ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-235

Issue No. \.Page 1 of 43


Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV)
1

TECHNICAL SPECIFICATION
OF
COMPACT TRANSFORMER SUBSTATION WITH
RMU(33/0.4KV)

Prepared by Sign Checked by Sign Approved by Sign Rev.No. Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept. 18,2020 No. 1
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-235

Issue No. \.Page 2 of 43


Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV)
1

Contents
compact TRANSFORMER substations with rmu 33/0.4kv...................................................................................3
1. Scope...............................................................................................................................................................3
2. SYSTEM PARAMETERS & Service Conditions..........................................................................................3
3. Reference standards.........................................................................................................................................3
4. Conflict............................................................................................................................................................4
5. DESIGN OF COMPACT SUBSTATIONS....................................................................................................4
6. MV COmpartment.........................................................................................................................................10
7. Transformer Compartment............................................................................................................................13
8. Low voltage compartment.............................................................................................................................17
9. Spare Parts.....................................................................................................................................................19
10. Documents to be submitted........................................................................................................................19
11. INSPECTION AND TESTing...................................................................................................................20
12. Packing and marking..................................................................................................................................22
13. Guaranteed Technical Particulars for 500KVA (33/0.4) kV Compact Transformer.................................25
14. Guaranteed Technical Particulars for 630KVA, (33/0.4) kV Compact Transformer................................31
15. Guaranteed Technical Particulars for 800KVA, (33/0.4) kV Compact Transformer................................37

Prepared by Sign Checked by Sign Approved by Sign Rev.No. Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept. 18,2020 No. 2
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 3 of 43
1

COMPACT TRANSFORMER SUBSTATIONS WITH RMU 33/0.4KV

1. SCOPE
This specification covers the design, manufacturing, testing, supply, delivery and
performance requirements of outdoor compact transformer substation with
RMU(33/0.4)kV

2. SYSTEM PARAMETERS & SERVICE CONDITIONS

Description Service Condition


Altitude Altitude 3000m
Annual Rainfall 1250mm
Period of exceptional Rains June to September
Ambient Air Temperatures:
Average +250c
Minimum -50c
Maximum 450c
Relative Air Humidity 70%
Wind Velocity:
Maximum wind (height above
ground level) 0-30m 35m/s
30-50m 45m/s
Isoceraunic Level Up to 100 thunderstorm days/year
Seismic Zone Zone 4

3. REFERENCE STANDARDS
The requirements of the following standards / specifications shall be met where
applicable unless otherwise stated in this specification.

Specification/ Standard Title


Number
IEC 61330 High voltage/Low voltage prefabricated Substations
IEC 60076 Power Transformers
IEC 60354 Loading guide for oil immersed Transformers
Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page
Abebaw Belay Elias Azene Chala Aman 0 Sept. No. 3
18,2020
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 4 of 43
1

IEC 60317 Copper wire Rods


IEC 60137 Insulated bushings for alternating voltages above 1000V
IEC 60521 Class 0.5, 1 and 2 alternating current watt hour meters
IEC 60551 Determination of Transformer and reactor sound level
IEC 60296 Specification for unused mineral insulating oils for
transformers and switchgear
IEC 60722 Guide to the lightning impulse and switching impulse
testing of power transformers and reactors
IEC 60282-1, DIN VDE 0670- MCCBs
4 and DIN 43625
IEC 62271 Switchgear design

4. CONFLICT
In the event of direct conflict between various order documents, the precedence of
authority of documents shall be as follows -
I. Guaranteed Technical Particulars (GTP)
II. Specification including applicable codes & standards
III. Approved Vendor Drawings
IV. Other documents

5. DESIGN OF COMPACT SUBSTATIONS


5.1 GENERAL
The compact substation shall be outdoor type comprising
 Fully Insulated Ring Main Unit
 hermetically sealed distribution transformer of various ratings
 LV Distribution pillar equipped with MCCB
All the equipment shall be outdoor type, interconnected, factory assembled as an
integral unit, mounted upon galvanized steel base-frame, housed in an approved
vandal-proof and weather proof metallic housing, ready for placing into position
upon a concrete base pad.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 4
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 5 of 43
1

The Transformer, LV and MV compartments shall be completely separated by steel


sheets. The Transformer shall be located in the middle of the Substation while the
MV and LV compartments are located at both ends of the Substation adjacent to the
corresponding bushing of the Transformer. The barrier between the MV switchgear
and the Transformer shall be provided with pressure relief flap and the LV separator
shall be provided with small door to access the Transformer tap changer and the
thermometer.
The Unit shall be delivered fully assembled and tested.
Where wiring, piping or ductwork passes through openings in equipment housings,
such openings shall be constructed to prevent ingress of vermin and dust. Wiring
and piping enclosures shall also be vermin proof. Operating boxes, kiosks, cubicles
and similar enclosed compartments forming part of auxiliary equipment shall be
adequately ventilated to restrict condensation. All contactors or relay coils and other
parts shall be suitably protected against corrosion. Anti-condensation heaters of an
approved make shall be provided inside each cubicle or where necessary in each
cubicle compartment.
Wherever possible all similar parts shall be made to gauge and be interchangeable
to enable substation or replacement by spare parts to be made easily and quickly in
case of wear or other failure.
The switchgear of the substation shall be complete with all required cable
connections.
The units are to be supplied as fully equipped packaged substations, including
1) Outer housing,
2) Medium voltage switchgear compartment,
3) Distribution transformer compartment,
4) Low voltage switchgear compartment.
As such only the incoming and outgoing cables need to be connected at site and the
site works are kept to an absolute minimum. And the required plug-in termination
kits for the connection of incoming and outgoing cables are to be supplied by this
contract supplier.
One set of medium voltage switchgear cable termination suitable for the offered
switchgear has to be supplied by the Supplier for connection of the incoming cable
from EEU. The connection between medium voltage switchgear and medium

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 5
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 6 of 43
1

voltage terminals of the transformer shall be via cables with touch-safe plug-in
terminations.
The connection between 0.4 kV switchgear and LV terminals of the transformers
shall be made with insulated bus bars. The terminals shall be touch-safe insulated.
Incoming and outgoing circuits shall be connected with cables entering from below.
The entire unit shall be mounted on Skid Base capable of being moved and hauled
as a single unit. The unit shall be “NON-EXTENSIBLE” type metal enclosed and
suitable for outdoor installation.
5.2 DESCRIPTION OF OUTER HOUSING
The compact substation is completely self-contained, mounted upon a 3mm thick
galvanized steel base frame, factory assembled in a totally enclosed aesthetically
acceptable metal cladding, vandal-proof and weather proof housing ready for
placing into position upon a concrete base. The complete housing assembly is
provided with four lifting eyes located on the sloping roofs for easy lifting and
positioning the whole equipment at the site by the use of crane. The transformer is
located in the middle of the substation while the MV and LV compartments are
located at both ends of the substation adjacent to the corresponding bushing of the
transformer.
The substation forms a complete metallic structure bolted together and each
compartment is provided with grounding bus bars. Bonding and interconnection of
the grounding buses are made of 70mm2 bare stranded copper conductors.
The design shall be such that the roof shall be removable to allow easy lifting of
any major part of the unit. The metallic ceiling shall be of a double roofing system
to diminish heating due to solar radiation.
Generally the class of enclosure shall be 10, having sufficient thermal insulation of
the roof for the sun radiation at site.
5.2.1 Protection degrees:
The minimum Protection index which ensures the direct- contact protection of each
compartment is specified as follows:

MV compartment IP54

Transformer compartment IP23

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 6
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 7 of 43
1

LV compartment IP23

5.2.2 Surface area


The design of the compact substation shall be such that it occupies minimum space.
The design concept is to use the substation is confined spaces.
5.3 ELECTRICAL INTERCONNECTIONS
Electrical connections to the Transformer shall be so designed that these may be
disconnected and re-connected at Site to facilitate the removal of any major
component of the unit. The inter-connection between 33kV Switchgear and
Transformer Terminals Bushings shall be as per relevant standards depending on
transformer size.
The connection between Transformer LV Bushing and the Feeder Pillar shall be by
means of flexible copper bus bars passing through an air-insulated duct/flange.
5.4 EARTHING
5.4.1 General
Each unit Substation assembly shall be provided with copper Earth Bar of 40mm x
5mm to which the Transformer LV neutral and metal frames of all items i.e. H.V.
Switchgear, Transformer and Feeder Pillar shall be connected. Two-earth terminal
shall be provided for connection to the external earthing system.
5.4.2 Metalwork Earthing Arrangements
(i) All Substation metalwork, including Transformer tank, cable screens, feeder
pillar, doors and any internal structural steel work shall be securely bonded together
so that a firm metallic connection existing between each of them and the Substation
metal work earthing terminal.
The metal work-earthing terminal shall be provided in an accessible position.
The position of the earthing terminal shall be shown in the appropriate drawing, and
shall be approved by engineer.
Two bolted (removable) links shall be provided in the LV Feeder Pillar - ‘ONE’
between the Transformer neutral and neutral busbar. The ‘OTHER’ shall be
between the neutral bar and the earth bar.
All panel and access covers or doors etc. rotating about hinges shall be earthed to
the adjacent main frames by copper flexible protective bonding conductors.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 7
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 8 of 43
1

(ii) The frame of each switch shall be provided with reliable earthing terminal
having a clamping screw of not less than 12 mm in diameter.
(iii) All the earthing terminals shall be inter-bonded for equal potential and brought
to main earthing terminals.
(iv) The earthing conductor or strap mainly of copper shall be mechanically
protected as well as against corrosion and be of adequate size for the coordinated
ratings as per schedule of particulars.
The details should be provided with the bid and shall also be incorporated into the
Maintenance Instruction Manual.
5.5 CORROSION PROTECTION
The Compact Substation housing shall be hot-dip galvanized. Galvanizing shall
consist of a continuous coating of zinc to a minimum weight of 600 g/m². The zinc
coating shall meet the requirements according to ASTM, A123, A143, A239 and
A385. Other type of corrosion protection that can be shown to give a similar
protection as hot-dip galvanizing may be accepted after special agreement.
5.6 TANK BOTTOM
Thickness of housing bottom shall not be less than 4 mm.
5.7 RATING, DIAGRAM AND PROPERTY PLATES
Each Compact Substation shall be provided with a rating plate showing the
information stated in the IEC standards. The plate shall be in English.
The following plates shall be fixed to the Compact substation at an average,
readable height.
a) A rating plate bearing the data specified in IEC shall be placed on the
MV,Transformer and LV compartments.
b) Name of manufacturer
c) Manufacturer’s serial number
d) Year of manufacture
e) Rated power
f) Rated frequency
g) Rated voltages
h) Rated currents

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 8
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 9 of 43
1

i) Connection group symbol


j) Short-circuit impedance
k) Total mass including oil
l) Temperature rise of oil and windings of the Transformer
m) Insulation level
n) Each bushing shall be marked with the name or trademark of the
manufacturer.
o) A diagram plate showing the internal connections and also the voltage vector
relationship of the several windings and in addition a plan view of the
transformer giving the correct physical relationship of the terminals. When
links are provided for changing the transformer group symbol and/or ratio,
then means shall be provided for clearly indicating in which mode the
transformer is connected.
p) A property plate engraved to the instructions of the Employer.
The above plates shall be of stainless steel or of other material capable of
withstanding continuous outdoor service and shall all be suitably mounted to
prevent vibration, rattling or corrosion.
5.8 LIGHTING
HV, LV and Transformer compartments shall each be fitted with a florescent lamp
controlled from door-operated switch. The lamp shall be combined with an
accumulator-cum-charger and shall be installed in such position to illuminate the
respective compartment.
5.9 VENTILATION
Adequate ventilation for natural circulation of air shall be provided to keep the
inside temperature within the limit. Ventilation apertures shall be suitably screened
and louvered to prevent the entry of vermin, dust and other foreign bodies.
5.10 DOORS AND WALLS
Double-leaf Doors shall be framed and panelled type. Doors shall be fixed on
opposite sides of the package unit (LV and MV Compartments), and on both sides
of the Transformer compartment. The doors shall be provided with stainless
steel/brass hinges and provided with stoppers. The edges of the doors shall be bent
on both sides to assure they fit properly to the door jambs to prevent misalignment.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 9
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 10 of 43
1

All door gaskets shall be of superior quality and capable of withstanding the severe
climatic conditions.
5.11 DOOR LOCKS
The doors shall be securely closed and then locked close with padlocks.
Each access door shall have arrangements to lock with a handle and secured closed
with a padlocks. Suitable door handles shall be fitted to the door.
Padlocks of a top quality make with a master key system shall be provided with
each unit including one spare padlock. The master key shall be advised by the
client.
The client is already using a master key system and the same shall be applied in this
compact substation.
5.12 NOISE LEVEL
The noise level of the completely assembled package Substation shall not exceed 44
dbA, when measured one (1) meter far from package unit housing in accordance
with IEC 60551. The package Substation shall be checked after assembly to ensure
that no rattling of individual components can occur.
5.13 MOUNTING ARRANGEMENT
The package Substation shall not require casting of concrete plinth at Site. Site
preparation shall be limited to levelling only.
5.14 LIFTING LUGS
Lifting lugs shall be provided so that the completely assembled package Substation
may be lifted without damage. The lifting lugs shall be designed to carry the weight
of the Substation complete with Transformer and switchgear. Required number of
lifting spread beams shall be supplied with each unit.
5.15 COLOUR
The surface colour of HV and LV Switchgear, Transformer and Housing shall be
RAL 7032 light grey.

6. MV COMPARTMENT
The medium voltage switchgear is gas insulated, consisting of two cable switches
disconnector (Load break switch) and transformer T-off with VCB. For other
particulars the provided specification may be referred.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 10
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 11 of 43
1

All individual switches shall be lockable in open position with padlock.


The switchgear shall be sealed for life. The Spring Mechanisms shall be of long-life
corrosion resistant material and dust proof. Degree of Protection shall not be less
than IP54.
6.1 ELECTRICAL DATA

Rated voltage 33kV


Highest system Voltage 36kV
Number of phases Three
Rated Frequency 50 Hz
Rated Short-time Withstand current for 3s 25 kA
Power frequency withstand voltage 70 kV
Lightning Impulse withstand Voltage (1.2/50 s) 170 kV

6.2 LOAD BREAK SWITCH


The switching compartment shall be SF6 insulated. The load break switch shall be
operable manually to OPEN, CLOSE and EARTHING positions. Beside that the
three position should have an Interlock.
The Load break switches shall be rated for the rated voltages. The temperature rise
limit for the silver faced copper contacts shall be 60°C and for the terminals 50° C.
6.3 TRANSFORMER BREAKER
A transformer breaker shall be provided to protect and control the distribution
transformer.
The Transformer breaker unit shall be fault-making and fault-breaking Tee-off
vacuum circuit breaker. The CB shall have Trip Coil also connected to Temperature
Indicator of the Transformer to protect the Transformer against over loading.
6.4 PROTECTION RELAYS
The circuit Breaker shall be equipped with self-powered numerical relay with
operating temperature of –5oC to +70oC, for OC/SC and E/F protection, which can
be adjusted to suit different Transformer capacities. The relay shall protect the

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 11
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 12 of 43
1

system from transformer faults, transformer through faults and transformer


overload. The protection relay shall be compatible to communication relay from the
SCADA system.
6.5 BUSHINGS
MV bushings shall be rated to withstand the highest equipment voltage of 52 kV
and the maximum fault current of the windings when connected to the 33kV
network and for the same period of time. Current carrying outer parts shall be made
of copper or copper alloy.
Each bushing shall be marked with manufacturer’ name and type. The marking
shall be visible after assembly of the fittings.
The outer creepage distance for outdoor bushings shall not be less than 25 mm/kV.
The insulation levels of the bushings shall be at least equal to those specified for the
windings.
6.6 CABLE TERMINATIONS
The cable boxes for Ring Circuits shall be suitable for accommodating 3 core or
single core cross-linked polyethylene insulated PVC sheathed over the range of 50
sq.mm to 300 sq.mm Copper or aluminium Conductor for Feeders.
The box shall be designed for air-insulated dry type heat shrinkable/cold shrinkable
termination. The design shall provide sufficient space for crossing of cores without
damage to core insulations. Cable glands and heat shrinkable/cold shrinkable
termination kits of acceptable make shall be supplied with the unit.
For Transformer Control Switch plug-in type Terminations of an acceptable make,
suitable up to 120 sq.mm Single Core Cable shall be supplied.
6.7 EARTH FAULT INDICATOR
Through-fault current indicators with core-balance Transformer (associated with the
one of the feeders) shall be supplied. These shall be supplied fixed flush mounted
on units facing glass windows on the Package Unit access Door, in such a way that
they can be seen without opening the door.
The through-fault current indicator shall operate on the passage of fault current
through its core-balance C.T. The indicator shall be clearly visible from ground
level. The unit shall be self-reset type upon restoration of power supply. The unit
shall have time delay to avoid operation during brief periods of unbalance.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 12
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 13 of 43
1

The through-fault indicator shall be of Siemens AG, GEC Measurement, U.K., or


REYROLLE AFB, ABB or other equivalent quality. The unit shall be adequately
protected to withstand severe weather conditions, as it is meant to be used for
outdoor installation on Ring Main Units.
6.8 EARTHING
Each unit assembly shall be provided with copper earth bar 40mm x 5mm, the metal
frames of all items shall be connected to one another firmly. Two earth terminals
shall be provided for connecting to the station earthing system.
6.9 ACCESSORIES
Each unit shall be supplied with the following accessories:
 Voltage Indicator lamps fixed on the front of the panel for both feeder
switches.
 Plug-in Voltage Indicator for phase comparison.
 Test Plugs with each batch of 10 (ten) Units.

7. TRANSFORMER COMPARTMENT
7.1 GENERAL
This section specifies the detailed requirements for distribution transformers,
complete with necessary fittings for 33/0.4kV Compact substations.
The transformer shall conform to the provided technical specification. A technical
schedule shall be completed for the transformer for ground mounted substation.
7.2 TRANSFORMER TYPE
The transformer shall be hermetically sealed, tank type, ONAN naturally cooled,
skid mounted, un-inhibited mineral oil immersed, core type and copper windings
suitable for operation outdoor in exposed location. The Transformer oil shall
confirm to BS 148 Class 1 Category / IEC 296.
7.3 VOLTAGE RATIOS
The normal voltage ratio of the Transformer on normal tapping and no-load shall be
33 /0.4 kV.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 13
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 14 of 43
1

7.4 RATINGS
The Transformer rated kVA shall be the continuous steady load rating under the
specified temperature and humidity without exceeding the average temperature rise
limits given in the technical specifications.
The full rating shall be at the rated output voltage with rated input voltage.
7.5 TEMPERATURE RISE
The Transformer shall be capable of carrying full rated current continuously under
the maximum specified ambient temperature (as per IEC60076-2) at any tapping,
without the temperature rise of oil at top exceeding 60 degree C, as measured by
thermometer and of the winding not exceeding 65 degree C and of the hot spot not
exceeding 78 degree C, as measured by resistance calculations demonstrating the
above shall be submitted with the Bid.
7.6 WINDING CONNECTION - VECTOR GROUP
The winding connection of the Transformers shall be connected Delta Star in
accordance with the group of symbols in IEC 60076-4, Vector Reference Dyn5.
The neutral terminal shall be brought out and shall be fully rated in all cases.
7.7 TRANSFORMER MECHANICAL DESIGN
The tank shall be constructed of high grade steel plate, suitably reinforced to
withstand handling and pressure during fault condition without any deformation.
Gaskets shall be oil resistant. Rubber gaskets used for flange connections of the
various oil compartments shall be laid in grooves. Gaskets any kind of impregnated/
bonded cork are not acceptable.
The tank shall be fitted with lifting lugs suitable for handling the mass of the
transformer complete with oil.
7.7.1 Accessories
At least the following accessories shall be included for the transformer:
a) Pressure relief device
b) Oil level indicator
c) Two earthing terminals
d) Oil thermometer
e) Rating and diagram plates

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 14
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 15 of 43
1

7.7.2 Electrical Design


The transformer windings shall be designed to meet the following electrical
characteristics:

Nominal System voltage 33kV


Highest system voltage 36kV
Highest equipment voltage rating 52kV
Ratted low-voltage at no-load 400 V
System frequency 50 Hz
Vector group Dyn5
Rated lightning impulse withstand voltage(1.2/50 s) for MV 125 kV
windings
Power frequency withstand voltage for MV windings 50kV
Rated one minute power frequency withstand voltage for LV 3 kV
windings

7.7.3 Guaranteed values


The following values are guaranteed by the manufacturer as stipulated in the
guaranteed characteristic table.
1) No-load loss
2) Load loss
3) No-load current
4) short-circuit impedance
5) Voltage ratio
7.8 OFF-LOAD TAP CHANGER
The MV transformer windings shall be provided with an off-load tap changer
providing 5 positions and each step shall be 2.5%.
The tap settings shall be +5%, +2.5%, 0%, -2.5%, -5%, for three phase
transformers.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 15
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 16 of 43
1

The off-load tap changer shall have an externally operated mechanism for manual
operation. Tap positions shall be clearly identified. The operating mechanism shall
have an effective locking device for locking of the tap changer in any desired
position.
7.9 BUSHINGS SPACING
Transformers shall have the bushings for HV and LV which fulfil the requirements
of IEC 60137
Minimum Distances between bushings shall be as per IEC standard.
7.10 EMERGENCY LOADING
The Tenderer shall demonstrate by calculation, the ability of the Transformer to
operate under emergency loading condition as per IEC 354 for the following
loading and ambient temperature conditions listed below with Transformer winding
hot spot temperature not exceeding 40 degree C, after thermal equilibrium has been
reached at rated load.
Transformer bushing, tap changer and terminations shall also be suitably rated for
over loading as specified in IEC 60354.

Load Minimum Duration in Minutes at Ambient


(% of Rating) Temperature
30 Degree C 40 Degree C 55 Degree C
120
130
150
7.11 LOSSES
The losses shall be stated and guaranteed in the Bid technical specifications (no
tolerance is permitted). For evaluation or other reasons losses will be capitalized at
the rates given below.
No Load Loss : US$ 6000 per kilowatt.
Load Loss : US$ 3200 per kilowatt.
If, on delivery, the tested losses exceed the guaranteed losses then losses in excess
of the guaranteed values shall be capitalized at the above rates and the amount
deducted from the contract price. There will be no credit for losses less than the
guaranteed value.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 16
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 17 of 43
1

8. LOW VOLTAGE COMPARTMENT


The main incoming cables/copper flat (provided with ring type current transformers
as per the details specified in the technical particulars) shall be connected to the bus
bars of phases. These bus bars shall be connected to the ACB/MCCB which are in
turn connected to the outgoing feeders using MCCB’s.
One neutral bar and earth bar also provided to meet the requirement.
The provided technical specifications may be referred regarding other particulars on
ACB and MCCBs.
The glanding arrangement shall fully ensure earth continuity through cable armour
in the cases of armoured cables.
8.1 DETAILS OF EQUIPMENT IN LV COMPARTMENT
The following shall be part of the LV cubicle.
8.1.1 Busbars
Set of busbars of hard drawn, high conductivity, tinned copper and rigidly
supported. The busbars to be positioned to give maximum access and shall be
colour coded for identification by shrinkable insulating tube. The size of the busbars
shall be stated in the Bid as (Cross-section Area sq.mm).
8.1.2 LV Incoming Isolator
One incoming unit with hook operated slow make and break off load hinged MCCB
on each phase for control of the Transformer supply. Switch- blades shall be fitted
with contact tightening clamps. It shall be possible to leave the incoming isolators
open ‘LIVE’ with the door closed.
8.1.3 ACBc/MCCBs
The circuit breaker for the incomer shall be MCCBs for 500KVA compact
substations and it shall be ACB for 630KVA and 800KVA compact transformers.
0.4 kV switchgear shall be air insulated Moulded Case Circuit Breakers (MCCB)
for the outgoing circuits. The provided specification may be referred for full details
The outgoing feeder MCCB complete with overload and short circuit protection
with ratings specified in the schedule of requirements are connected to the bus bars.
Required numbers as specified in Schedule of Bill of Quantities of 4 x MCCBs.
A separate MCCB shall be provided for street lighting.
A blank circuit label to be provided on each unit.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 17
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 18 of 43
1

8.1.4 CTs
On each phase current Transformer shall be provided for operation of instruments.
8.1.5 Energy Meter
The required wiring for connecting one smart energy meter at a future date shall be
complete and space made available. All wiring shall be terminated at a meter
terminating block to enable future meter installation and easy connection
8.1.6 Ammeter
Three Single-Phase Ammeters with instantaneous elements plus maximum current
demand indicators of the thermal type. The ammeters shall be suitable for operation
from the current Transformers specified. The maximum demand element shall be
compensated for 55 degree Celsius ambient temperature.
8.1.7 Voltmeter
One Voltmeter 0-500V with phase selector switch.
8.1.8 Light fitting
One Light Fitting for cubicle illumination complete with a door operated switch.
The maximum demand indicator voltmeters, selector switch and light fitting to be
mounted on an instrument panel.
8.1.9 Earth Bar
An Earth Bar not less than 50mm x 10mm shall be provided at the bottom and
secured so as to give a positive electrical connection. In addition, two 12mm with
Earth terminal shall be provided on the pillar shell and connected to the earth bar. A
detachable link between neutral and earth bar shall also be provided.
8.1.10 Cable Glands
The cable glands shall be brass or stainless steel compression type as per BS
suitable for the bales provided for the LV system. The glands shall be supplied
complete with earth tag PVC shrouds. Cross sectional details of the cable will be
supplied to the successful Tenderers. Earth tag of each gland shall be connected to
earth bar with tinned copper flexible earthing braid of adequate cross section having
at least 50 % of that of the phase conductor of the cable to be connected. Each cable
gland shall be supported on a removable gland plate.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 18
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 19 of 43
1

8.1.11 Miscellaneous
All instrument wiring shall be 2.5 sq.mm stranded copper conductor, 600 Volt
tropical grade PVC insulated.
The Base Plate of the feeder pillar shall be supplied with knockout holes.
Necessary Nuts, Bolts for cable lugs, spacers, etc., shall be supplied fitted with
feeder pillar. Cable clamps shall be provided at the bottom of the feeder pillar to
hold the cables in position.
The gland plate of the feeder pillar shall be so positioned to allow convenient bend
on the cable.
Cable glands with earth tag and plastic shrouds, cable lugs and fuses shall be
delivered separately.

9. SPARE PARTS
Different items ordered against spares shall be packed in separate casing with item
number and quantity clearly marked.

10. DOCUMENTS TO BE SUBMITTED


Prior to the tests the Supplier shall submit an outline of the procedures and tests in
its plans, to demonstrate fulfilment of the requirements specified in subsequent
sections of the detailed technical specification.
During the course of fabrications, tests shall be made on samples not less than 5%
of the respective items.
The Tenderer must submit all technical descriptions, data sheets, catalogues and
other supporting material with the Offer to enable the Purchaser’s Engineer to fully
evaluate the proposal as to its compliance with the Tender Specification. As a
minimum the Tenderer shall submit the following:
Guaranteed Technical Particulars.
Copies of required Type Test Certificates.
ISO 9000 certification and its relevant parts.
1) All drawings and information called for by this Specification, including:

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 19
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 20 of 43
1

10.2 FOR RING MAIN UNIT


1) General arrangement RMUs, dimensions, together with
mountings/accessories.
2) Details of HV Cable Terminations.
3) Details of fault current indicator.
4) Characteristics of the Transformer Control Unit.
10.3 FOR DISTRIBUTION TRANSFORMER
1) General arrangement of Transformer dimensions etc.
2) Details of HV and LV Bushings
3) Details of HV Cable Box.
4) Details of Tap Changer.
5) Details of Temperature Rise Indicator.
10.4 LV COMPARTMENT
1) Details and characteristics of ACBs and MCCBs.
2) Drawing Showing the Internal Arrangement of Feeder Pillar.
10.5 HOUSING
Construction details of the Housing.
10.6 GENERAL
1) Original Brochures and Catalogues for Standard Unit.
2) Applicable Design Specification.
3) Lists of Accessories included in the Bid.

11. INSPECTION AND TESTING


The Employer/Employer’s representative shall be given access to the
Manufacturing Works (Factory) at all reasonable times for the purpose of inspection
of the manufacturing and testing facilities available in addition to inspection of
equipment/material.
All the type test, routine and acceptance test shall be done as per relevant IEC
standard only. Three sets of complete test certificates (routine & acceptance tests)
need to be submitted along with delivery of the transformer.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 20
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 21 of 43
1

11.1 TYPE TEST:


11.1.1 GENERAL
The bidder should submit Type test certificate for compact transformer from
KEMA or equivalent along with bid. This is to prove that the offered equipment
satisfies all the design requirements set out in this specification.
11.2 ROUTINE TEST
These tests shall be carried out on each individual of the equipment offered as per
IEC at the manufacture’s works to ensure that the product is in accordance with the
requirements of this specification.
These tests shall include:
a) Induced over voltage withstand test at 66kV for 33kV winding,
b) Resistance test,
c) No-load test,
d) Short-circuit test,
e) Measurement of transformation ratio and vector group,
f) Measurement of impedance voltage,
g) A test report containing the test results is to be drawn up for each transformer.
h) Insulation test
i) AC hi-pot test
j) Dielectric loss test
k) Circuit Breaker cotnact resistance test
l) Circuit breaker time-travel resistance measurment
11.3 ACCEPTANCE TEST
The Acceptance test procedures for any delivery of the equipments are as
follows:
a) Visual inspection,
b) Inspection of the complete equipment,
c) Insulation test
d) AC hi-pot test

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 21
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 22 of 43
1

e) Dielectric loss test


f) Circuit Breaker contact resistance test
g) Circuit breaker time-travel resistance measurment
h) Checking of the result of the routine and type test as per IEC,
i) Carrying out all or part of tests mentioned in the routine test,
j) Checking of conformity to specification.
The following tests on transformer shall also be carried out,
1) dielectric tests of high voltage and low voltage winding(s) at rated one minute
power frequency withstand voltage,
2) double voltage test ( 1 minute at double voltage and double frequency)
induced via the low voltage winding;
3) measurement of no-load loss and no-load current,
4) measurement of load loss and impedance voltage with the off circuit tap
changer in the normal position,
5) Measurement of the insulation resistance (oil, paper and press board) between
high voltage and low voltage, and tank (Meggar test),
The Corporation reserves the right to apply, penalty or reject particular equipment
in the event of non-compliance with the guaranteed losses.

12. PACKING AND MARKING


The Compact Substations shall be packed in sea-worthy solid wall wooden cases in
a manner to avoid damage during transport, handling and storage. They shall also
be packed in such a way that no corrosion occurs on the equipments due to salty
moisture when stored at the port of destination.
Each package shall be marked with the main details of the equipment contained
therein, the type designation or the catalogue number and with the manufacturer's
name or trademark.
Each wooden case shall be clearly marked with the address of EEU and the relevant
contact number and title. All markings shall be legible and durable. Bushing units
shall be packed in a manner to avoid damage during transport, handling and storage.
The compact transformer and its wooden case shall be fitted with an easily readable
nameplate of weatherproof material giving the following details:

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 22
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 23 of 43
1

 Type of transformer
 Manufacturer's Name
 Manufacturer's Serial Number
 Year of Manufacture
 Rated Frequency
 Rated operating voltage
 Maximum operating voltage
 Maximum equipment rating voltage
 Rated Continuous Current (Max.)
 Rated power frequency Withstand Voltage
 Rated Impulse Withstand Voltage
 Gross Weight
 Purchase order number & date

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 23
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 24 of 43
1

Appendix A:- Guaranteed Technical Particulars


for 33/0.4kV Compact Transformer

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 24
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 25 of 43
1

13. GUARANTEED TECHNICAL PARTICULARS FOR 500KVA (33/0.4) KV


COMPACT TRANSFORMER
Offered
No. Description Required by EEU by
Bidder
I General
1 Manufacturer
2 Country of origin
3 Type designation
IEC 61330/IEC
62271-1/IEC62271-
200/
IEC62271-202/
IEC60076-2017/
4 Standard
IEC60044-1/
IEC61439/IEC/
TR62271-208/
IEC60529/IEC62262/
IEC60721
5 Composition of distribution substation
5.1  Number of medium voltage compartment 1
5.2  Number of transformer compartment 1
5.3 Number of low voltage compartment 1
II Medium voltage compartment
6 Size of cubicle
7 Type
8 Protection class IP54
9 Nominal system voltage, kV 33
9.1 Voltage Variation of the system, % ±10
Maximum system operating voltage, in
9.2 36
kV
Maximum equipment rating voltage, in
9.3 52
kV
Load break switch and earthing switch
10 2
(2 Incoming)
10.1 Type SF6

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 25
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 26 of 43
1

Offered
No. Description Required by EEU by
Bidder
10.2 Frequency, Hz 50
10.3 Insulation level
10.3. Power frequency withstand voltage,
70
1 kV(RMS)
10.3. Rated lightning, impulse withstand
170
2 voltage, kV(Peak)
10.4 Rated current, A 630
Rated short-time withstand current for 3s,
10.5 25
kA
Vacuum Circuit Breaker with Earthing
11 Switch (Open,close & earthing 1
operation)
11.1 Type  Vacuum
11.2 Rated voltage, kV 33
11.3 Rated frequency, Hz 50
11.4 Insulation level
11.4. Rated Power frequency withstand voltage,
70
1 kV
11.4. Rated lightning, impulse withstand
170
2 voltage, kV
Depends on the Rating
11.5 Current rating, A
of the transformer
Rated short-time withstand current for
11.6 25
3s,kA
III Low Voltage compartment
12 Size of cubicle
13 Protection class IP23
13.1 Bus Bar rating (A) Min.1500
No. of ways for outgoing Cable
13.2 >=4
Terminations
14 Incomer Main MCCB  1
14.1 Type
14.2 Nominal voltage, kV 0.4

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 26
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 27 of 43
1

Offered
No. Description Required by EEU by
Bidder
14.3 Rated frequency, Hz 50
14.4 Insulation level
14.4. Power frequency withstand voltage ,
3 for one minute
1 kV(RMS)
14.4. Rated lightning, impulse withstand
10
2 voltage, kV(peak), (1.2/50 ms)
14.5 Rated current, A 721
14.6 Rated short-time current rating, kA 50
15 Outgoing MCCB 6
15.1 Type
15.2 Nominal voltage, kV 0.4
15.3 Rated Current, A 721
15.4 Rated short-time current rating, kA 50
16 Current transformer
16.1 Type
16.2 Quantity for each s/s 3
16.3 Voltage rating 380V
16.4 Current ratio 1000/5
16.5 Frequency, Hz 50
16.6 Burden, VA 15
16.7 Class 0.5
17 Ammeter
17.1 Type
17.2 Quantity 3
17.3 Current range, A 0-1000
18 Voltmeter with selector switch
18.1 Type
18.2 Quantity 1
18.3 Voltage range, V 0-500
IV Transformer compartment
19 Protection class IP23

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 27
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 28 of 43
1

Offered
No. Description Required by EEU by
Bidder
Technical characteristics of the
V
distribution transformer
20 Method of cooling ONAN
21 No. of phases 3
22 Standard IEC 60076
23 Frequency, Hz 50
24 Rated Continuous Power, kVA

24.1 On HV side 500

24.2 On LV side 500


25 Rated Voltage, kV
25.1 On HV side 36
25.2 On LV side 0.4
26 Connections (Vector Group) Dyn5
No-load loss at rated voltage and
27 ≤0.59
frequency ,kW
28 Full load loss ,kW ≤5.94
 5 position step (+5%,
29 Off-load tap changer
+2.5%,0%,-2.5%,-5%)
Efficiency referred to 75oC at rated
30
voltage and
30.1 100% rated output and P.F= 1 (%)
30.2 50% rated output and P.F= 1 (%)
30.3 100% rated output and P.F= 0.95 (%)
30.4 50% rated output and P.F= 0.95 (%)
31 No load current as percent of rated current
31.1 At 90% voltage (%)
31.2 At 100% voltage (%)
31.3 At 110% voltage (%)
Mean level of noise at no load-Power
32
level (dB)
33 Color of the transformer Gray

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 28
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 29 of 43
1

Offered
No. Description Required by EEU by
Bidder
34 Thickness of surface treatment (µm) 140
Short-circuit impedance at principle
35 4
tapping (%)
36 Ability to withstand unbalanced load (%) >=90
37 Average temperature rise, oC
37.1 Windings 0c  65
37.2 Top oil 0c 60
38 Dimensions of complete transformer, mm
38.1 Height
38.2 Length
38.3 Width
39 Weight, kg
39.1 Core
39.2 Winding
 Uninhibited Mineral oil /
39.3 Transformer Oil Class 1 Category / IEC
60296/IEC60156.
39.4 Complete transformer
40 Transformer tank
40.1 Material Steel
40.2 Thickness of tank plate
40.2.
Top, mm
1
40.2.
Bottom, mm
2
40.2.
Sides, mm
3
41 Core
41.1 Type
41.2 Material Silicon Steel
41.3 Loss figure, W/kg
41.4 Type (wire or coil) wire or coil

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 29
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 30 of 43
1

Offered
No. Description Required by EEU by
Bidder
42 HV Windings
42.1 Material Copper
42.2 Insulation
Power frequency withstand voltage,
42.3 70
kV(RMS)
Rated lightning, impulse withstand
42.4 170
voltage, kV(peak)
42.5 Type wire or coil, round wire or coil
43 LV Windings
43.1 Material Copper
43.2 Insulation
Power frequency withstand voltage,
43.3 3
kV(RMS)
Rated lightning, impulse withstand
43.4 >=10
voltage, kV(peak)
44 Complete Compact Substation
44.1 Dimension
44.2 Weight, kg
45 Communication facility (GSM/GPRS) Must support

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 30
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 31 of 43
1

14. GUARANTEED TECHNICAL PARTICULARS FOR 630KVA, (33/0.4) KV


COMPACT TRANSFORMER
Offered
No. Description Required by EEU by
Bidder
I General
1 Manufacturer
2 Country of origin
3 Type designation
IEC 61330/IEC
62271-1/IEC62271
-200/
IEC62271-202/
IEC60076-2017/
4 Standard IEC60044-1/
IEC61439/IEC/
TR62271-208/
IEC60529/
IEC62262/
IEC60721
5 Composition of distribution substation
5.1  Number of medium voltage compartment 1
5.2  Number of transformer compartment 1

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 31
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 32 of 43
1

Offered
No. Description Required by EEU by
Bidder
5.3 Number of low voltage compartment 1
II Medium voltage compartment
6 Size of cubicle
7 Type
8 Protection class IP54
9 Nominal System voltage, kV 33
9.1 Voltage Variation of the system, % ±10
9.2 Maximum system operating voltage, in kV 36
9.3 Maximum equipment rating voltage, in kV 52
Load break switch with earthing switch
10 2
( 2 Incoming)
10.1 Type SF6
10.2 Frequency, Hz 50
10.3 Insulation level
Power frequency withstand voltage,
10.3.1 70
kV(RMS)
Rated lightning, impulse withstand voltage,
10.3.2 170
kV(Peak)
10.4 Rated current , A 630
10.5 Rated short-time withstand current for 3s,kA 25
Vacuum Circuit Breaker with Earthing
11 1
Switch (Open,close & earthing operation)
11.1 Type Vacuum
11.2 Nominal System voltage, kV 33
11.3 Rated frequency, Hz 50
11.4 Insulation level
Rated Power frequency withstand voltage,
11.4.1 70
kV
Rated lightning, impulse withstand voltage,
11.4.2 170
kV
Depends on the
11.5 Current rating, A Rating of the
transformer

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 32
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 33 of 43
1

Offered
No. Description Required by EEU by
Bidder
11.6 Rated short-time withstand current for 3s,kA 25
III Low Voltage compartment
12 Size of cubicle
13 Protection class IP23
13.1 Bus Bar rating (A) Min.2000
13.2 No.of ways for outgoing Cable Terminations >=4
14 Incomer Main ACB 1
14.1 Type
14.2 Nominal voltage, kV 0.4
14.3 Rated frequency, Hz 50
14.4 Insulation level
Power frequency withstand voltage ,
14.4.1 3 for one minute
kV(RMS)
Rated lightning, impulse withstand voltage,
14.4.2
kV(peak), (1.2/50 ms)
14.5 Rated current, A 909
14.6 Rated short-time current rating, kA 50
15 Outgoing MCCB 6
15.1 Type
15.2 Nominal voltage, kV 0.4
15.3 Rated Current, A 909
15.4 Rated short-time current rating,kA 50
16 Current transformer
16.1 Type
16.2 Quantity for each s/s 3
16.3 Voltage rating 380V
16.4 Current ratio 1250/5
16.5 Frequency, Hz 50
16.6 Burden, VA 15
16.7 Class 0.5
17 Ammeter

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 33
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 34 of 43
1

Offered
No. Description Required by EEU by
Bidder
17.1 Type
17.2 Quantity 3
17.3 Current range, A 0-1250
18 Voltmeter with selector switch
18.1 Type
18.2 Quantity 1
18.3 Voltage range, V 0-500
IV Transformer compartment
19 Protection class IP23
Technical characteristics of the
V
distribution transformer
20 Method of cooling ONAN
21 No. of phases 3
22 Standard IEC 60076
23 Frequency, Hz 50
24 Rated Continuous Power, kVA

24.1 On HV side 630

24.2 On LV side 630


25 Rated Voltage, kV
25.1 On HV side 36
25.2 On LV side 0.4
26 Connections (Vector Group) Dyn5
No-load loss at rated voltage and
27 ≤0.69
frequency ,kW
28 Full load loss ,kW ≤7.04
 5 position step
29 Off-load tap changer (+5%,+2.5%,0%,-
2.5%,-5%)
Efficiency referred to 75oC at rated voltage
30
and

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 34
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 35 of 43
1

Offered
No. Description Required by EEU by
Bidder
30.1 100% rated output and P.F= 1 (%)
30.2 50% rated output and P.F= 1 (%)
30.3 100% rated output and P.F= 0.95 (%)
30.4 50% rated output and P.F= 0.95 (%)
31 No load current as percent of rated current
31.1 At 90% voltage (%)
31.2 At 100% voltage (%)
31.3 At 110% voltage (%)
Mean level of noise at no load-Power level
32
(dB)
33 Color of the transformer Gray
34 Thickness of surface treatment (µm) 140
Short-circuit impedance at principle tapping
35 4
(%)
36 Ability to withstand unbalanced load (%) >=90
37 Average temperature rise, oC
37.1 Windings 0c  65
37.2 Top oil 0c 60
38 Dimensions of complete transformer, mm
38.1 Height
38.2 Length
38.3 Width
39 Weight, kg
39.1 Core
39.2 Winding
 Uninhibited Mineral
oil / Class 1
39.3 Transformer Oil Category / IEC
60296/IEC60156.
39.4 Complete transformer
40 Transformer tank
40.1 Material Steel

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 35
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 36 of 43
1

Offered
No. Description Required by EEU by
Bidder
40.2 Thickness of tank plate
40.2.1 Top, mm
40.2.2 Bottom, mm
40.2.3 Sides, mm
41 Core
41.1 Type
41.2 Material Silicon Steel
41.3 Loss figure, W/kg
41.4 Type (wire or coil) wire or coil
42 HV Windings
42.1 Material Copper
42.2 Insulation
Power frequency withstand voltage,
42.3 70
kV(RMS)
Rated lightning, impulse withstand voltage,
42.4 170
kV(peak)
42.5 Type wire or coil, round wire or coil
43 LV Windings
43.1 Material Copper
43.2 Insulation
Power frequency withstand voltage,
43.3 3
kV(RMS)
Rated lightning, impulse withstand voltage,
43.4
kV(peak)
44 Complete Compact Substation
44.1 Dimension
44.2 Weight, kg
45 Communication facility (GSM/GPRS) Must support

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 36
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 37 of 43
1

15. GUARANTEED TECHNICAL PARTICULARS FOR 800KVA, (33/0.4) KV


COMPACT TRANSFORMER
Offere
No. Description Required by EEU d by
Bidder
I General
1 Manufacturer
2 Country of origin
3 Type designation
IEC 61330/IEC 62271-
1/IEC62271-200/
IEC62271-202/
IEC60076-2017/
4 Standard IEC60044-1/
IEC61439/IEC/
TR62271-208/
IEC60529/IEC62262/
IEC60721
5 Composition of distribution substation

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 37
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 38 of 43
1

Offere
No. Description Required by EEU d by
Bidder
5.1  Number of medium voltage compartment 1
5.2  Number of transformer compartment 1
5.3 Number of low voltage compartment 1
II Medium voltage compartment
6 Size of cubicle
7 Type
8 Protection class IP54
9 Nominal System voltage, kV 33
9.1 Voltage Variation of the system, % ±10
9.2 Maximum system operating voltage, in kV 36
9.3 Maximum equipment rating voltage, in kV 52
10 RMU(Incoming 2+Outgoing 1) 2
10.1 Load break switch with earthing switch
10.1 Type SF6
10.2 Frequency, Hz 50
10.3 Insulation level
10.3. Power frequency withstand voltage,
70
1 kV(RMS)
10.3. Rated lightning, impulse withstand
170
2 voltage, kV(Peak)
10.4 Rated current , A 630
Rated short-time withstand current for
10.5 25
3s,kA
Vacuum Circuit Breaker with Earthing
11 Switch (Open,close & earthing 1
operation)
11.1 Type  Vacuum
11.2 Rated voltage, kV 33
11.3 Rated frequency, Hz 50
11.4 Insulation level
11.4. Rated Power frequency withstand voltage,
70
1 kV

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 38
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 39 of 43
1

Offere
No. Description Required by EEU d by
Bidder
11.4. Rated lightning, impulse withstand
170
2 voltage, kV
Depends on the Rating
11.5 Current rating, A
of the transformer
Rated short-time withstand current for
11.6 25
3s,kA
III Low Voltage compartment
12 Size of cubicle
13 Protection class IP23
13.1 Bus Bar rating (A) Min.2000
No.of ways for outgoing Cable
13.2 >=4
Terminations
14 Incomer Main MCCB
14.1 Type
14.2 Nominal voltage, kV 0.4
14.3 Rated frequency, Hz 50
14.4 Insulation level
14.4. Power frequency withstand voltage ,
3 for one minute
1 kV(RMS)
14.4. Rated lightning, impulse withstand
10
2 voltage, kV(peak), (1.2/50 ms)
14.5 Rated current, A 1154
14.6 Rated short-time current rating, kA 50
15 Outgoing MCCB 8
15.1 Type
15.2 Nominal voltage, kV 0.4
15.3 Rated Current, A 1154
15.4 Rated short-time current rating,kA 50
16 Current transformer
16.1 Type
16.2 Quantity for each s/s 3
16.3 Voltage rating 380V

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 39
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 40 of 43
1

Offere
No. Description Required by EEU d by
Bidder
16.4 Current ratio 1600/5
16.5 Frequency, Hz 50
16.6 Burden, VA 15
16.7 Class 0.5
17 Ammeter
17.1 Type
17.2 Quantity 3
17.3 Current range, A 0-1600
18 Voltmeter with selector switch
18.1 Type
18.2 Quantity 1
18.3 Voltage range,V 0-500
IV Transformer compartment
19 Protection class IP23
Technical characteristics of the
V
distribution transformer
20 Method of cooling ONAN
21 No. of phases 3
22 Standard IEC 60076
23 Frequency, Hz 50
24 Rated Continuous Power, kVA

24.1 On HV side 800

24.2 On LV side 800


25 Rated Voltage, kV
25.1 On HV side 36
25.2 On LV side 0.4
26 Connections (Vector Group) Dyn5
No-load loss at rated voltage and
27 ≤0.745
frequency, kW
28 Full load loss, kW ≤8.8

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 40
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 41 of 43
1

Offere
No. Description Required by EEU d by
Bidder
 5 position step (+5%,
29 Off-load tap changer
+2.5%,0%,-2.5%,-5%)
Efficiency referred to 75oC at rated voltage
30
and
30.1 100% rated output and P. F= 1 (%)
30.2 50% rated output and P.F= 1 (%)
30.3 100% rated output and P.F= 0.95 (%)
30.4 50% rated output and P.F= 0.95 (%)
31 No load current as percent of rated current
31.1 At 90% voltage (%)
31.2 At 100% voltage (%)
31.3 At 110% voltage (%)
Mean level of noise at no load-Power level
32
(dB)
33 Color of the transformer Gray
34 Thickness of surface treatment (µm) 140
Short-circuit impedance at principle
35 5
tapping (%)
36 Ability to withstand unbalanced load (%) >=90
37 Average temperature rise, oC
37.1 Windings 0c  65
37.2 Top oil 0c 60
38 Dimensions of complete transformer, mm
38.1 Height
38.2 Length
38.3 Width
39 Weight, kg
39.1 Core
39.2 Winding
 Uninhibited Mineral oil /
39.3 Transformer Oil Class 1 Category / IEC
60296/IEC60156.

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 41
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 42 of 43
1

Offere
No. Description Required by EEU d by
Bidder
39.4 Complete transformer
40 Transformer tank
40.1 Material Steel
40.2 Thickness of tank plate
40.2.
Top, mm
1
40.2.
Bottom, mm
2
40.2.
Sides, mm
3
41 Core
41.1 Type
41.2 Material Silicon Steel
41.3 Loss figure, W/kg
41.4 Type (wire or coil) wire or coil
42 HV Windings
42.1 Material Copper
42.2 Insulation
Power frequency withstand voltage,
42.3 70
kV(RMS)
Rated lightning, impulse withstand
42.4 170
voltage, kV(peak)
42.5 Type wire or coil, round wire or coil
43 LV Windings
43.1 Material Copper
43.2 Insulation
Power frequency withstand voltage,
43.3 3
kV(RMS)
Rated lightning, impulse withstand
43.4
voltage, kV(peak)
44 Complete Compact Substation
44.1 Dimension
44.2 Weight, kg

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 42
Company Name: Document NO.

ETHIOPIAN ELECTRIC UTILITY EEU/EQRD/TS/Co.Tr/04-


235

Title: Technical Specification of Compact Transformer Substation with RMU(33/0.4kV) Issue No. \.Page 43 of 43
1

Offere
No. Description Required by EEU d by
Bidder
Must support /RTU or
45 Communication facility (GSM/GPRS)
FTU

Prepared by Sign Checked by Sign Approved by Sign Rev.No Date Page


Abebaw Belay Elias Azene Chala Aman 0 Sept.18,2020 No. 43