Parallelvej 2
Sheikh Jaber Al Ahmed Al Sabah Causeway DK-2800 Kongens Lyngby
Denmark
Project
Tel +45 45 97 22 11
Calculation note - Mechanical systems Fax +45 45 97 22 12
www.cowi.dk
Table of Contents
1 Introduction 2
2 Ventilation 2
3 Dehumidification system 2
3.1 Conditions 3
3.2 Steel Girders 3
4 Water- and fire distribution systems 3
4.1 General 3
4.2 Kuwait City access area 4
4.3 KC Transition Island 4
4.4 Subiyah Transition Island 5
4.5 Pipelines 6
4.6 Water booster plants 7
5 Sewage System 7
5.1 Kuwait City access area: 7
5.2 KC Transition Island: 8
5.3 Subiyah Transition Island: 8
6 Drainage (Storm Water) 8
7 Access facilities 8
7.1 Loadings 8
Prepared EIS/JN
Checked
Approved
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC ABR
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 2/9
Calculation note - Mechanical systems
1 Introduction
This note summarise the preliminary calculations carried out for the mechanical
tender design.
• Ventilation systems
• Dehumidification systems
• Drainage systems
• Access facilities
2 Ventilation
Buildings
Bridges
Openings for fresh air.
3 Dehumidification system
The preliminary calculation for the dehumidification systems is based on the follow-
ing set of design data.
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 3/9
Calculation note - Mechanical systems
3.1 Conditions
Ambient conditions:
• Maximum air temperature +55°C
• Minimum air temperature -6°C
• Average air temperature +26°C
• Maximum air humidity 0,0639 kg water vapour/kg air
• Atmospheric air pressure 101.3 kPa
• Maximum internal air temperature +60°C
The ambient conditions are assumed to fluctuate within a 12 hour period as follows:
• Temperature: ±15 K
• Atmospheric air pressure: ±2.5 kPa
4.1 General
All following figures are based on preliminary calculation assumptions for the water
consumption and shall be verified according to national standards and code of prac-
tices.
• The consumption per person per day is estimated to be 100 litres.
• The consumption of water for buildings are including all sinks, toilets, flushing,
washing and fire fighting at same time
• The simultaneous flow is an estimate based on presumed water consumption
curve
• The consumption of water for Fire Stations is including filling up fire engine
etc
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 4/9
Calculation note - Mechanical systems
The fire hydrants shall be connected direct to the city municipally main water pipe
line.
Fire hydrant no 1 20
Fire hydrant no 2 20
Total 40
Fire Fighting system The consumption has been estimated for 2 nos. fire hydrants
simultaneous working.
The water reservoir tank net volume for domestic has been estimated for munici-
pally water of 1 day.
Q = 90 m3
Time for filling the reservoir tank has been estimated to 24 hours.
Q = 90 m3 x 1000/ 24h x 3600 = 1.04 l/s ⇒ Pipe dimension connecting the tank
with a nominal diameter of 40 mm.
peak full
l/sec m3 / day
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 5/9
Calculation note - Mechanical systems
peak full
l/sec m3 / day
The peak for fire hydrants input has been stipulated to 3.0 l/sec. About 24 hours fill-
ing up the reservoir tank for the consumption for fire fighting.
Fire fighting system. The consumption has been estimated for 2 nos. fire hydrants
simultaneous working in 2 hours in full stage.
The water reservoir tank net volume for fire fighting has been estimated to a fire
fighting hydrants consumption of 2 hours.
Q = 288 m3
The water reservoir tank net volume for domestic use water has been estimated to 1
day consumption.
Q = 200 m3
Time for filling the reservoir tanks have been estimated to 24 hours.
Q = (288 m3 +200 m3) x 1000/ 24h x 3600 = 5.65 l/s ⇒ Pipe dimension connecting
the tanks with a nominal diameter of 100 mm.
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 6/9
Calculation note - Mechanical systems
The peak for fire hydrants input has been stipulated to 3.0 l/sec. About 24 hours fill-
ing up the reservoir tank for the consumption for fire fighting.
Fire Fighting system. The consumption has been estimated for 2 nos. fire hydrants
simultaneous working in 2 hours in full stage.
The water reservoir tank net volume for fire fighting has been estimated to a fire
fighting hydrants consumption of 2 hours.
Q = 288 m3
The water reservoir tank net volume for domestic use has been estimated to 1 day
consumption.
Q = 200 m3
Time for filling the reservoir tanks have been estimated to 24 hours.
Q = (288 m3 +200 m3) x 1000/ 24h x 3600 = 5.65 l/s ⇒ Pipe dimension connecting
the tanks with a nominal diameter of 100 mm.
4.5 Pipelines
Pipeline in Shuwaik Bridge to KC Transition Island:
Q = 40 l/s +1.04 l/s+ 5.56l/s = 46.6 l/s ⇒ Pipe dimension of ø 200 mm.
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 7/9
Calculation note - Mechanical systems
Booster unit, sprinkler equipment, pressure head and flow = 8 barg, 12 l/sec
Booster unit, supply line to KC TI, pressure head and flow = 12 barg, 5.56 l/sec
Booster unit, sprinkler equipment, pressure head and flow = 8 barg, 12 l/sec
Booster units fire fighting, pressure head and flow = 8 barg, 40 l/sec
Booster unit, sprinkler equipment, pressure head and flow = 8 barg, 12 l/sec
Booster units fire fighting, pressure head and flow = 8 barg, 40 l/sec
5 Sewage System
Public buildings 10
Workshops and maintenance buildings 15
Life-saving service 5
Shops and restaurants 50
Recreational area and sport 40
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 8/9
Calculation note - Mechanical systems
Public buildings 20
Workshops and maintenance buildings 25
Life-saving service 10
Shops and restaurants 200
Recreational area and sport 100
Public buildings 20
Workshops and maintenance buildings 25
Life-saving service 10
Shops and restaurants 200
Recreational area and sport 100
The design storm frequency, or return period, has been selected according to the
importance of classification:
7 Access facilities
7.1 Loadings
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .
Sheikh Jaber Al Ahmed Al Sabah Causeway Project 9/9
Calculation note - Mechanical systems
P:\53229P\3_Pdoc\DATA\Design report and calculations\SJSC Causeway Kuwait Design Calculations\E&M\Kuwait causeway calculation note mech rev1.DOC .