You are on page 1of 6

Application of D-STATCOM to Improve Distribution

System Performance with Balanced and Unbalanced Fault


Conditions
S. H. Hosseini, A. Nazarloo and E. Babaei
Faculty of Electrical and Computer Engineering
University of Tabriz
Tabriz 51666-16471, Iran
hosseini@tabrizu.ac.ir, nazarloo@ieee.org and e-babaei@tabrizu.ac.ir

Abstract - This paper proposes a new control method for D- voltage across the storage device into a set of three-phase ac
STATCOM (Distribution STATIC Compensator) control system. output voltages. These voltages are in phase and coupled with
The operation of this proposed control method enables D- the ac system of network through the reactance of the coupling
STATCOM to mitigate all types of fault, intelligently (such as transformer [4]. A control method based on rms voltage
Single Line to Ground (SLG) fault and Double Phase to Ground measurement has been presented in [5], [6] where they have
(DPG) fault and three-phase fault). In this paper, the 12-pulse D-
STATCOM configuration with IGBT is designed and the graphic
been presented a PWM-based control scheme that requires
based models of the DSTATCOM are developed using the rms voltage measurements and no reactive power
PSCAD/EMTDC electromagnetic transient simulation program. measurements are required. Also in this given method, Clark
This paper validates the performance of a D-STATCOM system and Park transformations are not required. However, they have
for improving distribution system performance under all types of been investigated voltage sag/swell mitigation due to just load
fault. The reliability and robustness of the control scheme in the variation and using the same proportional gain for all types of
system response to the voltage sags caused by SLG and DPG and voltage distortions while no SLG and DPG and three-phase
three-phase faults is obviously proved in the simulation results. faults have been investigated. In this paper, a new control
method for mitigating the load voltage sags caused by all
types of fault is proposed. In this method, both dc side
Index Terms - D-STATCOM, Voltage Sags, Energy Storage
topology of the D-STATCOM is modified and the
Systems, Balanced and Unbalanced Faults.
I. INTRODUCTION proportional gain of the PI controller is selected intelligently
(based on the proposed Lookup Table) for mitigating voltage
Voltage sags are the most important power quality (PQ) distortions. In addition, effects of system faults on the
problems that many industries and utilities face it. It sensitive loads are investigated and the control of voltage sags
contributes more than 80% of power quality problems that are analysed and simulated.
exist in power systems. Voltage sags are not tolerated by
sensitive equipment used in modern industrial plants such as II. Configuration and operation of D-STATCOM
process controllers; programmable logic controllers (PLC), Fig. 1 shows the schematic representation of the D-
adjustable speed drive (ASD) and robotics [1]. Various STATCOM. The basic electronic block of the D-STATCOM
methods have been applied to reduce or mitigate voltage sags. is the voltage source inverter that converts an input dc voltage
The conventional methods are by using capacitor banks, into a three-phase output voltage at fundamental frequency.
introduction of new parallel feeders and by installing These voltages are in phase and coupled with the ac system
uninterruptible power supplies (UPS). However, the PQ through the reactance of the coupling transformer. Suitable
problems are not solved completely due to uncontrollable adjustment of the phase and magnitude of the D-STATCOM
reactive power compensation and high costs of new feeders output voltages allows effective control of active and reactive
and UPS. The D-STATCOM has emerged as a promising power exchanges between the DSTATCOM and the ac
device to provide not only for voltage sag mitigation but also system.
for a host of other power quality solutions such as voltage Fig. 2 shows a typical 12-pulse inverter arrangement
stabilization, flicker suppression, power factor correction, and utilizing two transformers with their primaries connected in
harmonic control [2]. D-STATCOM is a shunt device that series. The first inverter is connected to the system through a
generates a balanced three-phase voltage or current with Y-Y arrangement, whereas a Y-Δ connection is used for the
ability to control the magnitude and the phase angle [3]. second inverter. Each inverter operates as a 6-pulse inverter,
Generally, the D-STATCOM configuration consists of a with the Y-Δ inverter being delayed by 30 degrees with
typical 12-pulse inverter arrangement, a dc energy storage respect to the Y-Y inverter. The current flowing into each
device; a coupling transformer connected in shunt with ac inverter is the same, scaled by the transformer ratio, as the
system, and associated control circuits, as shown in Fig. 1. current being drawn from the system by the D-STATCOM.
The configurations that are more sophisticated use multipulse
and/or multilevel configurations. The VSC converts the dc

2010 IEEE Electrical Power & Energy Conference


978-1-4244-8188-0/10/$26.00 ©2010 IEEE
For the Y-Δ inverter, the current is also delayed by 30 degrees The voltage error signal is obtained by comparing the
with respect to the current of the Y-Y inverter [7]. measured Vrms voltage with a reference voltage, Vrms_ref. A PI
controller processes the difference between these two signals
in order to obtain the phase angle δ that is required to drive the
error to zero. The angle δ is used in the PWM generator as the
phase angle of the sinusoidal control signal. The switching
frequency used in the sinusoidal PWM generator is fsw=1450
(HZ) and the modulation index is Ma ≈ 1 [8].
The modulating angle δ is applied to the PWM generators
in phase A. The angles of phases B and C are shifted 120 and
240 degrees, respectively.
Fig. 4 shows the schematic diagram of the test system
used to carry out the transient modelling and analysis of the
D-STATCOM. A balanced load is connected to the 11 (kV),
Fig. 1. Schematic representation of the D-STATCOM as a custom power secondary side of the transformer. Brk. 1 is used to control the
controller period of operation of the D-STATCOM. In addition, when
Timed Fault Logic operates balanced (three-phase) and
unbalanced (SLG and DPG) faults are exerted, therefore, the
D-STATCOM supplies reactive power to the system.

Fig. 2. The 12-pulse D-STATCOM arrangement


Fig. 4. Schematic diagram of the test system used to carry out transient
analysis of the D-STATCOM
In addition, Fig. 2 shows the proposed 12-pulse D-
STATCOM configuration with the IGBTs used as power
devices. The IGBTs are connected anti parallel with diodes for III. PROPOSED CONTROL METHOD
commutation purposes and charging of the DC capacitor. The Proportional gain is playing a very important role in PI
DC side of D-STATCOM is connected in parallel to keep the controller in D-STATCOM. If proportional gain is considered
voltage on the DC side as low as possible and to improve smaller than a suitable value, it causes a decrease in mitigation
utilization of the DC side capacitor. The first transformer is in and if proportional gain is considered bigger than a correct
wye-to-wye connection and the second transformer is in wye- value, it causes an oscillation in rms voltage profile and
to-delta connection. This is to give a 30 degrees phase shift mitigation will not be perfect. For example, in mitigation of
between the pulses and to reduce harmonics generated from sags caused by unbalanced faults, the proportional gain should
the DSTATCOM. The D-STATCOM is connected in shunt to be selected rather small, and for mitigation of voltage drop
the system [7]. caused by three-phase fault, proportional gain should be
The block diagram of the control scheme designed for the selected big enough. Thus, proportional gain must be selected
D-STATCOM is shown in Fig. 3. It is based only on accurate.
measurements of the voltage Vrms at the load point. In this paper, in order to mitigate voltage sags caused by
balanced & unbalanced faults, a new method is proposed in
which firstly, D-STATCOM and Super-capacitor energy
storage system (ESS) are integrated and secondly, a Look-up
Table is used to determine the suitable proportional gain for
each one of different voltage sags.
Considering this fact that all types of fault may occur in
distribution system, controller system must be able to mitigate
Fig. 3. Control scheme designed for the D-STATCOM any types of voltage sags. The integration and control of ESSs,
such as Super-capacitor (Ultra capacitor - UCAP) into a D- TABLE I
LOOKUP TABLE ARRANGEMENT
STATCOM is developed to mitigate such problems, enhance
Unbalanced Faults Balanced Fault
power quality and improve distribution system reliability. The
first part of new method develops the control concepts of Rms load current
charging and discharging the UCAP by D-STATCOM, and 0 9 0 25
validates the performance of an integrated D- Proportional gain 650 750 750 3000
STATCOM/UCAP system for improving distribution system
performance under all types of system related disturbances
In this Lookup Table, proportional gains are determined
and system faults, such as SLG fault, DPG fault and three-
based on Trial And Error and then the optimum value is
phase fault . Fig. 5 shows a typical distribution system
selected for each boundary.
controlled by this method. A UCAP is integrated with dc
Whenever the measured current rms value at the load point is
capacitor. The UCAP capacitance is determined by applying a
situated in each boundary, the related proportional gain is
constant-current discharge with C = I × dt dv . Since dv/di is
extracted from proposed Lookup Table. For example, in SLG
almost constant, UCAP capacitance can be modelled as a or DPG fault when the load current rms value is smaller than 9
constant. The equivalent series resistance (ESR) is calculated the related proportional gain is 650 and when the rms load
by measuring the output voltage drop from no load to steady- current is bigger than 9 the related proportional gain is 750.
state load and then dividing by the load current. Since the Moreover, in three-phase fault when the load current rms
open-circuit voltage has no significant effect on the ESR, the value is bigger than 25 the related proportional gain is 3000.
ESR can be modelled as a constant [9]. The UCAP is The speed of response and robustness of the control scheme
modelled with 10.0 (mF) capacitance and 320 (mΩ) ESR. are clearly shown in the simulation results.
IV. SIMULATION RESULTS
Fig. 5 shows the test system implemented in
PSCAD/EMTDC to carry out simulations for the D-
STATCOM. The test system comprises a 230 (kV)
transmission system. A 12-pulse D-STATCOM is connected
to the tertiary winding by closing Brk. 1 at 0.2 (s), for
maintaining load rms voltage at 1pu. A 750 (µF) capacitor in
parallel with an Ultra capacitor - UCAP on the dc side provide
the D-STATCOM energy storage capabilities. Simulations are
carried out for both cases where the D-STATCOM is
Fig. 5. Distribution system with D-STATCOM integrated with connected to or disconnected from the system.
UCAP and controller The simulations of the D-STATCOM in fault condition
are done using unbalanced and balanced faults. In SLG fault
Every PI controller has a proportional gain that is playing analysis, phase A is the faulted phase, while in DPG fault the
an important role in D-STATCOM correct performance, and faulted phases are phases A and B. In addition, in three-phase
each voltage disturbance needs a special proportional gain, for fault, the faulted phases are phases A, B, and C. The duration
improving distribution system and D-STATCOM of the fault is set for about 0.4 (s) and the faults are exerted at
performance. Therefore, it is necessary to use a separated 0.6 (s). The total simulation time is 1.6 (s).
proportional gain for each type of voltage sags. The second Specifications of test system under all types of fault are
part of this method uses a Lookup Table for adjusting the presented in Table II.
proportional gain of the PI controller in D-STATCOM for TABLE II
mitigating of the voltage distortions, intelligently. CONDITIONS OF TEST SYSTEM UNDER ALL TYPES OF FAULT
As shown in Fig. 6, load current of one of the phases Type Fault Faulted Voltage Fault
Phases Drop Interval
(such as phase A) is measured and its rms value is calculated. SLG A 15% 0.6 – 1 (s)
Based on the load current rms value, the proportional gain is DPG A,B 12% 0.6 – 1 (s)
determined for each disturbance, formally. Three-Phase A,B,C 12% 0.6 – 1 (s)
Fault

In this paper, the D-STATCOM by using proposed


control method mitigates load point voltage sags due to all
types of faults. The simulations are done for all types of faults
Fig. 6. The application of Lookup Table for determining a suitable introduced in the 11 (kV) distribution systems as follows:
proportional gain

Every type of the voltage disturbances affects load A. Simulation results for SLG fault
current. In this part of method, a Look-up Table is arranged Fig. 7 shows the rms voltage at the load point for the case
based on these load current variations as shown in Table I: when the system operates without D-STATCOM and under
SLG fault. In this case, the voltage drops by almost 15% with Vab-Total Harmonic Distortion
1.00
respect to the reference value.
0.75
Vrms Vref
1.40
0.50
1.20
1.00 0.25
0.80
0.00
0.60
0.40 0.00 0.40 0.80 1.20 1.60
Fig. 10. Vab-THD using proposed method for mitigating SLG fault
0.20
0.20 0.60 1.00 1.40 Fig. 11 shows the dc voltage of the VSC. Before the D-
Fig. 7. The rms voltage (Vrms) at PCC without D-STATCOM under SLG fault STATCOM starts operating, the capacitor is charged to a
steady state voltage level of approximately 7 (kV). This initial
In t = 0.2 (s), D-STATCOM is connected to the condition of the capacitor improves the response of the D-
distribution system. The voltage drop of the sensitive load STATCOM and simplifies the requirements of the control
point is mitigated using the proposed control method. In this system. As shown in Fig. 11, in the periods 0.6-1 (s), the D-
method, proportional gain is obtained from Lookup Table. STATCOM absorbs active power from the ac system to
Fig. 8 shows the mitigated rms voltage using this new method charge the capacitor and maintain the required dc link voltage
where a very effective voltage regulation is provided. level.

Vrms Vref VDC


1.40 36.0
1.20 30.0
1.00 24.0
0.80 18.0
0.60 12.0
0.40 6.0
0.20 0.0
0.20 0.60 1.00 1.40 0.00 0.40 0.80 1.20 1.60
Fig. 8. Compensated rms voltage under SLG fault Fig. 11. DC link voltage under SLG fault

Fig. 9 shows the frequency spectrum for Vab (line voltage


B. Simulation results for DPG fault
at the load point) in interval 0.6-1 s, after eliminating transient
states. It is seen, all even harmonics are zero, and odd Fig. 12 shows the rms voltage at the load point for the
harmonics are mitigated, because a 12-pulse D-STATCOM is case when the system operates without D-STATCOM and
used in this paper. DPG fault is occurred. The rms voltage faces with 12%
decrease with respect to the reference voltage.
Vab - frequency spectrum
100.0 Vrms Vref
1.40
1.20
1.00
0.80
0.60
0.40
0.0
Fig. 9. Vab frequency spectrum during mitigation of voltage sag caused by 0.20
SLG fault 0.20 0.60 1.00 1.40
Fig. 12. Variation of rms voltage (Vrms) at PCC without
Moreover, the Total Harmonic Distortion (THD) for line D-STATCOM under DPG fault
voltage Vab for total time of simulation, i.e., in interval 0-1.6
(s) for every second of time is shown in Fig. 10. It is observed, Fig. 13 shows the compensated rms voltage at the load
the THD in percent for Vab in intervals of SLG fault point under DPG fault using proposed method. It is observed
occurrence is 0.0633%. that the proposed method has mitigated voltage sag, truly.
Vrms Vref C. Simulation results for three-phase fault
1.40
Fig. 17 shows the rms voltage at the PCC for the case
1.20 when the system operates without D-STATCOM and under
1.00 three-phase fault. In this case, the voltage drops by almost
0.80 12% with respect to the reference value.
0.60 Vrms Vref
1.40
0.40
0.20 1.20

0.20 0.60 1.00 1.40


1.00
Fig. 13. Compensated rms voltage under DPG fault 0.80

Fig. 14 shows the frequency spectrum for Vab in interval 0.60


0.6-1 (s), after eliminating transient states. It is observed that 0.40
all harmonics are mitigated.
0.20
Vab - frequency spectrum 0.20 0.60 1.00 1.40
100.0
Fig. 17. Variation of rms voltage (Vrms) at PCC without
D-STATCOM under three-phase fault

Fig. 18 shows the mitigated rms voltage at the load point


under three-phase fault using proposed method. It is observed
that the load voltage is very close to the reference value, i.e.,
1pu.
0.0
Vrms Vref
Fig. 14. Vab frequency spectrum during mitigation of voltage sag caused by 1.40
DPG fault
1.20
The THD for line voltage Vab in interval 0-1.6 (s) is 1.00
shown in Fig. 15 It is observed that the THD in percent for
0.80
mitigated line voltage in intervals of DPG fault occurrence is
very suitable and 0.0126%. 0.60
0.40
VabTHDTotal
1.00 0.20
0.75 0.20 0.60 1.00 1.40
0.50 Fig. 18. Compensated rms voltage under three-phase fault

0.25 Fig. 19 shows the frequency spectrum for Vab during


0.00 mitigation of voltage sag. It is seen, all harmonics are almost
zero.
0.00 0.40 0.80 1.20 1.60
Fig. 15. Vab-THD using proposed method for mitigating DPG fault Vab - frequency spectrum
100.0
In addition, the dc voltage of the VSC is shown in Fig. 16.

VDC
36.0
30.0
24.0
18.0
0.0
12.0
Fig. 19. Vab frequency spectrum during mitigation of voltage sag caused by
6.0 three-phase fault
0.0
The THD for the line voltage Vab in simulation interval
0.00 0.40 0.80 1.20 1.60 0-1.6 (s) is shown in Fig. 20. The THD for Vab in intervals of
Fig. 16. DC link voltage under DPG fault
three-phase fault occurrence for every second of time is REFERENCES
approximately zero and 0.0075%. [1] R. C. Dugan, M. F. McGranaghan and H. W. Beaty, “Electrical power
Then it is observed that using proposed control method, systems quality,” McGraw Hill Companies, Inc., 1996.
the THDs are very suitable and close to zero because of the [2] G. F. Reed, M. Takeda and I. Iyoda, “Improved power quality solutions
using advanced solid-state switching and static compensation
12-pulse D-STATCOM arrangement. technologies,” IEEE Power Engineering Society Winter Meeting, vol.2,
pp. 1132- 1137, 1999.
Vab-Total Harmonic Distortion [3] S. Aizam, Kok. B. C., N. Mariun, H. Hizam and N. I. Abd Wahab,
1.00 “Linear feedback controller for D-STATCOM in DPG fault
application,” IEEE Universities Power Engineering Conference, vol. 3,
0.75 pp.986-990, 2006.
[4] L. S. Patil and Ms. A. G. Thosar, “Application of D-STATCOM to
0.50 mitigate voltage sag due to DOL starting of three phase induction
motor,” IEEE International Conference on Control, Automation,
0.25 Communication and Energy Conservation, 4th-6th June 2009.
[5] O. Anaya-Lara and E. Acha, “Modelling and analysis of custom power
systems by PSCAD/EMTDC,” IEEE Trans. Power Del., Vol. 17, No. 1,
0.00 pp.266-272, Jan. 2002.
0.00 0.40 0.80 1.20 1.60 [6] H. Hatami, F. Shahnia, A. Pashaei and S.H. Hosseini, “Investigation on
D-STATCOM and DVR operation for voltage control in distribution
Fig. 20. Vab-THD using proposed method for mitigating networks with a new control strategy,” IEEE Power Tech., pp. 2207 –
three-phase fault 2212, 2007.
[7] N. Mariun1, H. Masdi1, S. M. Bashi1, A. Mohamed and S. Yusuf,
The dc voltage of the VSC is shown in Fig. 21 and it is “Design of a prototype D-STATCOM using DSP controller for voltage
observed that the charge/discharge of the capacitor is rapid sag mitigation,” IEEE International Power and Energy Conference,
2004.
using the proposed control method and hence the response of [8] E. Acha, V.G. Agelidis, O. Anaya-Lara and T.J.E. Miller, “Power
the controller is fast. Electronic Control in Electrical Systems,” Newness Power Engineering
Series, 2002, pp: 330-336.
VDC [9] Z. Xi, B. Parkhideh and S. Bhattacharya, “Improving distribution system
36.0 performance with integrated STATCOM and super-capacitor energy
storage system,” IEEE Power Electronics Specialists Conference, pp.
30.0 1390 - 1395, 2008.
24.0
18.0
12.0
6.0
0.0
0.00 0.40 0.80 1.20 1.60
Fig. 21. DC link voltage under three-phase fault

V. ConclusionS
In this paper, a new control method for mitigating the
voltage sags, caused by balanced and unbalanced faults, at the
PCC has been proposed. The proposed method has been made
up of two factors. The first factor was "Integrating D-
STATCOM and super-capacitor energy storage system" and
the second factor was "Lookup Table application in
determining a suitable proportional gain for each different
voltage disturbance". This proposed control scheme was tested
under a wide range of operating conditions (under all types of
fault), and it was observed that the proposed method is very
robust and intelligent in every case. In addition, the regulated
Vrms voltage showed a reasonably smooth profile. It was
observed that the load voltage is very close to the reference
value, i.e., 1pu and the voltage sags are minimized completely.
Moreover, the simulation results were shown that the
charge/discharge of the capacitor is rapid through this new
method and hence the response of the D-STATCOM is fast.
This custom power controller may find application in
automated industries with critical loads.

You might also like