You are on page 1of 6

PIPE WEIGHTS

STEEL PIPE
Pipe Insulation Weight per Foot (lbs)
Diameter Pipe Thickness
(in) Schedule (in) Pipe Water Insulation Total
1 40 1 1.7 0.4 0.7 2.8
11/4 40 1 2.3 0.7 0.8 3.8
11/2 40 1 2.7 0.9 0.9 4.5
2 40 1 3.7 1.5 1.0 6.2
21/2 40 1 5.8 2.1 1.2 9.1
3 40 1 7.6 3.2 1.3 12.1
4 40 1 11.0 5.5 1.8 18.3
5 40 11/2 15.0 8.7 2.9 26.6
6 40 11/2 19.0 12.5 3.3 34.8
8 40 11/2 29.0 22.0 4.1 55.1
10 40 11/2 41.0 34.0 5.2 80.2
12 40 11/2 54.0 49.0 6.0 109.0
14 30 11/2 55.0 60.0 7.0 122.0
16 30 11/2 63.0 79.0 7.5 150.0
18 30 11/2 82.0 100.0 8.0 190.0
20 20 11/2 79.0 126.0 8.5 214.0
24 20 11/2 95.0 184.0 10.0 289.0

COPPER PIPE
Pipe Insulation Weight per Foot (lbs)
Diameter Copper Thickness
(in) Type (in) Pipe Water Insulation Total
1 L 1 0.7 0.4 0.7 1.8
11/4 L 1 0.9 0.6 0.8 2.3
11/2 L 1 1.1 0.8 0.9 2.8
2 L 1 1.8 1.4 1.0 4.2
21/2 L 1 2.5 2.1 1.2 5.8
3 L 1 3.3 3.0 1.3 7.6
31/2 L 1 4.3 4.0 1.5 9.8
4 L 1 5.4 5.2 1.8 12.4
5 L 11/2 7.6 8.1 2.9 18.6
6 L 11/2 10.2 11.6 3.3 25.1
8 L 11/2 19.3 20.3 4.1 43.7
10 L 11/2 30.1 31.6 5.2 66.9
12 L 11/2 40.4 45.4 6.0 91.8

New OPM pre-approvals are required on OSHPD


2013 Code Projects. Refer to FM67-72 for current MASON INDUSTRIES, Inc.
OPM pre-approved products. Products will be added Manufacturers of Vibration Control Products
as testing is completed and they are OPM approved. 350 Rabro Drive 2101 W. Crescent Ave., Suite D
Hauppauge, NY 11788 Anaheim, CA 92801
631/348-0282 714/535-2727
FAX 631/348-0279 FAX 714/535-5738
APPROVED
California Office of Statewide
Info@Mason-Ind.com • www.Mason-Ind.com
Health Planning and Development
FIXED EQUIPMENT ANCHORAGE
OPA-0349 August 5, 2002 Page

Bill Staehlin (916) 654-3362


Dhiru Mali
Structural Engineer
California SE No. 2811
M1
PIPE WEIGHTS

STEEL PIPE
Pipe Insulation Weight per Meter (kg)
Diameter Pipe Thickness
(mm) Schedule (mm) Pipe Water Insulation Total
25 40 25 2.5 0.6 1.0 4.1
32 40 25 3.4 1.0 1.2 5.6
38 40 25 4.0 1.3 1.3 6.6
51 40 25 5.5 2.2 1.5 9.2
64 40 25 8.6 3.1 1.8 13.5
76 40 25 11.3 4.8 1.9 18.0
102 40 25 16.4 8.2 2.7 27.3
127 40 38 22.3 12.9 4.3 39.5
152 40 38 28.3 18.6 4.9 51.8
203 40 38 43.2 32.7 6.1 82.0
254 40 38 61.0 50.6 7.7 119.3
305 40 38 80.4 72.9 8.9 162.2
356 30 38 81.8 89.3 10.4 181.5
406 30 38 93.8 117.6 11.2 222.6
457 30 38 122.0 148.8 11.9 282.7
508 20 38 117.6 187.5 12.6 317.7
610 20 38 141.4 273.8 14.9 430.1

COPPER PIPE
Pipe Insulation Weight per Meter (kg)
Diameter Copper Thickness
(mm) Type (mm) Pipe Water Insulation Total
25 L 25 1.0 0.6 1.0 2.6
32 L 25 1.3 0.9 1.2 3.4
38 L 25 1.6 1.2 1.3 4.1
51 L 25 2.7 2.1 1.5 6.3
64 L 25 3.7 3.1 1.8 8.6
76 L 25 4.9 4.5 1.9 11.3
89 L 25 6.4 6.0 2.2 14.6
102 L 25 8.0 7.7 2.7 18.4
127 L 38 11.3 12.1 4.3 27.7
152 L 38 15.2 17.3 4.9 37.4
203 L 38 28.7 30.2 6.1 65.0
254 L 38 44.8 47.0 7.7 99.5
305 L 38 60.1 67.3 8.9 136.3

New OPM pre-approvals are required on OSHPD


MASON INDUSTRIES, Inc. 2013 Code Projects. Refer to FM67-72 for current
Manufacturers of Vibration Control Products OPM pre-approved products. Products will be added
350 Rabro Drive 2101 W. Crescent Ave., Suite D as testing is completed and they are OPM approved.
Hauppauge, NY 11788 Anaheim, CA 92801
631/348-0282 714/535-2727
FAX 631/348-0279 FAX 714/535-5738
APPROVED
Info@Mason-Ind.com • www.Mason-Ind.com
California Office of Statewide
Health Planning and Development
FIXED EQUIPMENT ANCHORAGE
Page
OPA-0349 August 5, 2002

M1m Dhiru Mali


Structural Engineer
California SE No. 2811 Bill Staehlin (916) 654-3362
PIPE WEIGHTS (continued)

SCHEDULE 40 PVC PIPE


Pipe Wall Weight per Foot (lbs)
Diameter Thickness
(in) (in) Pipe Water Total
1/2 0.109 0.15 0.13 0.28
3/4 0.113 0.20 0.23 0.43
1 0.133 0.30 0.37 0.67
11/4 0.140 0.40 0.65 1.05
11/2 0.145 0.48 0.88 1.36
2 0.154 0.64 1.45 2.10
21/2 0.203 1.02 2.07 3.09
3 0.216 1.33 3.20 4.53
31/2 0.226 1.60 4.28 5.88
4 0.237 1.90 5.51 7.41
5 0.258 2.77 8.66 11.43
6 0.280 3.34 12.15 15.49
8 0.322 5.28 21.60 26.88
10 0.366 7.51 34.10 41.61
12 0.406 10.02 48.50 58.52

SCHEDULE 80 PVC PIPE


Pipe Wall Weight per Foot (lbs)
Diameter Thickness
(in) (in) Pipe Water Total
1/2 0.147 0.15 0.10 0.25
3/4 0.154 0.26 0.19 0.45
1 0.179 0.38 0.31 0.69
11/4 0.191 0.53 0.56 1.08
11/2 0.200 0.64 0.77 1.40
2 0.218 0.88 1.28 2.16
21/2 0.276 1.35 1.83 3.18
3 0.300 1.80 2.86 4.66
31/2 0.318 2.20 3.85 6.05
4 0.337 2.64 4.98 7.62
5 0.375 4.13 7.87 12.00
6 0.432 5.03 11.29 16.32
8 0.500 8.02 19.80 27.82
10 0.593 11.89 31.10 42.99
12 0.687 16.37 44.00 60.37

New OPM pre-approvals are required on OSHPD


2013 Code Projects. Refer to FM67-72 for current MASON INDUSTRIES, Inc.
OPM pre-approved products. Products will be added Manufacturers of Vibration Control Products
as testing is completed and they are OPM approved. 350 Rabro Drive 2101 W. Crescent Ave., Suite D
Hauppauge, NY 11788 Anaheim, CA 92801
631/348-0282 714/535-2727
FAX 631/348-0279 FAX 714/535-5738
APPROVED
California Office of Statewide
Info@Mason-Ind.com • www.Mason-Ind.com
Health Planning and Development
FIXED EQUIPMENT ANCHORAGE
OPA-0349 August 5, 2002 Page

Bill Staehlin (916) 654-3362


Dhiru Mali
Structural Engineer
California SE No. 2811
M2
PIPE WEIGHTS (continued)

SCHEDULE 40 PVC PIPE


Pipe Wall Weight per Meter (kg)
Diameter Thickness
(mm) (mm) Pipe Water Total
13 2.8 0.22 0.19 0.41
19 2.9 0.30 0.34 0.64
25 3.4 0.45 0.55 1.00
32 3.6 0.60 0.97 1.57
38 3.7 0.71 1.31 2.02
51 3.9 0.95 2.16 3.11
64 5.2 1.52 3.08 4.60
76 5.5 1.98 4.76 6.74
89 5.7 2.38 6.37 8.75
102 6.0 2.83 8.20 11.03
127 6.6 4.12 12.89 17.01
152 7.1 4.97 18.08 23.05
203 8.2 7.86 32.14 40.00
254 9.3 11.18 50.75 61.93
305 10.3 14.91 72.18 87.06

SCHEDULE 80 PVC PIPE


Pipe Wall Weight per Meter (kg)
Diameter Thickness
(mm) (mm) Pipe Water Total
13 3.7 0.22 0.15 0.37
19 3.9 0.39 0.28 0.57
25 4.6 0.57 0.46 1.03
32 4.9 0.79 0.83 1.62
38 5.1 0.95 1.15 2.10
51 5.5 1.31 1.90 3.21
64 7.0 2.01 2.72 4.73
76 7.6 2.68 4.26 6.94
89 8.1 3.27 5.73 9.00
102 8.6 3.93 7.41 11.34
127 9.5 6.15 11.71 17.86
152 11.0 7.49 16.80 24.29
203 12.7 11.94 29.47 41.41
254 15.1 17.69 46.28 63.97
305 17.5 24.36 65.48 89.84

New OPM pre-approvals are required on OSHPD


MASON INDUSTRIES, Inc. 2013 Code Projects. Refer to FM67-72 for current
Manufacturers of Vibration Control Products OPM pre-approved products. Products will be added
350 Rabro Drive 2101 W. Crescent Ave., Suite D as testing is completed and they are OPM approved.
Hauppauge, NY 11788 Anaheim, CA 92801
631/348-0282 714/535-2727
FAX 631/348-0279 FAX 714/535-5738
APPROVED
Info@Mason-Ind.com • www.Mason-Ind.com
California Office of Statewide
Health Planning and Development
FIXED EQUIPMENT ANCHORAGE
Page
OPA-0349 August 5, 2002

M2m Dhiru Mali


Structural Engineer
California SE No. 2811 Bill Staehlin (916) 654-3362
PIPE WEIGHTS (continued)

CAST IRON PIPE


Pipe Weight per Foot (lbs)
Diameter
(in) Class Pipe Water Total
3 150 12.2 3.7 15.9
4 150 16.4 5.7 22.1
6 150 25.7 12.8 38.5
8 150 36.7 23.1 59.8
10 150 48.7 35.5 84.2
12 150 62.9 51.0 113.9
14 150 78.8 69.3 148.1
16 150 95.0 90.3 185.3
18 150 114.7 114.0 228.7
20 150 135.9 141.5 277.4
24 150 190.4 201.0 391.4

STEEL CONDUIT
Max. Wt./Ft. of Conduit
Conduit Wall Conduit and Conductor (lbs)
Diameter Thickness Wt./Ft. Lead Not Lead
(in) (in) (lbs) Covered Covered
1/2 0.112 0.852 1.172 1.042
3/4 0.124 1.134 1.754 1.398
1 0.124 1.684 2.614 2.347
11/4 0.155 2.281 4.311 3.581
11/2 0.167 2.731 5.891 4.546
2 0.172 3.678 8.528 7.208
21/2 0.219 5.819 11.509 10.219
3 0.219 7.616 16.506 14.506
31/2 0.219 9.202 19.052 17.491
4 0.219 10.889 24.749 21.479
5 0.367 14.810 35.870 30.830
6 0.367 19.185 50.685 43.425

New OPM pre-approvals are required on OSHPD


2013 Code Projects. Refer to FM67-72 for current MASON INDUSTRIES, Inc.
OPM pre-approved products. Products will be added Manufacturers of Vibration Control Products
as testing is completed and they are OPM approved. 350 Rabro Drive 2101 W. Crescent Ave., Suite D
Hauppauge, NY 11788 Anaheim, CA 92801
631/348-0282 714/535-2727
FAX 631/348-0279 FAX 714/535-5738
APPROVED
California Office of Statewide
Info@Mason-Ind.com • www.Mason-Ind.com
Health Planning and Development
FIXED EQUIPMENT ANCHORAGE
OPA-0349 August 5, 2002 Page

Bill Staehlin (916) 654-3362


Dhiru Mali
Structural Engineer
California SE No. 2811
M3
PIPE WEIGHTS (continued)

CAST IRON PIPE


Pipe Weight per Meter (kg)
Diameter
(mm) Class Pipe Water Total
76 150 18.2 5.5 23.7
102 150 24.4 8.5 32.9
152 150 38.2 19.0 57.2
203 150 54.6 34.4 89.0
254 150 72.5 52.8 125.3
305 150 93.6 75.9 169.5
356 150 117.3 103.1 220.4
406 150 141.4 134.4 275.8
457 150 170.7 169.7 370.4
508 150 202.2 210.6 412.8
610 150 283.3 299.1 582.4

STEEL CONDUIT
Max. Wt./m of Conduit
Conduit Wall Conduit and Conductor (kg)
Diameter Thickness Wt./m Lead Not Lead
(mm) (mm) (kg) Covered Covered
13 2.8 1.27 1.74 1.55
19 3.1 1.69 2.61 2.08
25 3.1 2.51 3.89 3.49
32 3.9 3.39 6.42 5.33
38 4.2 4.06 8.77 6.77
51 4.4 5.47 12.69 10.73
64 5.6 8.66 17.13 15.21
76 5.6 11.33 24.56 21.59
89 5.6 13.69 28.35 26.03
102 5.6 16.20 36.83 31.96
127 9.3 22.04 53.38 45.88
152 9.3 28.55 75.42 64.62

New OPM pre-approvals are required on OSHPD


MASON INDUSTRIES, Inc. 2013 Code Projects. Refer to FM67-72 for current
Manufacturers of Vibration Control Products OPM pre-approved products. Products will be added
350 Rabro Drive 2101 W. Crescent Ave., Suite D as testing is completed and they are OPM approved.
Hauppauge, NY 11788 Anaheim, CA 92801
631/348-0282 714/535-2727
FAX 631/348-0279 FAX 714/535-5738
APPROVED
Info@Mason-Ind.com • www.Mason-Ind.com
California Office of Statewide
Health Planning and Development
FIXED EQUIPMENT ANCHORAGE
Page OPA-0349 August 5, 2002

M3m Dhiru Mali


Structural Engineer
California SE No. 2811 Bill Staehlin (916) 654-3362