DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 ALARM LIST Ref. :4319410103 Ret BEA Acp.by: TS Rev. date: 040220. Replaces: 3.0 ALARM LIST “The alarm list contains al alarm messages (isted in numerical order) in the DELOMATIC system. NOTE! Some ofthe alarm messages mentioned in this chapter may correspond to functions, which may not be available in your specific DELOMATIC system. ‘The alarm Ist constitutes a very helpful and fast approach for the operator, in erder to locate a desired pleco of information in the DELOMATIC technical documentation based on an actual alarm te ‘The alarm list contains the following information: + the alarm ID no. the specific alarm text erie description of the event(s) which activated the alarm, and the status after the alarm handling ‘which alarm sequence is dedicated to the actual alarm wee orrve indicates in which chapter to find detailed information about any set-poins, timers and ‘drm conditions, which have influence on the generation ofthe alarm message in question. 1D no. ALARM TEXT | DESCRIPTION [ALARM SEQ. L REFERENCES ] | The control panel nas detected anothee CP ] | yith the same LAN node ID ané the same ‘AreNeterrorno.: | group number on the ARG-network. | (06: Dupl. 1D i System alarm 18. |The corresponding DGU wil possible ‘continue operation. ie ap ‘The contol panel has not received the data ae | | transmission token on the ARC-network, | ‘AreNet error n seeun = | os; No-Foken ‘The corresponding DGU will, if possible | | _exntine operation bi ‘The control panel is without communication | | | withthe corresponding DGU (with the | | ArcNet error no: |same I no.) on the ARC-network | 42: DGU Missing \ ‘System alarm | 18. | |-the corresponding DGU wil, if possible | continue operation | ‘The control panel is not able to measure | llarenet oroe no: | satisfactory activity at the ARC-network. | |13: No Activity - | | system alarm 18. The corresponding DGU wil if possible | | continue operation. T Te cota pare na rot been update by | | Trocorespending DU (withthe same ID | | DELOMATIC-3 |no,) since the last power up | cp Sw1XxX | system alarm | 18 | | tre conespondng GU wii pssbie | | |e cera | x | | The SCM module with the VO adr. n 5 | {To.2) hes repeatedly measured an | Sxbnormal voltage or frequency. 4.3. MEASURE ERRORN | The DGU is forced into SWBD control and | {is as such not included inthe automatic DMS control. | Lepeceta ae (oer) eb BE ALARM LIST Aoo.bv.TWS ___Rev. date: 040220 DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 Ref.:43134101030 ID no. ALARM TEXT 5.6 DESCRIPTION CBOPOS. FAIL. ‘A conficting ON and OFF status has been detected on the position feedback signals from the generator breaker controlled by the SCM-1 module in question. The DGU is forced into SWED control and. is as such not included in the automatic PMS control. ‘System alarm, 18. CBn POS. FAIL. VO ERROR #H:# LOW SUPPLY VOLT. | CP n COM. ERROR detected at the position feedback signals from circuit breaker no. n; controlled by a SCM-2 module. (CB n (n;1...2) correspond to the YO add. of the SCM-2 module). ‘The DGU |s forced into SWBD control and. |Is as such not included in the automatic PMS control ‘An IO hardware configuration error has been detected in the DGU by the system ‘supervision function. Please refer to the description in the technical documentation for detailed information about the defective module type and location. Notice that only one failed module at the time is shown. The DGU is forced into SWBD control and is as such not included in the automatic PMS control. “The supply voltage to the OGU has con tinuously been below 18 VDC (24 VDC - 25%). ‘The DGU is forced into SWBD control and is as such not included in the automatic, PMS control ‘A communication error has been detected between control panel n (n1.3) and cor- responding DGU. |9) The alarm message is dsplayed at the defective CP when the commun- ication between CP and DGU is re- established. b) Ifa DGU have more than one corre- sponding CP the alarm message is, displayed at all other operational CP's, ‘Aconflicting ON and OFF status has been | ‘System alarm 8. ‘System alarm 18. System alarm 18. ‘System alarm 18. (DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM ALARM LIST eB po. by av. date. 040220 PART 1 Ref.:4313410103A Replaces ID no. ALARM TEXT DESCRIPTION ALARM SEQ. REFERENCES 2 13.49 20 26 ar ‘COM. ERROR DGU1 COM. ERROR DGU n CABLE FAIL X:C##t {DG TOO LOW f-DG TOO HIGH U-DG Too Low UDG TOO HIGH ‘The generator voltage has continuously ex- ‘The DGU in question is unable to com- municate with the Master DGU (no. 1), ‘The DGU is forced into SWBD control and _ System alarm is as such not included in the automatic PMS control ‘The Master DGU (no.1) is unable to comn- municate with DGU no. n (072...8) System alarm ‘The Master DGU excludes DGU no. n from the automatic PMS control ‘The cable supervision function has detect= ‘ed a cable failure at the IPM-1 Channel no. +t, The defective module is located at /O ‘address X in the corresponding DGU. System alarm Notice that only one failed channel is ‘shown at the time. [The generator equency nas contnvously been below the programmed iit for bu bar under frequency during idle run (GB. open). DG Block ‘The defective generator set will not attempt to synchronize to the busbar A PMS start command has been trans- ferred to the next stand-by generator set The generator frequency has continuously exceeded the programmed limit for busbar over frequency during idle run (GB open) The defective generator set willnot attempt OG Block to synchronize to the busbar. ‘A PMS start command has been trans- ferred to the next stand-by generator set. ‘The generator voltage has continuously been below the programmed limit for bus- bar undervoltage during idle run. ‘The defective generator set will not attempt | OG Block to synchronize to the busbar | ‘A PMS start command has been trans- ferred to the next stand-by generator set. ‘ceeded the programmed limit for busbar overvottage during idle run. The defective genorator set will not attempt|_ Block to synchronize to the busbar. ‘A PMS start command has been trans- ferred to the next stand-by generator set. 18. 18. 18, 18. 18. 18. 18. (DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 ALARM LIST Ref.:4313410103A Bet BEA Ap. Ws Fev. date: 40220 enlaces 1Dno. | ALARM TEXT DESCRIPTION ALARM SEQ. | REFERENCES |The auxiliary engine is not running after ‘execution of the programmed number of start attempts, 29 | START FAILURE Tho defective generator setwinotte | DG Block 1” “ready for PMS start* until the alarm has been acknowledged. The PMS Sar command has boon rans- | ferred to the next stand-by generator set. The running feedback signal is missing. (Go) |TACHOFALURE |e generate set wilcontnue roma! | OG Block 8 operation but will not be able to synchro- nize to the busbar. ‘A negative sequential order of phases has | been detected at the generator wth regards to the busbar. | 31 | DGB PHASE SEQ. The defective generator set will not attempt | OS Block w. to synchronize tothe busbar. The PMS start command is traneforred to | | the next stand-by generator sat | | b i praia oper to the busbar within the programmable max. syn. time. 32 |DGSvNC. FAILURE | 7M2 PMS start command has been trans- ferred to the next stand-by generator set, | OC Block 17 is automatically acknowledged in out at the busbar. Deu to turn the generator breaker into ON positon. | | NOTE! The "DG SYNC. FAILURE" alarm 33 | DGBONFAILURE |p command to open the breaker is DG Block 17, tranemited A PMS start command is transferred to the | rt stand-by generator set. | ; The DGU has failed to turn the generator breaker into OFF position. ee DGB OFF FAILURE busbar ands included in the load share # tndoed depending at! sop fncton. | ‘A PMS stop command stansrited tothe ext generator set which are to be stopped | (ecrerdng te programmed Sarton priory). |The DGU has been unable to stop the DG Block | mW, DG Block. 1. DG STOP FAILURE | \The at 38 ‘engine continues idle run while | (DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM ALARM LIST aL BEA ID no. Ano. bys Rov. dot: 040220. PART 1 Ret :43134101038 Reclaces: 7 39 a | | The safety stop alarm sequence has been | | activated on this DG. The next stand-by generator set is started DG SAFETY STOP —_| and connected to the busbar. When Safety stop ‘sufficient available power is measured at the busbar the defective generator set is disconnected and stopped (incl. cooling | down ete.) | | The synchronization of the generator set to U-DIFF. MAX FAIL the busbar has failed due toa too high vol- OG Block tage deviation. ‘ALARM TEXT DESCRIPTION ‘ALARM SEQ. ees 13, 1” | The max. value for overspeed detection rogarding to the analogue input function has been achieved meaning that the ‘generator set has been shutdown due to aux. engine overspeed. /OVERSPEED | ‘Shutdown The aux. engine remains blocked for ‘automatic start until the alarm becomes in- active, APMS start command has been trans- _______| mitted to the next stand-by generator set The generator breaker nas been tripped due to the generator current has exceeded | the programmed limit for over current DG OVERCURRENT continuously during the programmed delay.| Trp of GB APMS start command has been trans- mitted to the next stand-by generator set. 18, 42 43 oy ‘The load on the generator sethasex- | | ceeded the programmable limit for DG high oad continuously during the programmed ‘Warning delay. DG HIGH LOAD ‘The generator breaker has been tripped due to the real power load on the generator ‘set has exceeded the programmed limit for DG OVERLOAD ‘overload continuously during the program- med delay Trip of GB A PMS start command has been trans- | |nited to the next stand-by generator set. | ‘The generator breaker has been tripped due to the reverse power at the generator set continuously has exceeded the prog- DG REVERSE POWER | rammed limit for reverse power during the programmed delay. Trip of GB APMS start command has been trans- mitted to the next stand-by generator set. 18. (DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 ALARM LIST Rof.:4313410103A, Ap bi iow date: 040220 Beclaces: ‘ALARM TEXT DESCRIPTION [ALARM sea. | REFERENCES The generator breaker has been tripped | due to detection of a short circuit above the 45 |GBSHORTCIRGUIT _|S#!POin (external or internal detection). Tipot Ga ie, A short circuit alarm blocks for black-out start ‘The generator breaker has been tripped | due to detection ofa differential current AT DG DIFF.CURRENT _ | above the setpoint (external or internal Trip of GB 18. detection). The frequency at the busbar hes contin- vuously been below the programmed limit for underfrequency. s0i;-| SEBO WARN. Warning 18. This alarm is also used during supervision | ‘of the shore supply when the shore con- nection breaker is closed. ‘The frequency at the busbar has cont nuously exceeded the programmed limit for {BB HIGH WARN. lt Eeaerea | This alarm is also used during supervision | of the shore supply when the shore con- nection breaker is closed. “The busbar voltage has been continuously below the programmed limit for busbar undervottage. 52 |U-BBLOWWARN. Waning 7 This alarm is also used during supervision | of the shore supply when the shore con- nection breaker is closed. a Waring | 18. |The busbar voltage has been continuously above the programmed limi for busbar U-BBHIGHWARN, §— °”e"0"808 | ris la evo used crngsuperson ofthe shore supply when the shore con- nection breaker is closed. ‘The generator breaker has been tripped f-BB TOO LOW due to the frequency at the busbar contin- uuously has been below the programmed Trip of GB 18. breaker has been tripped {BB TOO HIGH due to the frequency at the busbar has | continuously exceeded the programmed 55 Trip of GB 18, limit for overfrequency. The generator breaker has been tripped | u.BB Too Low due to the voltage the busbar continuously | has been below the programmed limit for undervottage. 56 Trip of GB. Dp Bef. BEA ALARM LIST Aco. by: TS. Rev date: 040220 DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 Rot :43134101030 Bovlecss 7 58 6 63 ‘ALARM TEXT DESCRIPTION ‘ALARM SEQ. REFERENCES U-BB TOO HIGH P LOADSHARE FAIL 60 DG-PNEL1 TRIP Non Essential Load group no. 2 has been DG-P NEL 2 TRIP DG-4NEL1 TRIP DG-+NEL2 TRIP ‘The generator breaker has been tripped _| due to the votage atthe busbar has contin uously exceeded the programmed limit for overvotiage ‘The power produced by the generator set has continuously deviated more than the max. acceptable limit from the power set- point Non Essential Load group no. 1 has been tripped due to one of the below mentioned cases: a) The real power load of the generator | set has continuously been above the | programmed limit for trip of NEL 1 b) —Asshutdown or trip of GB alarm sequence has disconnected the generator set from the busbar. ‘ripped due to one of the below mentioned | | cases: a) The real power load of the generator set has continuously been above the programmed limit for trip of NEL 2, b) —Ashutdown or trip of GB alarm sequence has disconnected the ‘generator set from the busbar. Non Essential Load group no. 1 has been tripped due to the frequency at the busbar has been continuously below the pro- ‘grammed mit for trip of NEL. 1 'Non Essential Load group no. 2 has been tripped due to the frequency atthe busbar has been continuously below the pro- grammed limit for trip of NEL 2. Trip of GB Warning Warning Warning 18. 18. 18, 18. 18. DG DELOAD FAIL. ‘The DGU has been unable to deload the generator set below the programmed | power limit for opening of the GB. The generator set remains connected to the busbar and is included in the load | share and load dependent start / stop | caleulation. A PMS stop command is transmitted to the next generator set which are to be stopped (according the programmed star/stop priority) | DG Block 70 DG ALARM 1 ‘The custom binary alarm input channel 1..6 has detected the programmed alarm | *) Selected ‘alarm 18. (DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 ALARM LIST Ref.:4313410103A, eB oo. bo dts 060229 Raclacas ‘ALARM TEXT DESCRIPTION I ALARM SEQ. | REFERENCES The designatodiselocted alarm sequence 71 DG ALARM 2 is carried out). The entered alarm text is displayed at the ‘corresponding CP. Please notice custom #2y, De ALARM alarm inputs can have a customised alarm text 73 |DGALARM4 80 | OVER SPEED Binary alarm input has detected an Over ‘Speed alarm and the genset is shutdown. | Shutdown Binary alarm input hae detected a Low 81 LUB.OIL PRESS. —_iybrcation pressure alarm and the genset Shutdown is shutdown Binary alarm input has detected a High 82 | COOLWATER TEMP. | Cooling Water alarm and the genset is ‘Shutdown | shutdown. | Binary alarm input has detected a Low 83 |LOWWATER FLOW | water Flow alarm and the genset is ‘Shutdown, shutdown, Binary alarm input has detected an 84 /EXT. START FAIL extemal start fal alarm and the gensetis._ DG Block | blocked. Binary alarm input has detected a Low 85 | LUB.OILWARNING __lUbrication pressure waming alarm and the DG genset is going into the pre-warning, Prowarning sequence (DEIF) DELOMATIC - MULTI-FUNCTION SYSTEM PART 1 ALARM LIST. Ref.:4313410103A Rai BEA 00. by TS, Rov. date 040720 Beolaces ALARM TEXT. DESCRIPTION ALARM SEQ. | REFERENCES Binary alarm input has detected a High 86 |COOLWATER WARN Cooling Water warning alarm and the genset is going into the pre-warning sequence. ‘The asymmetrical load share function is automatically cancelled due to the load 1 |asym.io.sH.canc. Staton ‘The connected DGU's forced back to sym- ‘metrical load share. The shore connection breaker is closed ‘and at the same time one or more ‘generator breakers aro closed, meaning the DG is running in parallel with the mains 93 | SCBPOS.ON! No DG is running frequency control DG Prewarning Warning ‘Warning 16. 20.

You might also like