DVM S AHU Kit for 10~40HP


MCM-D201N
MXD-A64K100E

SAMSUNG ELECTRONICS Co. LTD.


HQ

Samsung internal use only 1/28 This Document can not be used without Samsung's authorization
Contents
Chapter 1 : Sales course

1. Introduction
2. Function
3. Part introduction
4. Option setting
5. Changes from MXD-K***AN

SAMSUNG ELECTRONICS CO.LTD


Samsung internal use only 2/28 This Document can not be used without Samsung's authorization
Modified history
Date Ver. Modifier Detail Remarks
10 Jan 14 1.0 Lee Yihyeong Room temperature explanation revised
2015 SEP 30 1.1 Lee Yihyeong Discharge temp add
2016.07.11 1.2 Lee Yihyeong Install option update, skip the prevention of cold wind fix

Samsung internal use only 3/28 This Document can not be used without Samsung's authorization
Chapter 1 : Sales course

OBJECTIVES
1. To understand Feature of AHU kit for 10~40HP
2. To understand the difference between MXD-K***AN & AHU kit for 10~40HP

TRAINING TIME : 0.5 hour

* AHU training must be done prior to this training


File name : AHU Kit_DVM S_VER1.0_*****

Samsung internal use only 4/28 This Document can not be used without Samsung's authorization
1. Introduction
 Structure diagram of an AHU kit  One AHU kit will be counted as 1 Indoor unit
regardless of quantity of EEV connected.

 Room temperature sensor is not provided.(Field supply)


- PT1000 or current type(4mA~20mA, -50℃ ~50 ℃)

※ Field supply

Samsung internal use only 5/28 This Document can not be used without Samsung's authorization
1. Introduction
 DVM S AHU Kit for 10~40HP

 One AHU kit can be used as 10HP ~ 40HP


 EEV is excluded, so order EEV as required(One EEV = 10HP, Max 4 EEVs can be connected)

AHU kit : MCM-D201N EEV : MXD-A64K100E

EEV connector

Samsung internal use only 6/28 This Document can not be used without Samsung's authorization
1. Introduction
 EEV connection

 AHU KIT as 10 HP: Connect EEV-1


 AHU KIT as 20 HP: Connect EEV-1, EEV-2
 AHU KIT as 30 HP: Connect EEV-1, EEV-2, EEV-3.
 AHU KIT as 40 HP: Connect EEV-1, EEV-2, EEV-3, EEV-4

10HP 20HP 30HP 40HP

1 1 2 1 2 1 2

3 3 4

Samsung internal use only 7/28 This Document can not be used without Samsung's authorization
1. Introduction
 Benefit of AHU kit for 10~40HP

 Installation of 80HP AHU

MXD-K***AN MCM-D201N

- AHU kit : 8ea - AHU kit : 2ea

- EEV : 8ea(Included) - EEV : 8ea

- Room in sensor : 8ea - Room in sensor : 1ea(Room temperature sharing)

- Evap in sensor : 8ea - Evap in sensor : 2ea

- Evap out sensor : 8ea - Evap out sensor : 2ea

- Discharge temp sensor : 8ea - Discharge temp sensor : 1ea(temperature sharing)

- Wired remote controller : 1ea - Wired remote controller : 1ea

Return air E/A O/A Evap in sensor Supply air Return air E/A O/A Evap in sensor Supply air
Room sensor

Room sensor
Discharge sensor
H/X

H/X
Air Flow Air Flow

Evap out sensor Evap out sensor

Samsung internal use only 8/28 This Document can not be used without Samsung's authorization
1. Introduction
 Compatibility

 New communication is adapted

Compatible outdoor unit Not compatible

DVM S DVM+4
DVM S Water DVM+3
DVM S Eco …

Samsung internal use only 9/28 This Document can not be used without Samsung's authorization
2. Function
 Interlocking

Function Explanation

AHU Fan control 220~240V signal output when AHU is in Cool / Heat / Fan mode.

Dry contact signal input from AHU fan when fan is running.
AHU fan operation check
(Installation option setting required to use : 05 SEG21)

220~240V signal output during defrost.(3mins delay from starting)

Mode Heat Defrost Heat

Defrost signal Defrost signal off on off

3mins delay

(Installation option setting required to use: 05 SEG22)

Room temperature sharing Install one room/discharge sensor for multi AHU kit
Discharge temperature sharing (Wired R/C required , installation option setting required : 05 SEG24)

Comp check & Error check Dry contact signal output ※connector must be supplied from field

Dry contact signal input ※connector must be supplied from field


External contact input
(Installation option setting required : 02 SEG14)
Samsung internal use only 10/28 This Document can not be used without Samsung's authorization
2. Function
 Fan on

 AHU fan on

Samsung internal use only 11/28 This Document can not be used without Samsung's authorization
2. Function
 Room temperature sensor

 3 kinds of Room temperature can be choose by option setting

※Caution
- Master unit must have a room sensor(PT1000 or Current type) even though Seg24 option is set as “3”.
Otherwise room sensor error will be displayed.

05 Seg24 Sensor
▶ Slave unit
Sharing the temperature sensor value of a master 0
indoor unit
▶ Master indoor unit
- Room temperature : PT1000 Ω 1
- Discharge temperature : 4~20 mA
▶ Master indoor unit
- Room temperature : 4~20 mA 2
- Discharge temperature : PT1000 Ω
▶ Master indoor unit
- Room temperature : a wired remote controller’s
3
sensor
- Discharge temperature : 4~20 mA

 Output range of Current type sensor


4mA(-50℃) ~ 20mA(50 ℃)

Samsung internal use only 12/28 This Document can not be used without Samsung's authorization
2. Function
 Room temperature sharing (MCM-D201N only)

 Master AHU kit using PT1000 for room temperature sensor


Temperature will be shared through F3,F4 communication of Wired R/C so Wired R/C is required

Slave AHU kit #3 Slave AHU kit #2

Master AHU kit Slave AHU kit #1


05 Seg24 Sensor
Sharing the temperature sensor
0
value of a master indoor unit
PT1000
R : PT1000, D : 4~20 mA 1
or R : Current type, D : PT1000 2
Wired R/C
current type
R : Wired R/C sensor, D : 4~20 mA 3

Address setting Explanation Example


IDU address Must be different(00~63) Master kit : 00, Slave : 01,02,03
RMC No matter -
ODU address No matter -

Samsung internal use only 13/28 This Document can not be used without Samsung's authorization
2. Function
 Room temperature sharing (MCM-D201N only)

 Master AHU kit using Wired remote controller for temperature sensor

※Caution
- Master unit must have a room sensor(PT1000 or Current type) even though Seg24 option is set as “3”.

Slave AHU kit #3 Slave AHU kit #2

Master AHU kit Slave AHU kit #1 05 Seg24 Sensor


Sharing the temperature sensor
0
value of a master indoor unit
R : PT1000, D : 4~20 mA 1
R : Current type, D : PT1000 2
PT1000
or R : Wired R/C sensor, D : 4~20 mA 3
Wired R/C
current type

Address setting Explanation Example


IDU address Must be different(00~63) Master kit : 00, Slave : 01,02,03
RMC No matter -
ODU address No matter -
Samsung internal use only 14/28 This Document can not be used without Samsung's authorization
2. Function
 Room temperature sharing (MCM-D201N only) * ODU = Outdoor unit

 Temperature sharing in more than 2 system with 1 wired Remote controller


- Centralized controller for multi system  Enable

PT1000
Use different channel
or
current type

F1,F2
Master AHU Kit : 00
R1,R2
F3,F4
Slave AHU Kit : 01 ODU #1 address :05 CH : 00

F1,F2
Slave AHU Kit : 02
R1,R2 CH : 01

Slave AHU Kit : 03 ODU #2 address :05

Address setting Explanation Example


IDU address Must be different(00~63) Master kit : 00, Slave : 01,02,03
RMC No matter -
ODU address Must be same(00~15) ODU #1 : 05, ODU#2 : 05
DMS2 Use different channel  Enable CH 00, CH 01

Samsung internal use only 15/28 This Document can not be used without Samsung's authorization
2. Function
 Room temperature sharing (MCM-D201N only) * ODU = Outdoor unit

 Temperature sharing in more than 2 system with 1 wired Remote controller


- Centralized controller for multi system  Disable

PT1000
or
current type Use Same channel
F1,F2
Master AHU Kit : 00 R1,R2

F3,F4 Slave AHU Kit : 01 ODU #1 address :05

F1,F2 CH : 00
Slave AHU Kit : 02

Slave AHU Kit : 03 ODU #2 address :05

Address setting Explanation Example


IDU address Must be different(00~63) Master kit : 00, Slave : 01,02,03
RMC No matter -
ODU address Must be same(00~15) ODU #1 : 05, ODU#2 : 05
DMS2 Use Same channel  disable CH 00

Samsung internal use only 16/28 This Document can not be used without Samsung's authorization
2. Function
 Wired remote controller wring * ODU = Outdoor unit

 Wired remote controller wring for 2 system (Temperature sensor sharing no use)
※Caution : Master unit must have a room sensor(PT1000 or Current type) even though Seg24 option is set as “3”.

PT1000
or
current type

F1,F2
Master AHU Kit : 00 R1,R2
F3,F4

ODU #1 address :00


Master AHU Kit : 03
F1,F2 CH : 00

PT1000
or
current type ODU #2 address :01

Address setting Explanation Example


IDU address Must be different(00~63) Master kit : 00, 03
RMC No matter -
ODU address Must be different (00~15) / ODU #1 : 00, ODU#2 : 01

Samsung internal use only 17/28 This Document can not be used without Samsung's authorization
2. Function
 7-segment display

 K1 button : View mode / K2 button : Reset


K1 7 Segment Display
Item Remark
button Seg 1 Seg 2 Seg 3 Seg 4
1 Indoor Capacity 1 0 2 0 20HP
C C C (Auto)Cool
H H H (Auto)Heat
2 Operation Mode 2 D D D Dry
F F F Fan
0 F F OFF
3 Setting temperature 3 0 2 7 27℃
4 Room Temperature 4 - 4 2 -42℃
5 EVA In temperature 5 - 4 2 -42℃
6 EVA Out temperature 6 - 4 2 -42℃
7 EEV1 Step 7 1 4 0 1400
8 EEV2 Step 8 1 4 0 1400
9 EEV3 Step 9 1 4 0 1400
10 EEV4 Step A 1 4 0 1400
0 On
11 Fan on signal B 0 0
1 Off
0 On
12 Defrost Bypass signal C 0 0
1 Off
13 - D - - - -
14 Main address E 0 6 3 Address : 63
15 RMC address F 0 F E Address : FE
16 Version A A 2 9 2010/10/29
17 Finish View mode Finish View mode
Samsung internal use only 18/28 This Document can not be used without Samsung's authorization
3. Part introduction
 Accessories

 Room sensor is not provided. It should be supplied from the field.


 Wired remote controller is optional.

Samsung internal use only 19/28 This Document can not be used without Samsung's authorization
3. Part introduction
 AHU Kit : MCM-D201N - Terminal block

Samsung internal use only 20/28 This Document can not be used without Samsung's authorization
3. Part introduction
 AHU Kit PCB : MCM-D201N
14 13

12

10
15 11

8
9

1
2 3 4 5 6 7

Connected to terminal block Part connection Filed supply

① Power(220VAC) ② Fuse check ③ Current sensor(1,2) ④ H/X sensor connector ⑤ External contact input
PT1000 sensor(3,4,5) Eva In(1,2) (8,9)
Fan feedback(7,8) Eva Out(3,4)

⑥ EEV 4 ⑦ Com F1/F2 (1,2) ⑧ Download ⑨ Fan on (1,3) ⑩ Comp check(1,3)


Com F3/F4 (4,5) Defrost (5,7) Error check(6,8)
DC 12V (6,7)  Dry contact

⑪ EEPROM ⑫ Sub PBA for ⑬ Wireless signal ⑭ EEV1,2,3 ⑮ 7-segment display


wired remote controller receiver Tact switch
(for option setting only)

Samsung internal use only 21/28 This Document can not be used without Samsung's authorization
3. Part introduction
 Field supply connector

 The connector must be supplied from local market as no terminal block for below
- External contact
- Comp check & Error check

 Sample
External Manufacture Comp Check Manufacture
contact Yeonho JST Error check Yeonho JST
SMH250-09 XHP-9 YH396-08V VHR-8N
Housing Housing
(Pitch 2.5mm) (Pitch 2.5mm) (Pitch 3.93mm) (Pitch 3.93mm)
Terminal YST025 SXH-001T-P0.6 Terminal YT396 SVH-21T-P1.1
Wire AWG 22~28 AWG 22~28 Wire AWG 16~24 AWG 16~22

Comp check & Error check

External contact

Samsung internal use only 22/28 This Document can not be used without Samsung's authorization
3. Part introduction
 EEV : MXD-A64K100E

* EEV wire : 7m
Filter

Samsung internal use only 23/28 This Document can not be used without Samsung's authorization
3. Part introduction
 EEV : MXD-A64K100E

Samsung internal use only 24/28 This Document can not be used without Samsung's authorization
AHU KIT Installation
Product option code for discharge temperature control
 Option setting
MCM-D201N 01B054-105000-231C1C-331100

 Address setting - 0A series installation option code

Samsung internal use only 25/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 02 series installation option code

Samsung internal use only 26/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 02 series installation option code

Samsung internal use only 27/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 02 series installation option code

(*1) Minimizing fan operation when thermostat is off


Fan operates for 20 seconds at an interval of 5 minutes in heating mode.
Fan stops when thermostat is off in cooling mode.

Samsung internal use only 28/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 05 series installation option code

Samsung internal use only 29/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 05 series installation option code

Samsung internal use only 30/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 05 series installation option code

Samsung internal use only 31/28 This Document can not be used without Samsung's authorization
*
4. Option setting
 Option setting
 05 series installation option code

1) Height difference : The difference of the height between the corresponding indoor uint and the
indoor unit installed at the lowest place. For example, When the indoor unit is installed 40 m(131.23 ft)
higher than the indoor unit installed at the lowest place, select the option "1".

2) Distance : The difference between the pipe length of the indoor unit istalled at the farthest place
from an outdoor unit and the pipe length of the corresponding indoor unit from an outdoor unit.For
example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40
m(131.23 ft) away from an outdoor unit, select the option "2".(100 m(328 ft) - 40 m(131.23 ft) = 60
m(196.85 ft))

3) Regardless of the AHU KIT HP setting, one indoor unit will be recognized. Therefore, be careful
when setting the number of the indoor unit installation with an outdoor unit.

Samsung internal use only 32/28 This Document can not be used without Samsung's authorization
4. Option setting
 Option setting
 05 series installation option code

※ Skip the Prevention of cold air

To protect cold air inlet to the room fan staring will be delay till Evaporator get hot enough
This won’t work when you don’t use fan on signal to turn on the AHU Fan.

Use Disuse
(Skip the cold air prevention (prevent cold air)

32℃ 32℃

26℃ 26℃
Avg. Evap Temp

ON Avg. Evap Temp ON

FAN ON FAN OFF FAN ON FAN OFF

Samsung internal use only 33/28 This Document can not be used without Samsung's authorization
5. Changes
 Difference between 2.5~10HP & 10~40HP

Item MXD-K***AN MCM-D201N

Capacity 2.5 / 5 / 7.5 / 10HP(separated model) 10 / 20 / 30 / 40HP(1 model with option setting)

EEV Included in the model. Excluded

2.5 / 5HP(EDM type) 7.5 / 10hP(EDM type) 10HP(EDM type)


Wire : 2m Wire : 7m Wire : 7m

EEV type

1. Included 1. Local supply : PT1000 (3wire type)

- Type : 103AT & Length : (10m) 2. Local supply : 4~20 mA (2wire type, -50℃~50℃)
Room
3. Internal sensor of Wired remote controller
sensor 2. Internal sensor of Wired remote controller
* sensor 1 or 2 must be installed even though room sensor
ex) MRW-WE10N setting(seg24) is 3(internal sensor of wired r/c usage).

Samsung internal use only 34/28 This Document can not be used without Samsung's authorization
5. Changes
 Difference between 2.5~10HP & 10~40HP

Item MXD-K***AN MCM-D201N

- Fan on signal output(220V) - Fan on signal output(Dry contact)

Function - Fan check signal input(Dry contact) - Fan check signal input(Dry contact)

- Defrost signal output(220V) - Defrost signal output(Dry contact)

- MIM-B14(external contact I/M) is included - Room/Discharge temperature sharing by wired r/c

- Wireless signal receiver applied on PCB - Wireless signal receiver applied on PCB
Feature
- Simple BMS connection - MIM-B14 function included

- Discharge temperature control (Comp & Error condition output, External contact)

1. Capacity setting required (10~40HP)

1. Function setting 2. Room/Discharge sensor type setting


Setting
2. Product option setting for Discharge temp control 3. Function setting

4. Product option setting for Discharge temp control

Evap sensor Connect to the terminal block Connect to the PCB

DVM S

Compatibility DVM S Water ←(same)

DVM S Eco

Samsung internal use only 35/28 This Document can not be used without Samsung's authorization
Thank You !!!

This Training Manual is a property of Samsung Electronics Co.,Ltd.


Any unauthorized
Samsung internal use only use of Manual can be punished under
36/28
applicable International
This Document and/or
can not be domestic
used without law.
Samsung's authorization

You might also like