(DIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM Ref.: 43134101018,
‘Bol: BEA og. by TWS. ev. date. 091104 Roolaces:
1.0 THE PRESENT DELOMATIC SYSTEM
‘This paragraph introduces the functionality of the present DELOMATIC system solution. The plant is ilustrated in
the following one-core diagram (it may not be complete but it should reflect the plant as the Power Management
System see i),
CT ratio
VT ratio
1) The voltage is stated in phase to phase valuesDELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM Ref.: 4313410101,
Rats BES Aco. by: TWS. ev. cale: 031108 Rovlaces:
1.4 The present PMS functions
‘The following basic PMS functions are implemented in the present DELOMATIC system (please
‘remember that the PMS functions are the common functions controlled only by the Master DGU):
+ Plantmodes; — - SEML-AUTO
~ AUTOMATIC
- SECURED
+ User-programmabie start priority
+ Load dependent start/stop function incl
= transmission of PMS start/stop commands
~ safely start of stand-by generator sets due to expected stop of a running
generator set
~ transfer of PMS start command in case of failed engagement ofthe generator set
+ Common black-out detection and subsequently black-out start of two generator sets,
+ Load sharing:
= symmetrical load sharing
- asymmetrical load sharing
+ Conditional connection of 4 heavy consumers with fixed or variable load
= HG 1 and 2 on Bus A (setpoint 161)
~ HC 3and 4 on Bus B (setpoint 161)
+ Supervision of the shore connection position(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM Ref: 43134101018,
el BEA op. by: TW Bow, dot 031104 Rooiaces,
‘The following optional PMS functions can be implemented in the present DELOMATIC system (please
remember that the PMS functions are the common functions controlled only by the Master DGU)
No optional functions in this application
The following PMS special functions are implemented in the present DELOMATIC system (please
remember that the PMS functions are the common functions controlled only by the Master DGU)
+ Bi-directional serial interface which according to the standard communication protocol offers remote
control or supervision of the DELOMATIC system (ModBus RS 485)
= access to system control commands:
~ access to set-points and timers
= measured and calculated values
- system status feedback
alarm status feedback(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM Ref.: 43134101014,
_Aoo. by. TWS_ Rev. date 031104 Ranlaoes:
Rel: BEA
4.2 The present generator set functions
The following Generator set basic functions are implemented in the present DELOMATIC system
(carried out be each DGU):
+ Internal system supervision comprising
- iO error; supervision of hardware configuration
- breaker position feedback supervision
- supervision of ARC-network communication
= supervision of the power supply
= cable supervision
+ Selection of local control for each generator set
= PMS control: the generator set is included in the PMS functions
= SWBD control, the generator set is excluded from all automatic functions and only is to be
controlled manually (protection functions are stil active)
+ Automatically start sequence
= programmable start prepare output
= programmable number of start attempts
= programmable pause stop during the start sequence
- programmable priming output
+ Automatically stop sequence
= programmable cooling down time
~ programmable stop time
+ GBON sequence; dynamical synchronization of the generator set to the busbar
- programmable dynamical synchronization parameters (concerning voltage and
frequency)
- supervision of positive sequential order of phase before synchronization
- supervision of generator voltage and frequency before synchronization
= programmable closing time for the breaker
+ GBOFF sequence:
~ deloading the generator set before opening the generator breaker
+ Generator set load control
load share supervision
+ Generator protection:
supervision of generator voltage and frequency
“ over-current, I> (two step protection)
overload, P> (both protection and supervision)
= reverse power, -P> (protection)
+ Busbar supervision and protection:
undervoltage, Uss< (both protection and supervision)
~ overvoltage, Us: (both protection and supervision)
under-frequency, fix (both protection and supervision)
~ over-frequency, fc> (both protaction and supervision)
+S different alarm sequences
= DG warning (only information for operator)
DG blocked (inhibit of automatic functions of the DG)
~ Safety stop (expected stop when DG has been replaced by another unit)
Trip of the generator breaker (immediately opening of CB)DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM Rot asts4101014
‘Rol: BEA Ap_bv: TW Rev. cate 031108 Reclaces:
+ Trip of two non-essential loads groups in case of:
= trip of the generator breaker
~ high load at the generator set
~ low frequency at the busbar
+ User setup of all relevant parameters of the DG and the entire plant from the control panel
+ User scalable instrument outputs from the control pane!
+ Cable supervision for digital and analogue inputs
+ Alarm test function of all implemented alarms
+ "Test mode" function for indication of any used timer when status “running” is achieved.
+ Operator programmable binary alarm input function (machine interface):
~ programmable selection of designated alarm sequence
- programmable alarm delay
programmable status for alarm detection
~ programmable connection to the alarm inhibit function
+ Relay- or Analogue output for the speed governor
+ Running hour indication on display of the Control Panel
+ Indication of rpm at the Control Panel in case of analogue running feedbackEber)
el BEA
DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM Ref.: 43134101018,
soo. by. TWS. ev, cate: 031104 enlaces
‘The following Generator set optional functions can be implemented in the present DELOMATIC system
(cartied out be each DGU):
+ Analogue alarm input (for custom use)
~ programmable selection of designated alarm sequence
~ programmable alarm delay
= programmable alarm limit
= programmable minimax scale values
= programmable low level or high level
- programmable connection to the alarm inhibit function
+ Short circuit protection of generator breaker by means of a CRM-1 module
+ Voltage regulation by the SCM-1 module
+ Differential current protection of generator set by means of a CRN diff. module
+ Additional control panels; max. 3 control panels for each DGU
+ Analogue outputs by means of an AOM-1 module:
= programmable minimax soale values
= programmable offset (0 or 20%)
‘The following Generator set special functions are implemented in the present DELOMATIC system
(carried out be each DGU):
+ no special functions in this application(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
etiBEA
INTRODUCTION TO THE PRESENT SYSTEM Ref.: 43134101014
Avo. by TW ov, date: 031104 Roclaces:_
1.3 The Control Panels
‘The front caver layout for the Contro! Panel (CP) corresponding to the Master DGU is different from the
CP for the other DGU's,
The front cover for CP's corresponding to the rest of the DGU's have an identical layout (GU no. 2 and
Lup to DGU no. n, where n is the total number of DGU's inthe system).
CONTROL PANEL cP-1
AVAILABLE POWER
2RNkKW
Front layout for the CP for the master DGU
NOTE: Notice that the text shown in the display on the figure, only are for illustrative purposes,
‘and may as such not be present in Your system (or only present on one CP),
Please refer to the following tables regarding the text of the control push buitons.DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM ret: astsaro1010
‘als BEA 00. by TS, av. dats: 031104 enlaces
The CP push buttons
The push buttons located at the top of the CP's are designated for control of the display view and
Programming of setup values.
PUSH-BUTTON DESCRIPTION
Left arrow push-button:
|Moves display view to the left”
| Moves the cursorto the left”
‘Down arrow push-button:
“u Moves display view down”
Degrades a value or toggle a selection” *]
Up arrow push-button:
Moves display view up” :
Upgrades a value or toggle a selection”
[Right arrow push-button:
a 'Moves display view to the right”
___|Moves the cursor tothe right? i
= ‘Programming function control button
‘Selection of Master CP”
1) When the programming function is in-active
2) When the programming function is active
3) Only active when a DGU have more than one corresponding CP
Each Control Panel is provided with 10 push buttons located at the bottom of the CP's which are
‘designated for alarm handling and control of the DELOMATIC system.
‘No PUSH BUTTON
«f[exf[s]ule«|s« |||» |
+ [starr] oh Acar svor | Gre | prion | ARM | Test
2 [ser] oN Acar stor | Ger | prion | Auacon| eer
aDELOMATIC - MULTI-FUNCTION SYSTEM PART 14
INTRODUCTION TO THE PRESENT SYSTEM _ Ret. 4312410101
op, by. TW Rev date 031108 Replaces:
PUSH-BUTTON
DESCRIPTION
Initiates the automatic start sequence
‘START’ (oniyactvein semi-auto mode)
F Iniates the automatic stop sequence
Peso (only active in semi-auto mode)
"GBON' __ililates the GB ON sequence
I ‘am OW (only active in semi-auto mode) —_
“eB Orr’ __Iiiiates the GB OFF sequence
(GB OFF _(eniy active in semi-auto mode)
Not used
“tet PRIOR" Moves 0G up having frst start printy
"ACK ALARM" Used for acknowledgement of alarms
r ‘The display view moves to the nex! unacknowledged
"NEXT ALARM’ — alarm’
‘The display view jumps to the top of the alarm stack”
[Lamp test ofall LED's (tus yellow)
“LAMP TEST”
1) When the display view is located in the alarm stack
2) When the display view is located outside the alarm stackDELOMATIC - MULTI-FUNCTION SYSTEM
INTRODUCTION TO THE PRESENT SYSTEM Ret
PART 1
Ral BEA
Ao.
The control panel LED's
by TW
Rev date 031104
‘The DELOMATIC control panel has altogether 16 status LED's.
Loft side LED's
The 8 LED's located in the left side are basically used for identification of the operational status of the
generator set.
LED l COLOUR DESCRIPTION
va _Reaov Greon__[ndcaon of tat the ouniay engines roady for Ha
| Green ndicates ON status of the "START" output
H2 START ————_Yollow Indicates an active "START PREPARE” output previous
|to the automatic start sequence and the START OFF
| lime during the automatic start sequence.
| Groen indication of running feedback signal rom the auxllary
H3 RUNNING > ae
| Yettow Indication of tacho failure. i
| Green| indication ofa closed gonerator breaker feedback signa
Yellow [The generator sets currently carrying out the GB ON
Ha GBON sequence.
Dark (tumed of) indication of an open generator breaker feedback signal
a ° COLING BOWN Green kaon ott he aly age unin sng
ene ae
pre) STOP Yolow sequence Se ceect
FREQUENCY Green Indicates the DGU in question is carrying out Fequency
H7 |“ conTROL Icontrol.
| Green |The DGU is selected to be under PMS control and the
i laenerator sets ready to respond to PMS commands,
PMS CONTROL Yellow Indicates the OGU is actualy selected to be under PMS
Dark (tumed off)
[control but is forced into SWBD control
[The DGU is selected to be under SWBD control.Ret BES
DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM
Aco. by: TW:
Right side LED's
43134101014
ev. date: 031108 Reolaces
‘The 8 LED's located on the right side of the control panel are, with exception of the “st START
PRIORITY" LED, used by the alarm handing function for identification of alarm status etc.
LED
ALARM MESSAGE)
SEE DISPLAY
H10| ALARM INHIBIT _
411) SHUTDOWN
412) GBTRIPPED
H13| SAFETY STOP |
1 t
H14| BASE LoaD
H15| NOT USED
1 START
PRIORITY
M16
COLOUR
Flashes red
Red
Green
Red
Red
Red
Green
Yellow
DESCRIPTION
Indication of one or more unacknowledged alarms in the
Jalarm stack.
Indication of the alarm stack only contains acknowledged|
but stil active alarm(s)
Indicates that the alarm inhibit function is active.
Indicates the shutdown alarm sequence for the
|corresponding generator set has been activated.
Indicates the trip of GB alarm sequence for the
|corresponding generator set has been activated.
Indicates the safety stop alarm sequence has been
lactivated for the generator set in question,
Indicates that asymmetrical load sharing is selected and
this DG is running base load,
[Asymmetrical load sharing is selected but itis automati-
cally cancelled due to the load situation at the busbar.
Indicates that the generator set is designated with 1st
start priority,(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
INTRODUCTION TO THE PRESENT SYSTEM __ ref: 43134101014
Bel BEA Aco. by TW: fou. dato: 031104 Reclaces:
1.4 Hardware configuration of DGU's
‘The hardware configuration of the Master DGU is different from the rest of the DGU's. This is due to the
fact that the Master DGU is handling the common functions e.g. such as conditional connection of heavy
Consumers, and therefore require additional inputs and/or outputs. In the “General Description” of part 2
an illustration of the DGU is to be found,
‘The Master DGU (size 60 TE) is configured with the following hardware modules:
1 Power Supply Module (PSM-1)
1 Control Module (CM-2 incl. comm. Port RS 485)
2 Input Module (IPM-1)
2 Output Module (OPM-1)
1 Synchronizing, Control and Measuring module (SCM-1)
wocce
DGU no. 2 (size 60 TE) is configured with the following hardware modules:
1 Power Supply Module (PSM-1)
4 Control Module (CM-2)
1 Input Module (IPM-1)
1 Output Module (OPM-1)
11 Synchronizing, Control and Measuring module (SCM-1)