curve

➢ Two old 50Ah lithium manufactured in 2013s remains 50%SOH, after system accommodate
a new lithium module, the base station can work normally.
➢ The discharge current of battery basically coincides with the discharge current of bus-bar,
and the total voltage of battery also coincides with the bus-bar voltage. The self-adjustment
of discharge current timely following the fluctuation of load.
Application scenario
Case2--Lead acid mixed with IPF48100 lithium
⚫ C-RAN room in Nan-Tong city Lead acid
Lead acid
One of Chinese mobile roof base station was equipped with 2V500AH lead battery ( + Lithium
24pcs)exceed 5 years, and now expand one 48V100AH lithium module for parallel use.

500Ah 600Ah

100A discharge current

Hybrid discharge curve of intelligent lithium battery and lead acid battery
≈ 1hour ≈ 2.5 hours