TECHNICAL SPECIFICATION
OF
COMPACT TRANSFORMER SUBSTATION WITH
RMU(33/0.4KV)
Contents
compact TRANSFORMER substations with rmu 33/0.4kv...................................................................................3
1. Scope...............................................................................................................................................................3
2. SYSTEM PARAMETERS & Service Conditions..........................................................................................3
3. Reference standards.........................................................................................................................................3
4. Conflict............................................................................................................................................................4
5. DESIGN OF COMPACT SUBSTATIONS....................................................................................................4
6. MV COmpartment.........................................................................................................................................10
7. Transformer Compartment............................................................................................................................13
8. Low voltage compartment.............................................................................................................................17
9. Spare Parts.....................................................................................................................................................19
10. Documents to be submitted........................................................................................................................19
11. INSPECTION AND TESTing...................................................................................................................20
12. Packing and marking..................................................................................................................................22
13. Guaranteed Technical Particulars for 500KVA (33/0.4) kV Compact Transformer.................................25
14. Guaranteed Technical Particulars for 630KVA, (33/0.4) kV Compact Transformer................................31
15. Guaranteed Technical Particulars for 800KVA, (33/0.4) kV Compact Transformer................................37
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 3 of 43
1
1. SCOPE
This specification covers the design, manufacturing, testing, supply, delivery and
performance requirements of outdoor compact transformer substation with
RMU(33/0.4)kV
3. REFERENCE STANDARDS
The requirements of the following standards / specifications shall be met where
applicable unless otherwise stated in this specification.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 4 of 43
1
4. CONFLICT
In the event of direct conflict between various order documents, the precedence of
authority of documents shall be as follows -
I. Guaranteed Technical Particulars (GTP)
II. Specification including applicable codes & standards
III. Approved Vendor Drawings
IV. Other documents
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 5 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 6 of 43
1
voltage terminals of the transformer shall be via cables with touch-safe plug-in
terminations.
The connection between 0.4 kV switchgear and LV terminals of the transformers
shall be made with insulated bus bars. The terminals shall be touch-safe insulated.
Incoming and outgoing circuits shall be connected with cables entering from below.
The entire unit shall be mounted on Skid Base capable of being moved and hauled
as a single unit. The unit shall be “NON-EXTENSIBLE” type metal enclosed and
suitable for outdoor installation.
5.2 DESCRIPTION OF OUTER HOUSING
The compact substation is completely self-contained, mounted upon a 3mm thick
galvanized steel base frame, factory assembled in a totally enclosed aesthetically
acceptable metal cladding, vandal-proof and weather proof housing ready for
placing into position upon a concrete base. The complete housing assembly is
provided with four lifting eyes located on the sloping roofs for easy lifting and
positioning the whole equipment at the site by the use of crane. The transformer is
located in the middle of the substation while the MV and LV compartments are
located at both ends of the substation adjacent to the corresponding bushing of the
transformer.
The substation forms a complete metallic structure bolted together and each
compartment is provided with grounding bus bars. Bonding and interconnection of
the grounding buses are made of 70mm2 bare stranded copper conductors.
The design shall be such that the roof shall be removable to allow easy lifting of
any major part of the unit. The metallic ceiling shall be of a double roofing system
to diminish heating due to solar radiation.
Generally the class of enclosure shall be 10, having sufficient thermal insulation of
the roof for the sun radiation at site.
5.2.1 Protection degrees:
The minimum Protection index which ensures the direct- contact protection of each
compartment is specified as follows:
MV compartment IP54
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 7 of 43
1
LV compartment IP23
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 8 of 43
1
(ii) The frame of each switch shall be provided with reliable earthing terminal
having a clamping screw of not less than 12 mm in diameter.
(iii) All the earthing terminals shall be inter-bonded for equal potential and brought
to main earthing terminals.
(iv) The earthing conductor or strap mainly of copper shall be mechanically
protected as well as against corrosion and be of adequate size for the coordinated
ratings as per schedule of particulars.
The details should be provided with the bid and shall also be incorporated into the
Maintenance Instruction Manual.
5.5 CORROSION PROTECTION
The Compact Substation housing shall be hot-dip galvanized. Galvanizing shall
consist of a continuous coating of zinc to a minimum weight of 600 g/m². The zinc
coating shall meet the requirements according to ASTM, A123, A143, A239 and
A385. Other type of corrosion protection that can be shown to give a similar
protection as hot-dip galvanizing may be accepted after special agreement.
5.6 TANK BOTTOM
Thickness of housing bottom shall not be less than 4 mm.
5.7 RATING, DIAGRAM AND PROPERTY PLATES
Each Compact Substation shall be provided with a rating plate showing the
information stated in the IEC standards. The plate shall be in English.
The following plates shall be fixed to the Compact substation at an average,
readable height.
a) A rating plate bearing the data specified in IEC shall be placed on the
MV,Transformer and LV compartments.
b) Name of manufacturer
c) Manufacturer’s serial number
d) Year of manufacture
e) Rated power
f) Rated frequency
g) Rated voltages
h) Rated currents
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 9 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 10 of 43
1
All door gaskets shall be of superior quality and capable of withstanding the severe
climatic conditions.
5.11 DOOR LOCKS
The doors shall be securely closed and then locked close with padlocks.
Each access door shall have arrangements to lock with a handle and secured closed
with a padlocks. Suitable door handles shall be fitted to the door.
Padlocks of a top quality make with a master key system shall be provided with
each unit including one spare padlock. The master key shall be advised by the
client.
The client is already using a master key system and the same shall be applied in this
compact substation.
5.12 NOISE LEVEL
The noise level of the completely assembled package Substation shall not exceed 44
dbA, when measured one (1) meter far from package unit housing in accordance
with IEC 60551. The package Substation shall be checked after assembly to ensure
that no rattling of individual components can occur.
5.13 MOUNTING ARRANGEMENT
The package Substation shall not require casting of concrete plinth at Site. Site
preparation shall be limited to levelling only.
5.14 LIFTING LUGS
Lifting lugs shall be provided so that the completely assembled package Substation
may be lifted without damage. The lifting lugs shall be designed to carry the weight
of the Substation complete with Transformer and switchgear. Required number of
lifting spread beams shall be supplied with each unit.
5.15 COLOUR
The surface colour of HV and LV Switchgear, Transformer and Housing shall be
RAL 7032 light grey.
6. MV COMPARTMENT
The medium voltage switchgear is gas insulated, consisting of two cable switches
disconnector (Load break switch) and transformer T-off with VCB. For other
particulars the provided specification may be referred.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 11 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 12 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 13 of 43
1
7. TRANSFORMER COMPARTMENT
7.1 GENERAL
This section specifies the detailed requirements for distribution transformers,
complete with necessary fittings for 33/0.4kV Compact substations.
The transformer shall conform to the provided technical specification. A technical
schedule shall be completed for the transformer for ground mounted substation.
7.2 TRANSFORMER TYPE
The transformer shall be hermetically sealed, tank type, ONAN naturally cooled,
skid mounted, un-inhibited mineral oil immersed, core type and copper windings
suitable for operation outdoor in exposed location. The Transformer oil shall
confirm to BS 148 Class 1 Category / IEC 296.
7.3 VOLTAGE RATIOS
The normal voltage ratio of the Transformer on normal tapping and no-load shall be
33 /0.4 kV.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 14 of 43
1
7.4 RATINGS
The Transformer rated kVA shall be the continuous steady load rating under the
specified temperature and humidity without exceeding the average temperature rise
limits given in the technical specifications.
The full rating shall be at the rated output voltage with rated input voltage.
7.5 TEMPERATURE RISE
The Transformer shall be capable of carrying full rated current continuously under
the maximum specified ambient temperature (as per IEC60076-2) at any tapping,
without the temperature rise of oil at top exceeding 60 degree C, as measured by
thermometer and of the winding not exceeding 65 degree C and of the hot spot not
exceeding 78 degree C, as measured by resistance calculations demonstrating the
above shall be submitted with the Bid.
7.6 WINDING CONNECTION - VECTOR GROUP
The winding connection of the Transformers shall be connected Delta Star in
accordance with the group of symbols in IEC 60076-4, Vector Reference Dyn5.
The neutral terminal shall be brought out and shall be fully rated in all cases.
7.7 TRANSFORMER MECHANICAL DESIGN
The tank shall be constructed of high grade steel plate, suitably reinforced to
withstand handling and pressure during fault condition without any deformation.
Gaskets shall be oil resistant. Rubber gaskets used for flange connections of the
various oil compartments shall be laid in grooves. Gaskets any kind of impregnated/
bonded cork are not acceptable.
The tank shall be fitted with lifting lugs suitable for handling the mass of the
transformer complete with oil.
7.7.1 Accessories
At least the following accessories shall be included for the transformer:
a) Pressure relief device
b) Oil level indicator
c) Two earthing terminals
d) Oil thermometer
e) Rating and diagram plates
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 15 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 16 of 43
1
The off-load tap changer shall have an externally operated mechanism for manual
operation. Tap positions shall be clearly identified. The operating mechanism shall
have an effective locking device for locking of the tap changer in any desired
position.
7.9 BUSHINGS SPACING
Transformers shall have the bushings for HV and LV which fulfil the requirements
of IEC 60137
Minimum Distances between bushings shall be as per IEC standard.
7.10 EMERGENCY LOADING
The Tenderer shall demonstrate by calculation, the ability of the Transformer to
operate under emergency loading condition as per IEC 354 for the following
loading and ambient temperature conditions listed below with Transformer winding
hot spot temperature not exceeding 40 degree C, after thermal equilibrium has been
reached at rated load.
Transformer bushing, tap changer and terminations shall also be suitably rated for
over loading as specified in IEC 60354.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 17 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 18 of 43
1
8.1.4 CTs
On each phase current Transformer shall be provided for operation of instruments.
8.1.5 Energy Meter
The required wiring for connecting one smart energy meter at a future date shall be
complete and space made available. All wiring shall be terminated at a meter
terminating block to enable future meter installation and easy connection
8.1.6 Ammeter
Three Single-Phase Ammeters with instantaneous elements plus maximum current
demand indicators of the thermal type. The ammeters shall be suitable for operation
from the current Transformers specified. The maximum demand element shall be
compensated for 55 degree Celsius ambient temperature.
8.1.7 Voltmeter
One Voltmeter 0-500V with phase selector switch.
8.1.8 Light fitting
One Light Fitting for cubicle illumination complete with a door operated switch.
The maximum demand indicator voltmeters, selector switch and light fitting to be
mounted on an instrument panel.
8.1.9 Earth Bar
An Earth Bar not less than 50mm x 10mm shall be provided at the bottom and
secured so as to give a positive electrical connection. In addition, two 12mm with
Earth terminal shall be provided on the pillar shell and connected to the earth bar. A
detachable link between neutral and earth bar shall also be provided.
8.1.10 Cable Glands
The cable glands shall be brass or stainless steel compression type as per BS
suitable for the bales provided for the LV system. The glands shall be supplied
complete with earth tag PVC shrouds. Cross sectional details of the cable will be
supplied to the successful Tenderers. Earth tag of each gland shall be connected to
earth bar with tinned copper flexible earthing braid of adequate cross section having
at least 50 % of that of the phase conductor of the cable to be connected. Each cable
gland shall be supported on a removable gland plate.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 19 of 43
1
8.1.11 Miscellaneous
All instrument wiring shall be 2.5 sq.mm stranded copper conductor, 600 Volt
tropical grade PVC insulated.
The Base Plate of the feeder pillar shall be supplied with knockout holes.
Necessary Nuts, Bolts for cable lugs, spacers, etc., shall be supplied fitted with
feeder pillar. Cable clamps shall be provided at the bottom of the feeder pillar to
hold the cables in position.
The gland plate of the feeder pillar shall be so positioned to allow convenient bend
on the cable.
Cable glands with earth tag and plastic shrouds, cable lugs and fuses shall be
delivered separately.
9. SPARE PARTS
Different items ordered against spares shall be packed in separate casing with item
number and quantity clearly marked.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 20 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 21 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 22 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 23 of 43
1
Type of transformer
Manufacturer's Name
Manufacturer's Serial Number
Year of Manufacture
Rated Frequency
Rated operating voltage
Maximum operating voltage
Maximum equipment rating voltage
Rated Continuous Current (Max.)
Rated power frequency Withstand Voltage
Rated Impulse Withstand Voltage
Gross Weight
Purchase order number & date
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 24 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 25 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 26 of 43
1
Offered
No. Description Required by EEU by
Bidder
10.2 Frequency, Hz 50
10.3 Insulation level
10.3. Power frequency withstand voltage,
70
1 kV(RMS)
10.3. Rated lightning, impulse withstand
170
2 voltage, kV(Peak)
10.4 Rated current, A 630
Rated short-time withstand current for 3s,
10.5 25
kA
Vacuum Circuit Breaker with Earthing
11 Switch (Open,close & earthing 1
operation)
11.1 Type Vacuum
11.2 Rated voltage, kV 33
11.3 Rated frequency, Hz 50
11.4 Insulation level
11.4. Rated Power frequency withstand voltage,
70
1 kV
11.4. Rated lightning, impulse withstand
170
2 voltage, kV
Depends on the Rating
11.5 Current rating, A
of the transformer
Rated short-time withstand current for
11.6 25
3s,kA
III Low Voltage compartment
12 Size of cubicle
13 Protection class IP23
13.1 Bus Bar rating (A) Min.1500
No. of ways for outgoing Cable
13.2 >=4
Terminations
14 Incomer Main MCCB 1
14.1 Type
14.2 Nominal voltage, kV 0.4
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 27 of 43
1
Offered
No. Description Required by EEU by
Bidder
14.3 Rated frequency, Hz 50
14.4 Insulation level
14.4. Power frequency withstand voltage ,
3 for one minute
1 kV(RMS)
14.4. Rated lightning, impulse withstand
10
2 voltage, kV(peak), (1.2/50 ms)
14.5 Rated current, A 721
14.6 Rated short-time current rating, kA 50
15 Outgoing MCCB 6
15.1 Type
15.2 Nominal voltage, kV 0.4
15.3 Rated Current, A 721
15.4 Rated short-time current rating, kA 50
16 Current transformer
16.1 Type
16.2 Quantity for each s/s 3
16.3 Voltage rating 380V
16.4 Current ratio 1000/5
16.5 Frequency, Hz 50
16.6 Burden, VA 15
16.7 Class 0.5
17 Ammeter
17.1 Type
17.2 Quantity 3
17.3 Current range, A 0-1000
18 Voltmeter with selector switch
18.1 Type
18.2 Quantity 1
18.3 Voltage range, V 0-500
IV Transformer compartment
19 Protection class IP23
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 28 of 43
1
Offered
No. Description Required by EEU by
Bidder
Technical characteristics of the
V
distribution transformer
20 Method of cooling ONAN
21 No. of phases 3
22 Standard IEC 60076
23 Frequency, Hz 50
24 Rated Continuous Power, kVA
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 29 of 43
1
Offered
No. Description Required by EEU by
Bidder
34 Thickness of surface treatment (µm) 140
Short-circuit impedance at principle
35 4
tapping (%)
36 Ability to withstand unbalanced load (%) >=90
37 Average temperature rise, oC
37.1 Windings 0c 65
37.2 Top oil 0c 60
38 Dimensions of complete transformer, mm
38.1 Height
38.2 Length
38.3 Width
39 Weight, kg
39.1 Core
39.2 Winding
Uninhibited Mineral oil /
39.3 Transformer Oil Class 1 Category / IEC
60296/IEC60156.
39.4 Complete transformer
40 Transformer tank
40.1 Material Steel
40.2 Thickness of tank plate
40.2.
Top, mm
1
40.2.
Bottom, mm
2
40.2.
Sides, mm
3
41 Core
41.1 Type
41.2 Material Silicon Steel
41.3 Loss figure, W/kg
41.4 Type (wire or coil) wire or coil
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 30 of 43
1
Offered
No. Description Required by EEU by
Bidder
42 HV Windings
42.1 Material Copper
42.2 Insulation
Power frequency withstand voltage,
42.3 70
kV(RMS)
Rated lightning, impulse withstand
42.4 170
voltage, kV(peak)
42.5 Type wire or coil, round wire or coil
43 LV Windings
43.1 Material Copper
43.2 Insulation
Power frequency withstand voltage,
43.3 3
kV(RMS)
Rated lightning, impulse withstand
43.4 >=10
voltage, kV(peak)
44 Complete Compact Substation
44.1 Dimension
44.2 Weight, kg
45 Communication facility (GSM/GPRS) Must support
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 31 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 32 of 43
1
Offered
No. Description Required by EEU by
Bidder
5.3 Number of low voltage compartment 1
II Medium voltage compartment
6 Size of cubicle
7 Type
8 Protection class IP54
9 Nominal System voltage, kV 33
9.1 Voltage Variation of the system, % ±10
9.2 Maximum system operating voltage, in kV 36
9.3 Maximum equipment rating voltage, in kV 52
Load break switch with earthing switch
10 2
( 2 Incoming)
10.1 Type SF6
10.2 Frequency, Hz 50
10.3 Insulation level
Power frequency withstand voltage,
10.3.1 70
kV(RMS)
Rated lightning, impulse withstand voltage,
10.3.2 170
kV(Peak)
10.4 Rated current , A 630
10.5 Rated short-time withstand current for 3s,kA 25
Vacuum Circuit Breaker with Earthing
11 1
Switch (Open,close & earthing operation)
11.1 Type Vacuum
11.2 Nominal System voltage, kV 33
11.3 Rated frequency, Hz 50
11.4 Insulation level
Rated Power frequency withstand voltage,
11.4.1 70
kV
Rated lightning, impulse withstand voltage,
11.4.2 170
kV
Depends on the
11.5 Current rating, A Rating of the
transformer
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 33 of 43
1
Offered
No. Description Required by EEU by
Bidder
11.6 Rated short-time withstand current for 3s,kA 25
III Low Voltage compartment
12 Size of cubicle
13 Protection class IP23
13.1 Bus Bar rating (A) Min.2000
13.2 No.of ways for outgoing Cable Terminations >=4
14 Incomer Main ACB 1
14.1 Type
14.2 Nominal voltage, kV 0.4
14.3 Rated frequency, Hz 50
14.4 Insulation level
Power frequency withstand voltage ,
14.4.1 3 for one minute
kV(RMS)
Rated lightning, impulse withstand voltage,
14.4.2
kV(peak), (1.2/50 ms)
14.5 Rated current, A 909
14.6 Rated short-time current rating, kA 50
15 Outgoing MCCB 6
15.1 Type
15.2 Nominal voltage, kV 0.4
15.3 Rated Current, A 909
15.4 Rated short-time current rating,kA 50
16 Current transformer
16.1 Type
16.2 Quantity for each s/s 3
16.3 Voltage rating 380V
16.4 Current ratio 1250/5
16.5 Frequency, Hz 50
16.6 Burden, VA 15
16.7 Class 0.5
17 Ammeter
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 34 of 43
1
Offered
No. Description Required by EEU by
Bidder
17.1 Type
17.2 Quantity 3
17.3 Current range, A 0-1250
18 Voltmeter with selector switch
18.1 Type
18.2 Quantity 1
18.3 Voltage range, V 0-500
IV Transformer compartment
19 Protection class IP23
Technical characteristics of the
V
distribution transformer
20 Method of cooling ONAN
21 No. of phases 3
22 Standard IEC 60076
23 Frequency, Hz 50
24 Rated Continuous Power, kVA
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 35 of 43
1
Offered
No. Description Required by EEU by
Bidder
30.1 100% rated output and P.F= 1 (%)
30.2 50% rated output and P.F= 1 (%)
30.3 100% rated output and P.F= 0.95 (%)
30.4 50% rated output and P.F= 0.95 (%)
31 No load current as percent of rated current
31.1 At 90% voltage (%)
31.2 At 100% voltage (%)
31.3 At 110% voltage (%)
Mean level of noise at no load-Power level
32
(dB)
33 Color of the transformer Gray
34 Thickness of surface treatment (µm) 140
Short-circuit impedance at principle tapping
35 4
(%)
36 Ability to withstand unbalanced load (%) >=90
37 Average temperature rise, oC
37.1 Windings 0c 65
37.2 Top oil 0c 60
38 Dimensions of complete transformer, mm
38.1 Height
38.2 Length
38.3 Width
39 Weight, kg
39.1 Core
39.2 Winding
Uninhibited Mineral
oil / Class 1
39.3 Transformer Oil Category / IEC
60296/IEC60156.
39.4 Complete transformer
40 Transformer tank
40.1 Material Steel
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 36 of 43
1
Offered
No. Description Required by EEU by
Bidder
40.2 Thickness of tank plate
40.2.1 Top, mm
40.2.2 Bottom, mm
40.2.3 Sides, mm
41 Core
41.1 Type
41.2 Material Silicon Steel
41.3 Loss figure, W/kg
41.4 Type (wire or coil) wire or coil
42 HV Windings
42.1 Material Copper
42.2 Insulation
Power frequency withstand voltage,
42.3 70
kV(RMS)
Rated lightning, impulse withstand voltage,
42.4 170
kV(peak)
42.5 Type wire or coil, round wire or coil
43 LV Windings
43.1 Material Copper
43.2 Insulation
Power frequency withstand voltage,
43.3 3
kV(RMS)
Rated lightning, impulse withstand voltage,
43.4
kV(peak)
44 Complete Compact Substation
44.1 Dimension
44.2 Weight, kg
45 Communication facility (GSM/GPRS) Must support
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 37 of 43
1
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 38 of 43
1
Offere
No. Description Required by EEU d by
Bidder
5.1 Number of medium voltage compartment 1
5.2 Number of transformer compartment 1
5.3 Number of low voltage compartment 1
II Medium voltage compartment
6 Size of cubicle
7 Type
8 Protection class IP54
9 Nominal System voltage, kV 33
9.1 Voltage Variation of the system, % ±10
9.2 Maximum system operating voltage, in kV 36
9.3 Maximum equipment rating voltage, in kV 52
10 RMU(Incoming 2+Outgoing 1) 2
10.1 Load break switch with earthing switch
10.1 Type SF6
10.2 Frequency, Hz 50
10.3 Insulation level
10.3. Power frequency withstand voltage,
70
1 kV(RMS)
10.3. Rated lightning, impulse withstand
170
2 voltage, kV(Peak)
10.4 Rated current , A 630
Rated short-time withstand current for
10.5 25
3s,kA
Vacuum Circuit Breaker with Earthing
11 Switch (Open,close & earthing 1
operation)
11.1 Type Vacuum
11.2 Rated voltage, kV 33
11.3 Rated frequency, Hz 50
11.4 Insulation level
11.4. Rated Power frequency withstand voltage,
70
1 kV
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 39 of 43
1
Offere
No. Description Required by EEU d by
Bidder
11.4. Rated lightning, impulse withstand
170
2 voltage, kV
Depends on the Rating
11.5 Current rating, A
of the transformer
Rated short-time withstand current for
11.6 25
3s,kA
III Low Voltage compartment
12 Size of cubicle
13 Protection class IP23
13.1 Bus Bar rating (A) Min.2000
No.of ways for outgoing Cable
13.2 >=4
Terminations
14 Incomer Main MCCB
14.1 Type
14.2 Nominal voltage, kV 0.4
14.3 Rated frequency, Hz 50
14.4 Insulation level
14.4. Power frequency withstand voltage ,
3 for one minute
1 kV(RMS)
14.4. Rated lightning, impulse withstand
10
2 voltage, kV(peak), (1.2/50 ms)
14.5 Rated current, A 1154
14.6 Rated short-time current rating, kA 50
15 Outgoing MCCB 8
15.1 Type
15.2 Nominal voltage, kV 0.4
15.3 Rated Current, A 1154
15.4 Rated short-time current rating,kA 50
16 Current transformer
16.1 Type
16.2 Quantity for each s/s 3
16.3 Voltage rating 380V
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 40 of 43
1
Offere
No. Description Required by EEU d by
Bidder
16.4 Current ratio 1600/5
16.5 Frequency, Hz 50
16.6 Burden, VA 15
16.7 Class 0.5
17 Ammeter
17.1 Type
17.2 Quantity 3
17.3 Current range, A 0-1600
18 Voltmeter with selector switch
18.1 Type
18.2 Quantity 1
18.3 Voltage range,V 0-500
IV Transformer compartment
19 Protection class IP23
Technical characteristics of the
V
distribution transformer
20 Method of cooling ONAN
21 No. of phases 3
22 Standard IEC 60076
23 Frequency, Hz 50
24 Rated Continuous Power, kVA
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 41 of 43
1
Offere
No. Description Required by EEU d by
Bidder
5 position step (+5%,
29 Off-load tap changer
+2.5%,0%,-2.5%,-5%)
Efficiency referred to 75oC at rated voltage
30
and
30.1 100% rated output and P. F= 1 (%)
30.2 50% rated output and P.F= 1 (%)
30.3 100% rated output and P.F= 0.95 (%)
30.4 50% rated output and P.F= 0.95 (%)
31 No load current as percent of rated current
31.1 At 90% voltage (%)
31.2 At 100% voltage (%)
31.3 At 110% voltage (%)
Mean level of noise at no load-Power level
32
(dB)
33 Color of the transformer Gray
34 Thickness of surface treatment (µm) 140
Short-circuit impedance at principle
35 5
tapping (%)
36 Ability to withstand unbalanced load (%) >=90
37 Average temperature rise, oC
37.1 Windings 0c 65
37.2 Top oil 0c 60
38 Dimensions of complete transformer, mm
38.1 Height
38.2 Length
38.3 Width
39 Weight, kg
39.1 Core
39.2 Winding
Uninhibited Mineral oil /
39.3 Transformer Oil Class 1 Category / IEC
60296/IEC60156.
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 42 of 43
1
Offere
No. Description Required by EEU d by
Bidder
39.4 Complete transformer
40 Transformer tank
40.1 Material Steel
40.2 Thickness of tank plate
40.2.
Top, mm
1
40.2.
Bottom, mm
2
40.2.
Sides, mm
3
41 Core
41.1 Type
41.2 Material Silicon Steel
41.3 Loss figure, W/kg
41.4 Type (wire or coil) wire or coil
42 HV Windings
42.1 Material Copper
42.2 Insulation
Power frequency withstand voltage,
42.3 70
kV(RMS)
Rated lightning, impulse withstand
42.4 170
voltage, kV(peak)
42.5 Type wire or coil, round wire or coil
43 LV Windings
43.1 Material Copper
43.2 Insulation
Power frequency withstand voltage,
43.3 3
kV(RMS)
Rated lightning, impulse withstand
43.4
voltage, kV(peak)
44 Complete Compact Substation
44.1 Dimension
44.2 Weight, kg
Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 43 of 43
1
Offere
No. Description Required by EEU d by
Bidder
Must support /RTU or
45 Communication facility (GSM/GPRS)
FTU