General Description of Series

Part A General Description of Series

1 PIX-ROF

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 3 of 45


General Description of Series

Construction

The air insulated metal clad compartments of the circuit breakers and busbars are of non-magnetic CRCA/
Alu-zinc material construction.

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 4 of 45


General Description of Series

Operating Interface

Easy to operate

 Intuitive single line diagrams on the front door of each functional unit provide a clear description of the
cubicle components and power flows. This helps to optimize operations
 With the EasyPact EXE breaker, PIX RoF features direct access to an opening pushbutton on the front
door: this ensures better service continuity
 Voltage Presence Indicators (VPIS) are present on the front door of each functional unit: this can
instantly indicate voltage presence on a given cable!
 A floor rolling trolley provides quick and easy rack-in/rack-out operation for withdrawable devices

Busbar Connection

The air insulated busbar sections of copper/ aluminium make busbars are connected
through stud and bolts. Busbar joints are shrouded with soft PVC shrouds.

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 5 of 45


General Description of Series

Vacuum Circuit Breaker

A circuit breaker is a safety device enabling the switching and protection of electrical
distribution networks. It protects all components connected to the downstream
network by opening the circuit during a fault.

The withdrawable EasyPact EXE vacuum circuit breaker is mounted on an


integrated floor rolling trolley enabling easy handling.

EasyPact EXE vacuum circuit breaker is trolley mounted and horizontally


withdrawable type. Each phase is segregated by insulated barriers.

Cable Termination

Cable terminals are readily accessible from the rear and located at a convenient
connection height. In standard depth of panel 2R x 3C x 630 sq. mm. or 2R x 1C x
630 sq. mm/ Phase cable termination is possible. For additional cable runs,
extension chamber of 350mm/ 500mm are be considered.

Instrument Transformers

CTs, if any, are placed on the line side of the circuit breaker and are mounted in cable chamber. VTs can be
mounted on switchgear top or VCB or separate Line VT Panel based on requirement. The transformer ratio,
the accuracy class and the performance load are selected to suit the application requirements.

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 6 of 45


General Description of Series

Instrument Chamber or Low Voltage Cabinet

Operating Conditions and Standards


Normal operating conditions, according to the IEC International Standards listed below, for indoor
switchgear.

Ambient air temperature


 Less than or equal to 40 °C (other values available on request)
 Less than or equal to 35 °C on average over 24 hours
 Greater than or equal to – 5 °C

Altitude
 Less than or equal to 1000 m;
 Above 1000 m, a derating coefficient is applied (please contact us)

Atmosphere
 No dust, smoke or corrosive or inflammable gas and vapor, or salt

Humidity
 Average relative humidity over a 24-hour period ≤ 95%
 Average relative humidity over a 1-month period ≤ 90%
 Average vapor pressure over a 24-hour period ≤ 2.2 kPa
 Average vapor pressure over a 1-month period ≤ 1.8 kPa
Specific operating conditions (please contact us).

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 7 of 45


General Description of Series

Standards

The PIX RoF meets the following international standards:


 IEC 62271-1: High-voltage switchgear and controlgear: common specifications
 IEC 62271-200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up
to and including 52 kV
 IEC 62271-100: High-voltage switchgear and controlgear - Alternating current circuit breakers
 IEC 62271-103: High-voltage switchgear and controlgear - Switches for rated voltages above 1 kV up
to and including 52 kV
 IEC 62271-102: High-voltage switchgear and controlgear - Alternating current disconnectors and
earthing switches
 IEC 60255: Measuring relays and protection equipment - Common requirements
 IEC 61869-2: Instrument transformers - Current transformers
 IEC 61869-3: Instrument transformers - Inductive voltage transformers
 IEC 60044-8: Instrument transformers - Electronic current transformers

Typical Sectional View

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 8 of 45


Technical Part

1.3.4 11kV, 630A, 25kA CICO panel

Electrical Dimensions
Rated Voltage 12 kV
Rated Operating Voltage 11 kV
Rated Power Frequency Withstand Voltage 28 kV
Rated Lightning Impulse Withstand Voltage 75 kV
Rated Short-Time Withstand Current 25 kA
Rated Short-Circuit Duration 3s
Rated Peak Current 63 kA
Rated Current Busbar 800 A
Dimensions
End Panel Width Left 25 mm
End Panel Width Right 25 mm
Panel Depth max. 1650 mm
Total Width of Switch Board Section 1250 mm
Installation
Arrangement of Switchgear (Rear) Free-Standing
Minimum Ceiling Height 3200 mm
Minimum Clearance to Building Rear Wall 900 mm
Minimum Clearance Front 1500 mm
Minimum Clearance to Side Left 900 mm
Minimum Clearance to Side Right 900 mm
Degree of Protection
Degree of Protection IP 4X
Paint
Paint RAL 9003
Remark Characteristics
Heating Resistor In Breaker Compartment With
Heating Resistor In Cable Compartment With
Properties
Main Busbars Copper
Busbar Type Sleeved
IAC Classification AFLR
Degree of Protection Front Unit IP 4X
Earthing Switch Locks Electromagnetic Interlock
Internal Arc Fault Configuration 31.5kA for 1Sec
LV Cabinet Height 935 mm
Pressure Relief Attachment Deflector
Shrouds on Main Busbar With
Superior shunt Sleeved
Switchboards Standard
TemperatureasperIEC62271 45 °C
Earthing Switch Locks ES Open
Colour of Wiring Black

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 41 of 45


Technical Part

1.3.4.1 Outgoing Feeder (800A)


Quantity 1
Rated Operating Current Outgoing 800 A
Dimensions
Cubicle Width 600 mm
Cubicle Height 2500 mm
Cubicle Depth 1650 mm
Cubicle Depth with Rear VT Box 2150 mm
Properties
Cable clamping With
Cable Core Three Cores
Cables per Phase 1
CT1 Type GWP (Width:165mm)
Secondary Core(s) 1
CT Connection Type Sleeved
Cubicle Designation PIX-RoF
CT Connection Copper
Type of Cable Connection Bottom Cable Entry
Type of Gland Plate Split Type
Upper Busbar Copper
Voltage Indication System With
Voltage Transformer Attachment Withdrawable
Voltage Transformer Fuse With
VT Installed On Rear
Rear VT Inside Extension Box No
VT Quantity of Cores 2

Type of Construction
Current Transformer With
Earthing Switch Outgoing With
Primary Connection Cable
Truck Assembly EasyPactExe
Type of Cubicle Feeder
Voltage Transformer Outgoing With

Listing of Switching Devices


1 Vacuum Circuit Breaker

Drive 100-125V DC
Auxiliary Make Release 100 to 130 VDC - 100 to 130
VAC
1. Break Release 100 to 130 VDC - 100 to 130
VAC
1 Earthing Switch

3 Voltage Transformer with 2 nos. Secondary Winding


Make: ECS/NPT
Transformation-Ratio VT: 11/V3 / 0,11/V3 / 0,11/3 kV
VT-Winding 1: Accuracy Class 0,5 / 30 VA
VT-Winding 2: Accuracy Class 3P / 30 VA
3 Dual Core Block Type Current Transformer
Make: ECS/NPT
Transformation-Ratio CT: 600/1/1 A
CT-Core 1: 600 A / 1 A / 0,5 / 5 VA

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 42 of 45


Technical Part

CT-Core 2: 600 A / 1 A / 5P 10 / 5 VA

Listing of Secondary Equipment


1 Master Trip & Lockout Relay
Type: VAJH13YF
Make: GE
1 Easergy P3U20 with Mimic Display
Overcurrent and Earth Fault Protection Relay
Protection Functions: 50/51/50N/51N/95
Communication Port & Protocol: RJ45 port & IEC 61850
Make: Schneider Electric
1 Multifunction Meter, PM5110, Model - METSEPM5110
Make: Schneider Electric

Miscellaneous
1 Device Protection Cover for 150mm

1 Floor Rolling Trolley 150mm

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 43 of 45


Technical Part

1.3.4.2 Direct Incomer Feeder


Quantity 1
Rated Operating Current Outgoing 800 A
Dimensions
Cubicle Width 600 mm
Cubicle Height 2500 mm
Cubicle Depth 1650 mm
Properties
Cable clamping With
Cable Core Three Cores
Cables per Phase 1
Cubicle Designation PIX-RoF
CT Connection Copper
Type of Cable Connection Bottom Cable Entry
Type of Gland Plate Split Type
Upper Busbar Copper

Type of Construction
Primary Connection Cable
Type of Cubicle Direct Incomer Feeder

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 44 of 45


Technical Part

1.3.4.3 Accessories

2 Earth Switch Lever

2 CB Open-Close Stick

2 LV Compartment Door Lock

2 Extraction Ramp for 600mm

2 Addtional Operating Handle for Rear VT

2 Hand crank for manual operated Truck for EasyPact

Tender Number VDR002734 / A / 00 Key Word M2001512_SE Srilanka_Marina Squre -Colombo Date 24/11/2020

Customer Ref. M2001512 Customer SE Srilanka Page 45 of 45