240 Series DIN Panel Meters

An extensive range of 48, 72, 96 and 144mm DIN style panel meters offering
measurement of all electrical and electronic parameters. Meters are shock resistant
and vibration proof and supplied with terminal covers. A selection of slide in dials
and customised options are available.

Movements
In Crompton Instruments’ world-patented ‘Hi-Q’ taut band suspension, all the
delicate parts of the traditional instruments are eliminated. There are no pivots, no
jewel bearings, no hair-springs and no air damping vane. Instead, a tough platinum
ribbon suspends the moving element between front and rear tension springs.
Specially contoured pads are fitted to the ends of the spindle, and the working gap at
each end is filled with a high quality silicon fluid. The pads, together with the fluid
reservoir, form a system which acts as a resilient built-in shock absorber. This
provides both rotational and longitudinal damping as the moving element floats on
oil with no bearing friction and is effectively cushioned against shock and vibration.
360° Synchroscopes and power factor meters have robust pivot and jewel bearings
Features with oil damping.
An extensive range of specialist
measuring meters in 4 case sizes Dials, Scales and Pointers
Standard dials are matt white with black printed scales and bar knife-edge pointers.
Shock resistant taut band suspension
Black dials with white or yellow scales and pointers are also available.
Vibration-proof Hi-Q damping Interchangeable slide in dials are used on models 242, 243 and 244 90° moving iron,
Slide in dials for 90°current, voltage and moving coil and frequency meters.
frequency on models 242, 243 and 244 General options include red supplementary pointers, red indexes (quadrant scales),
red, green or blue lines, bands or segments, finely spaced divisions, multi-scales,
Terminal covers supplied as standard special scales and captions to customer' requirements.

Benefits Illumination
Low cost Internal illumination is available in the following models:
Local indication • 244 and 246 shortscale moving coil and moving iron vane.
• 243, 244 and 246 longscale moving coil and moving iron vane.
Ease of installation
Through dial (Translucent) illumination on 244 and 246 models.
Minimal training Edge illumination on 243, 244 and 246 models.
Low maintenance Replaceable 6, 12 or 24V lamps are used on all models except 243 longscale meters,
Customised options and features where the lamps are internal.

Applications Specification
Performance BSEN60051
Switchgear
Measuring Ranges DIN 43701
Distribution systems Accuracy Overload BSEN60051
Generator sets Dimensions DIN 43700
Scale Marking Generally DIN43802
Control panels
Magnetic Influence BSEN60051
Energy management Safety IEC414
Building management Terminals Clamp strap M4 up to 25A. Clamp strap M8 over 25A
Humidity Range Up to 95% RH (non condensing)
Utility power monitoring
Test Voltage @50Hz 2kV RMS for 1 minute
Process control Overload AC Current x 1.2 continuous x 10 for 5 seconds
Motor control Overload AC Voltage x 1.2 continuous x 2 for 5 seconds
Frequency See main pages for other instruments
Approvals Damping Time Less than 3 seconds is standard. More heavily damped
movements are available on request.
LRS and BV Approvals.
Standard Calibration 23°C
Operating Temperature -20°C to +60°C
Enclosure Code IP54 as standard (to BSEN60529). IP55 consult factory
Terminals IP20B with terminal cover or terminal
boots fitted
Case Grade UL94V0
Base Grade UL94V1

8
240 Series DIN Panel Meters

DIN 16257 symbol meaning for Specification Continued


calibration position Case Dimensions and panel cutout conform to IEC473, DIN
43700. Models 242, 243 and 244 have cases and bezels
Vertical injection moulded in flame retardant engineering
thermoplastic, recognised by Underwriters Laboratory
materials specification. All 246 models have pressed
steel cases.
Horizontal Bezel Slim-line DIN43802 black as standard
Bezel Window Standard sheet glass, with zero adjusters where
appropriate. Non reflecting glass or polycarbonate
shatterproof windows are available.
Installation Installations in switchboard panel or mosaic
Inclined 60° arrangement on equipment or machine with a panel
thickness of up to 40mm in a horizontal or vertical
plane. Installation Category III
Inclination of dial surface to the Fixing on Panel Models 242, 243 and 244 – 2 corner fixing clamps and
horizontal e.g 60°. tensioning thumb screws
Required orientation must always be Model 242 – available with a one piece ‘push on’ clamp.
stated when ordering if other than Model 246 - 2 side fixing spring clips
vertical mounting is required. Mounting Position Normal vertical mounting or as indicated on the scale
in accordance with DIN 16257. A deviation of ±15° is
permissible
Approvals Lloyds Shipping (LRS), Bureau Veritas (BV), EMC and LVD

Dimensions
Model 242 243 244 246
Bezel ‘A’ 48 x 48 72 x 72 96 x 96 144 x 144
Panel cut-out ‘B’ 45 x 45 68 x 68 92 x 92 138 x 138
Scale Length: 90° 42 65 94 145
Scale Length: 240° 72 112 150 230
Maximum overall depth ‘C’:
Ammeters and Voltmeters A.C. & D.C.* 64 64 64 60
Ammeters and Voltmeters with switch* – – 64 –
Dual Meters* – – 64 –
C Elapsed Time Meter/Hours Run* 64 64 64 –
Maximum Demand Indicator* – 64 64 60
Combined MDI & MI Indicator* – – 64 60
Maximum Demand Indicator with relay* – – 90 –
Frequency Meter 90°* 64 64 64 60
A Frequency Meter 240°* § § 120 125
Phase Angle, Power Factor Meter 90°* § § 107 §
240°* § § 107 §
M.C. Indicator with separate transducer* 64 64 64 60
Dynamometer 360° Synchroscope* – – 120 125
Dynamometer 360° Power Factor Meter* – – 120 –
A Phase Sequence Indicator* – 64 64 –
Position Indicator* § § 120 125
Speed Indicator* 64 64 64 60
Temperature Indicators* – – 120 125
Quadra Meters* – – 64 –
Panel cut-out Impulse Counters* 64 64 64 –
Wattmeter, Varmeter 90° § § 107 125
Maximum Panel B
Wattmeter, Varmeter 240° § § 107 125
thickness 10mm Model 244-21Y & 244-21Z – – 142 –
LED Synchroscope & Synchro Check Relay – – 80 –
LED 360° Synchroscope – – 80 –

§ Indicator Only
B * If separate terminal cover is used add 20 mm to dimension C
– Not available

9
240 Series DIN Panel Meters

Moving Iron A.C. Ammeters and Voltmeters


Designed to measure A.C. current or voltage, these meters indicate true r.m.s. values
and are substantially independent of system waveform. Scales are calibrated down
to 20%, and ammeters can have overload scales x2, x3, x5 or x6 for motor start duty.
Ammeters can be supplied for use with -/1A or -/5A current transformers, whilst
voltmeters can be scaled for use with voltage transformers. Heavy damping is
available as an option. Meters can be used to measure D.C. at reduced accuracy.

Specification – Short Scale


Accuracy: Class 1.5
Frequency: 50 or 60Hz, (400Hz on request)
Burden at 50Hz: Ammeters: 0.5VA
Voltmeters: Up to 4.5VA maximum
Ratings: Ammeters: 0.5A to 100A A.C. direct connected (40A for
242-75A and 246-07A). Maximum system voltage
Connections 720V A.C. Low load / high middle maximum 10A
A.C. Ammeter Voltmeters: 6V to 600V

Product Codes – Short Scale


Bezel Size mm 48 72 96 144
Scale length mm 42 65 94 145
Product Codes
A.C. ammeter 242-75A 243-02A 244-02A 246-07A
x2 overload ammeter 242-752 243-022 244-022 246-072
x3 overload ammeter 242-753 243-023 244-023 246-073
x5 overload ammeter 242-755 243-025 244-025 246-075
x6 overload ammeter 242-756 243-026 244-026 246-076
Low load ammeter – 243-02H 244-02H –
A.C. voltmeter 242-75V 243-02V 244-02V 246-07V
Low middle voltmeter – 243-02M 244-02M –

Specification – Long Scale


Accuracy: Class 1.5
Frequency: 50 or 60Hz, (400Hz on request)
A.C. Voltmeter Burden at 50Hz: Ammeters: 1.5VA
Voltmeters: 4.5VA maximum
Ratings: Ammeters: 0.5A to 25A A.C. direct connected
Maximum system voltage 720V A.C. Low load / high
middle (maximum 10A)
Voltmeters: 6V to 600V A.C.

Product Codes – Long Scale


Bezel Size mm 48 72 96 144
Scale length mm 72 112 150 230
Product Codes
Ammeter 242-03A 243-03A 244-03A 246-03A
x2 overload ammeters 242-032 243-032 244-032 246-032
x3 overload ammeters 242-033 243-033 244-033 246-034
x5 overload ammeters 242-035 243-035 244-035 246-035
x6 overload ammeters 242-036 243-036 244-036 246-036
Low load ammeters – 243-03H 244-03H –
Voltmeter 242-03V 243-03V 244-03V 246-03V

10
240 Series DIN Panel Meters

Maximum Demand Indicators


The thermal/time characteristic of an MDI monitors the most economic use of cable,
fusegear and transformers. The directly heated bimetal element indicates mean
r.m.s. current over 8, 15, or 20 mins, and a red slave pointer shows the highest value
reached. The reset knob is wire sealable. Scales are calibrated to match the C.T.
primary plus 20% overload. End values are selected from : 1.2, 1.8, 2.4, 3, 3.6, 4.8, 6,
7.2, 9 Amps and their multiples of 10 and 100.

Specification
Accuracy: Class 3
Options: 5A for use with separate C.T.
5/5A saturating C.T.
1/5A saturating C.T.
Burden at 50 Hz: MDI - 2.5VA, C.T. - 2VA
Overload withstand: Standard: 5 x FL for 5 seconds, 10 x FL for 1 second
Connections With Saturating C.T.: 10 x FL for 3 seconds,
20 x FL for 1 second
Frequency: 50/60Hz

Product Codes
Bezel Size mm 72 96 144
Scale length mm* 65 94 145
Product Codes
8 Minute Time Lag
Without limiting C.T. for use with 5A C.T. 243-16B 244-16B –
With self-contained 5/5A limiting C.T. – 244-16R –
15 Minute Time Lag
Without limiting C.T. for use with 5A C.T. 243-16A 244-16A 246-16A
With self-contained 5/5A limiting C.T. – 244-16E –
20 Minute Time Lag
Without limiting C.T. for use with 5A C.T. 243-16J 244-16J 246-16J
With self-contained 5/5A limiting C.T. – 244-16K –
* Scaled 0/100/120% of C.T. primary value.

Combined A.C. Ammeter and Maximum Demand


Indicator
Where the instantaneous and maximum demand currents are required, these
instruments combine both movements in one case. It can also replace an existing
A.C. Ammeter. Specification as above.

Specification
Accuracy: Moving Iron Ammeter: Class 1.5, MDI: Class 3
Burden at 50Hz: MI - 0.5VA, MDI - 2.5VA, Saturating C.T. - 2VA

Product Codes
Bezel Size mm 72 96 144
Scale length mm* 65 94 145
Product Codes
8 Minute Time Lag
Without limiting C.T. for use with 5A C.T. 3VA – 244-16Q –
With self-contained 5/5A limiting C.T. 5VA – 244-16T –
15 Minute Time Lag
Without limiting C.T. for use with 5A C.T. 3VA – 244-16C 246-16C
With self-contained 5/5A limiting C.T. 5VA – 244-16F 246-16F
20 Minute Time Lag
Without limiting C.T. for use with 5A C.T. 3VA – 244-16H –
With self-contained 5/5A limiting C.T. 5VA – 244-16L –
* Scaled 0/100/120% of C.T. primary value.

11
240 Series DIN Panel Meters

Frequency Meters
These Frequency meters use an integral electronic converter and a moving coil
indicator. This meter is easy to read with an accuracy Class 0.5.

Specification
Accuracy: Class 0.5
Ratings: 100V-125V A.C
200V-250V A.C.
380V-440V A.C.*
500V A.C.*
*For voltages above 380V use 242-013 with a 253-THZ,
in place of 242-41S
Models available for use with V.T.s
Frequency 0.5%: 45/55Hz,
55/65Hz,
Connections 45/65Hz,
360/440Hz
Other scalings available on request
Burden: 4VA Maximum

Product Code
Bezel Size mm 48 48 72 72 96 96 144 144
Scale length mm 42 72 65 112 94 145
Product Code 242-41S 242-053 243-41S 243-053 244-41S 244-41L 246-41S 246-41L
+253-THZ +253-THZ

Dual Frequency Meters


Two instruments in one case can be used to measure a wide range of frequencies.
These dual instruments save both panel space and assemly time. The 244-41D is an
ideal component in sychronising applications.

Specification
Accuracy: Class 0.5
Ratings: 100V-125V A.C
200V-250V A.C.
380V-440V A.C.
500V A.C.
Models available for use with V.T.s
Frequency 0.5%: 45/55Hz,
55/65Hz,
45/65Hz,
Connections 360/440Hz
Burden: 4VA Maximum

Product Code
Bezel Size mm 96
Scale length mm 65
Product Code 244-41D

12
240 Series DIN Panel Meters

Moving Coil Rectified A.C. Ammeters and Voltmeters


For high frequency or linear full scale A.C. measurements, these instruments
measure average values of sinusoidal waveforms and are scaled in r.m.s. values.
The high quality silicon bridge rectifier gives a linear scale down to near zero, where
some compression occurs.

Specification – Short Scale


Accuracy: 1.5% ES
Ratings: Ammeters: Model 242 from 250µA to 20mA
Model 243 from 250µA to 1A Models 244/246 from 250µA to 20A
Voltmeters: 15V to 600V a.c. direct connected
Models available for use with V.T.s
Frequency: 50/60Hz, (Single Frequencies 25Hz to 3kHz on request)

Connections Product Codes – Short Scale


A.C. Ammeter Bezel Size mm 48 72 96 144
Scale length mm 42 65 94 145
Product Codes
Ammeters 242-89B 243-01B 244-01B 246-10B
Voltmeters 242-89W 243-01W 244-01W 246-10W

Specification – Long Scale


Accuracy: 1.5 % ES
Ratings: Ammeters: 250µA to 1A A.C.Up to 30A on models 244/246-05B
Voltmeters: 15V to 600V Direct connected
A.C. Voltmeter Models available for use with V.Ts
Frequency: 50/60Hz. (Single frequencies 25Hz to 3kHz on request)

Product Codes – Long Scale


Bezel Size mm 48 72 96 144
Scale length mm 72 112 150 230
Product Codes
Ammeters 242-05B 243-05B 244-05B 246-05B
Voltmeters 242-05W 243-05W 244-05W 246-05W

Dual A.C. Ammeters and Voltmeters


The two instruments in one case can be used for independent measurement of 2
parameters or the comparison of the two inputs. For example, when an A.C.
generator is to be connected in parallel with mains supply where voltage, phase and
frequency must coincide.

Specification
Accuracy: 1.5% ES
Ratings: Ammeter: 250µA to 10A A.C.
Voltmeter: 15 to 600V direct connected
Frequency: 50/60Hz (single frequencies 25Hz to 3kHz on request)

Product Codes
Bezel Size mm 96
Scale length mm 65
Product Codes
Ammeters 244-80F
Voltmeters 244-80L
Dual A.C. Ammeter Dual A.C. Voltmeter
Direct Connected

13
240 Series DIN Panel Meters

Moving Coil Rectified A.C. Ammeters and Voltmeters


with Selector Switch
These moving coil rectified A.C. meters measure voltage or current and incorporate a
selector switch which eliminates the need to fit a separate selector switch, thus
saving panel space and assembly time.
A.C. Ammeters with selector switch are suitable for:
• Line current measurement in a single 96 DIN housing with an ‘off’ position.
• Internal 1A or 5A/10mA C.T.s are fitted to ensure the primary C.T.s are always
in circuit.
A.C. Voltmeters with selector switch are suitable for:
• Three phase four wire line to line and line to neutral voltage measurement in a
single 96 DIN housing.
• Three phase three wire line to line voltage measurement in a single 96 DIN
housing with ‘off’ position.
Connections
A.C. Ammeters with Selector Switch Specification
Accuracy: 1.5% ES
Frequency: 50/60Hz (single frequencies 25Hz to 3kHz on request)
Ratings: Ammeters: 250µA to 5A A.C. via 1:1 C.T.
Over 5A via C.T.s.
Voltmeters: 15V to 600V direct connected Models
available for use with V.T.s
Bezel Size: 96mm
Scale Length: 94mm

Product Codes – A.C. Ammeter with Selector Switch


Model Switch Notation
244-01E-AMP1 3 (+off) switch pos; T, S, R, Off
244-01E-AMP2 3 (+off) switch pos; B, Y, R, Off
244-01E-AMP3 3 (+off) switch pos; L3, L2, L1, Off
244-01E-AMP4 3 (+off) switch pos; Off, R, W, B

Product Codes – A.C. Voltmeters with Selector Switch


Model Switch Notation
244-01Q-SW1 6 switch pos; RT, ST, RS, RO, SO, TO
A.C. Voltmeters with Selector Switch 244-01Q-SW2 6 switch pos; RB, YR, BY, BN, YN, RN
244-01Q-SW3 6 switch pos; L1L3, L1L2, L2L3, L3N,
L2N, L1N
244-01Q-SW4 3 (+off) switch pos; RT, ST, RS, Off
244-01Q-SW5 3 (+off) switch pos; RY, YB, RB, Off
244-01Q-SW6 3 (+off) switch pos; L1L2, L2L3, L3L1, Off
244-01Q-SW7 6 switch pos; RN, WN, BN, BW, WR, RB
244-01Q-SW8 3 (+off) switch pos; RW, WB, RB, Off

14
240 Series DIN Panel Meters

Elapsed Time Meter or Hours Run Meters


Elapsed time meters or hours run meters monitor "ON/RUN" time of plant and
equipment allowing the user to perform functions such as production efficiency, cost
estimating and service period monitoring for preventative maintenance etc. The time
is measured in increments of 0.01h up to 99999.99 hours after which time the meter
resets to zero. Meters are non resettable to prevent accidental resetting.

Specification
Display: 99999.99
Voltage: 100-125V A.C.
200-250V A.C.
380-440V A.C.
Frequency: 50 or 60Hz
Burden: 2.5VA for D.C. input models
Voltage: 10/27V (12, 24V) D.C.
Connections 38/58V (48V) D.C.
Elapsed Time/Hours Run Meters A.C. 90/132V (110V) D.C.

Product Codes
Bezel Size mm 48 72 96
Scale length 99999.99h 99999.99h 99999.99h
Product Code
50Hz 242-158 243-155 244-155
60Hz 242-159 243-156 244-156
D.C. Input 242-157 243-151 244-151

Elapsed Time/Hours Run Meters D.C.

Impulse Counters
Impulse counters can be used to measure any parameter where a pulse can be
applied that is directly proportional to the parameter being measured. For example.
the number of motor starts or by using a combination of Paladin Transducers, kW.h.,
Ampere hour, VA hour etc., can be recorded. The Impulse counter counts one digit
every time an on/off voltage pulse is applied to the input terminals, and is non
resettable to prevent accidental resetting.

Specification
Accuracy: Pulse for Pulse
Display: 6 Digit 999999
Ratings: 110V,120V, 220V, 230V, 240V, or 415V A.C.±10%
50/60Hz
12V or 24V D.C. ±10%
Burden: 0.75VA (110V A.C.)
2.70VA (415V A.C.)
80mW (12V D.C.)
Pulse width: 50ms Minimum
Mark/Space Ratio: 1:1

Product Codes
Bezel Size mm 48 72 96
Scale length 999999 999999 999999
Product Codes
D.C. Input
12V 242-259G-MU 243-259G-MU 244-259G-MU
24V 242-259G-BD 243-259G-BD 244-259G-BD
A.C. Input
110V 242-259G-PM 243-259G-PM 244-259G-PM
120V 242-259G-PQ 243-259G-PQ 244-259G-PQ
220V 242-259G-R4 243-259G-R4 244-259G-R4
230V 242-259G-RQ 243-259G-RQ 244-259G-RQ
240V 242-259G-RR 243-259G-RR 244-259G-RR
380V 242-259G-RU 243-259G-RU 244-259G-RU
415V 242-259G-SB 243-259G-SB 244-259G-SB

15
240 Series DIN Panel Meters

Quadra 3 in 1 and 4 in 1
A range of 96mm2 DIN style 3 in 1 and 4 in 1 meters offering reduced stock holding
and savings on space, installation and commissioning. Ideally suited for generator
set applications, the range offers measurement of A.C. and D.C., current and voltage,
frequency or elapsed time. Options include customer logo on dial, coloured dial,
panel mounting gasket and heavily dampened movements.

Specification
Voltmeter: 110, 120, 200, 230, 240, 380, 400, 415, 440, 480V A.C.
nominal. Maximum end scale 600 volts.
Frequency Meter Inputs: 45/55Hz, 55/65Hz, 45/65Hz, 360/440Hz
Voltage inputs: As voltmeter inputs above
Ammeter inputs: 10mA A.C. 1 or 5A input (internal C.T.)
Hours Run: 110, 120, 220, 230, 240, 380, 400, 415, 440 Volts
50 or 60Hz
Hour Run Counting Range: 99999.99 hours
D.C. Current: 250µA to 1 Amp D.C. including 1, 5, 10, 20 and 4-20mA
D.C. for transducer inputs
D.C. Volts: 50mV to 600 Volts D.C. including 50, 60, 75 and 150mV
for shunt inputs
Burden: Current: 0.75VA per phase
Hours Run: 2.5VA
LCD Hours Run: 0.5VA
Voltage: 0.5VA
Frequency: 4VA
When ordering please specify the inputs for each parameter and the scaling required.

Product Codes
Code Description
244-80C ACV + DCI + ACA + DCA
244-80D 3 x DCI + D.C. ETM (LCD)
244-80G 3 x ACA
244-80H 3 x ACV + FRQ
244-80I 3 x ACA + ETM
244-80J 3 x ACA + ETM (LCD)
244-80K FRQ + ACV +DCI
244-80N ACA + ACV + FRQ + ETM
244-80P 3 x ACV
244-80Q ACV // FRQ // ETM + ACA
244-80R ACV // ETM + 2 x ACV
244-80S 2 x ACV + 2 x ACA
244-80T FRQ // ETM + ACV
244-80U 3 x ACA + ACV
244-80W ETM // FRQ + DCI + ACV
244-80X 4 x DCI
244-80Y ETM // FRQ + DCI
244-80Z ACV + ACA + FRQ // ETM
244-802 2 x ACV + ACA + ETM
244-803 ACV + FRQ + 2 x ACA
244-804 3 x ACA + DCI
244-806 3 x ACV + ACA
244-807 V, Hz, ETM + SWITCH

Description
ACV = Rectified A.C. voltmeter
ACA = Rectified A.C. ammeter
DCA = D.C. ammeter
DCI = D.C. indicator
ETM = Elapsed time meter
ETM(LCD) = LCD elapsed time meter
FRQ = Frequency Meter
// = In parallel with

16
240 Series DIN Panel Meters

Quadra 3 in 1 and 4 in 1

Connections

244-80H
Terminals
1 Volt Neutral L3
3 Volt Live L3
5 Frequency Neutral
6 Volt Live L2
7 Frequency Live
8 Volt Neutral L1
9 Volt Live L1
11 Volt Neutral L2

244-80I
Terminals
1 Neutral Hours Run
3 Live Hours Run
5 Current Start Red L1
10 Current Finish Black L1
11 Current Start Red L3
7 Current Finish Black L3
9 Current Start Red L2
8 Current Finish Black L2

244-80J
Terminals
1 Current Start Red L1
3 Current Finish Black L1
2 Live Hours Run
4 Neutral Hours Run
6 Current Start Red L2
8 Current Finish Black L2
9 Current Start Red L3
7 Current Finish Black L3

244-80Q
Terminals
1 Live Hours Run
5 Live Volts and Frequency
7 Neutral
8 Current Start Red
9 Current Finish Black

244-80T
Terminals
1 Voltmeter Input
3 Voltmeter Input
5 Hours Run & Frequency Meter Input
6 Hours Run & Frequency Meter Input

244-80X
Terminals
2 Positive DC 2
3 Positive DC 3
4 Negative DC 2
5 Negative DC 3
6 Positive DC 1
7 Positive DC 4
8 Negative DC 1
11 Negative DC 4

17
240 Series DIN Panel Meters

Moving Coil D.C. Ammeters and Voltmeters


Moving Coil Meters are suitable for all D.C. systems. The linear scale is calibrated
down to zero and the accuracy maintained down to 10%. High currents are measured
with separate shunts and suitably scaled indicators. Suppressed, centre and offset
zero models are available.

Specification
Accuracy: Class 1.5
Ratings: Ammeters: 100µA to 25A, (200µA for 05 model)
4/20mA suppressed zero
40A for model 243/244-01A
Voltmeters: 50mV to 600V
1/5V suppressed zero
50, 60, 75, 100, 150mV for use with shunts
Impedance: Ammeters: 75mV internal shunt above 60mA
Connections Voltmeters: 1000Ω/V above 1V
D.C. Ammeter
Further details on our T-Sheet T118 available on request.

Product Codes – Short Scale


Bezel Size mm 48 72 96 144
Scale length mm 42 65 94 145
Product Codes
Ammeters 242-89A 243-01A 244-01A 246-10A
Ammeters suppressed zero 242-89R 243-01R 244-01R 246-10R
D.C. Voltmeter Voltmeters 242-89V 243-01V 244-01V 246-10V
Voltmeters suppressed zero 242-89S 243-01S 244-01S 246-10S

Product Codes – Long Scale


Bezel Size mm 48 72 96 144
Scale length mm 72 112 150 230
Product Codes
Ammeter 242-05A 243-05A 244-05A 246-05A
Ammeters suppressed zero 242-05R 243-05R 244-05R 246-05R
Voltmeters 242-05V 243-05V 244-05V 246-05V
Voltmeters suppressed zero 242-05S 243-05S 244-05S 246-05S

Moving Coil Dual D.C. Ammeters and Voltmeters


Dual instruments can be used to measure a wide range of currents and voltages,
and save both space and time by requiring only one panel cut-out.
The 244-80M allows for independent measurement of two D.C. currents in one case.
The 244-80E allows for independent measurement of two D.C. voltages in one case.

Specification
Accuracy: Class 1.5
Ratings: D.C. Current: 100µA to 25A direct connected
Connections 4/20mA suppressed zero.
Dual D.C. Ammeter D.C. Volts: 50mV to 600V
1/5 volt suppressed zero
50, 60, 75, 150mV for use with shunts.

Product Codes
Bezel Size mm 96
Scale length mm 94
Product Code
Dual D.C. Voltmeter
Ammeters 244-80M
Voltmeters 244-80E

18
240 Series DIN Panel Meters

Temperature Indicators
Longscale Indicators to read temperature values, usually remotely with RTD or
thermocouple sensors supplied by the customer. RTD (Resistance Temperature
Detector) indicators measure the change in resistance of the sensor. A 2 or 3 wire
system may be used. Thermocouple indicators accept standard millivolt input
signals. Cold junction compensation is provided and thermocouple break indication
is incorporated.

Specification
Accuracy: Class 1.5 - Indicator only. RTD indicator suitable for
10Ω copper 100Ω platinum, 100 & 120Ω nickel sensors
Power in RTD is 100µW approximately. Thermocouple
indicator suitable for J (0-700°C), K (0-1200°C)
50Ω maximum Circuit Resistance.
Auxiliary Supply: Model 45R: from 63.5V to 480V A.C. at 50/60Hz
Connections Model 45T: 110, 115, 220, 240, 380, 400, 480V A.C.
Thermocouple Indicators -45TG and 12, 24, 48, 110, 125V D.C.
Burden: -45R 2VA, -45T 3VA

Product Codes
Bezel Size mm 96 144
Scale length mm 150 230
Product Codes
RTD 244-45R 246-45R
Thermocouple 244-45T 246-45T

RTD Indicators -45RG


Process Indicators
Used to check process functions locally or remotely at centralised controls. These
moving coil instruments offer a wide variety of electrical and mechanical readouts
operated by transducer, tachogenerator, thermocouple, resistance bulb or other D.C.
analogue signals. Suppressed, centre and offset zero models are available on request.

Specification
Accuracy: Class 1.5
Ratings: 1, 2, 5, 10 & 20mA. 4/20mA suppressed zero.
Burden: See our technical data sheet T118.

Product Codes – Short Scale Models


Bezel Size mm 48 72 96 144
Scale length mm 42 65 94 145
Product Codes
A.C. Current 242-89A 243-01A 244-01A 246-10A
A.C. Voltage 242-89V 243-01V 244-01V 246-10V
Speed 242-892 243-012 244-012 246-102
Frequency 242-893 243-013 244-013 246-103
Phase Angle 242-894 243-014 244-014 246-104
Watts 242-895 243-015 244-015 246-105
VArs 242-896 243-016 244-016 246-106
VA 242-897 243-017 244-017 246-107

Product Codes – Long Scale Models


Bezel Size mm 48 72 96 144
Scale length mm 72 112 150 230
Product Codes
Connections A.C. Current 242-05A 243-05A 244-05A 246-05A
A.C. Voltage 242-05V 243-05V 244-05V 246-05V
Speed 242-052 243-052 244-052 246-052
Frequency 242-053 243-053 244-053 246-053
Phase Angle 242-054 243-054 244-054 246-054
Watts 242-055 243-055 244-055 246-055
VArs 242-056 243-056 244-056 246-056
VA 242-057 243-057 244-057 246-057

19
240 Series DIN Panel Meters

Moving Coil Tap Position Indicators


These longscale position Indicators monitor transformer tap position, hoist or valve
position, etc. They employ a 3 wire system and 11 to 18 positions can be provided
using 400Ω steps. The measuring system comprises a moving coil indicator,
stabilised power supply & transducer. The remote potentiometer or resistance
thermometer sensor to be supplied by the customer.

Specification
Accuracy: Class 1.5
Auxiliary Supply: A.C.: 50, 110, 220, 240V 50/60Hz
D.C.: 50, 110, 125, 220V ±15%
Burden: 2VA

Product Code
Connections Bezel size mm 96 144
Tap position indicator with self Scale length mm 150 230
contained power source Product Code
Position Indicator 244-45P 246-45P

Phase Sequence Indicators


An Electronic Phase Sequence Indicator ensures correct phase rotation and the
presence of all 3 phase supplies. Incorrect phase or loss of phase can cause serious
damage in a wide range of electrical machines. Ship to shore supplies, mobile
generators and remote installations are particularly vulnerable to this problem.

Specification
Voltage: 151/300V, 301/500V
100/150V (Model 244-12P only)
Frequency: 50/60Hz
Burden: 2.5VA/phase

Product Code
Bezel size mm 72 96
Product Code
Connections
Phase Sequence Indicator 243-12P 244-12P
Phase Sequence Indicators

20
240 Series DIN Panel Meters

Electronic Phase Angle Meters


These Phase Angle meters indicate the phase displacement between current and
voltage. Used in applications where the phase angle must be monitored, for example
with tariffs having VAr penalties, or to optimise generator power delivery.
The measuring system comprises a moving coil indicator and a phase angle
transducer. The 244 and 246 models are self contained.

Specification
Accuracy: Class 2.5 (2° electrical)
Ratings: Current: 1A or 5A for C.T.s
Voltage: 100/130V, 200-250V & 380-450V
100 - 110 for V.T. use.
Frequency: 50Hz, 60Hz, 400Hz.
Burden at 50Hz: Current: 1VA
Voltage: 4VA per Phase
Connections Current range: 20% to 125%
Single Phase Systems
Product Code - Short Scale Models
Bezel Size mm 72 96 144
Scale length mm 65 94 145
Product Code
Single Phase 243-014G-FA+ 244-42B 246-425
256-TPS
3 Phase 3/4 wire 243-014G-FA+ 244-42A 246-42A
Balanced Load 256-TPT

Product Code - Long Scale Models


Bezel Size mm 72 96 144
Scale length mm 112 150 230
Product Code
Single Phase 243-054G-FA+ 244-425 246-425
256-TPS
3 Phase 3/4 wire – 244-427 246-427
Balanced Load

3 Phase, 3 or 4 Wire Balanced Systems

21
240 Series DIN Panel Meters

360° Dynamometer Power Factor Indicators


These Power Factor Indicators are suitable for generators or supplies operating in
parallel. The four quadrant 360° scale calibrated cos ø 0-1-0-1-0 indicates forward
(export) and reverse (import) power flow for inductive and capacitive loads.

Specification
Accuracy: Class 2.5 (2° electrical)
Ratings: Current: -/1A or -/5A for C.T.’s
Voltage: 60 to 600V, 100/110 for V.T. use.
Frequency: 50Hz or 60Hz
Burden: Current: 2VA per coil @ 50Hz
Voltage: 4VA per coil @ 50hz (7.5VA above 250V)

Product Codes
Bezel size mm 96 144
Scale length 360° 360°
Product Codes
Single Phase 244-137 246-137
3 Phase 3 or 4 Wire 3 Currents + 1 Voltage 244-131 246-131
3 Phase 3 or 4 Wire 1 Current + 3 Voltages 244-132 246-132
3 Phase 3 or 4 Wire Unbalanced Load 244-136 246-136

Connections
Single Phase

3 Phase 3 or 4 Wire 1 Current 3 Voltages Balanced Load

3 Phase 3 or 4 Wire Unbalanced Load

3 Phase 3 or 4 Wire 3 Currents 1 Voltage Balanced Load

3 Phase 3 Wire Using Two C.T.s Unbalanced Load

22
240 Series DIN Panel Meters

360° Dynamometer Synchroscope


Where manual parallelling of two A.C. systems is necessary, the frequency of both
systems can be monitored by a Synchroscope. The systems are synchronised when
the pointer is stationary in the 12 o'clock position. The instrument is rated for
continuous operation and connection, and silicon oil damping is employed.

Specification
Accuracy: Class 2.5 (2° electrical)
Ratings Voltage: 100-125V, 200-250V, 380-450V*
* Use transformer box 855-954 100-110V for V.T. use
Frequency: 50Hz,60Hz, 50/60Hz, 400Hz
Burden at 50Hz: 5VA maximum.

Product Codes
Connections Bezel size mm 96 144
Scale length 360° 360°
Product Codes
50Hz 244-145 246-145
60Hz 244-146 246-146
50/60Hz 244-147 246-147
400Hz 244-144 246-144

23
240 Series DIN Panel Meters

360° LED Synchroscope and Synchro Check Relay


Where manual parallelling of two A.C. systems is desired, the frequency of both
systems can be monitored by an LED Synchroscope. The systems are synchronised
when the green LED is lit in the 12 o’clock position. The instrument is rated for
continuous operation and connection. Where semi-automatic parallelling of two A.C.
systems is desired, the voltage, phase displacement and the frequency of both
systems can be monitored by an LED Synchroscope and Synchro Check Relay.
Voltage, Phase angle and time delay controls are provided. The systems are
synchronised when the green triangular LEDs are lit together with the GEN/BUS
green LEDs. A dead bus option is also available.

Specification
Ratings Voltage: 63.5, 110, 120, 220, 230, 240, 380, 400, 415, 440, 480V
110/120V (115V Nominal)
220/240V (230V nominal)
Connections 380/480V (430V nominal)
360° LED Synchroscope Volts A.C. or via V.T.
Frequency: 40/65Hz
Burden at 50Hz: 4VA maximum
Suitable for single or three phase systems
Safety: IEC1010-1 (300V A.C. rms installation degree 2)
Dielectric: 4kV rms for 1 minute
Isolation: BUS/GEN/RELAY
Vibration: To Lloyds shipping specification
*Phase difference: +0 to 20°. +/-1°
*Voltage difference: +0 to 20% +/-2%
0 to 10% for models G & H
*Time Delay: 0 to 2.5 seconds +10%
*Accuracy: Synchronisation at T.D.C. is +1˚
*360° LED Synchroscope and Synchro Check Relay Only.

360° LED Synchroscope and Synchro Product Codes


Check Relay Bezel Size mm 96 96 96
Scale Length mm 360° LED 360° LED 360° LED
3 or 4 Wire Synchroscope Synchroscope Synchroscope
40-65Hz and Synchro Check and Synchro
Check Relay
Relay (Dead Bus)
Product Code
110/120V – 244-14GG-POBX 244-14HG-POBX
220/240V – 244-14GG-R5BX 244-14HG-R5BX
380/480V – 244-14GG-RUBX 244-14HG-RUBX
63.5V 244-14AG-NXYY 244-14LG-NXBX 244-14DG-NXBX
110V 244-14AG-PMYY 244-14LG-PMBX 244-14DG-PMBX
220V 244-14AG-R4YY 244-14LG-R4BX 244-14DG-R4BX
230V 244-14AG-RQYY 244-14LG-RQBX 244-14DG-RQBX
240V 244-14AG-RRYY 244-14LG-RRBX 244-14DG-RRBX
380V 244-14AG-RUYY 244-14LG-RUBX 244-14DG-RUBX
400V 244-14AG-SCYY 244-14LG-SCBX 244-14DG-SCBX
415V 244-14AG-SBYY 244-14LG-SBBX 244-14DG-SBBX
440V 244-14AG-SHYY 244-14LG-SHBX 244-14DG-SHBX
480V 244-14AG-SEYY 244-14LG-SEBX 244-14DG-SEBX
For the 244-14L and 244-14D models, the generator voltage is compared to the
nominal input (bus) voltage specified at time of ordering. For the 244-14G and
244-14H models, the generator voltage is compared to the measured bus voltage.

24
240 Series DIN Panel Meters

Wattmeters & Varmeters


The 244/246 models are self contained and are available to measure active power
and reactive power in both balanced and unbalanced, single and 3 phase 3 or 4
wire systems. These Wattmeters are ideal for clear precise analogue indication of
power in applications such as power generation, industrial control panels and
power distribution.

Specification
Accuracy: Shortscale Class 2.5 Longscale Class 1.5
Measuring Ranges: Voltage 94-106%
Current 0-120%
Frequency Influence: 0.4% / Hz
Rating: Current: 0.2A to 5A direct connected 1A or 5A for C.T.’s.
Voltages: From 57.7 to 480V
Overload: 120% of nominal continuous voltage up to 600V maximum
Maximum Input: 600V
Frequency: 50Hz or 60Hz
Power factor: Unity Power Factor assumed range 0.5/1/0.5
Burden: Current: 1VA per phase
Voltage: 1VA per phase
Warm-up-Time: <15 minutes

Product Codes – Short Scale Models


Bezel Size mm 72 96 144
Scale Length mm 65 95 145
Wattmeters Product Code
Single Phase 243-015G-FA+256-TWK 244-210 246-210
3 Phase 3 Wire Balanced Load 243-015G-FA+256-TWL 244-211 246-211
3 Phase 4 Wire Balanced Load 243-015G-FA+256-TWH 244-21C 246-21C
3 Phase 3 Wire Unbalanced Load 243-015G-FA+256-TWM 244-213 246-213
3 Phase 4 Wire Unbal. Star C.T.s 243-015G-FA+256-TWN 244-214 246-214
3 Phase 4 Wire Unbal. Delta C.T.s 243-015G-FA+256-TWJ 244-21E 246-21E
3 Phase 4 Wire 3 Element 243-015G-FA+256-XWW 244-21Y 246-21Y
Varmeters Product Codes
3 Phase 3 or 4 Wire Balanced Load 243-016G-FA+256-TXG 244-310 246-310
3 Phase 3 Wire Unbalanced Load 243-016G-FA+256-TXM 244-31S 246-31S
3 Phase 4 Wire Unbal. Star C.T.s 243-016G-FA+256-TXN 244-314 246-314
3 Phase 4 Wire Unbal. Delta C.T.s 243-016G-FA+256-TXJ 244-31E 246-31E

Product Codes – Long Scale Models


Bezel Size mm 72 96 144
Scale Length mm 112 150 230
Wattmeters Product Code
Single Phase 243-055G-FA+256-TWK 244-215 246-215
3 Phase 3 Wire Balanced Load 243-055G-FA+256-TWL 244-216 246-216
3 Phase 4 Wire Balanced Load 243-055G-FA+256-TWH 244-21D 246-21D
3 Phase 3 Wire Unbalanced Load 243-055G-FA+256-TWM 244-218 246-218
3 Phase 4 Wire Unbal. Star C.T.s 243-055G-FA+256-TWN 244-219 246-219
3 Phase 4 Wire Unbal. Delta C.T.s 243-055G-FA+256-TWJ 244-21F 246-21F
3 Phase 4 Wire 3 Element 243-055G-FA+256-XWW 244-21Z 246-21Z
Varmeters Product Codes
3 Phase 3 or 4 Wire Balanced Load 243-056G-FA+256-TXG 244-315 246-315
3 Phase 3 Wire Unbalanced Load 243-056G-FA+256-TXM 244-31L 246-31L
3 Phase 4 Wire Unbal. Star C.T.s 243-056G-FA+256-TXN 244-319 246-319
3 Phase 4 Wire Unbal. Delta C.T.s 243-056G-FA+256-TXJ 244-31F 246-31F
Models 243-015, 243-016, 243-055 & 243-056 use a separate transducer.
Our transducer range is ideal for this application. Our product code reference
assumes a 1mA output. Other outputs of 5, 10, 20 or 4/20mA can also be used.

25
240 Series DIN Panel Meters

Wattmeter Connection Diagrams

Single Phase
224-210, 244-215, 246-210, 246-215

3 Phase 4 Wire Balanced Load


244-21C, 246-21C, 244-21D, 246-21D

3 Phase 3 Wire Balanced Load


244-211, 246-211, 244-216, 246-216

3 Phase 3 Wire Unbalanced Load 2 Element


244-213, 246-213, 244-218, 246-218

26
240 Series DIN Panel Meters

Wattmeter Connection Diagrams

3 Phase 4 Wire Unbalanced Load Star Connected C.T.s 2 1/2 Element


244-214, 246-214, 244-219, 246-219

3 Phase 4 Wire Unbalanced Load Delta Connected C.T.s


244-21E, 246-21E, 244-21F, 246-21F

3 Phase 4 Wire Unbalanced Load Star Connected C.T.s 3 Element


244-21Y, 246-21Y, 244-21Z, 246-21Z

27
240 Series DIN Panel Meters

Varmeter Connection Diagrams

3 Phase 3 or 4 Wire Balanced Load 1 Element


244-310, 246-310, 244-315, 246-315

3 Phase 4 Wire Unbalanced Star Connected C.T.s 2 1/2 Element


244-314, 246-314, 244-319, 246-319

3 Phase 3 Wire Unbalanced Load 2 Element


244-31S, 246-31S, 244-31L, 246-31L

3 Phase 4 Wire Unbalanced Delta Connected C.T.s 2 1/2 Element


244-31E, 246-31E, 244-31F, 246-31F

28