DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
ALARM LIST Ref. :4319410103
Ret BEA Acp.by: TS Rev. date: 040220. Replaces:
3.0 ALARM LIST
“The alarm list contains al alarm messages (isted in numerical order) in the DELOMATIC system.
NOTE! Some ofthe alarm messages mentioned in this chapter may correspond to functions, which may not be
available in your specific DELOMATIC system.
‘The alarm Ist constitutes a very helpful and fast approach for the operator, in erder to locate a desired pleco of
information in the DELOMATIC technical documentation based on an actual alarm te
‘The alarm list contains the following information:
+ the alarm ID no.
the specific alarm text
erie description of the event(s) which activated the alarm, and the status after the alarm handling
‘which alarm sequence is dedicated to the actual alarm
wee orrve indicates in which chapter to find detailed information about any set-poins, timers and
‘drm conditions, which have influence on the generation ofthe alarm message in question.
1D no. ALARM TEXT | DESCRIPTION [ALARM SEQ. L REFERENCES
] | The control panel nas detected anothee CP ]
| yith the same LAN node ID ané the same
‘AreNeterrorno.: | group number on the ARG-network. |
(06: Dupl. 1D i System alarm 18.
|The corresponding DGU wil possible
‘continue operation. ie
ap ‘The contol panel has not received the data ae
| | transmission token on the ARC-network, |
‘AreNet error n seeun =
| os; No-Foken ‘The corresponding DGU will, if possible | |
_exntine operation bi
‘The control panel is without communication |
| | withthe corresponding DGU (with the |
| ArcNet error no: |same I no.) on the ARC-network |
42: DGU Missing \ ‘System alarm | 18.
| |-the corresponding DGU wil, if possible |
continue operation |
‘The control panel is not able to measure |
llarenet oroe no: | satisfactory activity at the ARC-network. |
|13: No Activity - | | system alarm 18.
The corresponding DGU wil if possible
| | continue operation.
T Te cota pare na rot been update by | |
Trocorespending DU (withthe same ID | |
DELOMATIC-3 |no,) since the last power up |
cp Sw1XxX | system alarm | 18
| | tre conespondng GU wii pssbie |
| |e cera | x
| | The SCM module with the VO adr. n 5
| {To.2) hes repeatedly measured an |
Sxbnormal voltage or frequency.
4.3. MEASURE ERRORN |
The DGU is forced into SWBD control and
| {is as such not included inthe automatic
DMS control.
|
Lepeceta ae(oer)
eb BE
ALARM LIST
Aoo.bv.TWS ___Rev. date: 040220
DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
Ref.:43134101030
ID no. ALARM TEXT
5.6
DESCRIPTION
CBOPOS. FAIL.
‘A conficting ON and OFF status has been
detected on the position feedback signals
from the generator breaker controlled by
the SCM-1 module in question.
The DGU is forced into SWED control and.
is as such not included in the automatic
PMS control.
‘System alarm, 18.
CBn POS. FAIL.
VO ERROR #H:#
LOW SUPPLY VOLT.
|
CP n COM. ERROR
detected at the position feedback signals
from circuit breaker no. n; controlled by a
SCM-2 module.
(CB n (n;1...2) correspond to the YO add.
of the SCM-2 module).
‘The DGU |s forced into SWBD control and.
|Is as such not included in the automatic
PMS control
‘An IO hardware configuration error has
been detected in the DGU by the system
‘supervision function.
Please refer to the description in the
technical documentation for detailed
information about the defective module
type and location. Notice that only one
failed module at the time is shown.
The DGU is forced into SWBD control and
is as such not included in the automatic
PMS control.
“The supply voltage to the OGU has con
tinuously been below 18 VDC (24 VDC -
25%).
‘The DGU is forced into SWBD control and
is as such not included in the automatic,
PMS control
‘A communication error has been detected
between control panel n (n1.3) and cor-
responding DGU.
|9) The alarm message is dsplayed at
the defective CP when the commun-
ication between CP and DGU is re-
established.
b) Ifa DGU have more than one corre-
sponding CP the alarm message is,
displayed at all other operational
CP's,
‘Aconflicting ON and OFF status has been |
‘System alarm 8.
‘System alarm 18.
System alarm 18.
‘System alarm 18.(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM
ALARM LIST
eB
po. by
av. date. 040220
PART 1
Ref.:4313410103A
Replaces
ID no.
ALARM TEXT
DESCRIPTION ALARM SEQ.
REFERENCES
2
13.49
20
26
ar
‘COM. ERROR DGU1
COM. ERROR DGU n
CABLE FAIL X:C##t
{DG TOO LOW
f-DG TOO HIGH
U-DG Too Low
UDG TOO HIGH
‘The generator voltage has continuously ex-
‘The DGU in question is unable to com-
municate with the Master DGU (no. 1),
‘The DGU is forced into SWBD control and _ System alarm
is as such not included in the automatic
PMS control
‘The Master DGU (no.1) is unable to comn-
municate with DGU no. n (072...8)
System alarm
‘The Master DGU excludes DGU no. n from
the automatic PMS control
‘The cable supervision function has detect=
‘ed a cable failure at the IPM-1 Channel no.
+t, The defective module is located at /O
‘address X in the corresponding DGU. System alarm
Notice that only one failed channel is
‘shown at the time.
[The generator equency nas contnvously
been below the programmed iit for bu
bar under frequency during idle run (GB.
open).
DG Block
‘The defective generator set will not attempt
to synchronize to the busbar
A PMS start command has been trans-
ferred to the next stand-by generator set
The generator frequency has continuously
exceeded the programmed limit for busbar
over frequency during idle run (GB open)
The defective generator set willnot attempt OG Block
to synchronize to the busbar.
‘A PMS start command has been trans-
ferred to the next stand-by generator set.
‘The generator voltage has continuously
been below the programmed limit for bus-
bar undervoltage during idle run.
‘The defective generator set will not attempt | OG Block
to synchronize to the busbar |
‘A PMS start command has been trans-
ferred to the next stand-by generator set.
‘ceeded the programmed limit for busbar
overvottage during idle run.
The defective genorator set will not attempt|_ Block
to synchronize to the busbar.
‘A PMS start command has been trans-
ferred to the next stand-by generator set.
18.
18.
18,
18.
18.
18.
18.(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
ALARM LIST Ref.:4313410103A
Bet BEA Ap. Ws Fev. date: 40220 enlaces
1Dno. | ALARM TEXT DESCRIPTION ALARM SEQ. | REFERENCES
|The auxiliary engine is not running after
‘execution of the programmed number of
start attempts,
29 | START FAILURE
Tho defective generator setwinotte | DG Block 1”
“ready for PMS start* until the alarm has
been acknowledged.
The PMS Sar command has boon rans- |
ferred to the next stand-by generator set.
The running feedback signal is missing.
(Go) |TACHOFALURE |e generate set wilcontnue roma! | OG Block 8
operation but will not be able to synchro-
nize to the busbar.
‘A negative sequential order of phases has
| been detected at the generator wth
regards to the busbar. |
31 | DGB PHASE SEQ. The defective generator set will not attempt | OS Block w.
to synchronize tothe busbar.
The PMS start command is traneforred to |
| the next stand-by generator sat | |
b i praia oper
to the busbar within the programmable
max. syn. time.
32 |DGSvNC. FAILURE | 7M2 PMS start command has been trans-
ferred to the next stand-by generator set, | OC Block
17
is automatically acknowledged in
out at the busbar.
Deu to turn the generator
breaker into ON positon.
| | NOTE! The "DG SYNC. FAILURE" alarm
33 | DGBONFAILURE |p command to open the breaker is DG Block 17,
tranemited
A PMS start command is transferred to the |
rt stand-by generator set. |
; The DGU has failed to turn the generator
breaker into OFF position.
ee
DGB OFF FAILURE busbar ands included in the load share
# tndoed depending at! sop fncton. |
‘A PMS stop command stansrited tothe
ext generator set which are to be stopped
| (ecrerdng te programmed Sarton
priory).
|The DGU has been unable to stop the
DG Block | mW,
DG Block. 1.
DG STOP FAILURE
| \The at
38
‘engine continues idle run while |(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM
ALARM LIST
aL BEA
ID no.
Ano. bys Rov. dot: 040220.
PART 1
Ret :43134101038
Reclaces:
7
39
a
| | The safety stop alarm sequence has been
| | activated on this DG.
The next stand-by generator set is started
DG SAFETY STOP —_| and connected to the busbar. When Safety stop
‘sufficient available power is measured at
the busbar the defective generator set is
disconnected and stopped (incl. cooling
| down ete.)
| | The synchronization of the generator set to
U-DIFF. MAX FAIL the busbar has failed due toa too high vol- OG Block
tage deviation.
‘ALARM TEXT DESCRIPTION ‘ALARM SEQ.
ees
13,
1”
| The max. value for overspeed detection
rogarding to the analogue input function
has been achieved meaning that the
‘generator set has been shutdown due to
aux. engine overspeed.
/OVERSPEED | ‘Shutdown
The aux. engine remains blocked for
‘automatic start until the alarm becomes in-
active,
APMS start command has been trans-
_______| mitted to the next stand-by generator set
The generator breaker nas been tripped
due to the generator current has exceeded |
the programmed limit for over current
DG OVERCURRENT continuously during the programmed delay.| Trp of GB
APMS start command has been trans-
mitted to the next stand-by generator set.
18,
42
43
oy
‘The load on the generator sethasex- |
| ceeded the programmable limit for DG high
oad continuously during the programmed ‘Warning
delay.
DG HIGH LOAD
‘The generator breaker has been tripped
due to the real power load on the generator
‘set has exceeded the programmed limit for
DG OVERLOAD ‘overload continuously during the program-
med delay Trip of GB
A PMS start command has been trans-
| |nited to the next stand-by generator set. |
‘The generator breaker has been tripped
due to the reverse power at the generator
set continuously has exceeded the prog-
DG REVERSE POWER | rammed limit for reverse power during the
programmed delay.
Trip of GB
APMS start command has been trans-
mitted to the next stand-by generator set.
18.(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
ALARM LIST Rof.:4313410103A,
Ap bi iow date: 040220 Beclaces:
‘ALARM TEXT DESCRIPTION [ALARM sea. | REFERENCES
The generator breaker has been tripped |
due to detection of a short circuit above the
45 |GBSHORTCIRGUIT _|S#!POin (external or internal detection). Tipot Ga ie,
A short circuit alarm blocks for black-out
start
‘The generator breaker has been tripped
| due to detection ofa differential current
AT DG DIFF.CURRENT _ | above the setpoint (external or internal Trip of GB 18.
detection).
The frequency at the busbar hes contin-
vuously been below the programmed limit
for underfrequency.
s0i;-| SEBO WARN. Warning 18.
This alarm is also used during supervision
| ‘of the shore supply when the shore con-
nection breaker is closed.
‘The frequency at the busbar has cont
nuously exceeded the programmed limit for
{BB HIGH WARN. lt Eeaerea
| This alarm is also used during supervision
| of the shore supply when the shore con-
nection breaker is closed.
“The busbar voltage has been continuously
below the programmed limit for busbar
undervottage.
52 |U-BBLOWWARN. Waning 7
This alarm is also used during supervision
| of the shore supply when the shore con-
nection breaker is closed.
a Waring | 18.
|The busbar voltage has been continuously
above the programmed limi for busbar
U-BBHIGHWARN, §— °”e"0"808
| ris la evo used crngsuperson
ofthe shore supply when the shore con-
nection breaker is closed.
‘The generator breaker has been tripped
f-BB TOO LOW due to the frequency at the busbar contin-
uuously has been below the programmed
Trip of GB 18.
breaker has been tripped
{BB TOO HIGH due to the frequency at the busbar has
| continuously exceeded the programmed
55
Trip of GB 18,
limit for overfrequency.
The generator breaker has been tripped
| u.BB Too Low due to the voltage the busbar continuously |
has been below the programmed limit for
undervottage.
56 Trip of GB.Dp
Bef. BEA
ALARM LIST
Aco. by: TS.
Rev date: 040220
DELOMATIC - MULTI-FUNCTION SYSTEM
PART 1
Rot :43134101030
Bovlecss
7
58
6
63
‘ALARM TEXT
DESCRIPTION
‘ALARM SEQ.
REFERENCES
U-BB TOO HIGH
P LOADSHARE FAIL
60 DG-PNEL1 TRIP
Non Essential Load group no. 2 has been
DG-P NEL 2 TRIP
DG-4NEL1 TRIP
DG-+NEL2 TRIP
‘The generator breaker has been tripped _|
due to the votage atthe busbar has contin
uously exceeded the programmed limit for
overvotiage
‘The power produced by the generator set
has continuously deviated more than the
max. acceptable limit from the power set-
point
Non Essential Load group no. 1 has been
tripped due to one of the below mentioned
cases:
a) The real power load of the generator |
set has continuously been above the |
programmed limit for trip of NEL 1
b) —Asshutdown or trip of GB alarm
sequence has disconnected the
generator set from the busbar.
‘ripped due to one of the below mentioned |
| cases:
a) The real power load of the generator
set has continuously been above the
programmed limit for trip of NEL 2,
b) —Ashutdown or trip of GB alarm
sequence has disconnected the
‘generator set from the busbar.
Non Essential Load group no. 1 has been
tripped due to the frequency at the busbar
has been continuously below the pro-
‘grammed mit for trip of NEL. 1
'Non Essential Load group no. 2 has been
tripped due to the frequency atthe busbar
has been continuously below the pro-
grammed limit for trip of NEL 2.
Trip of GB
Warning
Warning
Warning
18.
18.
18,
18.
18.
DG DELOAD FAIL.
‘The DGU has been unable to deload the
generator set below the programmed
| power limit for opening of the GB.
The generator set remains connected to
the busbar and is included in the load
| share and load dependent start / stop |
caleulation.
A PMS stop command is transmitted to the
next generator set which are to be stopped
(according the programmed star/stop
priority) |
DG Block
70
DG ALARM 1
‘The custom binary alarm input channel 1..6
has detected the programmed alarm |
*) Selected
‘alarm
18.(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1
ALARM LIST Ref.:4313410103A,
eB oo. bo dts 060229 Raclacas
‘ALARM TEXT DESCRIPTION I ALARM SEQ. | REFERENCES
The designatodiselocted alarm sequence
71 DG ALARM 2 is carried out).
The entered alarm text is displayed at the
‘corresponding CP. Please notice custom
#2y, De ALARM alarm inputs can have a customised alarm
text
73 |DGALARM4
80 | OVER SPEED Binary alarm input has detected an Over
‘Speed alarm and the genset is shutdown. | Shutdown
Binary alarm input hae detected a Low
81 LUB.OIL PRESS. —_iybrcation pressure alarm and the genset Shutdown
is shutdown
Binary alarm input has detected a High
82 | COOLWATER TEMP. | Cooling Water alarm and the genset is ‘Shutdown
| shutdown.
| Binary alarm input has detected a Low
83 |LOWWATER FLOW | water Flow alarm and the genset is ‘Shutdown,
shutdown,
Binary alarm input has detected an
84 /EXT. START FAIL extemal start fal alarm and the gensetis._ DG Block
| blocked.
Binary alarm input has detected a Low
85 | LUB.OILWARNING __lUbrication pressure waming alarm and the DG
genset is going into the pre-warning, Prowarning
sequence(DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM
PART 1
ALARM LIST. Ref.:4313410103A
Rai BEA 00. by TS, Rov. date 040720 Beolaces
ALARM TEXT. DESCRIPTION ALARM SEQ. | REFERENCES
Binary alarm input has detected a High
86 |COOLWATER WARN Cooling Water warning alarm and the
genset is going into the pre-warning
sequence.
‘The asymmetrical load share function is
automatically cancelled due to the load
1 |asym.io.sH.canc. Staton
‘The connected DGU's forced back to sym-
‘metrical load share.
The shore connection breaker is closed
‘and at the same time one or more
‘generator breakers aro closed, meaning
the DG is running in parallel with the
mains
93 | SCBPOS.ON!
No DG is running frequency control
DG
Prewarning
Warning
‘Warning
16.
20.