X1-Hybrid Series

User Manual
3.0kW - 7.5kW

EN

Copyright Declaration

SolaX Power Network Technology (Zhe jiang) Co. , Ltd.


ADD:No.288 Shizhu Road, Tonglu Economic Development Zone,
Tonglu City, Zhejiang Province, China.
Tel:+0571-5626 0011
E-mail:info@solaxpower.com 614.00495.01
Contents
1Note on this Manual ...................................................................03
1.1 Scope of Validity ................................................................................... 03
1.2 Target Group ........................................................................................... 03
1.3 Symbols Used ......................................................................................... 03
1.3.1 Important Safety Instructions....................................................... 04
1.3.2ExplanationofSymbols ................................................................... 10
1.3.3 CE Directives......................................................................................... 12

2 Introduction...........................................................................................13
2.1 Basic Feature ............................................................................................ 13
2.2 System Diagram .................................................................................... 13
2.3 Work Modes............................................................................................... 16
2.4 Dimension................................................................................................... 18
2.5 Terminals of Inverter .......................................................................... 18

3TechnicalData.................................................................................... 20
3.1 DC Input ....................................................................................................... 20
3.2 AC Output/Input................................................................................... 20
3.3 Battery ............................................................................................................ 21
3.4 Efficiency ,Safety and Protection.............................................. 21
3.5 Off-grid Output ...................................................................................... 22
3.6 General Data...................................................................................... ...... 22

4 I nstallation ............................................................................................ 23
4.1 Check for Transport Damage ...................................................... 23
4.2 Packing List ............................................................................................... 23
4.3 Installation Precautions ................................................................... 25
4.4 Tool Preparation..................................................................................... 26
4.5 Installation Site Conditions .......................................................... 28
4.5.1 Installation Carrier Requirements .............................................. 28
4.5.2 Installation Requirements ............................................................. 28
4.5.3 Installation Space Requirements ............................................... 29
4.6 Mounting ..................................................................................................... 30

01
5 Electrical Connections ........................................................... 33 1 Notes on this Manual
5.1 PV Connection ......................................................................................... 33
5.2 Grid Port and Off-grid Output Connection ....................... 37 1.1 Scope of Validity
5.3 Off-grid Block Diagram ...................................................................... 38
5.4 Battery Connection .............................................................................. 46
5.5 Communication Connection ....................................................... 50
5.5.1 Introduction to DRM Communication..................................... 50
5.5.2 Introduction to Meter/CT Communication........................... 51 X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
5.5.3 COM Communication...................................................................... 55 X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
5.5.4 Communication Connection Steps........................................... 56
5.6 Grounding (mandatory) .................................................................... 61 Note: ”X1-Hybrid G4"Series refers to the energy storage inverter
5.7 Monitoring Connection .................................................................... 63 that supports photovoltaic grid-connected.
5.8 Check All Below Steps Before Starting Inverter............................... 65 “5.0"means 5.0kW.
5.9 Inverter Operation ................................................................................. 66 “D”means with “DC Switch” , “ M”means externally attached
X1-Matebox for full load off-grid operation.
Keep this manual available at any time.
6 Firmware upgrading...........................................................................................67
1.2 Target Group
7 Setting ........................................................................................ 71 This manual is for quali ed electricians.The tasks described in this
manual only can be performed by quali ed electricians.
7.1 Control Panel................................................................................ 71
7.2 Menu Structure........................................................................... 72 1.3 Symbols Used
7.3 LCD Operation ........................................................................................... 73 The following types of safety instructions and general information
appear in this document as described below:

8 Troubleshooting ............................................................... 97 Danger!


“Danger" refers to a dangerous situation that, if not
8.1 Trouble Shooting .................................................................... 97 avoided, will result in a high level of risk such as serious
8.2 Routine Maintenance.............................................................103 injury or even death.

Warning!
9 Decommissioning....................................................................104 “Warning” indicates a hazardous situation which, if not
9.1 Disassemble the Inverter .................................................................104 avoided, could result in serious injury or death.
9.2 Packaging ...................................................................................................... 104
9.3 Storage and Transportation ..................................................................104 Caution!
9.4 Waste Disposal ........................................................................................104 “Caution” indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.

10 Disclaimer ........................................................................................105 Note!


“Note” provides tips that are valuable for the optimal
operation of our product.

02 03
Safety

Warning!

Danger! Authorized service personnel must disconnect the AC and DC


power supply of the inverter before per forming any
Danger to life due to high voltages in the inverter! maintenance, cleaning or operation of any circuit connected to
The personnel responsible for the installation, electrical the inverter.
connection, debugging, maintenance and fault handling
operation of this product need to be trained, master the correct
operation method, have the corresponding electrician Warning!
qualification and safety operation knowledge. The inverter can not be operated when it is running.

Caution! Warning!
When the inverter is working, it is strictly forbidden to touch the Risk of electric shock!
shell. The temperature of the shell canis high and there is a risk
of scalding.
Strictly follow relevant safety specifications for product installation
and testing. During installation, operation or maintenance, please
read carefully and follow the instructions and precautions on the
Caution! inverter or user manual. If the operation is incorrect, it may cause
personal and property losses. Please keep the user manual properly
Radiation may be harmful to health!
after use.
Do not stay for a long time and keep at least 20 cm away from
the inverter.
This inverter can only use the accessories sold and recommended by
SolaX , otherwise it may cause fire, electric shock or casualties.
Without the authorization of our company, you may not open the
Attention! inverter cover or replace the inverter parts , otherwise the warranty
promise of the inverter will be invalid.
Ground PV system.
Finish PV modules and photovoltaic system grounding in The use and operation of the inverter must be carried out in
accordance with local requirements to achieve optimal accordance with the instructions in this manual, otherwise this
protection of systems and personnel. protection will fail and the warranty of the inverter will also fail.
During working, the inverter surface temperature may exceed 60 °C ,
please make sure the inverter cools down before touching, and
make sure children can not touch.
Warning!
When exposed to sunlight, photovoltaic arrays generate dangerous
Ensure that the input DC voltage is below the inverter limit. high DC voltages. Please follow our instructions, otherwise it will be
Excessive DC voltage and current may cause permanent life-threatening.
damage or other losses to the inverter, which is not covered by
the warranty. All DC and AC power sources must be disconnected from the
inverter for at least 5 minutes before any wiring or electrical
operation is performed on the inverter to ensure complete isolation
of the inverter and avoid electric shock.

04 05
Safety

A photovoltaic module used on the inverter must have a IEC61730A If the building installed with external light protection device is far
rating, and the total open circuit voltage of the photovoltaic string /
array is lower than the maximum rated DC input voltage of the away from the inverter location, in order to protect the inverter from
inverter. Any damage caused by photovoltaic over voltage is not electrical and mechanical damage, the inverter should also install an
covered by warranty. external lightning protection equipment.

Installation position should be away from wet environment and In order to protect DC system, two-stage surge protection equipment
corrosive substances.
is needed between DC cable of inverter and photovoltaic equipment
module.
After the inverter and power grid cut off the PV power supply , there
will be a certain amount of residual current in a short time, be In order to protect the AC system, the level 2 surge protection
cautious or it may lead to serious personal injury and even high risk
of death.Use a multimeter (impedance at least 1 MΩ) to measure the equipment should be installed at the AC output, located between
voltage between the UDC and the UDC- to ensure that the inverter the inverter and the grid. Installation requirements must comply with
port is discharged below the safe voltage before starting operation IEC61643-21 standard.
(35 VDC).
All DC cables shall be installed in a distance as short as possible, and
the positive and negative cables of the same input need to be
bundled together to avoid causing loops in the system. Minimum
distance installation and binding requirements also apply to auxiliary
Ø Surge protection devices (SPDs) for PV installation grounding and shielding grounding conductors.

Warning!
Over-voltage protection with surge arresters should be
provided when the PV power system is installed.
The grid connected inverter is fitted with SPDs in both
PV input side and MAINS side.

Direct or indirect lightning strikes can cause failures. Surge is the main
cause of lightning damage to most devices. Surge voltage may occur
at photovoltaic input or AC output, especially in remote mountain
areas where long distance cable is supplied.

Please consult professionals before installing SPDs.

The external lightning protection device can reduce the in uence of


direct lightning strike, and the lightning protection device can release
surge current to the earth.

06 07
Safety

Ø • A faulty ground connection can result in equipment failure, personal


and death injuries, and electromagnetic interference.
The islanding effect means that when the power grid is cut off, the grid- • Ensure correct according to grounding to IEC62109 and conductor
connected power generation system fails to detect the power outage and diameter according to STANDARD specification.
still supplies power to the power grid. This is very dangerous for the • Do not connect the grounding end of the equipment in series to
maintenance personnel and the power grid on the transmission line. prevent multi-point grounding.
• Electrical appliances must be installed in accordance with the wiring
X1-Hybrid G4 series inverters use active frequency offset method to rules of each country.
prevent islanding effect.
For United Kingdom
• The installation that connects the equipment to the supply terminals
shall comply with the requirements of BS 7671.
• Electrical installation of PV system shall comply with requirements of
BS 7671 and IEC 60364-7-712.
• All protective devices cannot be changed.
• User shall ensure that equipment is so installed, designed and
operated to maintain at all times compliance with the requirements of
Ø ESQCR22(1)(a).
• All inverter’s incorporate a certified internal Residual Current Monitoring
(RCM) in order to protect against possible electrocution and fire hazard
in case of a malfunction in the PV array, cables or inverter.
There are 2 trip thresholds for the RCM as required for certification
(IEC 62109-2:2011). Ø
The default value for electrocution protection is 30mA, and for slow
rising current is 300mA. SolaX X1-Hybrid G4 Series inverter should pair with high voltage battery,
• The inverter, with built-in RCM, will exclude possibility of DC residual for the speci c parameters such as battery type, nominal voltage and
current to 6mA,thus in the system an external RCD (type A) can be used nominal capacity etc., please refer to section 3.3.
(≥30mA).
Please refer to the matching battery speci cation for details.

Warning!

08 09
Safety

1.3.2 Explanation of Symbols Beware of hot surface.


This section gives an explanation of all the symbols shown on the inverter The inverter can become hot during operation. Avoid
and on the type label contact during operation.

Danger of high voltages.


Denger to life due to high voltages in the inverter!

Danger.
Risk of electric shock!

Observe enclosed documentation.

Battery status The inverter can not be disposed together with the
household waste.Disposal information can be found in the
enclosed documentation.

CE mark.
The inverter complies with the requirements of the
applicable CE guidelines.

UKCA mark.
The inverter complies with the requirements of the
applicable UKCA guidelines.

UKNI mark.
The inverter complies with the requirements of the
applicable UKNI guidelines.

Type Approved
Safety
Regular Production
Sur veillance

www.tuv.com
ID 1111227431

10 11
Introduction

2 Introduction
This chapter describes the requirements of the European low voltage
regulations, including safety instructions and system licensing 2.1 Basic Features
conditions, the user must comply with these regulations when X1-Hybrid G4 series is a high-quality inverter that can convert solar energy
installing, operating, and maintaining the inverter , otherwise it will into alternating current and store energy into batteries.
cause personal injury or death, and the inverter will cause damage. The inverter can be used to optimize self-consumption, stored in batteries
for future use or fed into the public grid. The way it works depends on
Please read the manual carefully when operating the inverter .If you do user preferences. It can provide emergency power during power outages.
not understand "danger", "warning", "caution" and the description in the
manual, please contact the manufacturer or service agent before installing 2.2 System Diagram
and operating the inverter.
X1-Hybrid G4 series are designed to has four Off-grid wiring schemes,
Grid-connected inverter comply with low voltage directive (LVD) customers can choose Off-grid compatible parts Load and Off-grid
2014/35/EU and Electromagnetic compatibility directive (EMC) compatible with all load use.
2014/30/EU.Detection of components is based on: There are different ways of wiring in different countries, one is to
EN 62109-1:2010; connect N line with PE line, the other is to separate the line from the
EN 62109-2:2011;
PE line wiring, see below;
IEC 62109-1(ed.1);
IEC62109-2(ed.1);
EN 61000-6-3:2007+A:2011;
EN 61000-6-1:2007;
EN 61000-6-2:2005; Diagram A: Neutral line and PE line are separated from each other,
and the common load is connected to the off-grid port;
(For most countries)
For installation in photovoltaic module system, it is necessary to
make sure that the whole system complies with the requirements of
PV 1
EC(2014/35/EU,2014/30/EU, etc.) before starting the module (i.e. to
PV 2
start the operation). The assembly shall be installed in accordance X1-Hybrid G4
with the statutory wiring rules. Install and configure the system in CT

accordance with safety rules, including the use of specified wiring


methods. The installation of the system can only be done by BAT Grid Off-grid
Breaker CT Main Breaker

professional assemblers who are familiar with safety requirements N


PE
and EMC. The assembler shall ensure that the system complies with
the relevant national laws.

Breaker
Breaker E-BAR Grid

The individual subassembly of the system shall be interconnected by


means of the wiring methods outlined in national/international such as RCD RCD

the national electric code (NFPA) No.70 or VDE regulation 0107.

Breaker
Breaker
Battery
off-grid loads Loads

N-BAR for off-grid loads N-BAR for loads

12 13
Introduction Introduction

Diagram B: Neutral line and PE line are separated from each other, Diagram D: Neutral line and PE line are combined together, all
all loads connect to the Off-grid port;(For most countries) loads connect to the Off-grid port;(Apply to Australia)

X1-Hybrid G4 X1-Hybrid G4

PV 1PV 2 BAT CT PV 1PV 2 BAT CT

Grid Off-grid Grid Off-grid

Main Breaker
Main Breaker
X1-Matebox X1-Matebox
N N
PE

E-BAR E-BAR

Grid Grid

Breaker

Breaker
Battery Battery

Loads Distrbution Box Loads


Distrbution Box

N-BAR for loads N-BAR for loads

Diagram C: Neutral line and PE line are combined togeter, and the
common load is connected to the off-grid port;(Apply to Australia)
Note!
• When power cuts suddenly, the inverter connects the N
PV 1
line of off-grid load with the ground through relay,
PV 2
X1-Hybrid G4 providing a xed zero potential for off-grid load and
CT ensuring the safety of electricity use by users.
Main Breaker/RCD
BAT Grid Off-grid
Breaker CT • Please control the inverter load and make sure it is
N "output value" in "within " Off-grid mode, otherwise the
inverter will stop and alarm overload fault".
Breaker

Breaker E-BAR Grid


• Please confirm with the grid operator whether there are
special regulations for grid connection.
RCD RCD
Breaker

Breaker

Battery
off-grid loads Loads

N-BAR for off-grid loads N-BAR for loads

14 15
Introduction Introduction

2.3 Work Modes ③Without PV power


Active Charging time period:The grid will power
X1-Hybrid G4 series, can be based on different needs, there are a variety of models. the home loads and also charge the battery;
(PV=0 , Grid → Load +Battery)
Self Use Active Discharge time period:The battery will
power the home loads rstly.If the battery power
The self-use mode is suitable for areas with low feed-in ②

is not enough,the remaining power will be taken


subsidies and high electricity prices. ①
from the grid.The inverter will enter into the
① When the power of PV is sufficient
standby state.
Active Charging or Discharge time period:PV will power the
(PV=0 , Battery+Grid → Load)
loads rstly, and surplus power will charge to the battery .
Battery min SOC can be set:10%-100%
If the battery is fully charged, then sell the surplus power to
the grid;( The inverter will limit the output if Feed-in limit or
zero feed-in is needed ) Backup mode
(PV>Load ,PV →Load→Battery → Grid)
① The back-up mode is suitable for areas with

② When the power of PV is insufficient frequent power outages.
Active Charging time period: PV will power the loads rstly ,

Same working logic with “Self-use” mode.This
the remaining power will be taken from the grid , the battery
mode will maintain the battery capacity at a
will not discharge at this time. ①

relatively high level.(Users' setting) to ensure
(PV<Load ,PV + Grid → Load) ② that the emergency loads can be used when
Active Discharge time period: PV+BAT will power the loads
the grid is off. Customers no need to worry
together. If the power is still not enough, the remaining
about the battery capacity.
power will be taken from the grid.
Battery min SOC can be set:30%-100%
(PV<Load ,PV + Battery + Grid → Load)
③ Without PV power
Active Charging time period: The grid supplies the loads Backup mode SOC adjustment range :30%-100%;
and also can charge the battery; In Backup mode, SOC-min under off-grid
(PV=0 , Grid → Load + Battery) ②
condition is 10%, which cannot be modi ed;
Active Discharge time period:The battery will power the ①


home loads rstly.If the battery power is not enough ,the
remaining power will be taken from the grid.The inverter

will enter into the standby state.
(PV=0 , Battery+Grid → Load ) Off-grid
Battery min SOC can be set:10%-100%
The off-grid is used when the power grid is off.
System will provides emergency power
Feed-in priority through PV and batteries to supply power to the
The Feed-in priority mode is suitable for areas with high household loads.
feed-in subsidies, but has feed-in power limitation. (Battery must be installed for this mode)
①When the power of PV is sufficient ①When the power of PV is sufficent
Active Charging time period :PV will power the loads rstly, ③
① PV will power the loads rstly, and surplus power
and surplus power will feed-in to the grid. If the feed-in power will charge to the battery.

has been limited ,the surplus power can charge the battery. (PV฀Load ,PV ฀ Load ฀ Battery)

(PV>Load ,PV → Load → Grid → Battery) ②When the power of PV is insufficient
Active Discharge time period :PV will power the loads rstly, The remaining power will be taken from the battery.
③ and surplus power will feed-in to the grid. (PV฀Load ,PV ฀ Load)
② (PV>Load ,PV → Load → Grid ) ③ Without PV power
②When the power of PV is insufficient The battery will power the emergency loads until
Active Charging time period :PV will power the loads rstly, the battery reached the min SOC,then the inverter
the remaining power will be taken from the grid. The battery will enter into the idle mode.
will not discharge. (PV=0, Battery ฀ Load)
(PV<Load,PV + Grid → Load) Note: in the case of grid connection, all working modes work normally when the battery
Discharge time period: PV+BAT will power the loads together. SOC >5%.When the battery charge rate is below 5%, the PV or Grid will first charge the
If the power is still not enough, the remaining power will be battery SOC11%, and then return to the working mode selected by the user.
taken from the grid.
(PV<Load ,PV + Battery + Grid → Load)

16 17
Introduction Introduction

2.4 Dimension Object Description


A DC switch
482mm 181mm
B PV connection port
C Battery connection port
D USB port for upgrading
E
417mm

Battery communication
F Meter/CT Port
G CAN is a reserved port
H Load/Off-grid Output
I Ground connection port
J External monitoring connection port
K DRM Port(only for Australia)
L Communications/ LCD is a reserved port
M Waterproof valve
N Fans(only for X1-Hybrid-7.5-D and X1-Hybrid-7.5-M )
2.5 Terminals of Inverter

A B C D E F G H

Warning !
ON
Qualified electrician required for the installation.
PV 1 PV 2 BAT BMS Meter/CT CAN
Upgrade
OFF

Dongle DRM COM/LCD

J K L M
I
A

ON

PV 1 PV 2 BAT
BMS Meter/CT CAN
Upgrade
OFF

Dongle DRM COM/LCD

18 19
Technical Data Technical Data

3 Technical Data 3.3 Battery


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model
3.1 DC Input X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M

Battery type Lithium batteries


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model Battery Full Voltage [V] 80-480
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
Max. recommended PV power[W] Maximum charge/discharge flow [A] 30A
4500 5500 7500 9000 10000
Max. DC voltage[V] Communication interface CAN/RS485
600 600 600 600 600
Nominal DC operating voltage[V] Reverse connection protection Yes
360 360 360 360 360
MPPT voltage range[V] 70-550
MPPT Full Powervoltage range [V] 115-480 135-480 190-480 225-480 280-480
Max. input current[A] 14/14 14/14 14/14 14/14 14/14
Max. short circuit current[A] 16/16 16/16 16/16 16/16 16/16
Start output voltage[V] 90 90 90 90 90
No. of MPP trackers 2 2 2 2 2
Strings per MPP tracker 1 1 1 1 1

3.2 AC Output/Input 3.4 Efficiency, Safety and Protection


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model Model
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
AC Output
MPPT efficiency 99.9% 99.9% 99.9% 99.9% 99.9%
5000(Germany
Nominal AC power[ VA] 3000 3680 6000 7500 European efficiency 97.0% 97.0% 97.0% 97.0% 97.0%
4600,AU4999)
Maximum efficiency 97.6% 97.6% 97.6% 97.6% 97.6%
5500(Germany
Max. apparent AC 3300 3680 6600 7500 Max. battery charge efficiency
power[ VA] 4600,AU4999) 97.0% 97.0% 97.0% 97.0% 97.0%
(PV to BAT )(@ full load)
Rated AC voltage[V] 220/230/240 (180 to 270)
Max. battery discharge efficiency
97.0% 97.0% 97.0% 97.0% 97.0%
Rated grid frequency[Hz] 50/60 (BAT to AC)(@ full load)
23.9(Germany20, Security & Protection
Max.AC current[A] 14.4 16 28.6 32.6
AU21.7) DC SPD Protection Integrated(TypeIII)
Displacement power factor 0.8 leading...0.8 lagging AC SPD Protection Integrated(TypeIII)
Total harmonic distortion(THDi) < 2% Over/under voltage protection YES
AC Input Grid protection YES
Max. apparent power[VA] 6300 7360 9200 9200 9200 DC injection monitoring YES
Rated AC power[W] 3000 3680 5000 6000 7500 Back feed current monitoring YES
Rated grid voltage(range)[V] 220/230/240 (180 to 270) Residual current detection YES
Rated grid frequency[Hz] 50/60 Anti-islanding protection YES

Max.AC current[A] 27.4 32 40 40 40 Over load protection YES

Displacement power factor 0.8 leading...0.8 lagging Over heat protection YES
Array insulation resistance detection YES

20 21
Technical Data Installation

3.5 Off-grid Output 4 Installation


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M

Off-grid rated [VA]] power 3000 3680 5000 6000 7500 4.1 Check for Transport Damage
Off-grid rated voltage [V] 230VAC
Ensure that the inverter is in good condition via transportation. If there
Frequency ][ Hz] 50/60 is any visible damage such as cracks, please contact the dealer
Off-grid rated current [A] 13 16 21.7 26.1 32.6 immediately.
Off-grid Peak Power [VA] 120%rated,1h 120%rated,1h 120%rated,1h 120%rated,10min 100%rated
Switching time(typical value) [ms] internal switch<10,external switch<100
Total harmonic distortion (THDv) <2%
4.2 Packing List
Open the package and check the materials and accessories
according to the following list.

3.6 Generic Data


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D A B C D
Model
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M

Dimensions (W/H/D)[mm] 482*417*181


Dimensions of Packing (W/H/D)[mm] 590*530*315
Net weight [kg] 22 22 22 22 23

Gross weight [kg] 27 27 27 27 28


E F G H
Heat dissipation treatment Natural Cooling Forced airflow
Noise emission(typical)[dB] <30 <45

Storage temperature range [°C] -40~+70


Operating temperature range[°C] -35~+60 (derating at 45)
Humidity [%] 0%~100%
Altitude [m] <3000 I J K L
Protection level IP65
Security level I
X1-Hybrid User Manual

Cold standby consumption


3.0kW - 7.5kW

<3W
Over voltage category
X1-Hybrid Series 3.0KW-7.5KW

III(MAINS),II(PV, Battery) EN

Pollution Degree III


Installation mode
M N O P
Wall mounted
Inverter Topology non-isolated
Communication interface Meter/ CT, external control RS485, Pocket series (optional), DRM,USB
Standard warranty Standard 10 years

Q R S

22 23
Installation Installation

Number Quantity Description 4.3 Installation Precautions


A 1 X1-Hybrid G4 series inverter. The protection level of X1-Hybrid G4 series inverters is IP 65, so that the
B 1 Bracket inverter can be installed outdoors.
C☆ 1 Waterproof connector with Rj45 Check the installation environment and pay attention to the following
conditions when installing:
D☆ 4 PV terminal (positive*2 , negative*2 )
• Do not expose to strong light.
E☆ 4 PV pin angle(positive*2,negative*2) • Do not touch flammable building materials.
F☆ 3 8AWG European terminals • Do not approach flammable and explosive gases or liquids (e.g. where
chemicals are stored).
G☆ 1 OT terminal(inverter grounding)
• Do not touch cold air directly.
H 3 (Expansion bolt ,Gasket,Self-tapping bolt)*3 • Do not approach TV antenna or cable.
I☆ 2 10AWG European terminals • Do not place in areas above 3000 meters above sea level.
• Do not install in precipitation or high humidity, which may cause
J 1 M5 inner hexagon bolt
corrosion or damage Internal devices.
K☆ 4/3 Waterproof connector with RJ45 (COM/CAN/DRM/CT) • Keep the system out of reach of children.
L 2 Battery connection terminals(positive*1 , negative*1 ) If the inverter is installed in a narrow area, be sure to reserve appropriate
M 1 space for heat dissipation.
RJ 45 terminals
The ambient temperature of the installation site is -35°C~60°C.
N 1 Manual The maximum angle range of wall tilt ±5°.
O 1 Quick Installation Guide Avoid direct sunlight, rain and snow weather.

P 1 Warranty Card
Q▲ 1 Pocket WiFi
R 1 Meter( optional )
S☆ 1 CT

Note : “ C” \“ D” \“ E” \“ F” \”G“ \” I”and ”S“ accessoriesare not included in the accessory package of M No direct sunlight No Rain Exposure No snow Lay up
series inverter ,but included in X1-Matebox.
“K ” The inverter in Australia needs to be connected to DRM , which is 1 more
communication line adapter than that in other countries, while the other countries only
need 2 communication line adapters.
“ Q ” is the standardpart of M-series inverter and the optional part of D-series.

Stay away from Direct Sunlight Rain Exposure Snow Lay up Stay away from
combustibles antenna cables

24 25
Installation Installation

4.4 Tool preparation


Tool equipment
Type Name Image Name Image
Tool equipment
Type Name Image Name Image Individual
Safety Safety
Protection
DC Voltage gloves shoes
Bit φ10 Tool
Range ≥1100 V DC

Hammer Multimeter
drill
Type Name Image Requirement
Crosshead M5
Socket
Torque
wrench set Equipment Breaker Grid port and Off-grid port wiring
screwdriver Preparation
(Hexagon) section (4.5.2)

0.5mm²~6mm²
OT
Machine Installation Tools

Diagonal Dedicated PV wire, line number


terminals #12 AWG withstand voltage 1000V,
press clamp pliers PV end
temperature resistance 105℃ fire
wire
resistance grade VW-1
Multifunction
Utility knife terminal
crimping
tool (RJ45) Off-grid Double Core Cables
end wire

Marker Cable
Preparation
Grid end
Triple Core Cables
wire
Rubber
Tape ruler
hammer
Communi- Twisted pair with shield
cation lines
Hexagon
Crimping
keys
Tool
Battery
Cable Conventional wire
Euro
terminal
crimping Spirit level
tool
PE Cable Conventional wire
Individual
Protection Dustproof Protective
Tools Cover glasses

26 27
Installation Installation

4.5 Installation Site Conditions 4.5.3 Installation Space Requirements


Reserve enough space when installing inverter (at least 300mm) for heat
4.5.1 Installation Carrier Requirements
dissipation.
Do not install the inverter near flammable materials.
Please install the inverter on a solid object that can withstand the weight Reserved space dimensions of
≥300mm
requirements of the inverter and energy storage system. installation
Please be careful not to install the inverter in the plasterboard wall or
similar to the residential places with poor sound insulation ,so as not to Position Min Distance
work with noise and interfere with the residents life in the morning. Left 300mm
≥300mm ≥300mm
Right 300mm
Up 300mm
Down 300mm
4.5.2 Installation Requirements
Forward 300mm
Install the inverter at a maximum back tilt of 5 degrees, the inverter can
≥300mm
not be tilted forward, inverted, excessive back tilted or side tilted.

The distance of installation space for multiple inverters is as follows:

≥300mm ≥300mm

≥300mm ≥300mm ≥300mm


≤5°

≥300mm ≥300mm

≥300mm ≥300mm ≥300mm

≥300mm ≥300mm

28 29
Installation Installation

4.6 Mounting
m
80.00 m
Ø Preparation

Please prepare the following tools before installation.

Φ10 Drill
Installation tools: screwdriver, wrench ,Φ10 drill, hammer, socket wrench set
b) (Depth :80 mm)
and Hexagon keys.
Ø Step 2: hang the inverter on the bracket.
Ø Step 1: Fix the wall bracket to the wall.

First find the expansion screw and the wall bracket in the accessory bag, c) Insert expansion bolt into the hole, use rubber hammer to knock the
expansion screw bolt into the wall;
as shown below:
d) The bracket is aligned with the screw uses the inner hexagonal wrench to
screw the tapping screw until the expansion bolt "bang" is heard.

Expansion bolts, Gasket,Tapping screws Bracket

a)Use a marker to mark drilling holes of the bracket on the wall .Drill Expansion bolts
holes at marked spots with depth of 80mm. Rubber hammer
c)

Self-tapping Gasket
screws

Outer hexagon wrench


a) (Torque :2.5±0.2 N·m)
d)

30 31
Installation Electrical Connections

Ø Step 3: Tighten the inverter and bracket. 5 Electrical Connections


e) Hang the buckle on the inverter to the corresponding position of the
backplane; 5.1 PV Connection
f ) Use the inner hexagonal wrench to tighten the inner hexagonal screw X1-Hybrid G4 series inverter have two PV inputs. Please select
on the right side of the inverter. photovoltaic modules with good performance and quality assurance.
The open circuit voltage of the module array should be less than the
maximum PV input voltage specified by the inverter, and the working
voltage should be within the MPPT voltage range.

Table 1: Maximum input voltage limit


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M

Max. DC input voltage 600V

Warning!
The voltage of photovoltaic modules is very high, and is
dangerous voltage. When wiring, please follow the safe
e) electricity regulations.

Note!
Do not ground the positive or negative pole of the
photovoltaic module!

Note!
The following PV module requirements need to be applied to
each input range:
1. Same model
2. Same quantity
3. The same queue
4. The same angle

x
Note!
f) X1-Hybrid G4 series inverters do not support the following PV
module connection modes.
+ + +
- PV1
-
+ + PV2
- - -
PV Inverter


Inner hexagonal wrench
X1-Hybrid G4 series inverters support the following PV
(Torque :1.2±0.1 N·m) module connection modes.
+ + +
- - PV1
+
+- PV2
-
PV Inverter
32 33
Electrical Connections Electrical Connections

Ø Connection step Step 4. Tighten the PV pin needle and the wiring harness to make the
connection tight without looseness.
The PV port wiring of X1-Hybrid G4 M series inverter has been
completed. On X1-Matebox, the D series needs to be wired
according to the following steps.

Step 1. Turn off the DC switch, connect the PV module, prepare a 12AWG
PV cable, and find the PV (+) terminal and PV (-) terminal in the package.

Crimping Tool

Negative terminal
PV cable PV pin Step 5. The PV joint is divided into 2 parts - the plug and the fastening head.
Positive terminal
Insert the cable through the fastening head and the opposite plug.
Note that the red and black lines correspond to different of plugs. Finally,
Step 2. Use a wire stripper to strip the 7mm insulation layer of the wire end.
force the cable pair into the plug, will a "click" sound, which indicates that the
connection is complete.

Positive terminal
mm
7.0
Wire stripper

Step 3. Tighten the cable with the insulation layer stripped and insert it into
the metal terminal (see Figure 1), make sure all wires are inserted Into the Negative terminal
metal terminal (see Figure 2).
Step 6. Tighten the fastening head and into insert the corresponding
positive and negative (PV-/PV+) ports of the inverter.

PV+

Positive
Positive PV pin
Negative PV pin PV-
Figure 1

Negative
Positive metal terminal
Negative metal terminal

Figure 2

34 35
Electrical Connections Electrical Connections

The following is the location of the inverter positive and negative 5.2 Grid Port and Off-grid Output Connection
(PV-/PV+) ports.
X1-Hybrid G4 series inverter are single-phase inverter . Suitable for rated
voltage 220/230/240V, frequency 50/60Hz. For more technical
requirements, please consult the requirements of the local public grid.

Ø Grid port connection

Grid Cable and Micro-breaker recommended


Model X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Cable (copper) 4-6mm² 6-8mm² 8-10mm² 8-10mm² 8-10mm²

PV1+ Micro-Breaker 32A 40A 50A 50A 50A

PV2+
Model X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
PV1- Cable (copper) X1-Hybrid-3.0-M
3-4mm²
PV2- 3-4mm² 4-6mm² 4-6mm² 6-8mm²
Micro-Breaker 25A 25A 32A 32A 40A

Off-grid Cable and Micro-breaker recommended


X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model
Schematic diagram of the inverter PV connected. X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M

Cable (copper) 3-4mm² 3-4mm² 4-6mm² 4-6mm² 6-8mm²


Micro-Breaker 25A 25A 32A 32A 40A

The circuit breaker should be installed between the inverter and the mains,
and the load should not be directly connected to the inverter.

Figure: Wrong connection of load and inverter

36 37
Electrical Connections Electrical Connections

5.3 Off-grid Bolck Diagram Diagram B: Neutral line and PE line are separated from each other,
all loads connect to the Off-grid port;(For most countries)
X1-Hybrid G4 series inverter has an off-grid function. When the grid is
connected, the inverter outputs go through the Grid port, and when the grid
is disconnected, the inverter outputs go through the Off-grid port.
X1-Hybrid G4
The Off-grid function can be connected to part of the load, and it can also be
used to connect to all loads. Please refer to the following diagram for the
wiring .
To be compatible with all loads, you will need an addition a accessory. If you PV 1PV 2 BAT CT

need a solution, please contact our sales. Grid Off-grid

Ø Off-grid wiring diagram


Main Breaker
X1-Matebox
For to different local wiring rules, please refer to the diagram below N
PE
Please select the appropriate wiring method according to local wiring rules.
E-BAR

Grid

Breaker
Battery
Diagram A: Neutral line and PE line are separated from each other, and the
common load is connected to the off-grid port;(For most countries) Loads Distrbution Box

N-BAR for loads


PV 1
PV 2
X1-Hybrid G4 Diagram C: Neutral line and PE line are combined togeter, and the
CT
common load is connected to the off-grid port;(Apply to Australia)
Breaker CT Main Breaker
BAT Grid Off-grid
N PV 1
PE
PV 2
X1-Hybrid G4
Breaker

CT
Breaker E-BAR Grid
Main Breaker/RCD
Breaker CT
BAT Grid Off-grid
RCD RCD N
Breaker
Breaker

Breaker
Battery Breaker E-BAR Grid

off-grid loads Loads


RCD RCD

N-BAR for off-grid loads N-BAR for loads

Breaker

Breaker
Battery
off-grid loads Loads

N-BAR for off-grid loads N-BAR for loads

38 39
Electrical Connections Electrical Connections

Diagram D: Neutral line and PE line are combined together, all Ø Off-grid load requirements
loads connect to the Off-grid port;(Apply to Australia)
Warning!
Ensure that the Off-grid load rated power is within the Off-grid
X1-Hybrid G4 rated output power range, otherwise, the inverter will report
an "overload" warning.

PV 1PV 2 BAT CT When “overload” occurs, adjust the load power to make sure it
Grid Off-grid
is within the Off-grid rated output power range, and the
inverter will automatically return to normal.
Main Breaker
For non-linear loads, ensure that the inrush current power is
X1-Matebox
N within the Off-grid rated output power range.
When the configuration current is less than the maximum DC
E-BAR
input current, the capacity and voltage of lithium battery and
Grid lead acid battery will decrease linearly.

Breaker
Battery
The following table shows some common loads for your reference.
Loads
Distrbution Box
Note: Please check with the manufacturer for high-power inductive loads.
N-BAR for loads

Power Instance
Common
Content
equipment Equipment
Start Rated Start Rated

X1-Matebox is a convenient wiring and accessory that can realize 100W 100VA 100VA
Resistive load X1 X1 (W) (W)
off-grid full load. For more information, please refer to X1-
Incandescent Incandescent
Matebox. If you need to buy X1-Matebox, please contact us.
lamp lamp

In full load scheme Diagram B and Diagram D, set "X1-


Matebox" to "Enable" under Settings;
Inductive load X 3~5 X2 450 - 750VA 300VA
The Australian customer must shorten the N lines of the 150W (W) (W)
Grid and the off-Grid in the X1-Matebox.
Fan Fridge Fridge
If your local wiring method does not follow the above
operation guide, especially the neutral wire, ground
wire, RCD wire, please contact our company before
operation.

40 41
Electrical Connection Electrical Connection

Ø Grid and Off-grid connection steps Step 3. Remove the 12mm insulation layer at the end of the wire. Insert
the European-style terminals respectively, and make sure that the stripped
Connection requirements ends are inserted into the European-style terminal ,and finally use
Note: Check the grid voltage and compare the voltage range crimping pliers to press tightly.
(see technical data).
Disconnect the circuit board from all power sources to prevent electric
shock.
The Grid and the Off-grid ports of X1-Hybrid G4 M series inverter have
been connected, for specific installation details, please refer to the Diagonal pliers
X3-Matebox Quick Installation Guide. And the D series needs to be
wired according to the following steps.
L L= 12 m m
Step 1. Prepare a Grid cable (three-core wire) and an Off-grid cable
(two-core wire), and then find the European terminal and waterproof
cover in the accessory bag.

Grid( Triple Core Cable) Off-grid( Double Core Cable) 10AWG Euro Terminal*2
8AWG*3 10AWG*2

Euro Terminal 8AWG *3 Waterproof cover

Step 2: The Grid and Off-grid cables go through the corresponding Grid
and Off-grid ports of the waterproof cover.
Crimping Tool

Grid

Grid
Off-grid

Off-grid
42 43
Electrical Connection Electrical Connection

Step 4. Find the location of the AC interface on the inverter, insert the Step 6. Tighten the waterproof fastening head.
crimped terminals into the UW10 terminals L, N, and P according to the
wire sequence, and use a flat-blade screwdriver to tighten the screws.
(Torque: 0.2±0.1N ·m)

GRID Off-grid

L N PE L N
Torque screwdriver
( Torque: 0.2±0.1N ·m)

Step 5. Install the AC waterproof cover, and tighten the screws on the four
sides of the waterproof cover with an Allen wrench.

Hexagon keys
( Torque: 0.4±0.1N ·m)

44 45
Electrical Connection Electrical Connection

5.4 Battery Connection Ø Battery connection steps:


Ø Connection requirements Battery port connection line of the X1-Hybrid G4 M series
inverter is on the X1-Matebox, just connect it. It is necessary to
X1-Hybrid G4 series inverter charge and discharge system can be
wire the D series according to the following steps.
equipped with high voltage lithium battery and lead acid battery.
Please note that the maximum voltage of the battery should not Step 1. Prepare 8 AWG battery power line , find the DC plug (+), DC plug (-)
exceed 480 V, battery communication should be compatible with the in the accessory bag.
X1-Hybrid G4 inverter.
8 AWG
Ø Battery Breaker
Before connecting the battery, a non-polar DC MCB must be installed to
ensure safety.
Before maintenance, the inverter need to be safely disconnected.
Power line BAT plug (+) BAT plug (-)
X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D X1-Hybrid-7.5-D
Model
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
Nominal voltage of DC breaker should be larger than maximum Step 2. Strip the insulation layer (length:15mm) at one end of the power line.
Voltage
voltage of battery.
Current[A] 32A

m
0m
Ø Battery connection diagram 15.
Diagonal pliers

ON

PV 1 PV 2 BAT BMS Meter/CT CAN

Step 3. Insert the stripped cables into the DC plug (-) and DC Plug (+)
Upgrade
OFF

Dongle DRM COM/LCD


respectively.

Non-polar
DC MCB
Communication line connection

Power line connection


CAN/RS485
- +

DC plug (-) DC plug (+)


... ...

Spring

Note: High voltage lithium battery

When using SolaX batteries, it is recommended that the number Cavity


of battery control (T-BAT-5.8) is 1 and the number of battery
modules (HV11550) is 1-3; the number of battery control (MC0600)
is 1 and the number of battery control (HV10230) is 1-4 pcs.
The cable must pass through here
46 47
Electrical Connection Electrical Connection

Step 3. Press down on the spring by hand, you can hear a click sound , Ø Communication connection
then push the ends together, and tighten the screw joints.
BMS port definition
The communication interface between the inverter and the battery uses
the waterproof connector with RJ45.
Spring
Spring
1) White with orange stripes
2) Orange
1 2 3 4 5 6 7 8
3) White with green stripes
4) Blue
5) White with blue stripes
Crack 6) Green
7) White with brown stripes
8) Brown

PIN 1 2 3 4 5 6 7 8
Definition BAT_TEMP GND GND BMS_CANH BMS_CANL X BMS_485A BMS_485B

Note!
After the BMS communication between the battery
and the inverter is finished, the battery will work
Step 4. Insert the battery power lines into the corresponding BAT port (+), (-) normally.
of the inverter.

Note: BAT port, not PV port!


Note: The positive and negative
wires of the battery are not
allowed to be reversed!

48 49
Electrical Connection Electrical Connection

5.5 Communication Connection 5.5.2 Introduction to meter/CT Communication

X1-Hybrid G4 inverter should work with an electric meter or current


5.5.1 Introduction to DRM communication (AS4777 regulatory requirements) sensor (CT for short) to monitor household electricity usage.
The electricity meter or CT can transmit the relevant electricity data
to the inverter or platform , which is convenient for users to read at
DRM requirements:
anytime.
Mode Requirement
DRM0 Operation disconnect device Users can choose to use electric meters or CTs according to demand.

DRM1 Do not consume power Please note that the meter/CT brand required by SolaX must be used.
DRM2 Do not consume more than 50% of rated power Note!
The meter or CT must be connected to the inverter, otherwise
Do not consume more than 75% of rated power AND the inverter will shut down and alarm SolaX "meter failure"alarm.
DRM3
Source reactive power if capable Smart meters must be authorized by SolaX , third party or
other companies ,Unauthorized meter may be incompatible
Increase power consumption
DRM4 with the inverter.
(subject to constraints from other active DRMs)
SolaX will not be responsible for the impact caused by the use
DRM5 Do not generate power
of other appliances.
DRM6 Do not generate more than 50% of rated power

Do not generate more than 75% of rated power AND


DRM7 Ø Electric meter connection diagram
Sink reactive power if capable

Increase power generation


DRM8 (subject to constraints from other active DRMs)
ON

PV 1 PV 2 BAT BMS METER/CT CAN


Upgrade
OFF

DONGLE DRM COM/LCD

1 1 2 3 4 5 6 7 8

8 DRM1/5 DRM2/6 DRM3/7 DRM4/8 +3.3V DRM0 GND GND

Grid Load
Single-phase meter
Remarks:
L
Currently only PIN6 (DRM0) and PIN1 (DRM1/5) are functional, other
PIN functions are under development. N
Household Meter
Meter1

If the user has other power generation


equipment (such as inverter) at home and
wants to monitor both, X1-Hybrid G4 inverter X1

provides Meter2 communication function to Meter2


monitor the power generation equipment. Other power generation
For more information, please contact SolaX. equipment

50 51
Electrical Connection Electrical Connection

Ø CT Connection Note for CT connection:

The current sensor measures the current on the live wire between the Note!
inverter and the public grid. • Do not place the CT on the N wire or ground wire.
• Do not put CT on the N line and L line at the same time.
CT connection diagram • Do not place the CT on the side where the arrow points to
the inverter.
• Do not place the CT on non-insulated wires.
ON
• The cable length between CT and inverter should not
OFF
PV 1 PV 2 BAT
Upgrade
BMS Meter/CT CAN
exceed 25 meters.
• After CT is connected, prevent the CT clip from falling off.
It is recommended to wrap the CT clip around in circles with
Dongle DRM COM/LCD

insulating tape.

Grid Loads

L CT 1 1 2 3 4 5 6 7 8

N 1
Household Meter 1 2 3 4 5 6 7 8

8 CT1-1 X CT2-1 485A 485B CT2-2 X CT1-2


Note:The arrow on the CT Meter/CT port is at the CT 2
must point at the public bottom of the inverter.
grid. Other power
generation
Public grid L Line X1
equipment
electricity
CT
Meter/CT

Note!
Only one of the Meter and CT connections can be selected.
If the user has other power generation equipment (such as inverter) at home Meter cable goes to pin terminal 4 and 5;CT cable goes to pin
and wants to monitor both, X1-Hybrid G4 inverter provides CT2 terminal 1 and 8; reserve CT cable goes to pin terminal 3 and 6.
communication function to monitor the power generation equipment.

LCD settings
To select CT, you need to enter Use setting ,then enter CT/Meter
Setting.

CT/Meter Setting
>Select
CT

52 53
Electrical Connection Electrical Connection

Ø BMS communication cable. 5.5.3 COM Communication

COM communication interface is mainly provided to the customer to do


The BMS pin is defined as follows: the second step of development use.

Ø Application occasion
1 2 3 4 5 6 7 8
COM is a standard communication interface, through which the
1
1 2 3 4 5 6 7 8 monitoring data of the inverter can be directly obtained. Also, external
8
BAT_TEMP GND GND BMS_CANH BMS_CANL X BMS_485A BMS_485B communication devices can be connected to carry out the secondary
development of the inverter .For specific technical docking,
please contact SolaX.

Note!
The communication port on the lithium battery must be consistent with the
definition of pins 4, 5, 7, and 8 above;

Data Read

Ø DRM communication cable


The DRM pin is defined as follows:

Data Read
1 2 3 4 5 6 7 8 Data Write
Smart control device
1 1 2 3 4 5 6 7 8 (developing)

8 DRM1/5 DRM2/6 DRM3/7 DRM4/8 +3.3V DRM0 GND GND


Ø COM PIN Definition

1 1 2 3 4 5 6 7 8

8 Drycontact_A(in) Drycontact_B(in) +13V 485A 485B GND Drycontact_A(out) Drycontact_B(out)

Note!
The communication port on the COM must be consistent with the definition of
pins 1,2,3,4,5 ,6,7,8 above;

54 55
Electrical Connection Electrical Connection

5.5.4 Communication Connection Steps Step 3. Insert the prepared communication cables into the RJ45 terminals
in sequence , and then use network cable crimping pliers to
Step 1. Prepare a communication cable, and then find the communication press them tightly.
adapter in the accessory bag.
1) White with orange stripes
2) Orange
1 2 3 4 5 6 7 8
3) White with green stripes
4) Blue
5) White with blue stripes
6) Green
Communication cable Waterproof connector with Rj45 Rj45 terminal 7) White with brown stripes
8) Brown

Step 2 Insert the communication cable through the communication


adapter, and peel off the outer insulation layer of 15 mm.

Multifunction terminal
crimping tool (RJ45)

Diagonal pliers

m
00m
15.

56 57
Electrical Connection Electrical Connection

Ø METER/CT communication cable 2) One side of the finished cable, Waterproof connector with RJ45 is inserted
into the inverter, and one side of the RJ45 terminal is inserted into the
METER/CT pin is defined as follow: CT connection.

1 2 3 4 5 6 7 8

1 1 2 3 4 5 6 7 8
Meter/CT CAN

8 CT1-1 X CT2-1 485A 485B CT2-2 X CT1-2 COM/LCD

Note!
Only one of the Meter and CT connections can be selected..
Meter cable goes to pin terminal 4 and 5;CT cable goes to pin
teminal 1 and 8; CT2 cable goed to pin terminal 3 and 6.
distribution box

Note!
1) Users can customize the length of the CT communication cable. The When installing, pay attention to water resistance. All the
accessory package provides 1*RJ45 and 1*waterproof connector with connected parts of CT must be put into the distribution cabinet.
RJ45 terminals.
When the CT cable is completed, connect the A terminal to the
"CT/METER" port of the inverter and tighten the waterproof screw , and
Step 4. Tighten the completed Meter/CT/BMS communication line and
connect the B terminal to the RJ45 coupler
tighten the waterproof plug.

A
B

58 59
Electrical Connection Electrical Connection

Step 5: Finally, find the corresponding COM, METER, CT, DRM ,LCD poets on the 5.6 Grounding Connection (mandatory)
inverter and insert the communication cable into the corresponding ports.
The user must make two ground connections :one shell grounding, and one
equipotentialgrounding.This prevents electric shock.
Note: If the PV end of the inverter is not connected with earth , the inverter
will turn on a red light Inspect and report ISO Fault .This inverter complies
with IEC 62109-2 clause 13.9 for earth fault alarm monitoring.

The ground wire port of X1-Hybrid G4 M series inverter has been


connected, and the D series needs to be wired according to the
following steps.
Ø Ground connection steps:
Meter/CT Step 1. Prepare a one-core cable (12AWG), and then find the ground
terminal in the accessories.
12AWG

One-core cable (12 AWG) OT terminal Hexagon socket screws


Step 2. Strip the grounding cable insulation(length”L2), insert the
striped cable into the ring terminal, and then clamp it.

L1
m
3m
L 1+
=
L2
Diagonal pliers

Meter/CT C
Step 3. Insert the stripped cable into OT terminal and tighten the terminal
with a terminal crimping tool.

COM/LCD

Leaking cable

Crimping Tool

60 61
Electrical Connection Electrical Connection

Step 4. Find the ground connection port on the inverter, and screw the 5.7 Monitoring Connection (Accessories)
ground wire on the inverter with an M5 Allen key.
The inverter provides a DONGLE port, which can transmit data of the
inverter to the monitoring website via Pocket WiFi Plus, Pocket 4G, Pocket
GPRS, and Pocket LAN. (If necessary, purchase products from SolaX)

Ø WiFi connection diagram

SolaX Cloud

Router

Ø Wireless monitoring accessories connection steps:


Step 1. Of the DONGLE port of the inverter needs to unscrew the screw
and take off the cover.

Dongle Dongle

Cover

Phillips screwdriver
Torque: 1.2±0.1N·m

Hexagon keys
Torque: 1.5±0.2N·m
Dongle

62 63
Electrical Connection Electrical Connection

Step 2. Plug the Pocket WiFi Plus into the DONGLE port, use the screws 5.8 Check All Below Steps Before Starting Inverter
in the Pocket WiFi Plus accessory to tighten it.

Ø After the inverter is checked, the condnct the following


steps:
Make sure that the inverter is fixed on the wall.
Ensure that all ground wires are grounded.
Confirm that all DC lines and AC lines are connected.
DONGLE

Make sure the CT is connected.


Make sure the battery is well connected.
Turn on the Load switch and Off-grid switch.
Turn on the battery switch.
Long press the “Enter “key for 5 seconds to exit the Off mode.
(The mode is factory defaulted as Off Mode)

PV 1
PV 2
X1-Hybrid G4
CT
NGLE

Breaker CT Main Breaker


BAT Grid Off-grid
N
PE

Phillips screwdriver

Breaker
Torque: 1.2±0.1N·m Breaker E-BAR Grid

RCD RCD

Breaker
Breaker
Battery
NGLE

off-grid loads Loads

N-BAR for off-grid loads N-BAR for loads

64 65
Electrical Connection Firmware Upgrading

5.9 Inverter Operation 6 Firmware Upgrading


Ø Before operation,check the inverter according to the following steps Ø Upgrade notes
a) Check that the inverter is well xed on the wall. Please read the following precautions before upgrading.
b) Ensure that all ground wires are well tightened.
c) Ensure that all DC and AC circuit breakers are disconnected.
d) Ensure that all ground wires are well tightened. Warning!
e) The AC output terminal is correctly connected to the mains. -In order to upgrade the firmware smoothly, if the DSP and
f ) Ensure that all photovoltaic panels and inverter are properly connected. ARM firmware need to be upgraded, please note that ARM
Unused DC connectors should be blocked with caps. firmware must be upgraded first, then DSP firmware!
-Please make sure that the category format is correct, do
Start the inverter not modify the firmware file name, Otherwise, the inverter
Steps to start the inverter
may not work!
- Turn on the AC switch between the X1-Hybrid G4 and the power grid.
- (Optional) Remove the locking screw from the DC switch.
- Turn on the DC switch between the PV string and the X1-Hybrid G4 if there is Warning!
any. -For X1-Hybrid G4, ensure that the PV input voltage is
- Turn on the DC switch at the bottom of the X1-Hybrid G4 . greater than 100V (upgrade on sunny days). please ensure
When the photovoltaic panel generates enough power, the inverter will start that the battery SOC is greater than 20% or the battery
automatically. input voltage is greater than 90V. Otherwise, it may cause
Check the status of the LED and LCD screen, the LED is green, and the LCD serious failure during the upgrade process!
screen displays the main interface.
If the LED is not green, please check the following:
-All connections are correct.
Caution!
-All external disconnect switches are closed.
-If the ARM firmware upgrade fails or stops, please do not
The following are 3 different states of inverter operation, which means that unplug the U disk power off the inverter and restart it., Then
the inverter starts successfully. repeat the upgrade steps.
Waiting: When the DC output voltage of the photovoltaic panel is higher than
100V (lowest starting voltage) and lower than 150V (lowest working voltage), the
inverter waits for checking. Caution!
Checking: The inverter will automatically detect the DC input. When the DC input -If the DSP firmware upgrade fails or stops, please check
voltage of the photovoltaic panel is higher than 150V and the photovoltaic panel whether the power is off. If it is normal, plug in the U disk
has enough energy to start the inverter, the inverter will enter the checking state. again and repeat the upgrade.
Normal: When the inverter is working normally, the green light is always on. At
the same time, the power is fed back to the grid, and the LCD displays the output
power.
Ø Upgrade preparation
If it is the rst time to boot, please follow the prompts to enter the setting interface.
Warning! 1) Please check the inverter version and prepare a U disk (USB 2.0) and
The input terminal of the inverter can be opened only when all the personal computer before upgrading.
installation work of the inverter has been completed. All electrical
connections must be performed by professionals in accordance with
Caution!
local regulations.
-Please make sure that the size of the U disk is smaller than
Note! 32G, and the format is fat16 or fat 32.
If it is the first time to operate the inverter, the system will
automatically display setup guide. Please follow the setup guide to
complete the basic inverter settings.
66 67
Firmware Upgrading Firmware Upgrading

2) Please contact our service support through service@solaxpower.com to


obtain the firmware, and store the firmware in the U disk according to the
following path.

Update:
For ARM le:“update \ARM\618.00361.00_Hybrid_X1G4_ARM_V1.01.0710.usb”;
For DSP le:“update\DSP\618.00360.00_Hybrid_X1G4_DSP_V1.01.0710.hex”; U Disk

Ø Upgrade steps
Step 1. Please save the "Upgrade" firmware in your U disk first, and press
the "Enter" button on the inverter screen for 5 seconds to enter the OFF
mode.

Step 3. LCD operation, enter the upgrade interface "update", as shown


Long press for 5 below(a): Please press the up and down keys to select ARM, then press
seconds down to set "OK", press the enter key to enter the software version
interface;
Step 2. Find the "update" port of the inverter, use a flat-blade screwdriver
or coin with the same width to remove the waterproof cover, and insert
Upgrade Selection Upgrade(ARM)
the U disk.
>ARM Cancel
DSP >OK

(a) (b)
Step 4. Please confirm the new firmware version again and select the
Flat-blade screwdriver or coin Waterproof cover firmware to upgrade. The upgrade takes about 20 seconds.
(Port size: 12·2mm; (d) When it is completed, the LCD screen returns to the "Update" page.
Torque: 1.5±0.2N·M)
Update(ARM) Update(ARM) Update
>618.00361.00_Hybrid_ Upgrading---------25% >ARM
X1G4_ARM_V1.01 DSP
0710.usb

(c) (d) (e)

68 69
Firmware Upgrading Setting

Step 5. For DSP: Please wait for 10 seconds. When "Update" page shown as 7 Setting
as below, press down to select "DSP" and then press Enter. Please
confirm the firmware version again and press Enter to upgrade. The upgrade
takes about 2 minutes.

Update Update(DSP) Update(DSP) 7.1 Control Panel


ARM >618.00360.00_Hybrid_ connect
>DSP X1G4_DSP_V1.01_07
10.hex

( f) (g) (h)

Update(DSP) Update(DSP)

DSP Erasing--------- Upgrading---------25%

(i) (j)

Step 6. After the upgrade is completed, the LCD screen displays "Upgrade
Successful".
Upgrade(DSP)

Upgrade Successful Name Description


LCD Display inverter information on the LCD display.
(k) Screen
Blue light: The inverter is in normal state or Off-grid mode.
Step 7. Plug off the U disk, press "Esc" to return to the main interface, and Blue ashing: The inverter is in the waiting, checking state
long press the enter key to exit the mode. or the system switch is off.
Off: The inverter is in a fault state.
LED Green: The battery communication is normal but the battery
Caution! Indicator MCB is disconnected, and the battery communication is
light normal and working normally.
-Please strictly follow each step from step 1-6, don't miss Green ashing: The battery communication is normal and
it. in an idle state.
-Please confirm the ARM/DSP firmware version on the Off: The battery does not communicate with the inverter.
USB flash drive. Red light on: The inverter is in a fault state.
Off: The inverter has no error.
ESC button: Return from the current interface or function.
Tip: If the display screen is stuck on "X1-Hybrid G4" after the upgrade,
Up button: Move the cursor to the upper part or increase the
please turn off the photovoltaic power supply and restart, and the inverter Key value.
will restart and return to normal. If not, Function
Down button: Move the cursor down or decrease the value.
please contact our service @solaxpower.com for help.
Enter button: Con rm selection.

70 71
Setting Setting

7.2 Menu Structure 7.3 LCD Operation


1
System ON/OFF The main inter face is the default inter face, the inver ter will
automatically return to this interface when the system started up
successfully or not operated for a period of time.
Self Use
The information of the interface is as below. “Power” means the
Work Mode

2 Feed-in priority
instant output power; “ Today” means the power generated within
Backup mode Forced discharge the day. “Battery” means the left capacity of battery energy.
Manual Forced charge
Stopcharge&discharge Date&Time
Language Power 0W
PV1
Off-grid mode Today 0.0KWh
System Status

PV2
Battery 80%
3 Battery User settings Self-use mode
Normal
Feed-in Priority
On-grid
Off-grid Backup mode
Chrg & dischrg period
Meter/CT
User Password

On-grid

Safety Code
History Data

Off-grid
4 Grid Parameters Ø Menu interface
Meter/CT-1
Export Control
Meter/CT-2
Meter/CT Settings
The menu interface is another interface for users to change settings
Error Logs or obtain information.
Self Test
-When the LCD displays the main interface, click "OK" to enter this
Shadow Fix
interface.
Modbus
-The user can select up and down the menu, and press the "OK" key
X1-Matebox Setting
to con rm.
settings

5
Advanced settings Power Factor
Pu Function
LVRT Function Menu
Power limit
>System ON/OFF
Work Mode
DRM Function System Status
Inverter
6 Main Breaker Limit
About

Battery
Reset
Internal Code
Advance Password

DIO Function
Manufactory settings Safety Mode

COM Port Select

Note:"  "This part of the content cannot be set by the end user.
Please contact the installer or SolaX if necessary.

72 73
Setting Setting

Ø Mode Selection
System ON/OFF Self Use

Mode Select
Work Mode Feed-in priority

System Status Backup mode

History Data Manual

Settings Mode selection, there are 4 working modes to choose from.

About Name Description


The self-use mode is suitable for areas with low feed-in subsidies
and high electricity prices.
① When the power of PV is sufficient
Active Charging or Discharge time period :PV will power the loads
rstly, and surplus power will charge to the battery .If the battery
is fully charged, then sell the surplus power to the grid;
( The inverter will limit the output if Feed-in limit or zero feed-in is
needed )
(PV>Load ,PV →Load→Battery → Grid)
Self Use ② When the power of PV is insufficient
Ø System ON/OFF Active Charging time period: PV will power the loads rstly ,the
remaining power will be taken from the grid , the battery will not
discharge at this time.
(PV<Load ,PV + Grid → Load)
"ON" indicates that the inverter is in working state, which is Active Discharge time period: PV+BAT will power the loads
generally the default state. together. If the power is still not enough, the remaining power
will be taken from the grid.
“OFF" means that the inverter stops running and only the LCD (PV<Load ,PV + Battery + Grid → Load)
screen is turned on. ③ Without PV power
Active Charging time period: The grid supplies the loads and also
can charge the battery;
(PV=0 , Grid → Load + Battery)
Active Discharge time period :The battery will power the home
loads rstly .If the battery power is not enough ,the remaining
System
power will be taken from the grid .The inverter will enter into the
Switch standby state.
(PV=0 , Battery+Grid → Load )
>OFF< Battery min SOC can be set:10%-100%

The Feed-in priority mode is suitable for areas with high feed-in
subsidies, but has feed-in power limitation.
①When the power of PV is sufficient
Active Charging time period:PV will power the loads rstly, and
Feed-in surplus power will feed-in to the grid. If the feed-in power has
priority been limited,the surplus power can charge the battery.
(PV>Load ,PV → Load → Grid → Battery)
Active Discharge time period:PV will power the loads rstly,and
surplus power will feed-in to the grid.
(PV<Load ,PV → Load → Grid )

74 75
Setting Setting

②When the power of PV is insufficient Ø System Status


Active Charging time period :PV will power the loads rstly, the
remaining power will be taken from the grid. The battery will not PV1 a)
discharge.
(PV<Load ,PV + Grid → Load) PV2 b)

System Status
Discharge time period: PV+BAT will power the loads together. If the
power is still not enough, the remaining power will be taken from the Battery c)
grid.
On-grid d)
Feed-in (PV<Load ,PV + Battery + Grid → Load)
priority ③Without PV power
Off-grid e)
Active Charging time period :The grid will power the home loads and
also charge the battery; Meter/CT f)
(PV=0 , Grid → Load +Battery)
Active Discharge time period :The battery will power the home loads
rstly .If the battery power is not enough ,the remaining power will be System status contains six content:PV1/PV2/Battery/On-grid
taken from the grid .The inverter will enter into the standby state. (energy feed into or buy from the grid)and Off-grid and so on.
(PV=0 , Battery+Grid → Load)
Battery min SOC can be set:10%-100%.
Press up and down to select, press "Enter" to con rm the selection,
The back-up mode is suitable for areas with frequent power outages.
and press "ESC" to return to the menu.
Same working logic with “Self-use” mode.This mode will maintain the
Backup battery capacity at a relatively high level.(Users' setting) to ensure that a/b) PV1, PV2
mode the emergency loads can be used when the grid is off. Customers no Here you can see the voltage, current and power of the pv1 and
need to worry about the battery capacity. PV2.photovoltaic panels respectively;
Battery min SOC can be set:30%-100%.
Backup mode SOC adjustment range :30%-100%;In Backup mode,
SOC-min under off-grid condition is 10%, which cannot be modi ed.
The off-grid mode is used when the power grid is off .System will PV1 PV2
provides emergency power through PV and batteries to supply power
>U 0.0V >U 0.0V
to the household loads. (Battery is necessray)
Off-grid ①When the power of PV is sufficent I 0.0A I 0.0A
PV will power the loads rstly, and surplus power will charge to the
battery.(PV฀Load ,PV ฀ Load ฀ Battery)
②When the power of PV is insufficient
The remaining power will be taken from the battery.
(PV฀Load ,PV+Battery ฀ Load)
③Without PV power
c) Battery
The battery will power the emergency loads until the battery reached
the min SOC,then the inverter will enter into the idle mode.
This status shows the battery condition of the system. Including
(PV=0, Battery ฀ Load) battery voltage and battery current, Battery power, battery
capacity, battery temperature, BMS connection status. The
Note: in the case of grid connection, all working modes work normally when the
battery SOC >5%.When the battery charge rate is below 5%, the PV or Grid will first meaning of the sign of battery current and power: "+" means
charge the battery SOC11%, and then return to the working mode selected by the charging; "-" means discharging.
user. f
Manual mode (manual mode), there are three options to choose from: forced
Battery
charging, forced discharge, stop charging and discharging (grid-connected 0
power). U 400.0V
I -1.0A
Work Select Work Select P -400W
>Manual >Manual
Forced Charge Forced Discharge

Work Select
>Manual
Stop Cha&Discha

76 77
Setting Setting

d)On-grid Ø History Yield


Here you can see the voltage, current, frequency, and power of the
On-grid a)
grid.
Off-grid

History Data
b)

On-grid Meter/CT-1 c)
U 0.0V
I 0.0A Meter/CT-2 d)
P 0.0W
Error Logs e)

The history data contains five pieces of information: on-grid power of


the inverter, off-grid power generation, power of the meter/CT and error
e) Off-grid Error logs.
Here you can see the voltage, current, frequency and power of the
inverter when it is disconnected from the grid.
Press up and down to select, press Enter to confirm selection, and press
ESC to return to the menu.

Off-grid
U 0.0V a)On-grid
I 0.0A Here is a record of the power capacity of the inverter connected to the
P 0.0W grid today, yesterday, this month, last month and the total.

On-grid
Output Today
f )Meter/CT Output Total
Here you can see the data showing the meter or the CT. Input Today

Meter/CT b)Off-grid
>Meter/CT-1 Here you can see the off-grid output of the inverter today, yesterday,
Meter/CT-2 this month, last month and the total output.

Off-grid
Meter/CT Meter/CT Today
>Meter/CT-1 >Meter/CT-2 Total
4000w 4000w 00.0KWh

78 79
Setting Setting

c)Meter /CT-1Here you can see the inverter electricity sold, total Ø Settings
electricity sold, electricity bought from the grid and total electricity
Date&Time a)
bought on that day.
Language b)

User settings
Off-grid mute c)
Meter CT-1
>FeedInToday: Self-use mode d)

00.0KWh Feed-in Priority mode e)

Backup mode f)
d)Meter /CT-2
Here you can see the total power output of the inverter for the day. Chrg & dischrg period g)

User Password h)

Meter CT-2
>Output Today: Here you can set the inverter time, language, working mode, charging and
discharging time period and user password.
00.0KWh
User Setting
Date Time
Language
Off-grid mode
e) Error Logs
Here you can see the most recent six error messages.
a) Date time
This interface is for users to set the system date and time.
Error logs
>No error Date time

>2019 - 11 - 15
10 : 19

b) Language
This inverter provides multiple languages for customers to choose.

Language
>Select:
English

80 81
Setting Setting

c )Off-grid Mute f ) Backup mode


Here you can choose whether the buzzer is turned on when the inverter In this mode, you can set the minimum backup battery power
is running in off-grid mode. Select Yes, the buzzer mutes, select NO, percentage and battery power percentage.
off-grid mode, the buzzer will sound once every 4s when the battery is For example: Min SOC is set to "10%", which means that the battery is
fully charged, the closer the battery is to the empty state, the higher the discharged to 10% of the battery capacity, and the battery is not
buzzer will sound, to remind users to avoid battery loss . allowed to continue to discharge.
Charge battery to is set to "90%", which means that the maximum
charge to the battery is 90%.
Off-grid Mute
> Mute:
Backup mode Backup mode
Yes >Min SOC: >Charge battery to

10% 90%

d) Self-use mode
g) Charge and discharge time
In this mode, you can set the minimum battery state of chargereserve
Here you can set the charge and discharge time period.
percentage, whether to charge at night, and the percentage of battery
If two charging and discharging periods are needed, turn on the
charge.
charging and discharging period 2 and set the period.
For example: Min SOC is set to "10%", which means that the battery is
discharged to 10% of the battery capacity, and the battery is not allowed to
Chrg&Dischrg Period Charge Period
continue to discharge.
Charge at night set to "Disable" means not to charge the battery at night, > Charge Period > Charge Period
set to "Enable" means to charge the battery at night. Start Time End Time
Charge battery to is set to "90%", which means that the maximum charge
to the battery is 90%.
Allowed Disc Period Allowed Disc Period
Self-use mode Self-use mode Self-use mode > Start Time > End Time

>Min SOC: >Charge at night >Charge battery to

10% Disable 90%


Chrg&Dischrg Period2
>Function

e)Feed-in Priority mode Enable Disable


In this mode, you can set minimum battery state of chargereserve
percentage and battery power percentage.
h)User Password
For example: Min SOC is set to "10%", which means that the battery is
The default password for the end user is "0000", where you can reset
discharged to 10% of the battery capacity, and the battery is not allowed to
the new password and press the up/down key to increase or decrease
continue to discharge.
the value. Press "Enter" to confirm the value and jump to the next digit
Charge battery to is set to "90%", which means that the maximum charge to
.When all passwords have been entered and confirmed, press "OK" to
the battery is 90%.
set the password successfully.
Feed-in Priorty mode Feed-in Priorty mode
>Min SOC: >Charge battery to User Password

10% 90%
0 0 0 0

82 83
Setting Setting

Ø Advance settings a) Safety Code


User can set safety standard according to different countries and grid tied
Safety Code a) . There are now 1 standards to choose from. (The here may be changes in
Grid Parameters b) the future ,please refer to the screen display)
Export Control c)
Item Standard Country
Meter/CT Settings d) 1 ARN 4105 German

Self Test e)
Shadow Fix f)
OverVoltage_L1
Advanced settings

Modbus g)
UnderVoltage_L1
X1-Matebox Setting h)
OverFreq_L1
Power Factor i)
UnderFreq_L1
Pu Function j)
Vac 10min Avg
LVRT Function k)
OverVoltage_L2
Power limit l)
UnderVoltage_L2
DRM Function m) OverFreq_L2
Main Breaker Limit n) UnderFreq_L2
Reset o) OverFreq_L2
Advance Password p) UnderFreq_L2

Grid Parameters Tovp_L1


Tuvp_L1
All advanced settings can be set here, such as battery, grid, off-grid, etc..
"Advanced" setting is generally customization and resetting for battery Tofp_L1
and grid . Each part has lower level parts. Tovp_L2
Please contact your installer or factory and enter the installer password.
Tuvp_L2
Advanced Tofp_L2
Safety Code Tufp_Fast
> Grid Parameters
Reconnection Time
Checking Time
W(Gra)
* Please note that when the inverter DSP communication fails, all
advanced settings will be hidden. OFPL_StartPoint
OFPL_SetRate
Advanced Charger OFPL_DelayTime
DSP-COMM failed >Battery Awaken UFPL_StartPoint
>Battery NO UFPL_SetRate

84 UFPL_DelayTime 85
Setting Setting

b) Grid Parameters CT/Meter Setting CT/Meter Setting


Here you can set the protection value of grid voltage and frequency. >Select >Meter 1Addr:
The default value is the specified value under the current safety xxxxxxxx
Meter
regulations, and the user cannot change it .
The display content will be displayed according to the requirements
of local laws and regulations, which are constantly increasing. Please
refer to the contents displayed on the inverter screen. e) Self Test (only for CEI 0-21)
The self test function allows users to test the following items. "Full test",
"Ovp(59.S2) test"27. "Uvp (s1) test", "Uvp (27. s2) test", "Ofp (81> .S1) test",
Grid Grid
"Ufp (81 <.S1) test", "Ufp (81> .S2) test", "Ufp (81 <.S2) test",
>OverVoltage_L1 >UnderVoltage_L1 "Ovp10 (59. s1) test".
0.0V 0.0V
In the self-test interface, the user can select "all tests" or a single test item for
testing.
Before testing, make sure that the inverter is connected to the grid.
Grid Grid All tests take about 6 minutes. And it will display "Success" and then "Delivery".
>OverFreq_L1 >UnderFreq_L1 For a single test item, it takes about a few seconds or minutes.
Click "Test Report" to view the test results of all items.
0.0Hz 0.0Hz

Grid Grid
>Vac 10min Avg >OverVoltage_L2 ALL Test
Test report
0.0V 0.0V
Uvp(27.S1) test

c)Export Control >Ofp2(81>.S2)result >Ovp2(59.S2)result


This feature allows the inverter to control the amount of electricity Ft: 51.50Hz Tt:1000ms Vt: 264.5V Tt: 300ms
output to the grid. Fs: 0.00Hz To: 998ms Vs: 0.0V To: 200ms
The factory value is the default and can be changed by the user. The F0: 0.00Hz pass V0: 0.0V pass
user value set by setup must be less than the maximum. If the user
does not want to supply power to the grid, set it to 0. >Ofp2(27.S2)result >Uvp2(27.S1)result
Vt: 92.0V Tt: 200ms Vt: 195.5V Tt: 400ms
Export Control Vs: 0.0V To: 196ms Vs: 0.0V To: 200ms
V0: 0.2V pass V0: 0.0V pass
User value:
0W
>Ofp2(81>S1)result >Ufp2(81<.S1)result
Ft: 50.50Hz Tt: 100ms Ft: 49.50Hz Tt: 100ms
Fs: 0.00Hz To: 96ms Fs: 0.00Hz To: 98ms
F0: 0.2Hz pass F0: 0.02Hz pass
d)Meter/CT Settings
The user needs to select the CT or electricity meter to connect the
inverter here. Select the address of the meter. CT does not need to select >Ufp2(81<.S2)result >Ovp10(59.S1)result
the address. Ft: 47.50Hz Tt: 400ms Vt: 253.0V Tt: 600ms
Fs: 0.00Hz To: 3999ms Vs: 0.0V To: 598ms
F0: 0.02Hz pass V0: 0.0V pass

86 87
Setting Setting

f )Shadow Fix Power Factor


Here, you can set the shadow tracking with four options, which are off, Mode Select
low, medium, and high.
> Q(u) <
Shadow Fix
>Func Select
Mode Comment
>OFF< Off -
Over-Excited PF value
Under-Excited PF value
g) Modbus Upper limit
Here you select the baud rate of the external communication Lower limit
protocol, the default location of 19200 and 485 addresses. Power Upper
Curve
Power Lower
Modbus RTU/485 Modbus RTU/485 PFLockInPoint ( CEI 0-21 only)
Baud Rate: RS485 Addr: PFLockOutPoint ( CEI 0-21 only)
115200 3Tau
1 VoltRATIO 1 ( AS4777.2 only)
VoltRATIO 4 ( AS4777.2 only)
QURESPONSEV2 ( AS4777.2 only)
h)X1-Matebox Setting Q( u ) QURESPONSEV3 ( AS4777.2 only)
If you want X1-Matebox installed, you need to turn this feature on here. QURESPONSEV4 ( AS4777.2 only)
K Value (CEI 0-21 only)
Fixed Q Power Q Power
X1-Matebox Setting
>Select ● Reactive power control, reactive power standard curve cos φ = f(P)
Eisable Enable For VDE ARN 4105, the curve cos = f(P) should refer to curve B. The set
default value is shown in curve B.

I) Power Factor (applicable to specific countries, please refer to local grid For e8001, the curve cos = f(P) should be curve A. The set default value is
requirements.) shown in curve A.

There are 5 modes for selecting: Off , Under-Excited, Over-Excited, Curve, Q( u ). For CEI 0-21, the default value of PFLockInPoint is 1.05. When Vac> 1.05Vn,
(May be changed or added without notice) Pac> 0.2 Pn, curve cos cp = f(P) corresponds to curve B.
User press up and down key to select, press enter key to confirm.
cos φ
leading
Power Factor Power Factor 0.9/0.95*
Mode Select

over-excited
Mode Select

> Off < > Over-Excited <
1
0.2 0.5 1.0

under-excited
p/pEmax
Power Factor Power Factor
Mode Select Mode Select
0.9/0.95*
lagging
> Under-Excited < > Curve < curve A

88 89
Setting Setting

cosφ Upper limit


k) LVRT Function(apply to50549)
0.95 0.9 Here you can set the high and low enable or disable..

inductive

inductive
Power Upper LVRT Function
0.2 0.5 1.0 0.7 0.8
f (P) 0.2 0.3
f (P)
Function Control
capacitive

capacitive
Power Lower
Disable Enable

0.95 0.9
Lower limit

curve B curve C

● Reactive power control, reactive power standard curve Q= f(V) l) Power limit
Q
Power limit function, the maximum power of the AC port can be set
V2s=1.10Vn
by percentage.
Qmax V1s=1.08Vn=QuVlowRate
V2i=0.90Vn
V2i=0.92Vn=QuVlowRate Power Limit
V1s V2s
>Proportion
V2i V1i V
1.00

-Qmax

j) PU Function (applicable to specific countries, please refer to local m) DRM function (applied to NZS4777.2)
grid requirements) The DRM function is a demand response method required by the
NZS4777.2 standard and is only applicable to NZS4777.2.
The PU function is a volt-watt response mode required by certain The default value is "enable". Select "Disable" to disable this function.
national standards such as AS4777.2. This function can control the
active power of the inverter according to the grid voltage.
Selecting "Enable" means that this function is turned on and is the DRM Function
default value. >Function Control
Select "Disable" to deactivate the function.
Enable

PU Function PU Function
>PuFunction Response V2
n)Main Breaker Limit
Enable 220.0V Here you can set an open minimum current here.

PU Function PU Function Main Breaker Limit


Response V3 Response V4 >Current
40A
250.0V 265.0V

90 91
Setting Setting

o) Reset Ø Manufactory Setting


Users can reset the reset error log, meter power ,inverter power, and

Manufactory settings
restore factory settings here. DIO Function a)

Safety Mode b)
Reset Error Log Reset Meter/CT_1

>Reset >Reset COM Port Select c)


Yes Yes

Reset Meter/CT_2 Reset INV Energy a) DIO Function

>Reset >Reset The reserved functions will be displayed after being added later.
Yes Yes
DIO Function
Factory Reset >function
Enable
>Reset
Yes

b) Safety Mode
Safety scale, choose whether to be Italian safety.

Safety Mode Safety Mode


>Select >Select
p)Advance Password
Only Italy Except Italy
Here you can reset the advanced password. "Set OK!" is displayed on
success, and “Setup Failed!” Will also displayed on failure.

Advance Password Advance Password


c)COM Port Select
Here external communication protocol or external indoor screen of
Set OK! Setup failed the inverter can be set. When it is used for external communication
protocol, it can choose RS485 or MOBUS. When it is used for external
indoor screen, it can choose YES or NO.

RS485/MOBUS External LCD


>RS485 >Yes
MOBUS No

92 93
Setting Setting

Ø About a) About
Here you can see some basic information of the inverter and battery.
such as the inverter and battery SN number, software version number,
and system run time.

About
Inverter SN >Inverter
Battery
Register SN
DSP
Inverter
ARM
On-grid Run Time
About
Off-grid Run Time
Bat_PS1 SN Inverter
Bat_PS2 SN
Battery
Bat_PS4 SN Inverter Inverter
>Inverter SN >Register
BatteryM Version 01234560123456 01234560123456

BatteryS Version

Inverter code Inverter Inverter


Internal Code >DSP >ARM
BMS Code 2.07 1.03

Inverter Inverter
>System runtime > Internal code
1.02 2.3 1.03 2.07
Register1 SN: Represents the serial number of external monitoring
equipment, such as Pocket WiFi, Pocket LAN and Pocket GPRS.

94 95
Setting Troubleshooting

Battery
8 Troubleshooting
Battery Battery
> BatBrand:BAK > Bat-M SN 8.1 Troubleshooting
6S012345012345 This section contains information and procedures for
resolving possible problems with X1-Hybird G4, and
provides you with troubleshooting tips to identify and
Battery Battery solve most problems that may occur in X1-Hybrid G4.This
> Bat-PS1 SN > Bat-PS2 SN section will help you narrow down the source of any
6S012345012345 6S012345012345
problems you may encounter. Please read the
troubleshooting steps below.
Battery Battery Check the warning or fault information on the system
> Bat-PS3 SN > Bat-PS4 SN control panel or the fault code on the inverter information
6S012345012345 6S012345012345 panel. If a message is displayed, log it before doing
anything further.
Battery Battery Try the solutions indicated in the table below.
> BatteryM Version > BatteryM Version
2.01 2.01
Number
Overcurrent fault.
• Wait for a while to check if you're back to normal.
IE 001 TZ Protect Fault • Disconnect PV+ PV- and batteries, reconnect.
• Or ask for help from the installer if itcan not return to normal.

Internal Code
IE 002 Grid Lost Fult

Internal Code Internal Code Power grid voltage overrun


• Wait a moment, if the utility returns to normal, the system will reconnect.
> Inverter code > BMS code IE 003 Grid Volt Fault • Please check if the grid voltage is within normal range.
01 00 01 xx • Or ask the installer for help.

Electricity frequency beyond range


IE 004 Grid Freq Fault • If the utility returns to normal, the system reconnects.
Internal Code Internal Code • Or ask the installer for help.

> BAT-M > BAT-S1


2.01 1.01 50 IE 005 PV Volt Fault

• press the “ESC" key to restart the inverter.


IE 006 Bus Volt Fault • Check that the PV input open circuit voltage is in the normal range.

...
Internal Code Internal Code
• Or ask the installer for help.
> BAT-S2 > BAT-S8
1.01 50 1.01 50 IE 007 Bat Volt Fault

• The grid voltage was out of range in the last 10 minutes.


IE 008 AC10M Volt Fault • The system will return to normal if the grid returns to normal.
• Or ask the installer for help.

96 97
Troubleshooting Troubleshooting

Number Number
DCI overcurrent protection fault.
ARM software version mismatch Fault
IE 009 DCI OCP Fault • Wait for a while to check if it's back to normal.
IE 022 ARM Unmatched • update the software and press the ESC" key to restart the inverter.
• Or ask the installer for help.
• Or ask for help from the installer if itcan not return to normal .
DCV Off-grid overvoltage protection failure.
IE 010 DCV OVP Fault • Wait for a while to check if it's back to normal.
• Or ask the installer for help. Other device Fault
IE 023 Other Device Fault • update the software and press the ESC" key to restart the inverter.
• Or ask for help from the installer if itcan not return to normal .

IE 011 SW OCP Fault Mgr InterCom Fault


IE 025 InterComms Error • Shut down photovoltaic, battery and grid, reconnect.
• Or ask for help from the installer if itcan not return to normal .
Overcurrent protection fault.
• Check the impedance of DC input and AC output. • Internal communication errors
IE 012 RC OCP Fault • Wait for a while to check if it's back to normal.
IE 025 InterComms Error • Shut down photovoltaic, battery and grid connections.
• Or ask the installer for help. • Or ask for help from the installer if itcan not return to normal.
Insulation Fault
IE 013 Isolation Fault • Please check the wire insulation for damage.
• Wait for a while to check if it’s back to normal.
• Or ask the installer for help. IE 026 Inv EEPROM Fault

Temperature beyond limit


IE 014 Temp Over Fault • Check if ambient temperature exceeds the limit. Fault of Residual Current Device
• Or ask the installer for help. • Check the impedance of DC input and AC output.
IE 027 RCD Fault • Disconnect PV + PV - and batteries, reconnect.
Off-gridmode current is too strong. • Or ask for help from the installer if itcan not return to normal.
• Ensure that the load power is within the Off-gridpower range.
IE 015 Bat Con Dir Fault • Check for any non-linear load connections on the Off-grid. Electrical relay failure
• Move this load to check for recovery. IE 028 Grid Relay Fault • Disconnect PV+ PV- grid and batteries and reconnect.
• Or ask for help from the installer if itcan not return to normal. • Or ask for help from the installer if itcan not return to normal.

Off-grid over load fault.


• Shutdown the high-power device and press the “ESC" key to Off-gridrelay failure
IE 016 Off-grid Overload Fault IE 029 Off-grid Relay Fault • Disconnect PV+ ,PV-, grid and batteries and reconnect.
restart the inverter.
•Or ask for help from the installer if it can not return to normal. • Or ask for help from the installer if itcan not return to normal.

On-grid mode overload PVdirectionfault


• Shutdownthehigh-power device and press the" ESC" key to IE 030 PV ConnDirFault • Check if the PV input lines are connected in the opposite direction.
IE 017 OverLoad Fault restart the inverter. • Or ask for help from the installer if itcannotreturntonormal.
•Or ask for help from the installer if it can not return to normal.
Charge relay fault
IE 031 ChargerRelayFault • Press the ESC" key to restart the inverter. .
IE 018 BatPowerLow • Or ask for help from the installer if itcannotreturntonormal.

Off-grid earth relay fault


Battery communication loss IE 032 EarthRaleyFault • Press the ESC" key to restart the inverter. .
• Check that the communication lines between the battery and • Or ask for help from the installer if itcannotreturntonormal.
IE 019 BMS Lost the inverter are properly connected.
• Or ask for help from the installer if it can not return to normal. Power type fault
IE 101 PowerTypeFault • Upgrade the software and press the ESC" key to restart the inverter.
Fan Fault • Or ask for help from the installer if itcannotreturntonormal.
• Check for any foreign matter that may have caused the fan not to
IE 020 Fan Fault function properly. Off-grid port over current fault
• Or ask for help from the installer if it can not return to normal. • Check that the off-grid load does not exceed the system requirements,
IE 102 Port OC Warning and press the ESC" key to restart the inverter. .
Low temperature fault. • Or ask for help from the installer if itcannotreturntonormal.
IE 021 Low Temp • Check if the ambient temperature is too low.
• Or ask for help from the installer if it can not return to normal.

98 99
Troubleshooting Troubleshooting

Number Number

Manager EEEPROM Fault. Battery Unbalanced Failure


BE 009 BMS_CellImblance • Please contact the battery supplier.
.• Shut down photovoltaic ,battery and grid ,reconnect.
IE 103 Mgr EEPROM Fault
• Or seek help from the installer if it can not return to normal.
Battery hardware protection failure
BE 010 BMS_Hardware Protect • Please contact the battery supplier.

IE 104 DSPunmatched
Battery circuit failure
BE 011 BMS_Circuit_Fault • Restart the battery .
• Please contact the battery supplier.
NTC invalid
• Make sure the NTC is properly connected and the NTC is in good Battery insulation failure
IE 105 NTC Sample Invalid condition. BE 012 BMS_ISO_Fault • Check that the battery is properly grounded and restart the battery.
• Please confirm that the installation environment is normal • Please contact the battery supplier.
• Or ask for help from the installer, if itcannotreturnto normal.
Battery voltage sensor fault
Batterytemplow BE 013 BMS_VolSen_Fault • Please contact the battery supplier.
• Check the battery installation environment to ensure good heat
IE 106 Bat Temp Low dissipation. Temperature sensor failure
• Or ask for help from the installer, if itcannot returnto normal. BE 014 BMS_TemppSen_Fault • Restart the battery .
• Please contact the battery supplier.
Batterytemphigh
• Check the battery installation environment to ensure good heat Battery current sensor fault
IE 107 Bat Temp High BE 015 BMS_CurSensor Fault
dissipation. • Please contact the battery supplier.
• Or ask for help from the installer, if itcannotreturnto normal.
Battery relay failure
Meter error BE 016 BMS_Relay Fault • Please contact the battery supplier.
IE 109 Meter Fault •Please check that the instrument is working properly
• Or seek help from the installer if it can not return to normal. Battery type failure
BE 017 BMS_Type_Unmatch • Upgrade the battery BMS software.
Bypass relay fault • Please contact the battery supplier.
IE 110 BypassRaleyFault • Press the ESC" key to restart the inverter. .
• Or ask for help from the installer if itcannotreturntonormal. Battery version mismatch failure
BE 018 BMS_Ver_ Unmatch • Upgrade the battery BMS software.
Battery Error - External Communication Fault • Please contact the battery supplier.
BE 001 BMS_External_Err • Please contact the battery supplier.
Batterymanufacturer did not match the fault
BE 019 BMS_MFR_ Unmatch • Upgrade the battery BMS software.
Battery Error - Internal Communication Fault • Please contact the battery supplier.
BE 002 BMS_Internal_Err • Please contact the battery supplier.
Battery hardware and software mismatch failure
Over voltage in battery system BE 020 BMS_SW_ Unmatch • Upgrade the battery BMS software.
BE 003 BMS_OverVoltage • Please contact the battery supplier. • Please contact the battery supplier.

Low voltage in battery system Battery master slave control mismatches


BE 004 BMS_LowerVoltage • Please contact the battery supplier. • Upgrade the battery BMS software.
BE 021 BMS_M&S_ Unmatch
• Please contact the battery supplier.
Battery fault - over charge fault
BE 005 BMS_ChargeOCP Battery charging request does not respond to a fault
• Please contact the battery supplier.
BE 022 BMS_CR_ NORespond • Upgrade the battery BMS software.
• Please contact the battery supplier.
Battery fault-discharge over current fault
BE 006 BMS_DischargeOCP • Please contact the battery supplier. Battery slave software protection failure
BE 023 BMS_SW_ Protect • Upgrade the battery BMS software.
Over temperature in battery system • Please contact the battery supplier.
BE 007 BMS_TemHigh • Please contact the battery supplier.
Battery fault-discharge over current fault
BE 024 BMS_536_Fault • Please contact the battery supplier.
Battery temperature sensor malfunction
BE 008 BMS_TempSensor Fault • Please contact the battery supplier.
Over temperature in battery system
BE 025 BMS_SelfcheckErr • Please contact the battery supplier.

100 101
Troubleshooting Troubleshooting

Number 8.2 Routine Maintenance


BE 026 BMS_TempdiffErr
Battery temperature sensor malfunction Inverter do not require any maintenance or correction in most
• Please contact the battery supplier.
cases, but if the inverter often loses power due to overheating,
Battery Unbalanced Failure this can be attributed to the following reason:
BE 027 BMS_BreakFault • Please contact the battery supplier.
heat sink behind the inverter is covered with dirt.
Battery hardware protection failure
BE 028 BMS_Flash_Fault • Please contact the battery supplier. If necessary, clean the cooling heat sink with a soft dry cloth or
brush.
BE 029 BMS_Precharge_Fault
Battery precharge failure Only trained and authorized professionals familiar with safety
• Please contact the battery supplier.
requirements can perform maintenance and maintenance work.
Battery air switch failure
BE 030 BMS_AirSwitch_Fault • Check that the battery breaker is off.
• Please contact the battery supplier. Ø Safety inspections
Safety checks should be conducted at least every 12 months, please
If the information panel of your inverter does not show the fault light, check contact the manufacturer to arrange for appropriate training,
the following list to ensure the current installation status, correct operation. expertise, and practical experience in performing these tests.
(Please note that this action is not covered by warranty).
------Is the inverter located in a clean, dry and well-ventilated place?
These data should be recorded in the device log. If the equipment
------Is the DC input circuit breaker open?
is not running properly or any test fails, the equipment must be
------Is the specification and length of the cable adequate? repaired for details of safety inspections, refer to section 2 of this
------Are the input and output connections and wiring in good condition? manual for safety instructions and europe commission instructions.
------Is the configuration set correct for your particular installation?

Ø Regular maintenance
Please coritact SolaX customer service for further assistance. Please be prepared to describe
the details of your system installation and provide the inverter serial number.
Only quali ed people can do the following work.
In the process of using frequency converter, the manager should
check and maintain the machine regularly. The specific operation
is as follows.

1.Check whether the heat sink is covered with dirt, clean the inverter
and absorb dust if necessary. This work should be performed from
time to time.

2.Check whether the frequency converter indicator is normal,


check whether the frequency converter button is normal, check
whether the frequency converter display is normal.
This inspection should be conducted at least every 6 months.

3.Check the input and output lines for damage or aging. This
inspection should be conducted at least every 6 months.

4.Cleaning and safety inspection of PV modules shouldbe


carriedoutatleastonceevery6months.

102 103
Decommisioning Disclaimer

9 Decommissioning 10 Disclaimer
The XI-Hybrid G4 series hybrid inverters are transported, used and
9.1 Disassemble of Inverter operated under limited condition, such as environmental, electrical etc.
SolaX shall not be liable to provide the service, technical support or
Remove DC input line and AC output line of inverter. compensation under conditions listed below, including but not limited
Wait for at least 5 minutes to power off. to:
Remove all cable connections from the inverter.
Remove inverter from finger support the bracket. Inverter is damaged or broken by force majeure (such as earthquake,
Remove the bracket if necessary. flooding, thunderstorm, lighting, fire hazard, volcanic eruption etc).
Inverter's warranty is expired and doesn't buy extended warranty.
Can't provide the inverter's SN, warranty card or invoice.
Inverter is damaged by man-made cause.Inverter is used or operated
against any items in local policy.
9.2 Packing
Inverter's installation, configuration, commissioning doesn't follow the
requirements mentioned in this manual.
Load the inverter into the original package if possible. Inverter is installed, refitted or operated in improper ways mentioned
in this manual without authority from SolaX.
If the original package can not be found, you can also use the
Inverter is installed, operated under improper environment or
following requirements of the carton packaging:
electrical condition mentioned in this manual without authority from
Bearing capacity of more than 30kg.
SolaX.
Easy to carry.
Inverter is changed, updated or disassembled on hardware or
Can completely seal the cover.
software without authority from SolaX.
Obtain the communication protocol from other illegal channels.
Build monitoring, control system without authority from SolaX.
9.3 Storage and Transportation
Connect to other brands batteries without authority from SolaX.
Store the inverter in a dry, temperature -40°C~70°C environment.
SolaX will keep right to explain all the contents in this user manual.
Pay attention to less than four inverter on each stack board during
storage and transportation.

9.4 Waste Disposal


If it is necessary to scrap the inverter or other related parts,
be sure to send the waste inverter and packaging materials
to the designated location for recycling by the relevant
department.

104 105