Contents
Chapter 1 : Sales course
1. Introduction
2. Function
3. Part introduction
4. Option setting
5. Changes from MXD-K***AN
Samsung internal use only 3/28 This Document can not be used without Samsung's authorization
Chapter 1 : Sales course
OBJECTIVES
1. To understand Feature of AHU kit for 10~40HP
2. To understand the difference between MXD-K***AN & AHU kit for 10~40HP
Samsung internal use only 4/28 This Document can not be used without Samsung's authorization
1. Introduction
Structure diagram of an AHU kit One AHU kit will be counted as 1 Indoor unit
regardless of quantity of EEV connected.
※ Field supply
Samsung internal use only 5/28 This Document can not be used without Samsung's authorization
1. Introduction
DVM S AHU Kit for 10~40HP
EEV connector
Samsung internal use only 6/28 This Document can not be used without Samsung's authorization
1. Introduction
EEV connection
1 1 2 1 2 1 2
3 3 4
Samsung internal use only 7/28 This Document can not be used without Samsung's authorization
1. Introduction
Benefit of AHU kit for 10~40HP
MXD-K***AN MCM-D201N
Return air E/A O/A Evap in sensor Supply air Return air E/A O/A Evap in sensor Supply air
Room sensor
Room sensor
Discharge sensor
H/X
H/X
Air Flow Air Flow
Samsung internal use only 8/28 This Document can not be used without Samsung's authorization
1. Introduction
Compatibility
DVM S DVM+4
DVM S Water DVM+3
DVM S Eco …
…
Samsung internal use only 9/28 This Document can not be used without Samsung's authorization
2. Function
Interlocking
Function Explanation
AHU Fan control 220~240V signal output when AHU is in Cool / Heat / Fan mode.
Dry contact signal input from AHU fan when fan is running.
AHU fan operation check
(Installation option setting required to use : 05 SEG21)
3mins delay
Room temperature sharing Install one room/discharge sensor for multi AHU kit
Discharge temperature sharing (Wired R/C required , installation option setting required : 05 SEG24)
Comp check & Error check Dry contact signal output ※connector must be supplied from field
AHU fan on
Samsung internal use only 11/28 This Document can not be used without Samsung's authorization
2. Function
Room temperature sensor
※Caution
- Master unit must have a room sensor(PT1000 or Current type) even though Seg24 option is set as “3”.
Otherwise room sensor error will be displayed.
05 Seg24 Sensor
▶ Slave unit
Sharing the temperature sensor value of a master 0
indoor unit
▶ Master indoor unit
- Room temperature : PT1000 Ω 1
- Discharge temperature : 4~20 mA
▶ Master indoor unit
- Room temperature : 4~20 mA 2
- Discharge temperature : PT1000 Ω
▶ Master indoor unit
- Room temperature : a wired remote controller’s
3
sensor
- Discharge temperature : 4~20 mA
Samsung internal use only 12/28 This Document can not be used without Samsung's authorization
2. Function
Room temperature sharing (MCM-D201N only)
Samsung internal use only 13/28 This Document can not be used without Samsung's authorization
2. Function
Room temperature sharing (MCM-D201N only)
Master AHU kit using Wired remote controller for temperature sensor
※Caution
- Master unit must have a room sensor(PT1000 or Current type) even though Seg24 option is set as “3”.
PT1000
Use different channel
or
current type
F1,F2
Master AHU Kit : 00
R1,R2
F3,F4
Slave AHU Kit : 01 ODU #1 address :05 CH : 00
F1,F2
Slave AHU Kit : 02
R1,R2 CH : 01
Samsung internal use only 15/28 This Document can not be used without Samsung's authorization
2. Function
Room temperature sharing (MCM-D201N only) * ODU = Outdoor unit
PT1000
or
current type Use Same channel
F1,F2
Master AHU Kit : 00 R1,R2
F1,F2 CH : 00
Slave AHU Kit : 02
Samsung internal use only 16/28 This Document can not be used without Samsung's authorization
2. Function
Wired remote controller wring * ODU = Outdoor unit
Wired remote controller wring for 2 system (Temperature sensor sharing no use)
※Caution : Master unit must have a room sensor(PT1000 or Current type) even though Seg24 option is set as “3”.
PT1000
or
current type
F1,F2
Master AHU Kit : 00 R1,R2
F3,F4
PT1000
or
current type ODU #2 address :01
Samsung internal use only 17/28 This Document can not be used without Samsung's authorization
2. Function
7-segment display
Samsung internal use only 19/28 This Document can not be used without Samsung's authorization
3. Part introduction
AHU Kit : MCM-D201N - Terminal block
Samsung internal use only 20/28 This Document can not be used without Samsung's authorization
3. Part introduction
AHU Kit PCB : MCM-D201N
14 13
12
10
15 11
8
9
1
2 3 4 5 6 7
① Power(220VAC) ② Fuse check ③ Current sensor(1,2) ④ H/X sensor connector ⑤ External contact input
PT1000 sensor(3,4,5) Eva In(1,2) (8,9)
Fan feedback(7,8) Eva Out(3,4)
Samsung internal use only 21/28 This Document can not be used without Samsung's authorization
3. Part introduction
Field supply connector
The connector must be supplied from local market as no terminal block for below
- External contact
- Comp check & Error check
Sample
External Manufacture Comp Check Manufacture
contact Yeonho JST Error check Yeonho JST
SMH250-09 XHP-9 YH396-08V VHR-8N
Housing Housing
(Pitch 2.5mm) (Pitch 2.5mm) (Pitch 3.93mm) (Pitch 3.93mm)
Terminal YST025 SXH-001T-P0.6 Terminal YT396 SVH-21T-P1.1
Wire AWG 22~28 AWG 22~28 Wire AWG 16~24 AWG 16~22
External contact
Samsung internal use only 22/28 This Document can not be used without Samsung's authorization
3. Part introduction
EEV : MXD-A64K100E
* EEV wire : 7m
Filter
Samsung internal use only 23/28 This Document can not be used without Samsung's authorization
3. Part introduction
EEV : MXD-A64K100E
Samsung internal use only 24/28 This Document can not be used without Samsung's authorization
AHU KIT Installation
Product option code for discharge temperature control
Option setting
MCM-D201N 01B054-105000-231C1C-331100
Samsung internal use only 25/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
02 series installation option code
Samsung internal use only 26/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
02 series installation option code
Samsung internal use only 27/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
02 series installation option code
Samsung internal use only 28/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
05 series installation option code
Samsung internal use only 29/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
05 series installation option code
Samsung internal use only 30/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
05 series installation option code
Samsung internal use only 31/28 This Document can not be used without Samsung's authorization
*
4. Option setting
Option setting
05 series installation option code
1) Height difference : The difference of the height between the corresponding indoor uint and the
indoor unit installed at the lowest place. For example, When the indoor unit is installed 40 m(131.23 ft)
higher than the indoor unit installed at the lowest place, select the option "1".
2) Distance : The difference between the pipe length of the indoor unit istalled at the farthest place
from an outdoor unit and the pipe length of the corresponding indoor unit from an outdoor unit.For
example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40
m(131.23 ft) away from an outdoor unit, select the option "2".(100 m(328 ft) - 40 m(131.23 ft) = 60
m(196.85 ft))
3) Regardless of the AHU KIT HP setting, one indoor unit will be recognized. Therefore, be careful
when setting the number of the indoor unit installation with an outdoor unit.
Samsung internal use only 32/28 This Document can not be used without Samsung's authorization
4. Option setting
Option setting
05 series installation option code
To protect cold air inlet to the room fan staring will be delay till Evaporator get hot enough
This won’t work when you don’t use fan on signal to turn on the AHU Fan.
Use Disuse
(Skip the cold air prevention (prevent cold air)
32℃ 32℃
26℃ 26℃
Avg. Evap Temp
Samsung internal use only 33/28 This Document can not be used without Samsung's authorization
5. Changes
Difference between 2.5~10HP & 10~40HP
Capacity 2.5 / 5 / 7.5 / 10HP(separated model) 10 / 20 / 30 / 40HP(1 model with option setting)
EEV type
- Type : 103AT & Length : (10m) 2. Local supply : 4~20 mA (2wire type, -50℃~50℃)
Room
3. Internal sensor of Wired remote controller
sensor 2. Internal sensor of Wired remote controller
* sensor 1 or 2 must be installed even though room sensor
ex) MRW-WE10N setting(seg24) is 3(internal sensor of wired r/c usage).
Samsung internal use only 34/28 This Document can not be used without Samsung's authorization
5. Changes
Difference between 2.5~10HP & 10~40HP
Function - Fan check signal input(Dry contact) - Fan check signal input(Dry contact)
- Wireless signal receiver applied on PCB - Wireless signal receiver applied on PCB
Feature
- Simple BMS connection - MIM-B14 function included
- Discharge temperature control (Comp & Error condition output, External contact)
DVM S
DVM S Eco
Samsung internal use only 35/28 This Document can not be used without Samsung's authorization