Professional Documents
Culture Documents
AGENDA
Chapter 7: Documentation
Chapter 10: Fundamentals
Chapter 14: Inspection, Testing, and Maintenance
Chapter 17: Initiating Devices
Chapter 18: Notification Appliances
Chapter 23: Protected Premises Fire Alarm Systems
Chapter 24: Emergency Communications Systems
Chapter 26: Supervising Station Alarm Systems
INTRODUCTION
3
CHAPTER 7 - DOCUMENTATION
7.3.3.6 Design documents shall indicate the pathway class designations in accordance with
Section 12.3 .
7.3.3.7 Design documents shall indicate the pathway survivability level designations in
accordance with Section 12.4 .
7.4.5 Floor plan drawings shall comply with both of the following:
1) Be drawn to an indicated scale
2) Include the following information, where applicable for the particular system:
p) Pathway class designations in accordance with Section 12.3 , including the location of any
end of-line supervisory or power devices that are required by the pathway class
q) Pathway survivability level designations in accordance with Section 12.4
4
CHAPTER 7 - DOCUMENTATION
7.4.6 System riser diagrams shall comply with both of the following:
(1) Be coordinated with the floor plans
(2) Include the following information, where applicable for the particular system:
f) Pathway class designation in accordance with Section 12.3 , including the
location of any end of-line supervisory or power devices that are required by
the pathway class
g) Pathway survivability level designations in accordance with Section 12.4
5
CHAPTER 10 - FUNDAMENTALS
10.4.7.2 Abandoned fire alarm equipment shall be marked “not in service” until removed.
10.6.7.2.1.1* Battery calculations shall include a minimum 20 percent safety margin above
the calculated amp-hour capacity required.
10.6.7.2.14* As a minimum, battery calculations shall apply a correction factor of 1.25 for
aging to ensure the battery can meet its current demand at the end of service life.
6
CHAPTER 10 - FUNDAMENTALS
10.6.7.2.11 The secondary power supply for communications equipment at the protected
premises that is used to transmit signals to a supervising station shall have sufficient
capacity to operate the system under quiescent load (system operating in a nonalarm
condition) for a minimum of 24 hours.
10.6.7.2.12 At the end of that period in 10.6.7.2.11, shall be capable of transmitting signals
for a period of 5 minutes.
7
CHAPTER 10 - FUNDAMENTALS
10.6.10.1.2 Where the battery is not marked with the month/year by the manufacturer, the installer
shall obtain the date code and mark the battery with the month/year of battery manufacture.
10.6.10.1.3* The installer shall label the battery with a replacement date that does not exceed 4
years from the installation date.
10.6.10.1.4 The battery shall be replaced on or before the replacement date identified in 10.6.10.1.3.
10.6.10.1.5* Effective January 1, 2024, rechargeable batteries for the secondary power supply used
in control units, devices, and accessories shall be listed or component recognized by a nationally
recognized testing laboratory.
A.10.6.10.1.5 Examples of listing standards are: UL 1989 Standard for Standby Batteries and UL
2054 Standard for Household and Commercial Batteries.
8
CHAPTER 10 - FUNDAMENTALS
3.3.302 Supervised Notification Appliance Control Circuit. An output circuit that is monitored
for integrity and used exclusively to activate control equipment for notification appliance circuits.
10.17 Notification Appliance Circuits and Supervised Notification Appliance Control Circuits.
10.17.1 An open, ground-fault, or short-circuit fault on the installation conductors of one alarm
notification appliance circuit shall not affect the operation of any other alarm notification appliance
circuit for more than 200 seconds regardless of whether the short-circuit fault is present during
the normal or activated circuit state.
10.17.2* Notification appliance circuits that do not have notification appliances connected directly
to the circuit shall be considered control circuits
9
CHAPTER 10 - FUNDAMENTALS
10.17.2 Supervised notification appliance control circuits shall comply with all of the following:
1. A supervised notification appliance control circuit shall not serve more than one
notification zone.
2. The supervised notification appliance control circuit shall be monitored for integrity in
accordance with Section 12.6.
3. A fault in the supervised notification appliance control circuit installation conductors shall
result in a trouble signal in accordance with Section 10.15.
10
CHAPTER 14 - INSPECTION, TESTING, MAINTENANCE
14.2.2.4 Observations.
14.2.2.4.1 If observations are noted, they shall be permitted to be communicated to the system
owner.
14.2.2.4.2 The system owner shall not be required to address such observations unless the
observations become an impairment or deficiency.
14.4.4.3.3 After the second required calibration test, if sensitivity tests indicate that the device
has remained within its listed and marked sensitivity range, (or 4 percent obscuration light gray
smoke, if not marked), the length of time between calibration tests shall be permitted to be
extended to a maximum of 5 years.
11
CHAPTER 14 - INSPECTION, TESTING, MAINTENANCE
14.4.2.6 Where changes are made to system executive software or site-specific software for
control equipment or transmitting equipment from a remote location not on the protected
premises, such changes shall not be made without an individual, meeting the qualifications of
10.6.3.2 , 10.6.3.3 , or 10.6.3.5 , being at the protected premises to verify that testing is
accomplished in accordance with 14.4.2 .
Table 14.4.3.2
(b) For initial and reacceptance testing, confirm the introduction of a fault in any Class A or B
radio-frequency-specified pathway results in a trouble indication at fire alarm control unit
(c) For periodic testing, test each Class A and B radio frequency initiating device circuit radio
pathway, notification appliance circuit radio pathway, and signaling line circuit radio pathway
for correct indication at the control unit
12
CHAPTER 14 - INSPECTION, TESTING, MAINTENANCE
Many AHJs adopt color-coded system status tagging programs to provide a readily accessible
means of determining the status of a system following its most current inspection or test. NFPA
72 does not mandate system status tagging, it is desirable that a certain level of consistency
exist between programs.
14
CHAPTER 18 – NOTIFICATION APPLIANCES
15
CHAPTER 18 – NOTIFICATION APPLIANCES
A.18.4.6.1 The intent of this section is to require the use of the low frequency signal in
areas intended for sleeping and in areas that might reasonably be used for sleeping.
Some of these rooms/areas include:
1) Hotel guest rooms
2) Common spaces of a hotel suite, such as living rooms, etc. that have couches, beds,
or sleeping furniture.
3) Common spaces within dwelling units, such as living rooms, dens, etc. that have
couches, beds, or sleeping furniture.
4) Areas and rooms with “Murphy” beds
5) Doctor’s/Staff sleeping rooms
6) Nap rooms or sleeping areas in any occupancy
All notification appliances and notification systems should be listed for low frequency
operation.
16
CHAPTER 23 – PROTECTED PREMISES ALARM SYSTEMS
17
CHAPTER 23 – PROTECTED PREMISES ALARM SYSTEMS
18
CHAPTER 23 – PROTECTED PREMISES ALARM SYSTEMS
23.8.2.11.2 Remote access shall not affect the operation or response of the fire alarm or
signaling systems unless permitted by 23.8.2.11.3 or 23.8.2.11.5.
23.8.2.11.3 Remote access shall be permitted for testing and maintenance activities, including
resetting, silencing, or operation of emergency control functions provided all of the following
are met:
1) *The system shall provide a means to manually terminate the remote access connection
at the remote device and at the fire alarm or signaling system control unit at any time.
2) *Remote access shall be automatically terminated within a maximum of 1 hour of inactivity
in the remote access mode.
3) Resetting, silencing, or operation of emergency control functions shall be limited to
portion(s) of the system taken out of service.
4) Qualified personnel shall be on-site to enable resetting, silencing, and operation of
emergency control functions at the affected system(s) by password or limited access.
19
CHAPTER 23 – PROTECTED PREMISES ALARM SYSTEMS
20
CHAPTER 23 – PROTECTED PREMISES ALARM SYSTEMS
23.8.2.11.5 Remote access for the purposes of software updating shall be permitted when all
of the following are met:
1) *The system shall provide a means to manually terminate the remote access connection
at the remote device and at the fire alarm or signaling system control unit at any time.
2) *Remote access shall be automatically terminated within a maximum of 1 hour of inactivity
in the remote access mode.
3) Qualified personnel shall be on-site to enable software updating at the affected fire alarm
or signaling system control unit by password or limited access.
4) All software changes shall be tested in accordance with Section 14.4.
21
CHAPTER 23 – PROTECTED PREMISES ALARM SYSTEMS
23
CHAPTER 24 – EMERGENCY COMMUNICATION SYSTEMS
24.3.10* Control Unit Listing for Mass Notification Systems. Control units installed as part
of a mass notification system shall be listed in compliance with this Code and accordance with
applicable standards such as UL 2572, Mass Notification Systems at least one of the following
applicable standards:
1) ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems
2) ANSI/UL 2572, Mass Notification Systems
A. 24.3.10 Fire emergency voice/alarm communications systems (EVACS) that are listed in
accordance with ANSI/ UL 864, Standard for Control Units and Accessories for Fire Alarm
Systems, can be used for MNS only if they are also listed in accordance with UL 2572, Mass
Notification Systems . A control unit only listed in accordance with ANSI/ UL 2572, Mass
Notification Systems , cannot be used as a fire alarm control unit
24
CHAPTER 26 – SUPERVISING STATION ALARM SYSTEMS
25
CHAPTER 26 – SUPERVISING STATION ALARM SYSTEMS
26.6.2.3.1 A qualified person in accordance with 14.4.2.6 shall be at the protected premises at
all times during the remote programming.
26
CHAPTER 26 – SUPERVISING STATION ALARM SYSTEMS
26.6.2.3.4 A mitigation plan shall be initiated by the responsible party for the alarm system,
which assigns an individual, or individuals, who will be charged with contacting the
communications center in the event that an actual alarm occurs during the remote
programming of the transmitting equipment.
26.6.2.3.5 Where the transmission technology is integral to the control unit, reacceptance
testing shall occur in accordance with 14.4.2.5 and item 4, Supervising station alarm systems
transmission equipment, in Table 14.4.3.2 when executive software for the transmission
technology is changed.
26.6.2.3.6 Where the transmission technology is integral to the control unit, reacceptance
testing shall occur in accordance with 14.4.2.4 and item 4, Supervising station alarm systems
transmission equipment, in Table 14.4.3.2 when site-specific software for the transmission
technology is changed.
27
CHAPTER 26 – SUPERVISING STATION ALARM SYSTEMS
28
CHAPTER 26 – SUPERVISING STATION ALARM SYSTEMS
26.6.4.1.1 The requirements of 26.6.4.2 shall not apply when a DACT is used as a signaling
interface from a fire alarm control unit to another listed communications means.
26.6.4.1.2 The listed communications means shall meet the requirements of either 26.6.3 or
26.6.5.
26.6.4.2 DACT.
29
QUESTIONS & ANSWERS
Richard Roberts
Industry Affairs Manager
Honeywell Fire Safety
richard.roberts@systemsensor.com
630.338.7025
THANK #HTechForum
YOU