The operation and functions described in this manual are available from Software Version Ex-3000-V2.05C onwards.
www.advancedco.com
Specifications:
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
1
The overall capability of the power supply is restricted to panel loading and maximum power available from the AUX outputs. Refer to the
relevant sections of this manual for the minimum and maximum output voltages of each circuit.
2
The charger is turned off in alarm.
www.advancedco.com
Table of Contents Page
1 INTRODUCTION 5
1.1 STANDARDS 5
1.2 CAUTIONS AND W ARNINGS 5
1.3 DESCRIPTION 5
1.1 EN54 FUNCTIONS 6
1.1.1 EN54 Optional Features with Requirements 6
1.2 EN12094 FUNCTIONS 7
1.2.1 EN12094-1 Optional Features with Requirements 7
1.3 INSTALLATION APPROVALS 9
1.3.1 Fire System Installations 9
1.3.2 Wiring Regulations 9
2 INSTALLATION 10
2.1 IDENTIFICATION OF PARTS 10
2.2 INSTALLING THE BACK BOX 11
2.3 WIRING INSTALLATION 12
2.3.1 AC Mains Wiring 12
2.3.1.1 Cable Gland 12
2.3.2 Battery Wiring 12
2.3.3 24VDC Power Supply Wiring 13
2.3.4 PSE Configuration 13
2.3.5 External Wiring 13
2.3.5.1 Relay Outputs 14
2.3.5.2 RS485 Communications 14
2.3.5.3 AUX DC Supply Output 15
2.3.5.4 Detection Zone Inputs 15
2.3.5.5 Sounder / Monitored Output Circuits 16
2.3.5.6 Input Circuits 18
2.3.5.7 Actuator Output Circuit 18
2.3.5.8 USB 19
2.3.5.9 Recommended Cable Routing 20
2.4 KEY-SWITCH INSTALLATION 21
2.5 ADJUSTING THE LCD CONTRAST 21
2.6 LOADING CALCULATIONS 22
2.6.1 Panel Loading 22
2.6.2 Battery Standby Calculation 22
3 PROGRAMMING 23
3.1 INTRODUCTION 23
3.1.1 Access Levels 23
3.1.2 Front Panel Controls and Indications 23
3.1.3 Enable Controls 24
3.1.4 Navigating through menus 24
3.1.5 Numeric data entry 25
3.2 RECOMMENDED PROGRAMMING PROCEDURE 25
3.3 LEVEL 3 MENU FUNCTIONS 25
3.3.1 Detection Zones 26
3.3.2 Alarms 26
3.3.2.1 Sounder Configuration 27
3.3.2.2 Pulse Pattern Configuration 28
3.3.3 Extinguishing 29
3.3.3.1 Output Set-Up 29
3.3.3.2 Cause and Effects Programming 29
3.3.3.3 Extract Set-Up 30
3.3.3.4 Release Signal Termination (Test Function) 30
3.3.4 Inputs 31
3.3.5 Outputs 32
3.3.5.1 Switched AUX Output 33
3.3.6 Passwords 33
3.3.6.1 Default Passwords 33
3.3.7 General Options 34
3.3.7.1 Daylight Saving Options 34
www.advancedco.com 3
3.3.8 Status Indicators 35
3.3.9 Enable PC LINK 36
3.3.10 Exit 36
4 SERVICE AND MAINTENANCE 37
4.1 M AINTENANCE SCHEDULE 37
4.1.1 Daily Actions 37
4.1.2 Monthly Actions 37
4.1.3 Quarterly Actions 37
4.1.4 Annual Actions 37
4.2 REPLACEMENT OF COMPONENTS 38
4.2.1 Batteries 38
4.2.2 Liquid Crystal Display 38
5 APPENDICES 39
5.1 APPENDIX 1 – FORGOTTEN LEVEL 3 PASSWORD 39
5.2 APPENDIX 2 – COMPATIBLE DEVICES 40
5.2.1 Detectors 40
5.3 APPENDIX 3 – RECOMMENDED CABLES 42
5.3.1 Fire Rated Cables 42
5.3.2 Non-Fire rated cables 42
5.4 APPENDIX 4 – TROUBLESHOOTING 43
4 www.advancedco.com
1 Introduction
1.1 Standards
Advanced Electronics Ltd declare that the ExGo Gas Extinguishing Control Panel conforms to the essential
requirements specified in the Construction Products Directive 89/106/EEC: Refer to the full CPD schedule on
the back page.
EN12094-1:2003
EN54-2:1997 +A1:2006
EN54-4:1997 +A1:2002 +A2:2006
EN54-13:2005
This product has been designed to comply with the requirements of the Low
Voltage Safety, EMC and the CPD Directives. Failure to follow the installation
instructions may compromise its adherence to these standards.
This equipment is constructed with static sensitive components. Observe anti-
static precautions at all times when handling printed circuit boards. Wear an
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
anti-static earth strap connected to panel enclosure earth point. Before installing
SENSITIVE DEVICES
or removing any printed circuit boards remove all sources of power (mains and
battery).
1.3 Description
This manual covers the installation, programming and commissioning of the ExGo Extinguishing Control Panel.
Refer to the User Manual (Document No. 680-148) for details of how to operate the panel.
The ExGo is a Single Flooding Zone Control Panel with up to three detection zone circuits.
The detection zones are compatible with conventional detectors and call points. Refer to the compatibility
section for full details of the compatible devices tested.
Install the panel, detection circuits, sounder circuits, etc. in accordance with the instructions in Section
2 and then program the operation in accordance with the instructions detailed in Section 3.
www.advancedco.com 5
1.1 EN54 Functions
This Control Panel is compliant with the requirements of EN54-2: 1997 +A1: 2006
and EN54-4: 1997 +A1: 2002 +A2: 2006.
In addition to the basic requirements, the following optional functions are provided
and these comply with the requirements of EN54.
This Fire Alarm Control Panel also supports additional functions that are not covered
by EN54. These are as follows:
Refer to
Additional Function
Paragraphs
The CIE has provision for connection to Fire Alarm Devices. It is possible to Silence
and Re-sound the alarms at Level 2. Refer to the User Manual for further
Section 7.8 information.
Refer to Sections 2.3.5.5 and 3.3.5 for information on installation and output
programming.
Delays to Outputs.
The CIE has provision for delaying the activation of outputs in response to zone fire
conditions. These delays are programmable on a zone–by–zone basis.
Section 7.11
Refer to Section 3.3.1 for information on delay programming.
Alarm Counter.
The CIE has provision record the number of times that the fire alarm condition is
Section 7.13 entered. Refer to the User Manual for further information.
6 www.advancedco.com
Total Loss of Power.
The CIE has provision to annunciate a total loss of power for one hour. Refer to
Section 3.3.7 for information on configuring this option.
Section 8.4
Conditions:
- Requires installation of 7Ah batteries
- The minimum battery operating voltage is 20.4V
- Output Power AUX2 must not be used for external equipment.
- Output Power AUX1 will be switched off when battery voltage is <20.4V
Test Condition.
The CIE has provision for testing the installation on a per zone basis. Refer to the
Section 10 User Manual for further information.
This control panel incorporates a manual triggering device in accordance with the
requirements of EN12094-3: 2003.
The ECD has provision to delay the transmission of the extinguishing signal. This can
be programmed in 1-second intervals up to a maximum of 60-seconds. Refer to
Section 4.17 Section 3.3.3.1 for programming.
The ECD has provision to monitor the flow of the extinguishing agent once released.
One fixed input is provided. Programmable inputs can also be configured as flow
Section 4.18 inputs. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
The ECD has the provision to monitor the status of extinguishing components such as
loss of agent, temperature, etc. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Section 4.19
Means shall be provided to transmit the information concerning the blocked position
of a manual control device. Refer to sections 2.3.5.1 and 3.3.5 for further information.
www.advancedco.com 7
Emergency Hold Device.
The ECD has provision for an emergency hold device. Refer to Sections 2.3.5.6, 3.3.4
and 3.3.3.1.
Section 4.20
Means shall be provided to transmit the information concerning the activation of an
emergency hold device. Refer to sections 2.3.5.1 and 3.3.5 for further information.
The ECD has provision to control the duration of the flooding time. Refer to Section
3.3.3.1 for programming.
Section 4.21
The ECD has provision to switch from Auto/Manual to Manual Only means of
establishing the extinguishing signal. This can be by Level 2 User Menu Option, fixed
Section 4.23 input, programmable input or by Key-Switch Option. Refer to Sections 2.3.5.6, 3.3.4
and 3.3.3.1.
These circuits are required to be monitored for fault conditions by the ECD.
The ECD has provision to transmit triggering signals to other equipment such as
doors, ventilation shut down, etc. Refer to Sections 2.3.5.1 and 3.3.5.
Section 4.26
These circuits are to be monitored for fault conditions by the receiving device.
The ECD has provision for an emergency abort device. This can be by fixed input or
programmable input option. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Section 4.27
Means shall be provided to transmit the information concerning the activation of an
emergency abort device. Refer to sections 2.3.5.1 and 3.3.5 for further information.
The ECD has provision to activate sounding devices with different signals to indicate
the pre-discharge warning condition (pulsing, 1s/1s), the release condition
Section 4.30 (continuous) and the hold condition (pulsing, 1s/4s). Refer to Sections 3.3.2.1 and
3.3.2.2. Three pulsing patterns can be defined.
8 www.advancedco.com
1.3 Installation Approvals
www.advancedco.com 9
2 Installation
2.1 Identification of Parts
The following diagram shows the major parts of the panel.
LIVE
EARTH
NEUTRAL
u P MO D E
PSU USB
R e la y- 1 R e la y -2
Comms RUN PROG
F IR E FA U LT R S485 AU X ZO NE ZONE ZO NE SN D R SNDR SN D R M OD E M an ua l H O LD A B O R T P r essu r e VA LV E F L O W A c tu a t o r PROG PROG PROG PROG
R e la y R e la y Sup pl y -1- -2 - - 3-
SUPPLY -1- -2- -3- S e le c t Tr ig g e r M on it or M o n it o r M o n it o r O u t p u t Inp ut-1 In put-2 Input- 3 Inpu t-4 R EBO O T
D E T E C T IO N Z O N E S
-1-
-2-
-3- E X T IN G U IS H A N T
F IR E F A U LT / R E LE A S E
T ES T /
D ISA B L E PULL DOWN AND PRESS BUTTON
G E NE R A L E X T IN G U IS H A N T
R ES ET RELEASE
F I RE SILENCED IMMINENT
RELEASED
S OU ND AUTO +
POWER SYSTEM FAULT A LAR M S MANUAL ONLY
MANUAL
(HOLD 2s) ESC MENU
CHASSIS
DOOR ASSEMBLY
BACK BOX MANUAL RELEASE
COVER
The panel comprises a back box, door, chassis assembly and PSE module.
The chassis is mounted onto the back box via two screws and keyhole mounting holes. The screws do not have
to be removed to remove the chassis.
The chassis contains the main printed circuit card with terminal block connections for field wiring. A fascia label
is affixed to the front of the chassis providing the user controls and indications (LCD and LED indicators). A
hinged yellow plastic cover is fitted to the front face and provides access to the manual release button.
The PSE module converts the in-coming AC Supply to 24V DC (nominal) and provides battery charging. The
PSE is connected to the chassis via a DC Cable and a serial communications cable. The PSE design is to BS
EN54-4: 1998 +A2 and provides monitoring for AC failure, battery missing, battery low, charger failure and
battery high internal resistance.
Standoff pillars are provided in the back box to fit a standard Exp-008 8-Way Relay Module. This is connected
to the main printed circuit card via ribbon cable.
Up to two (programmable function) key-switch assemblies (Exp-001 & Exp-002) can be fitted to the chassis
plate below the manual release cover. The cables plug onto the main printed circuit card. Slide-in labels with
pre-printed text are available.
10 www.advancedco.com
2.2 Installing the back box
Enclosure dimensions and fixing points are shown in the diagram below. Remove the chassis before installing
the enclosure (retain in a safe place).
90
LIVE
EARTH
NEUTRAL
275
330
26
160 160
400
When batteries are installed, the ExGo can weigh in excess of 10Kg. Use appropriate fixing hardware to secure
the panel to the wall.
For example, drill the required holes in the supporting wall using a drill bit diameter 7.0 mm and plug with a
suitable 40mm long expansion plug. Affix the panel to the wall with M5 screws (length 40mm) or No.10 screws
(length 1½”).
Ensure that there is sufficient space to allow the cover to be removed / opened when the panel is finally
mounted.
www.advancedco.com 11
2.3 Wiring Installation
Type Manufacturer
Gland IP65 – Brass M20, EExd / Eexe Lappcable
Gland IP68 – Nylon 66 M20 Black, UL94V2 Multicomp
Bushing – Nylon 66 M20 Black, UL94V2 Multipcomp
0V DC POWER
12 www.advancedco.com
2.3.3 24VDC Power Supply Wiring
The main printed circuit card on the chassis
is supplied with 24V DC from the power +V DC POWER
supply. 0V DC POWER
BATTERY +
BATTERY –
wiring and be wired using cable with suitable for the loading conditions.
DISABLE SOUNDER DISABLED GHI JKL MNO DISABLED
insulation suitable for the application. S IIn
LEareas
N C E / where cabling may come into contact
NB: Minimum / Maximum cable size for all RE with
SO Uhigh
N D frequency interference, such as MANUAL
TEST LOW
connectionsSOisUNlimited
DER DELtoAY0.35mm²
ED / 2.5mm² portable radio transceivers
PQRS etc.
TUV theWoutput
XYZ wiring DISABLED
(22-14AWG). cable should be of a twisted pair construction
S OU ND
PO WERspecific recommendations
Any SYSTEM FAULT are detailed A Lwithin
AR M S an overall screen. The screen should be MANUAL ONLY
below for each type of circuit. terminated
(HOLD 2s) to one of
ESC
the dedicatedMearth
ENU
studs /
bus bar available in the panel.
Refer to the Recommended Wiring Routing
section for details of cable routing within the
enclosure.
3
This configuration is not in accordance with the requirements of EN54-4. If configured for PSE ONLY, the panel will not report fault
conditions for battery missing, charger failure or battery high resistance.
www.advancedco.com 13
2.3.5.1 Relay Outputs
Fault Output.
A B
RS485 AUX Supply
G E NE R A L
14 R ES ET
www.advancedco.com
F I RE SILENCED
2.3.5.3 AUX DC Supply Output
Two Auxiliary Power Outputs are provided. AUX-2 AUX-1
4
18.0 – 28.0 V DC, 0.5A SUPERVISED. POWER
LIMITED.
AUX #1 : 4-Wire Smoke Detector Power or other
similar application. Power turns off for
4-5 seconds on reset and when EN54-
2 Clause 8.4 limit is reached.
AUX #2 : 24V DC (nominal) power output for PSU
Comms
external equipment
R e la y-(remote
1 R e lastatus
y -2 F IR E FA U LT R S 485 AU X ZO NE ZON E ZO NE
SUPPLY
5 R e la y R e la y S up pl y -1- -2 - -3-
indicators) .
Use appropriately sized cable for the current load
to ensure device compatibility.
Section 12.5.2
Three conventional detection zone inputs are
provided. These are nominally 20V DC circuits
and are current limited.
The circuits are monitored for open and short
circuits. For normal monitoring, a 6800Ω End-of-
Line resistor is required. Maximum line PSU
impedance 32Ω. R e la y- 1 R e la y -2 F IR E
GE NEFARUA
LTL R S 485 AU X ZO N E ZON E ZO N E
Comms
R e la y R e la y S up pl y - 1 - R E-S2E- T - 3 -
SUPPLY
F I RE
The circuit is designed to be compliant with SILENCED
conventional detectors and call points with an ABC
equivalent series resistance of 470Ω or 270Ω.
FAULT SOUNDER FAULT
If using devices that apply a short across the zone circuit, refer to Section 3.3.1 for how to configure this ! M U TE
Detector Detector
SCall
ILPoint
E NCE /
6 RE SO U N D
2.3.5.4.1 Standard Arrangement TEST SOUNDER DELAYED
6800Ω
PQRS TUV
Connect the detectors and manual call points (if
S OU ND
required) in series with no spurs. POWER SYSTEM FAULT A LAR M S
Connect the end-of-line resistor across the (HOLD 2s) ESC
terminals of the last device.
OBSERVE POLARITY OF CONNECTIONS!
Zone-1 Zone-2 Zone-3
6
2.3.5.4.2 Diode Base Arrangement G E NE R A L
AEL
R ES ET
If the installation requires conformance toF I RE SILENCED
BS5839-1: 2002 Code of Practice regarding the
ABC
supervision of removal of detectors and /ForAULT SOUNDER FAULT
operation of call points when detectors are
removed, then install the detectors using diode
! M U TE
S OU ND
POWER SYSTEM FAULT A LAR M S
(HOLD 2s) ESC
4
TOTAL OUTPUT LOAD must not exceed panel supply rating – maximum 2A.
5
AUX-2 also provides power for the Exp-008 8-Way Relay card. This current must be subtracted from the total available AUX-2 power to
give the available output power. If EN54-2 Clause 8.4 function is enabled then, to ensure that the minimum buzzer alert time of 1 hour is
maintained, AUX2 should not be used to power external equipment.
6
The system has been tested for compliance with the circuit impedance monitoring requirements of EN54-13 using the standard EOL
resistor. No EN54-13 compliance is declared for the use of an Active End-of-Line (EXP-006).
www.advancedco.com 15
HAZARDOUS AREA
2.3.5.4.3 Intrinsic Safe Arrangement 7 Isolation
IS Detector IS Detector IS Call Point
Barrier
The Zone Circuit can be configured for use with 11 + 1
6800Ω
Intrinsic Safety detectors and barriers – see
12 – 2
programming section.
The recommended isolation barrier is a
PEPPERL+FUCHS Model: KFDO-CS-Ex1.51P or
SAFE AREA
MTL Model: 5061
Only use intrinsic safe detectors and call points.
Zone-1 Zone-2 Zone-3
The number of devices permitted and cables will
depend on the IS classification – refer to the The End-of-line resistor used must be rated for the
detector manufacturers’ information for further appropriate IS zone classification.
details.
E NE R A L E X T IN G U IS H A N T
R ES ET Isolation RELEASE
SILENCED Barrier IS Sounders - Polarised RELEASED
IMMINENT
2.3.5.5.1 Intrinsic Safe Arrangement + +
EOL
10k ohm
ABC DEF
The Sounder Circuit can be configured for use TIMER HELD ABORTED
SOUNDER FAULT
!
– –
MU
with Intrinsic Safety sounders T E barriers.
and
HAZARDOUS AREA
The recommended isolation barrier is a MTL
SOUNDER DISABLED GHI JKL MNO DISABLED FAULT
Model: 778ac S ILE N C E / SAFE AREA
7
Due to the isolation barrier internal resistance, intrinsic safe circuits are not monitored in accordance with the circuit impedance monitoring
requirements of EN54-13.
8
By default, SNDR1 & SNDR2 are for configured for general fire alarms. SND3 is dedicated to the extinguishant alarm (flooding zone)
output in accordance with EN12094-1.
9
TOTAL OUTPUT LOAD (continuous) must not exceed panel supply rating – maximum 2A.
16 www.advancedco.com
2.3.5.5.2 EN54-13 Monitoring
The sounder outputs support monitoring with an Active EOL device to ensure circuit
integrity in accordance with the requirements of EN54-13.
Active
EOL
panel sounder outputs must be fitted with the +
Active EOL device (Mxp-505)
The panel uses techniques to ensure that a Typical
fault warning condition is reported if the circuit Arrangement
resistance increases to a condition where the
voltage at the last device may fall below its
minimum operating voltage level. This is Typical Sounder Arrangement.
compatible for load currents from minimum up OBSERVE POLARITY
to maximum (1 ampere).
The Active EOL device is polarity
Install the Active EOL device at the end of the sensitive.
sounder circuit instead of the normal EOL
resistor – this device is polarity sensitive. The Active EOL is fuse protected –
Connect the Red lead to the sounder + signal however, if connected incorrectly
line. and the sounder circuit is activated,
the fuse will open and is not user
replaceable.
www.advancedco.com 17
2.3.5.6 Input Circuits
Seven Fixed function Input circuits are provided for
the following functions:
MODE SELECT [Auto / Manual], MANUAL TRIGGER, HOLD,
ABORT, PRESSURE MONITOR, VALVE MONITOR and FLOW
MONITOR.
Four Programmable Function Input Circuits are
PSU
provided. Each input circuit
Commsis monitored for open
85 AU X
S up pl y
ZO N E ZON E ZO N E
and short
-1-
circuit
-2 -
conditions
-3-
– see
SUtypical
PPLY SN D R S N D R
-1- -2-
SN D R
-3-
M O D E M a n u a l H O L D A B O R T P ressu re VA LV E FL O W A c tu a t o r PROG
S e le c t Tr ig g e r M on it or M o n it o r M o n it o r O u t p u t Inp ut-1
PROG
In put-2
PROG
Input-3
PROG
Inpu t-4
arrangement below.
EOL = 6800Ω. Maximum line impedance 50Ω.
Connect to volt-free switches / relay contacts only.
D E T E C T IO N Z O N E S
6K8 TYPICAL SWITCH -1-
ARRANGEMENT
470R
-2-
-3- u P MODE
E X T IN G U IS H A N T
USB R E LE A S E
s F IR E FA U LT /
SN D R SNDR SN D R M O D E M a n u a l H O L D A B O R T P ressu re VA LV E FL O W A c tu a t o r PROG PROG P RUN PROG
SUPPLY TREOSGT / PROG
-1- -2- -3- S e le c t Tr ig g e r M on it or M o n it o r M o n it o r O u t p u t Inp ut-1 In put-2 Input-3 Inpu t-4 RPEU
BLOLOD
T OWN AND PRESS BUTTON
DISA BL E
-2-
10
- 3 rating
TOTAL OUTPUT LOAD (continuous) must not exceed panel supply - – maximum 2A. E X T IN G U IS H A N T
F IR E FA U LT / R E LE A S E
T ES T /
18 DISA BL E PULL DOWN AND PRESS BUTTON
www.advancedco.com
2.3.5.7.1 Igniting Actuators M M M M Up to 4 igniting
actuators in series
The circuit is current limited and one to four
igniting actuators can be wired in series without
special requirements.
No additional resistance is required in the circuit
Maximum line impedance 7Ω including the internal
resistance of the actuators.
Insulation Resistance
(Core-Core and Core- 2M Ω
Screen)
2.3.5.8 USB
The USB socket is for connection to a Laptop or
PC.
This can be used for upload of a new logo or
download of the configuration and log files.
Refer to section 3.3.9 for further information.
u P MODE
USB
SN D R SNDR SN D R M O D E M a n u a l H O L D A B O R T P ressu re VA LV E FL O W A c tu a t o r PROG PROG PROG PROG RUN PROG
SUPPLY -1- -2- -3- S e le c t Tr ig g e r M on it or M o n it o r M o n it o r O u t p u t Inp ut-1 In put-2 Input-3 Inpu t-4 R EBO O T
D E T E C T IO N Z O N E S
-1-
www.advancedco.com - 2 - 19
2.3.5.9 Recommended Cable Routing
The following diagram shows the recommended cable routing within the enclosure.
Zone Inputs
Actuator
AC IN Output
AC INPUT
Cable Tie
LIVE
EARTH
NEUTRAL
u P MO D E
PSU USB
R e la y - 1 R e la y - 2
Comms RUN PROG
F IR E FA U LT R S 485 AU X ZO NE ZONE ZO NE SN D R SNDR SN D R M O D E M an ua l H O LD A B O R T P res su r e VA LV E F L O W A c tu a t o r PROG PROG PROG PROG
R e la y R e la y Sup ply -1- -2 - - 3-
SUPPLY -1- -2- -3- S e le c t Tr ig g e r M on it or M o n it o r M o n it o r O u t p u t Inp ut-1 In put-2 Input-3 Inpu t-4 R EBO O T
D E T E C T IO N Z O N E S
-1-
-2-
-3- E X T IN G U IS H A N T
F IR E FA U LT / R E LE A S E
T ES T /
DISA BL E PULL DOWN AND PRESS BUTTON
G E NE R A L E X T IN G U IS H A N T
R ES ET RELEASE
F I RE SILENCED IMMINENT
RELEASED
SOU ND AUTO +
POWER SYSTEM FAULT A LAR M S MANUAL ONLY
MANUAL
(HOLD 2s) ESC MENU
20 www.advancedco.com
2.4 Key-Switch Installation
uP M ODE
PS U U SB
C omms RUN PROG
R ela y- 1 R e la y - 2 F IR E F A U LT R S485 AU X ZO N E ZONE ZO N E SN DR S NDR SN DR MODE M anua l H O LD A B O R T P r e s s u r e V A L V E F L O W A c tu a t o r P R O G PR O G P R OG P RO G
R e la y Sup ply - 1 - - 2 - - 3 -
SUPP LY - 1 - - 2 - - 3 - S e le c t Tr ig g e r M o n it o r M o n it o r M o n i t o r O u t p u t I n p u t - 1 In p u t - 2 I n p ut - 3 I n p u t- 4
R e la y R EBO OT
DETECTION ZONES
-1-
-2-
-3- EXTINGUISHANT
F IR E F A U LT / RELEASE
TEST/
D IS A B L E PULL DOWN AN D P RES S BU TTON
GENERAL EXTINGUISHANT
PL3 PL4
RESET RELE ASE
FIRE SILENC ED IMMINEN T
RELEASED
! M U TE
SILENCE /
PQRS TUV WXYZ
AU TO +
PL3: KEY-SW #2
POW ER SYS TEM FAU LT SOUND MANUAL ON LY
MA NUA L
ALARMS ESC MENU
Using a sharp knife, cut through the fascia label using the key-switch mounting hole as a template.
Insert the key-switch assembly through the hole and secure with the fixing nut. Before fully tightening, insert the
slide-in label with the required function description into the pocket in the fascia label.
Plug the connector into the respective connector on the card.
Key-Switch assemblies are available in both trapped (Exp-001) and non-trapped (Exp-002) versions.
Refer to the Programming section to define the action of the key-switch.
www.advancedco.com 21
2.6 Loading Calculations
2.6.1 Panel Loading
The Total Panel Load must not exceed the rating of the power supply. The power supply can deliver a 2A total
load maximum.
The panel loading includes the panel itself (70/125mA), any power required for additional option modules and all
external power required for the Input, Output and AUX circuits.
The backlight is turned off during AC supply failure (after 60 seconds). It turns on in Alarm or if the panel keys
are pressed.
2.6.2 Battery Standby Calculation
Quiescent Load Fire Alarm Load
Equipment I (A) x Total I (A) x Total
11 12
EX-3001 Panel 0.070 1.0 = 0.070 0.125 1.0 = 0.125
13
Exp-008 0.000 1.0 = 0.065 1.0 =
14
AUX #1 Supply Output 1.0 = 1.0 =
14
AUX #2 Supply Output 1.0 = 1.0 =
15
Sounder Output 1 1.0 =
15
Sounder Output 2 1.0 =
15
Sounder Output 3 1.0 =
Actuator Output 1.0 =
Total Quiescent Load = Alarm Load =
x 24 hr = Ahr
16
x 72 hr = Ahr 2 x 0.5 hr = Ahr
(carry forward) + Ahr
Total Load (Quiescent + Alarm) = Ahr
16
x 1.25 (Battery De-rating factor) = Ahr
11
Figure quoted is for mains fail condition (backlight off) – add 15mA for first hour of fault when the backlight is on.
12
Figure quoted is for fire in mains fail condition – with Relay1, Relay 2 & Fire relay energised (backlight on).
13
Figure quoted is for all relays on. 8mA per relay output on.
14
Maximum 0.5A load per AUX. Calculate the required load for each auxiliary output in both the quiescent and alarm conditions. Refer to
the technical information for each device that is to be powered from the panel AUX Output to determine the overall AUX loading currents.
The sum of all these additional currents should be entered in these fields.
15
Maximum 1.0A load per Sounder.
16
The alarm load should be doubled to allow for changes in battery efficiency for loads in excess of the recommended C/20 discharge rate.
The total load calculated should be multiplied by a de-rating factor of 1.25 to allow for changes in battery efficiency over time. The above
calculation is in accordance with the recommendations in BS5839-1: 2002.
22 www.advancedco.com
3 Programming
3.1 Introduction
These instructions cover the configuration and programming of the panels.
NOTE: The panel is delivered in a non-configured condition. In this mode (or if the panel is
returned to factory default settings) the panel defaults to MANUAL ONLY mode of operation.
After configuring the panel, use the Level 2 EXTINGUISH MODES menu option (or the
configured key-switch / inputs) to set the panel into the AUTO+MANUAL mode.
This document covers the Level 3 functions. For details on the operation and use of the panel at Levels 1 & 2,
refer to User Manual 680-148. Full details are supplied with any special tools.
A level-3 password is required to enter the commissioning menus. For details of Passwords, refer to Section
3.3.6.
Level-3 Passwords.
If this number is lost, it is not possible to enter commission mode functions.
Refer to 5.1 for further information.
uP M ODE
PSU U SB
C omms RUN PROG
R ela y-1 R e la y - 2 F IR E F A U LT R S485 AU X ZO N E ZONE ZO N E SN DR S NDR SN DR MODE M an ua l H O LD A B O R T P r e s s u r e V A L V E F L O W A c tu a t o r P R O G PRO G P R OG P RO G
R e la y S up p ly - 1 - - 2 - - 3 -
SUPP LY - 1 - - 2 - - 3 - S e le c t Tr ig g e r M o n i t o r M o n it o r M o n i t o r O u t p u t I n p u t - 1 In p u t - 2 I n p ut - 3 I n p u t- 4
R e la y R EBO OT
DETECTION ZONES
-1-
-2-
-3- EXTINGUISHANT
F IR E F A U LT / RELEASE
TEST/
D IS A B L E PULL DOWN AN D P RESS BU TTON
GENERAL EXTINGUISHANT
RESET RELEASE
FIRE SILENC ED IMMINEN T
RELEASED
! M U TE
General Status Control Buttons Number Buttons Extinguishant Status Key-Switch Assembly
(Optional)
The LCD along with the LED Indicators shows the operating status of the system. Examples of the information
presented are shown below:
www.advancedco.com 23
Normal Display Non-normal Display Typical Menu Display
[System status] [Level 2 Menu]
1 of 1 conditions: VIEW .
DETECTION ZONE3 TEST
SYSTEM NORMAL OPEN CIRCUIT EXTINGUISH MODES
22 AUG 2007 16:39:00 [Release status] DISABLE/ENABLE
UNAFFECTED EXIT LEVEL 2
Press the button to select the The display prompts for entry of Enter the password. As each
‘Enable Controls’ option. the password. number is pressed, an * character
is displayed. Finally, press the
button to confirm.
24 www.advancedco.com
3.1.5 Numeric data entry
Numbers are entered by moving to the required field, and then typing in the required number, followed by the
button. The display returns to the previous menu.
If the number is entered incorrectly, press the button to clear the entry and then re-enter the required
number. Alternatively, press the ‘Esc’ button to cancel the number entry and return to the previous menu.
To enter the Commissioning / Programming Menu, select the COMMISSION option in the Level 2 Menu and
press the button. The display prompts for the Level 3 password.
To exit from the Commissioning / Programming Menu, select the EXIT option and press the button. The
display prompts for the Level 3 password.
www.advancedco.com 25
3.3.1 Detection Zones
This menu configures each of the three detection zone input circuits. Highlight the DETECTION option and
press the button. The following Zone Select Menu will be shown.
[Zone Select] Use the buttons to highlight the required zone and
ZONE 1 . then press the button to select it.
ZONE 2 A menu of parameters is then presented for the selected
ZONE 3 zone.
LEARN ZONE LOADS Select the Learn Zone Load option and follow instructions
(loads learned) to maximise zone sensitivity to open-circuit conditions.
Note that the Learn Zone Load process must only be performed when all detection zones are in their normal
operating state. The process should be repeated whenever any changes to the zone configuration are made.
The presence of the “(loads learned)” text indicates that the process has been compled successfully.
The Learn Zone Load process must be completed to ensure that the system complies fully
with the requirements of EN54-13.
[Zone 1 Settings]
SNDR DELAY : 0 .
VERIFY TIME : 0
Use the buttons to highlight the required parameter
I.S. ZONE : NO
and then press the button to select / change it.
SHORT=ALARM : NO
NON-LATCH : NO The table below details the parameters can be adjusted:
3.3.2 Alarms
SNDR3 is dedicated to the flooding zone (protected area) sounders and is part of the ECD. SNDR1 & SNDR2
are general fire alarm sounders.
17
Settings in excess of 9 seconds are not in accordance with BS EN 54-2: 1998.
18
This Setting is not in accordance with BS EN 54-2:1998.
19
This setting is not in accordance with BS EN 54-2: 1998.
26 www.advancedco.com
This menu configures each of the three alarm output circuits. Highlight the ALARM OUTPUTS option and press
the button. The following Sounder Select Menu will be shown.
[Sounder Select]
Sounder-1 (Fire) . Use the buttons to highlight the required sounder (or
Sounder-2 (Fire) the pulse pattern option) and then press the button to
Sounder-3 (Gas) select it.
PULSE PATTERN A menu of parameters is presented for the selected
sounder.
ZONE 1 FIRE Determines the response of the output to a fire OFF, PULSED, ON ON ON OFF
alarm condition from this zone.
ZONE 2 FIRE Determines the response of the output to a fire OFF, PULSED, ON ON ON OFF
alarm condition from this zone.
ZONE 3 FIRE Determines the response of the output to a fire OFF, PULSED, ON ON ON OFF
alarm condition from this zone.
STAGE-1 Determines the response of the output when at OFF, PULSED, ON ON ON OFF
least one of the qualifying conditions for release
has been established.
COUNTDOWN Determines the response of the output when the OFF, PULSED, ON ON ON PULSE2
activated condition has been established and
the ECD is in the Imminent Release phase. This
setting overrides any pre-existing state during
the countdown period.
STAGE-2 Determines the response of the output when the OFF, PULSED, ON ON ON ON
actuator output activated condition has been
established.
SOUND ALARMS Determines the response of the output when the OFF, PULSED, ON ON ON ON
front panel EVACUATE button is pressed.
PULSE ON HOLD Determines the response of the output when the NO / YES NO NO YES
hold button / input is active. This setting
overrides any pre-existing state during the hold
condition. If ‘YES’ the hold pulse pattern is
enforced, if ‘NO’ the programmed ‘countdown’
mode is enforced.
MAY SILENCE Determines the response of the output when the NO / YES YES YES YES
front panel SILENCE button is pressed. If set to
NO, the output will not be turned off when the
sounders are silenced.
SOUND IN TEST Determines the response of the output to a zone NO / YES YES YES YES
test fire (with sounders). Set to yes, the output
will activate momentarily on any test fire.
EN54-13 Determines whether extended transmission path NONE, 100mA, NONE NONE NONE
monitoring is in use and defines the maximum 250mA, 500mA,
1000mA
alarm load current.21
20
SNDR3 is dedicated to the Gas ECD for the flooding zone alarm. For compliance with EN12094-1, this alarm circuit will turn ON during
the released state regardless of any configuration settings.
21
If enabled, the panel monitors the circuits to ensure that at the specified load current, the circuit can deliver the load current whilst still
maintaining circuit device voltage compatibility levels via the transmission path resistance. If enabled, the sounder circuit must be fitted with
an Mxp-505 EOL Device.
www.advancedco.com 27
22
Triggering Signals to Equipment within the System.
The general fire alarm outputs can be used / configured to transmit triggering signals
to extinguishing system equipment such as pilot cylinders, warning devices, etc.
If required, the outputs can be non-silencing. These outputs can be individually
Section 4.24 disabled (sounder-1 / sounder-2).
Signals during the pre-discharge warning period should be intermittent and signals
Section 4.30 during the activated / released condition should be continuous.
In addition to turning the sounders ON, the sounders can be pulsed as an alert tone. Three separate pulse
patterns can be configured.
[Pulse Pattern]
PULSE-1 ON 1s. Use the buttons to highlight the required pulse period
PULSE-1 OFF 4s and then press the button to select it.
PULSE-2 ON 1s
A menu of parameters is presented for the selected
PULSE-2 OFF 1s sounder.
HOLD PULSE ON 1s
Maximum: 7
22
Do not use SNDR3 for these functions.
23
ON normally takes precedence over PULSE patterns. Exceptions: during the pre-discharge countdown or during a hold condition.
24
The mark to space ratio of the HOLD PULSE signal should be configured to create a different and unique pattern to the standard Alert
PULSE-1 or PULSE-2 patterns.
28 www.advancedco.com
3.3.3 Extinguishing
The Extinguishing Menu comprises three separate sub-menus. These cover the operating parameters of the
actuator output (Output Set-Up), the fire alarm and manual conditions required to activate the output (Cause &
Effect) and operating parameters for any Extract output (Extract Set-Up).
[Extinguish Select]
Output Set-Up .
Cause & Effect
Extract Set-Up
Use the buttons to highlight the required menu option
and then press the button to select it.
IN COUNTDOWN Specifies whether a RESET can be performed during the ALLOW RESET 26 PREVENT
countdown period. PREVENT RESET
FLOW DETECTION Specifies whether Flow Detection is in use. When set to YES/NO27 YES
YES, the “Released” condition will not be established if
flow is not detected during the release period. The
display will also show “No flow Detected”.
25
This setting is not in accordance with BS EN 12094-1: 2003.
26
This setting is not in accordance with BS EN 12094-1: 2003.
27
When set to NO, the RELEASED condition is established at the instance the actuator output is turned on.
NOTE: Irrespective of the setting for this parameter, if a valid signal is received on the flow input circuit then a RELEASED condition will be
established.
www.advancedco.com 29
[Extinguish C&E] Some options are mutually exclusive. Depending on the
Release Active When:- options selected, some options are inhibited and cannot be
TWO Z1&Z2 : √ . adjusted – the current setting is shown as ‘- -‘.
TWO Z1&Z3 : X The settings only apply to the AFD inputs. A Manual
TWO Z2&Z3 : X Trigger input will immediately generate the activated
ALL Z1&Z2&Z3 : -- condition.
IMMEDIATE Z1 : -- If all three ‘Two Zone’ parameters are enabled then the
IMMEDIATE Z2 : -- activated condition is established when any two of the
three zones are in the fire condition.
IMMEDIATE Z3 : --
Use the buttons to highlight the required option and then press the button to select it. The table below
details each available option.
Parameter Comments / Description Options Default
Setting
TWO Z1&Z2 Determines if the activated condition is established by a , X, --
fire condition in two zones – Zones 1 and 2.
TWO Z1&Z3 Determines if the activated condition is established by a , X, -- X
fire condition in two zones – Zones 1 and 3.
TWO Z2&Z3 Determines if the activated condition is established by a , X, -- X
fire condition in two zones – Zones 2 and 3.
ALL Z1&Z2&Z3 Determines if the activated condition is established only 28, X, -- --
when all three zone detection circuits are in a fire
condition.
IMMEDIATE Z1 Determines if the activated condition is established when a , X, -- --
fire occurs on Zone 1
IMMEDIATE Z2 Determines if the activated condition is established when a , X, -- --
fire occurs on Zone 2
IMMEDIATE Z2 Determines if the activated condition is established when a , X, -- --
fire occurs on Zone 3
28
This setting is not in accordance with BS EN 12094-1: 2003.
30 www.advancedco.com
3.3.4 Inputs
The display presents a list of the programmable inputs along with their current settings.
[Input Settings] Use the buttons to highlight the required input and
PROG INPUT 1: . then press the button to select / change it.
NOT IN USE . The table below details each available input and the
PROG INPUT 2: programmable settings.
NOT IN USE
The default setting for all inputs is NOT IN USE except:
PROG INPUT 3:
KEY-SWITCH 1 = LEVEL 2 ACCESS
KEY-SWITCH 2 = MODE SELECT
29
Inputs Setting Options Comments
PROG INPUT 1 NOT IN USE The Input is not used.
PROG INPUT 2 * SOUND ALARMS Activating an input with this setting will cause all sounder outputs to operate as
programmed.
PROG INPUT 3 * SILENCE ALARMS Activating an input with this setting will cause all sounder outputs to be Silenced
(where permitted).
PROG INPUT 4 * RESET Activating an input with this setting will cause the panel to be reset (if permitted).
KEY-SWITCH 1 EXT. FAULT Activating an input with this setting will register a fault condition on the panel.
KEY-SWITCH 2 MANUAL TRIGGER Activating an input with this setting will initiate the manual release activated
condition.
PRESSURE Activating an input with this setting will register a pressure warning condition.
VALVE MON Activating an input with this setting will register a Valve Monitor warning
condition.
MODE SELECT Activating an input with this setting will select MANUAL ONLY mode. Note: When
multiple inputs are defined as mode select, then any switch in the active state will
set the system into MANUAL ONLY mode.
HOLD Activating an input with this setting will stop the activated condition countdown
timer preventing the release of the extinguishant.
ABORT Activating an input with this setting will abort the activated condition.
* LEVEL-2 ACCESS Activating an input with this setting will enable Level-2 Control Keys and Menu
functions. A password is not required.
START EXTRACT Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on for the programmed time.
KEEP EXTRACT ON Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on irrespective of any programmed
operation or times.
DISABLE GAS Activating one or more inputs with this setting will disable extinguishing (in the
same manner as the level-2 Disable/Enable menu option). Manual and automatic
triggering of gas release will be inhibited.
* DISABLE ZONES Activating one or more inputs with this setting will disable all detection zones.
DISABLE AUTO ZN Activating one or more inputs with this setting will disable all detection zones
which can affect an automatic release of gas (zones included in the cause &
effect logic).
29
For compliance with EN54-13 monitoring requirements, Inputs 1-4 shall only be used for EN12094-1 functions. Functions marked with a ‘*’
should not be used.
www.advancedco.com 31
3.3.5 Outputs
The display presents a list of the programmable outputs along with their current settings.
[Prog. Outputs] Use the buttons to highlight the required output and then
press the button to select / change it.
RELAY 1 .
> NOT IN USE . The table below details each available output and the
RELAY 2 programmable settings available. The output can also be
configured as an INVERTED output (indicated by an *
* GENERAL FAULT
character). In this mode, it is normally turned on and will turn off
AUX RELAY 1 when the applicable cause & effect occurs.
[Output Settings] Use the buttons to highlight the required option and then
press the button to select / change it.
MODE: .
NOT IN USE . The default settings are as follows:
INVERTED: NO RELAY 1: STAGE-1 [INVERTED = NO]
RELAY 2: RELEASED [INVERTED = NO]
AUX RELAY 1 – 8: NOT IN USE [INVERTED = NO]
SWITCHED AUX: RESET [INVERTED = YES]
AUX RELAY 1 FOLLOW SOUNDER 2 The output is activated when Sounder 2 is activated.
AUX RELAY 2 FOLLOW SOUNDER 3 The output is activated when Sounder 3 is activated.
AUX RELAY 3 GENERAL FIRE The output is activated if any fire condition event occurs.
AUX RELAY 4 GENERAL FAULT The output is activated if any fault condition event occurs.
AUX RELAY 5 STAGE-1 The output is activated when a first stage alarm is recognized.30
AUX RELAY 6 STAGE-2 The output is activated when a second stage release is recognized and the
actuator output is due to be operated.
AUX RELAY 7 RELEASED The output is activated when the release of extinguishant has been completed.
AUX RELAY 8 ON HOLD The output is activated when the release of extinguishant has been held.
SWITCHED AUX ABORTED The output is activated when the release is aborted. It remains in this state until
the panel is reset.
MANUAL MODE The output is activated when the manual only mode is selected. (In the off
position the output indicates auto+manual).
VALVE CLOSED The output is activated when the valve monitor is active.
RESET The output is activated for approximately 10-15 seconds when the panel is
reset.
ZONE1 or STAGE-2 The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 1.
ZONE2 or STAGE-2 The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 2.
ZONE3 or STAGE-2 The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 3.
EXTRACT The output is activated when the extract phase is in process.
TEST MODE The output is activated when any of the zones are in a test state.
SUPERVISORY The output is activated during a ‘Pressure Low’ or ‘Valve Stuck’ condition.
DISABLEMENT The output is activated whenever any disablement condition is present except
for the disablement of programmable releays.
WARNING The output is activated whenever a “Valve Closed”, “Aborted”, “Hold” or
“Manual Only” condition is present.
FIRE + MAN. TRIG The output is activated whenever a Fire condition exists or a manual trigger
has been used to initiate the release of gas. Remains active until a successful
Gas Reset (for Manual trigger condition) or while ever the Fire state persists.
30
NOTE: Stage-1 will also be activated as soon as an immediate Stage-2 condition (i.e. manual release or single zone fire alarm activation)
occurs.
32 www.advancedco.com
Outputs Setting Options Comments
MANUAL TRIGGER The output is activated whenever a manual trigger has been used to initiate the
release of gas. Remains active until a successful Gas Reset.
3.3.6 Passwords
The display presents a menu of user password options.
[Select User]
USER 1 1234
USER 1 1234
USER 2 1234
USER 3 1234 Use the buttons to highlight the required password
ENGINEER 7654 and then press the button to select / change it.
Maximum: 99999999
A time-out for Level 2 access can be configured – See Section 3.3.7 – if no buttons are pressed, the panel will
then automatically cancel Level 2 access and return to Level 1 access when the time-out has elapsed.
3.3.6.1 Default Passwords
USER 1 1234
USER 2 1234
USER 3 1234
USER 4 1234
ENGINEERS CODE 7654
www.advancedco.com 33
3.3.7 General Options
The display presents a menu of user general options.
Parameter Comments / Description Options Default
Setting
Level 2 Time Out The Level 2 Time Out can be configured in the range 0 – 5 0 – 5 Minutes 5 Minutes
minutes (0 = No time out – stay in Level 2)
After the timeout, the menu functions and user controls are
inhibited. Password entry is required to re-enable these.
Earth Detection Determines if the panel shall report earth detection faults. YES/NO YES
Pressure Inputs Determines the normal, quiescent state of the contacts Normally Open / Normally
associated with the equipment used to sense loss of Normally Closed Open
extinguishant pressure (applies to all system inputs used
for pressure loss detection).
Config Shows the checksum of the configuration memory. > Erase N/A
Configuration
Option to erase the configuration (press the button).
Program Shows the current program version > Show Checksum N/A
Press the button to show the program checksum.
Log Determines the information that is recorded in the log. Standard, Standard
Standard+
Standard+ Mode also records the return to normal
transitions.
Service Number Determines the telephone contact number that is shown ---
on the normal display when there is an acknowledged fault
condition.
Service Due Date Determines the date/time at which a fault warning dd-mmm-yyyy 06-01-2020
messages will be displayed to indicate service is overdue. hh:mm 10:00
Mute Determines if the panel permits the buzzer to be muted at LEVEL-1 LEVEL-1
Level 1 or if it can only be muted at Level 2. LEVEL-2
Reset Mode Determines if the user is presented with the choice of PROMPT PROMPT
resetting ‘gas only’ or ‘fire & gas’ on a reset , alternativley ALL
no menu is presented and ‘fire & gas’ are always reset.
Daylight Saving Used to turn on/ off daylight saving mode – which YES YES
automatically shifts the current time forward/ backwards by NO
1 hour on programmed days of the year.
EN54-2 [8.4] Determines if the panel shall annunciate a total loss of YES NO
power. NO
Forward Day Specifies on which day of the week the time will be shifted MON – SUN SUN
forwards by 1 hour.
34 www.advancedco.com
Parameter Comments / Description Options Default
Setting
Forward Month Specifies in which month the time will be shifted forwards JAN – DEC MAR
by 1 hour .
ST
Back Order Specifies which occurance of the day specified (below) in 1 LAST
ND
the month specified (below) the time will be shifted back by 2
RD
1 hour (at 2AM the time will change to 1AM). 3
4TH
LAST
Back Day Specifies on which day of the week the time will be shifted MON – SUN SUN
back by 1 hour.
Back Month Specifies in which month the time will be shifted back by 1 JAN – DEC OCT
hour.
OUTPUT-1 31 Determines the action if this output See Section 0 NOT IN USE
OUT-1 INVERT Determines whether the output is inverted (normally on) NO / YES NO
31 See Section 0
OUTPUT-2 Determines the action if this output NOT IN USE
OUT-2 INVERT Determines whether the output is inverted (normally on) NO / YES NO
BUZZER Determines if the buzzer is in use or not at this RSI NO / YES YES
TICK=MUTE Detemined if the buzzers in the panel and all other RSI NO / YES YES
can be muted from this RSI.
31
The optional 2-Way Relay card (Exp-007) must be installed in the RSI for these outputs.
www.advancedco.com 35
3.3.9 Enable PC LINK
The ENABLE PC LINK menu option allows a PC to be connected to the panel for upload / download.
[USB Port Enabled] The display shows the current status of the link. Possible
status messages are:
CURRENT STATUS: LOGO UPDATE (< PC)
IDLE
EVENT DATA TRANSFER (> PC)
CONFIG DATA TRANSGER (> PC)
NOTE: When this function is enabled and in use, any fault reporting of power supply (PSE)
fault conditions is temporarily suspended.
3.3.10 Exit
To exit from the Commissioning / Programming Menu, select the EXIT option and press the button. The
display prompts for the Level 3 password.
36 www.advancedco.com
4 Service and Maintenance
4.1 Maintenance Schedule
This equipment should be maintained in accordance with the regulations and codes appropriate to the country
and location of installation. The following is recommended if no other regulations apply.
4.1.1 Daily Actions
The site operator / user should perform the following checks and actions:
a) The panel indicates normal operation. If any faults exist, these should be recorded in a logbook.
b) Any recorded faults have received attention and have been signed off.
4.1.2 Monthly Actions
The site operator / user should perform the following checks and actions:
a) Any stand-by generators should be started and fuel levels checked.
b) Operate at least one call point or detector (from different zones each month) and check that the panel
enters a fire alarm condition and that the appropriate / programmed alarm or warning devices are sounded /
operated. Where permissible, this should include any links to the fire brigade or remote centre.
c) Check that all outstanding faults have been recorded and have received attention.
4.1.3 Quarterly Actions
The service / maintenance contractor should perform the following checks and actions:
a) Check that all entries in the logbook have been addressed, check the event log in the panel and take the
necessary remedial actions.
b) Visually inspect the panel for any moisture ingress or other deterioration, check all battery connections and
test / check the alarm, fault and other functions of the panel operation.
c) Ascertain if any building or structural alterations have been carried out that would affect the placement /
location of call points or detectors. If so, perform a visual inspection.
d) Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be
carried out as soon as possible.
4.1.4 Annual Actions
The service / maintenance contractor should perform the following checks and actions:
a) Perform the checks as recommended above in the daily, monthly and quarterly schedules.
b) Perform a complete “Walk Test” of the system to check that each call point and detector is operating to its
manufacturers’ specification.
c) Visually inspect all cable fittings. Check that the equipment is undamaged and that the conditions of
installation have not changed such that they fall outside of the equipment specifications.
d) Inspect and test all batteries and replace as required – refer to Section 4.2 for recommended replacement
schedule.
e) Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be
carried out as soon as possible.
www.advancedco.com 37
4.2 Replacement of Components
In general, all of the components parts used in the construction of the panel have been selected for long life and
reliability.
However, certain components may require to be changed on a regular service basis. The details of these are as
follows:
4.2.1 Batteries
For battery installation, see section 2.3.2
38 www.advancedco.com
5 Appendices
5.1 Appendix 1 – Forgotten Level 3 Password
Should the Level-3 password be forgotten, contact Customer Support to obtain a temporary permit number to
regain access to the panel programming functions.
Customer Support will require a decryption key displayed by the panel. To obtain this number, attempt to gain
access to the Level-3 Programming Functions entering “1” when prompted for the password. As soon as the
“Password Invalid” message is shown, press the “0” button and the display will show a decryption key. Make a
note of this number.
For example:
Enter Your Password
214728378
Customer Support will provide a temporary permit number that you can enter when prompted for the Level-3
password. As soon as access has been regained to the Level-3 Programming Functions, select the Passwords
Menu Option and check / change the Level-3 password. (Refer to Section 3.3.6 for further information).
www.advancedco.com 39
5.2 Appendix 2 – Compatible Devices
5.2.1 Detectors
Manufacturer Part Number Description №/ № / Zone
Zone (Schottky
32
bases)
Apollo 55000-215 Series-65 Ion smoke 32 26
55000-216 Series-65 Ion smoke 32 26
55000-217 Series-65 Ion smoke 32 26
55000-218 Series-65 Ion smoke (Integrating) 32 26
55000-219 Series-65 Ion smoke (Integrating) 32 26
55000-220 Series-65 Ion smoke (Integrating) 32 26
55000-315 Series-65 Photo-smoke 32 26
55000-316 Series-65 Photo-smoke 32 26
55000-317 Series-65 Photo-smoke 32 26
55000-120 Series-65 Heat A1R 30 26
55000-121 Series-65 Heat A1R 30 26
55000-122 Series-65 Heat A1R 32 26
55000-125 Series-65 Heat BR 30 26
55000-126 Series-65 Heat BR 30 26
55000-127 Series-65 Heat BR 32 26
55000-130 Series-65 Heat CR 30 26
55000-131 Series-65 Heat CR 30 26
55000-132 Series-65 Heat CR 32 26
55000-135 Series-65 Heat CS 30 26
55000-136 Series-65 Heat CS 30 26
55000-137 Series-65 Heat CS 32 26
32
The number of devices that can be fitted to a zone when using schottky diode bases. The figure stated ensures that all detector fires/
faults are registered under various worst case scenarios e.g. Fire detection with devices removed from bases:- all but the last device
removed from it’s base; 32 Ohms cable impedance; no E.O.L device fitted (open circuit).
Also note that calculations assume an Active end of line device exhibiting a ‘fault current’ of no more than 40uA.
40 www.advancedco.com
Manufacturer Part Number Description №/ № / Zone
Zone (Schottky
32
bases)
DCD-CE3 CDX Heat 32 24
DFG-60E CDX Heat 32 16
DFJ-AE3 CDX Heat 32 24
DFJ-CE3 CDX Heat 32 24
HF-24 UV Flame 8 8
SPC-ET CDX Beam 6 6
SPB-ET CDX Beam 7 6
SRA-ET CDX Beam 4 4
www.advancedco.com 41
5.3 Appendix 3 – Recommended Cables
5.3.1 Fire Rated Cables
For best performance, the prefered cables are 2-core twisted with overall shield.
33
1.5mm2 only.
34
Also available in steel wire armoured (SWA) and steel wire braid (SWB) formats. 1.0mm2 preferred for network.
35
Twisted pair cable suitable for use underground (NB NOT SINGLE WIRE ARMOURED)
42 www.advancedco.com
5.4 Appendix 4 – Troubleshooting
After commissioning, the control panel The factory settings of the control panel mean that the level-2 menu
appears to be stuck in Manual Only Mode. mode select function defaults to Manual Only Mode – to avoid inadvertant
I have no key-switches fitted/ activated. triggering during installation.
Change the level-2 menu mode from the following menu:-
Level 2 Menu->EXTINGUISHIN MODES->TRIGGER (select
‘AUTO+MANUAL’).
Note that if factory settings are restored, from the commissioniong menu,
the Manual Only Mode will automatically be re-instated.
I can’t reset the control panel during the As default, resetting the gas release during the countdown is prevented
pre-discharge countdown. (to comply with EN12094-1). A configuration setting can be changed to
allow reset during this time – see section 3.3.3.1 (IN COUNTDOWN
setting).
When testing the system, during the By entering the engineers code to select the EXTINGUISH MODES
discharge period, I have to wait until the menu from the Level-2 Menu, an option ‘STOP RELEASE’ is presented –
reset allowed time has elapsed. select this option to cancel the current activation sequence (allow a
reset).
The display shows the condition Note that the Valve monitor Input requires a different End Of Line resistor
“VALVE MONITOR INPUT” value for the ‘normal’ condition. If no valve is being monitored fit two 6.8K
Ohms resistors in parallel across the terminals (or a single 3.3K Ohms
“VALVE STUCK” resistor).
The pressure switch I am using has Various types of pressure monitoring equipment are available. To use
normally open contacts – when I connect it normally open contacts, modify the ‘Pressure Inputs’ configuration setting
to the system I continually get a ‘low in the Level-3->General Menu, see section 3.3.7.
pressure’ condition reported.
The control panel does not detect battery Ensure that the jumper link on the power supply module is in the correct
missing. position. See section 2.3.4
www.advancedco.com 43
This page is intentionally left blank.
44 www.advancedco.com
This page is intentionally left blank.
www.advancedco.com 45
This page is intentionally left blank.
46 www.advancedco.com
USER NOTES
www.advancedco.com 47
0086-CPD-541661
11
EN 12094-1: 2003
Electrical automatic control and delay device
Environmental class: A
1 Flooding Zone
Provided options:
- Delay of extinguishing signal
- Monitor Flow of Extinguishing Agent
- Monitoring of status of components
- Emergency Hold Device
- Control of flooding time: 0 – 1800s
- Manual Only Mode
- Triggering Signals to Equipment within the System
- Triggering Signals to Equipment outside the System
- Emergency Abort Device
- Activation of Alarm Devices with Different Signals
Provided options:
- Outputs to Fire Alarm Devices
- Delays to outputs
- Alarm Counter
- Test Condition
Ex-3001
Revision: 06
Advanced Electronics Ltd
Moorland Way, Cramlington, Northumberland, NE23 1WE UK
Tel: +44 (0)1670 707 111 Fax: +44 (0)1670 707 222
Email: sales@advancedco.com Web: www.advancedco.com
www.advancedco.com