You are on page 1of 71

CUSTOMER : ARMAK TAPE CORPORATION

P.O REF NO. : 20-000409

PROJECT NAME : Electrical Preventive Maintenance

DOC. NO. : n/a

Thermographic Inspection for


Semi-Annual Electrical
Preventive Maintenance
(Post Survey - Free of Charge)

TITLE Thermographic Inspection for Semi-Annual Electrical Preventive


Maintenance (Post Survey - Free of Charge)
PROJECT
Electrical Preventive Maintenance

DOC NO.
N/A
PRD DATE SHT NO.
JPA 25-Jun-21 i
CH DATE
APC 25-Jun-21 CONTD
0 25-Jun-21 FIRST ISSUE JPA APC APP DATE 1
REV DATE COMMENTS RVD BY CKD BY - -

Page 1 of 71
Inspection Data
POST THERMOGRAPHIC INSPECTION OF ELECTRICAL PANELS AND ASSOCIATED COMPONENTS FOR THE PURPOSE
Reason for Survey OF ON-GOING RISK MANAGEMENT BEFORE THE SCHEDULED ELECTRICAL MAINTENANCE.
THERMAL SCANNING INSPECTION OF ELECTRICAL PANELS IN ORDER TO UNCOVER ANOMALOUS COMPONENT
Purpose of Survey TEMPERATURES AND TO OFFER ROOT CAUSE AND REMEDIAL SUGGESTIONS

Inspection Commencing N/A

Camera FLUKE Ti350

Software FLUKE SOFTWARE VIEW 4.3

Thermographer Certification Level I Thermographer

Inspector Joahnber Aguirre

Pre Survey Date 24-Nov-20

Post Survey Date 6-Jan-21

Post Survey Date 25-Jun-21

Problem Classification (Temperature Difference)


NORMAL MINOR IMPORTANT SERIOUS CRITICAL

0.0°C (Same as 
0.0‐7.0°C 8.0‐15.0°C 16.0‐32.0°C 33.0°C +
Ambient)

Overall Recommendation
ALL MCB WITH TWO SEPARATE CABLES MUST USED A DOUBLE MECHANICAL LUG TO SECURE TERMINATION.

ALL UNDERATED CIRCUIT BREAKER MUST BE REPLACED BY A HIGHER RATING.

COMPLETE ALL MISSING SCREWS.

CLOSELY MONITOR ALL PANEL WITH HIGH HOT SPOT. 

CONDUCT BOTH PREVENTIVE MAINTENANCE AND THERMAL IMAGE SURVEY AFTER 6 MONTHS.

Page 2 of 71
ELECTRICAL PANEL LIST
 OLD CODE NEW PANEL CODE PANEL NAME LOCATION
BUILDING 1
MDP‐2‐B12F ARMAK‐EPMP‐B12F‐20171011‐01 MAIN DISTRIBUTION PANEL 2 BLDG 1, 2ND FLOOR ‐ PILLOW PACK
MDP‐3‐B12F ARMAK‐EPMP‐B12F‐20171207‐02 MAIN DISTRIBUTION PANEL 3 BLDG 1, 2ND FLOOR ‐ PILLOW PACK
DP‐1‐B11F ARMAK‐EPDP‐B11F‐20171011‐01 DISTRIBUTION PANEL 1 BLDG 1, 1ST FLOOR ‐ ELEVATOR
DP‐2‐B11F ARMAK‐EPDP‐B11F‐20171011‐02 DISTRIBUTION PANEL 2 BLDG 1, 1ST FLOOR ‐ FULLY AUTO
DP‐3‐B12F ARMAK‐EPDP‐B12F‐20171011‐03 DISTRIBUTION PANEL 3 BLDG 1, 2ND FLOOR ‐ ELEVATOR
DP‐4‐B12F ARMAK‐EPDP‐B12F‐20171011‐04 DISTRIBUTION PANEL 4 BLDG 1, 2ND FLOOR ‐ EMERGENCY EXIT
PB‐2‐B12F ARMAK‐EPMP‐B1QC‐20180309‐07 PANEL BOARD 2 BLDG 1, 2ND FLOOR ‐ QCQA
PB‐1‐B12F ARMAK‐EPDP‐B1AD‐20060801‐13 PANEL BOARD 1 BLDG 1, 2ND FLOOR ‐ QCQA
PB‐3‐B12F ARMAK‐EPDP‐B1QC‐20060801‐12 PANEL BOARD 3 BLDG 1, 2ND FLOOR ‐ QCQA
PB‐1‐B12F ARMAK‐EPDP‐B1QC‐20060801‐11 PANEL BOARD 1 BLDG 1, 1ST FLOOR ‐ ADMIN
BLDG‐1‐GF‐LP‐1 ARMAK‐EPLP‐B11F‐20180716‐01 LIGHTING PANEL 1 BLDG 1, 1ST FLOOR ‐ ADMIN
BLDG‐1‐GF‐LP‐2 ARMAK‐EPLP‐B11F‐20180716‐02 LIGHTING PANEL 2 BLDG 1, 1ST FLOOR ‐ FULLY AUTO
BLDG‐1‐2F‐LP‐2 ARMAK‐EPLP‐B12F‐20180716‐03 LIGHTING PANEL 2 BLDG 1, 2ND FLOOR ‐ PILLOW PACK
BLDG‐1‐2F‐LP‐1 ARMAK‐EPLP‐B12F‐20180716‐04 LIGHTING PANEL 1 BLDG 1, 2ND FLOOR ‐ ELECTRICAL
GF‐DP ARMAK‐EPFP‐B11F‐20180716‐01 FACILITIES PANEL BLDG 1, 1ST FLOOR ‐ FULLY AUTO
MTS 500A ARMAK‐EPFP‐B11F‐20120515‐02 AIR COMPRESSOR BLDG 1, 1ST FLOOR ‐ LOCKER AREA
75 HP ARMAK‐EPFP‐B11F‐20120515‐03 AIR COMPRESSOR BLDG 1, 1ST FLOOR ‐ LOCKER AREA
100 HP ARMAK‐EPFP‐B11F‐20120515‐04 AIR COMPRESSOR BLDG 1, 1ST FLOOR ‐ LOCKER AREA

BUILDING 2
MDP‐1‐B22F ARMAK‐EPMP‐B22F‐20171011‐03 MAIN DISTRIBUTION PANEL 1 BLDG 2, 2ND FLOOR ‐ PILLOW PACK
MDP‐3‐B22F ARMAK‐EPMP‐B22F‐20190328‐04 MAIN DISTRIBUTION PANEL 3 BLDG 2, 2ND FLOOR ‐ PILLOW PACK
DP‐5‐B22F ARMAK‐EPDP‐B22F‐20171011‐05 DISTRIBUTION PANEL 5 BLDG 2, 2ND FLOOR ‐ CORE CUTTER
DP‐6‐B22F ARMAK‐EPDP‐B22F‐20171011‐06 DISTRIBUTION PANEL 6 BLDG 2, 2ND FLOOR ‐ PILLOW PACK
LP‐1 ARMAK‐EPLP‐B22F‐20180716‐05 LIGHTING PANEL 1 BLDG 2, 2ND FLOOR ‐ PILLOW PACK
BLDG‐2‐GF‐LP ARMAK‐EPLP‐B21F‐20190328‐06 LIGHTING PANEL B2GF BLDG 2, 1ST FLOOR
BLDG‐2‐3F‐LP‐1 ARMAK‐EPLP‐B23F‐20190328‐07 LIGHTING PANEL 1 BLDG 2, 3RD FLOOR
FAC‐1 ARMAK‐EPFP‐B21F‐20190328‐06 FACILITIES PANEL BLDG. 2, 2ND FLOOR ‐ PILLOW PACK
BLDG‐2‐FAC ARMAK‐EPFP‐B22F‐20190328‐05 FACILITIES PANEL BLDG. 2, 1ST FLOOR
FAC‐3 ARMAK‐EPFP‐B21F‐20200724‐07 FACILITIES PANEL BLDG. 2, 1ST FLOOR ‐ FIRE PUMP

BUILDING 3
MFG‐3‐B32F ARMAK‐EPMP‐B32F‐20190328‐05 MAIN DISTRIBUTION PANEL B3 BLDG 3, 2ND FLOOR ‐ PACKAGING
DP‐1‐B32F ARMAK‐EPDP‐B32F‐20180831‐07 DISTRIBUTION PANEL 1 BLDG 3, 2ND FLOOR ‐ PACKAGING
DP‐2‐B32F ARMAK‐EPDP‐B31F‐20180426‐04 DISTRIBUTION PANEL 2 BLDG 3, 2ND FLOOR ‐ PACKAGING
PB‐B22F ARMAK‐EPFP‐B32F‐20180207‐08 PANEL BOX ‐ COMPRESSOR BLDG 3, 2ND FLOOR ‐ COMPRESSOR
PB‐1‐B33F ARMAK‐EPDP‐B33F‐20180720‐14 PANEL BOX ‐ 3RD FLOOR BLDG 3, 3RD FLOOR
PB‐1‐B31F ARMAK‐EPMP‐B31F‐20180426‐06 PANEL BOARD 1 ‐ CORE MAKER BLDG 3, 1ST FLOOR
DP‐2‐B31F ARMAK‐EPDP‐B32F‐20190328‐08 DISTRIBUTION PANEL 2 ‐ PAPER CORE BLDG 3, 1ST FLOOR ‐ CORE MAKER 1
DP‐3‐B31F ARMAK‐EPDP‐B31F‐20181106‐10 DISTRIBUTION PANEL 3 BLDG 3, 1ST FLOOR ‐ CORE MAKER 2
ETP‐B31F ARMAK‐EPFP‐B31F‐20160223‐09 ELECTRICAL PANEL ‐ B3 FACILITIES BLDG 3, 1ST FLOOR ‐ FORKLIFT AREA
DP‐B31F ARMAK‐EPFP‐B31F‐20160223‐10 DISTRIBUTION PANEL ‐ B3 FACILITIES BLDG 3, 1ST FLOOR ‐ FORKLIFT AREA
DP‐M‐B31F ARMAK‐EPFP‐B31F‐20160223‐11 DISTRIBUTION PANEL ‐ B3 FORKLIFT BLDG 3, 1ST FLOOR ‐ FORKLIFT AREA
LP‐B31F ARMAK‐EPLP‐B31F‐20150831‐08 LIGHTING PANEL ‐ B3 BLDG 3, 1ST FLOOR ‐ FORKLIFT AREA
MTS ARMAK‐EPFP‐B31F‐20160223‐12 MANUAL TRANSFER BLDG 3, 1ST FLOOR ‐ FORKLIFT AREA
ECB 300 ARMAK‐EPFP‐B31F‐20160223‐13 ‐ BLDG 3, 1ST FLOOR
LP‐B32F ARMAK‐EPLP‐B32F‐20150831‐09 LIGHTING PANEL BLDG 3, 2ND FLOOR
LP‐B33F ARMAK‐EPLP‐B33F‐20150831‐10 LIGHTING PANEL BLDG 3, 3RD FLOOR
LP‐B34F ARMAK‐EPLP‐B34F‐20150831‐11 LIGHTING PANEL BLDG 3, 4TH FLOOR
LP‐B35F ARMAK‐EPLP‐B35F‐20150831‐12 LIGHTING PANEL BLDG 3, 5TH FLOOR

Page 3 of 71
BUILDING 1

Page 4 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-Annual
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Electrical Preventive Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088,, 09178865414

Maintenance
LOCATION: BLDG. 1,2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 600 Amp
TAG NAME: MAIN DISTRIBUTION PANEL 2 FROM: SG2‐800A
CODE: ARMAK‐EPMP‐B12F‐20171011‐01 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MDP‐2‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00002.IS2 FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME:  IR_00001.JPG FILE NAME:  IR_00221.IS2

HI Temp. Range Temp. Range Background Emissivity Distance DATE


36.3°C 31.8°C to 36.3°C 22.0°C 0.95 1.43m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

ACTUAL PHOTO AND IDENTIFICATION PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020)

FILE NAME:  IR_00001.JPG FILE NAME: 

Page 5 of 71
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020)

FILE NAME:  IR_00001.JPG FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


35.9°C 31.2°C to 35.9°C 22.0°C 0.95 1.43m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Findings
NO SIGNIFICANT CHANGES ON ITS THERMAL SIGNATURE. CONNECTIONS WERE LOOSE, AT LEAST 3 TURNS WAS MADE FOR EACH 
TERMINALS. RETIGHTEN AND CLEAN TERMINALS AND CALBES. 

Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
ALL MCB & MCCB WITH TWO SEPARATE CABLES MUST USE A DOUBLE MECHANICAL LUG TO SECURE TERMINATION.

Page 6 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.

Inspection for Semi-Annual


Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Electrical Preventive Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Maintenance
LOCATION: BLDG. 1, 2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 600 Amp
TAG NAME: MAIN DISTRIBUTION PANEL 3 FROM: SG‐3‐600A
CODE: ARMAK‐EPMP‐B12F‐20171207‐02 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MDP‐3‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021)

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.6°C 31.4°C to 34.6°C 22.0°C 0.95 1.06m 12-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 7 of 71
Findings
 LOOSE CONNECTION WAS FOUND, CHECK , CLEAN TERMINALS AND RETIGHTEN .

RECOMMENDATION
REPEAT THE PERIODIC INSPECTION PROGRAM.
RECHECK THE LOAD OF EACH CB.

Page 8 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 1st FLOOR, ELEVATOR MAIN BREAKER RATING: 3 Phase, 350 Amp
TAG NAME: DISTRIBUTION PANEL 1 FROM: MDP‐3‐B12F
CODE: ARMAK‐EPDP‐B11F‐20171011‐01 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐1‐B11F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 26, 2021) POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

Remarks Recommendation
SIGNIFICANT CHANGES ON ITS THERMAL SIGNATURE PROVIDE AUXILARY CONNECTION TO SEPARATE 2 
DIFFERENT CABLE SIZE IN MCB TERMINATION ,  THEN WE 
TEMPERATURE HOT SPOT DECREASE ABOUT 10.0°C, BUT  CAN PERFORM AGAIN ANOTHER SCAN IF NO 
STILL NEED SOME RECTIFICATION. TERMINALS WERE FOUND  IMPROVEMENT WE CAN PROCEED  IN MCB REPLACEMENT 
WITH LOOSE SCREW. USED DOUBLE MECHANICAL LUG TO  AND LOAD RATING RE COMPUTATION.
SECURE TERMINATION.

HI Temp. Range Temp. Range Background Emissivity Distance DATE


80.9°C 371.°C to 80.9°C 22.0°C 0.95 1.42 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 9 of 71
INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00062.IS2 FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

Remarks Recommendation
Terminals was found with loose screw. Continue the Preriodic Thermal Inspection Program.

HI Temp. Range Temp. Range Background Emissivity Distance DATE


43.2°C 31.7°C to 43.2°C 22.0°C 0.95 1.42 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 10 of 71
INSPECTION ITEM #3
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00066.IS2 FILE NAME: 

POST‐THERMAL IMAGE SURVEY  (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY  (JUNE 25, 2021)

FILE NAME:  IR_00066.IS2 FILE NAME: 

Remarks Recommendation
No significant changes on its thermal signature Replace by a higher rated Mini‐Circuit Breaker.

Terminals was found with loose screw.

HI Temp. Range Temp. Range Background Emissivity Distance DATE


39.4°C 30.7°C to 39.4°C 22.0°C 0.95 1.42 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 11 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 1st FLOOR, FULLY AUTO MAIN BREAKER RATING: 3 Phase, 350 Amp
TAG NAME: DISTRIBUTION PANEL 2 FROM: MDP‐3‐B12F
CODE: ARMAK‐EPDP‐B11F‐20171011‐02 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐2‐B11F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

Remarks Recommendation
INCREASING TEMPERATURE. TERMINALS WERE FOUND WITH  PROVIDE AUXILARY CONNECTION TO SEPARATE 2 
LOOSE SCREW. DIFFERENT CABLE SIZE IN MCB TERMINATION ,  THEN WE 
TWO CABLES ARE IN A SINGLE MECHANICAL LUG. USED  CAN PERFORM AGAIN ANOTHER SCAN IF NO 
DOUBLE MECHANICAL LUG TO SECURE TERMINATION. IMPROVEMENT WE CAN PROCEED  IN MCB REPLACEMENT 
RETIGHTEN THE MECHANICAL TERMINAL LUG AND LOAD RATING RE COMPUTATION
HI Temp. Range Temp. Range Background Emissivity Distance DATE
48.0°C 31.1°C to 48.0°C 22.0°C 0.95 1.42 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 12 of 71
INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

Remarks Recommendation
SIGNIFICANT DECREASE ON ONE OF THE HOT SPOT.  REPLACE BY A HIGHER RATED MINI‐CIRCUIT BREAKER.
RETIGHTEN THE MECHANICAL TERMINAL LUG

HI Temp. Range Temp. Range Background Emissivity Distance DATE


46.6°C 30.7°C to 46.6°C 22.0°C 0.95 1.10 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

INSPECTION ITEM #3
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

Page 13 of 71
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

Remarks Recommendation
SIGNIFICANT DECREASE ON THE HOT SPOT. RETIGHTEN THE 
Continue the Preriodic Thermal Inspection Program.
MECHANICAL TERMINAL LUG. TERMINALS WERE FOUND 
WITH LOOSE SCREW.

HI Temp. Range Temp. Range Background Emissivity Distance DATE


39.4°C 30.7°C to 39.4°C 22.0°C 0.95 1.10 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: TEMPERATURE HOT SPOT INCREASES AGAIN.
INSPECTION ITEM#2: NO SIGNIFICANT CHANGES. CB UNDERRATED.
INSPECTION ITEM#3: NO MORE HOT SPOT AFTER PM.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
RECHECK THE LOAD OF EACH CB.

Page 14 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 2nd Floor, ELEVATOR MAIN BREAKER RATING: 3 Phase, 400 Amp
TAG NAME: DISTRIBUTION PANEL 3 FROM: MDP‐2‐B12F
CODE: ARMAK‐EPDP‐B12F‐20171011‐03 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐3‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00022.JPG FILE NAME: 

Remarks Recommendation
SIGNIFICANT DECREASE ON HOT SPOT TEMPERATURE.  Continue the Preriodic Thermal Inspection Program.
TERMINALS WERE FOUND WITH LOOSE SCREW.
RETIGHTEN THE MECHANICAL TERMINAL LUG

HI Temp. Range Temp. Range Background Emissivity Distance DATE


43.6°C 31.7°C to 43.6°C 22.0°C 0.95 0.48m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 15 of 71
INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 12, 2021)

FILE NAME:  FILE NAME: 

Remarks Recommendation
ALMOST SAME TEMPERATURE WAS FOUND ON HOT SPOT  CHECK THE LOAD. REPLACE THE CIRCCUIT BREAKER 
TEMPERATURE. TERMINALS WERE FOUND WITH LOOSE  .Continue the Preriodic Thermal Inspection Program.
RETIGHTEN THE MECHANICAL TERMINAL LUG

HI Temp. Range Temp. Range Background Emissivity Distance DATE


56.2°C 32.9°C to 56.2°C 22.0°C 0.95 1.08 m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

INSPECTION ITEM #3
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

Page 16 of 71
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00024.JPG FILE NAME:  IR_00041.IS2

Remarks Recommendation
ALMOST SAME TEMPERATURE WAS FOUND ON HOT SPOT  CHECK THE LOAD. REPLACE THE CIRCCUIT BREAKER 
TEMPERATURE. TERMINALS WERE FOUND WITH LOOSE  .CONTINUE THE PRERIODIC THERMAL INSPECTION 
RETIGHTEN THE MECHANICAL TERMINAL LUG PROGRAM. REPLACE A HIGHER RATED MINI‐CIRCUIT 
BREAKER. AND LOAD RATING RE COMPUTATION.

HI Temp. Range Temp. Range Background Emissivity Distance DATE


56.3°C 32.4°C to 56.3°C 22.0°C 0.95 1.08m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL
INSPECTION ITEM#2: Replace by a higher rated Mini‐Circuit Breaker.
INSPECTION ITEM#3: Replace by a higher rated Mini‐Circuit Breaker.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
RECHECK THE LOAD OF EACH CB.

Page 17 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.

Inspection for Semi-


Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 2nd Floor, EMERGENCY EXIT MAIN BREAKER RATING: 3 Phase, 400 Amp
TAG NAME: DISTRIBUTION PANEL 4 FROM: MDP‐2‐B12F
CODE: ARMAK‐EPDP‐B12F‐20171011‐04 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐4‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.6°C 31.4°C to 34°C 22.0°C 0.95 0.48m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 18 of 71
INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.6°C 31.4°C to 34°C 22.0°C 0.95 0.48m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

Page 19 of 71
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


32.9°C 29.5°C to 32.9°C 22.0°C 0.95 1.42m 25-Jun-21

Problem Classification NORMAL MINOR INTERMEDIATE SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN
INSPECTION ITEM#2: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN
INSPECTION ITEM#3: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 20 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 2ND FLOOR ‐ QCQA MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: PANEL BOARD 2 FROM: ‐
CODE: ARMAK‐EPMP‐B1QC‐20180309‐07 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB‐2‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00059.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


32.0°C 28.3°C to 32.0°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 21 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 2ND FLOOR ‐ QCQA MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: PANEL BOARD 1 FROM: ‐
CODE: ARMAK‐EPDP‐B1AD‐20060801‐13 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB‐1‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


39.3°C 28.1°C to 39.3°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 22 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 2ND FLOOR ‐ QCQA MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: PANEL BOARD 3 FROM: ‐
CODE: ARMAK‐EPDP‐B1QC‐20060801‐12 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB‐3‐B12F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2020)

FILE NAME:  IR_00059.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


31.6°C 27.8°C to 31.6°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 23 of 71
INSPECTION ITEM #2
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00059.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


39.3°C 28.1°C to 39.3°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 24 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 1ST FLOOR ‐ ADMIN MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: PANEL BOARD 1 FROM: ‐
CODE: ARMAK‐EPDP‐B1QC‐20060801‐11 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB‐1‐B11F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2020)

FILE NAME:  IR_00059.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.7°C 29.9°C to 34.7°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 25 of 71
INSPECTION ITEM #2
POST‐THERMAL IMAGE SURVEY (JAN 6, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.9°C 29.5°C to 33.9°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 26 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 1ST FLOOR, ADMIN MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: LIGHTING PANEL 1 FROM: ‐
CODE: ARMAK‐EPLP‐B11F‐20180716‐01 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.1‐GF‐LP 1 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00059.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.7°C 29.8°C to 33.7°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 27 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 1ST FLOOR, FULLY AUTO MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: LIGHTING PANEL 2 FROM: ‐
CODE: ARMAK‐EPLP‐B11F‐20180716‐02 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.1‐GF‐LP 2 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.9°C 30.2°C to 34.9°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 28 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.

Inspection for Semi-


Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: LIGHTING PANEL 2 FROM: ‐
CODE: ARMAK‐EPLP‐B12F‐20180716‐03 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.1‐2F‐LP 2 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

30.1°C 29.1°C to 32.1°C 22.0°C 0.95 1.14m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION.  RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 29 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: LIGHTING PANEL 1 FROM: ‐
CODE: ARMAK‐EPLP‐B12F‐20180716‐04 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.1‐2F‐LP 1 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.3°C 31.3°C to 34.3°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION. RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 30 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG. 1, 1ST FLOOR, FULLY AUTO MAIN BREAKER RATING: 3 Phase, 160Amp
TAG NAME: FACILITIES PANEL FROM: MDP 3
CODE: ARMAK‐EPFP‐B11F‐20180716‐01 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: GF DP REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00055.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.5°C 31.5°C to 34.5°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION. RETIGHNTEN

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 31 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 1ST FLOOR ‐ LOCKER AREA MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: AIR COMPRESSOR FROM: ‐
CODE: ARMAK‐EPFP‐B11F‐20120515‐02 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MTS 500A REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00055.jpg FILE NAME:  IR_00078.IS2

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  IR_00055.jpg

HI Temp. Range Temp. Range Background Emissivity Distance DATE


54.5°C 30.2°C to 54.5°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: HIGH TEMPERATURE CAUSE BY HIGH CURRENT, FOUND SLIGHTLY LOOSE TERMINAL SCREW 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 32 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 1ST FLOOR ‐ LOCKER AREA MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: AIR COMPRESSOR FROM: ‐
CODE: ARMAK‐EPFP‐B11F‐20120515‐03 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: 75 HP REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


55.3°C 30.9°C to 55.3°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: HIGH TEMPERATURE CAUSE BY HIGH CURRENT, FOUND SLIGHTLY LOOSE TERMINAL SCREW 
CONNECTION. RETIGHNTEN. THIS REPORT WILL BE USED AS THE BASIS FOR THE NEXT INSPECTION. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 33 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, , 09178865414

Preventive Maintenance
LOCATION: BLDG 1, 1ST FLOOR ‐ LOCKER AREA MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: AIR COMPRESSOR FROM: ‐
CODE: ARMAK‐EPFP‐B11F‐20120515‐04 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: 100 HP REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


31.9°C 28.2°C to 31.9°C 22.0°C 0.95 1.21m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: HIGH TEMPERATURE CAUSE BY HIGH CURRENT, FOUND SLIGHTLY LOOSE TERMINAL SCREW CONNECTION. 
RETIGHNTEN. THIS REPORT WILL BE USED AS THE BASIS FOR THE NEXT INSPECTION. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 34 of 71
BUILDING 2

Page 35 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 600 Amp
TAG NAME: MAIN DISTRIBUTION PANEL 1 FROM: ‐
CODE: ARMAK‐EPMP‐B22F‐20171011‐03 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MDP‐1‐B22F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf
INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


36.2°C 30.2°C to 36.2°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, MINOR HOT SPOTS TEMPERATURE WERE REMOVE AFTER PM.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 36 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 350 Amp
TAG NAME: MAIN DISTRIBUTION PANEL 3 FROM: ‐
CODE: ARMAK‐EPMP‐B22F‐20190328‐04 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MDP‐3‐B22F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.2°C 30.5°C to 34.2°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: STILL MINOR HOT SPOTS TEMPERATURE FOUND. MINI‐CIRCUIT BREAKER UNDERRATED.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 37 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.

Inspection for Semi-


Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 2nd Floor, CORE CUTTER MAIN BREAKER RATING: 3 Phase, 350 Amp
TAG NAME: DISTRIBUTION PANEL 5 FROM: MDP‐1‐B22F
CODE: ARMAK‐EPDP‐B22F‐20171011‐05 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐5‐B22F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.5°C 30.2°C to 33.5°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 38 of 71
INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.2°C 29.8°C to 34.2°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

INSPECTION ITEM #3
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

Page 39 of 71
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.2°C 30.7°C to 33.4°C 22.0°C 0.95 1.37m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 40 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 2ND FLOOR ‐ PILLOW PACK MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: LIGHTING PANEL 1 FROM: ‐
CODE: ARMAK‐EPLP‐B22F‐20180716‐05 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: LP‐1 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


31.3°C 28.3°C to 31.3°C 22.0°C 0.95 1.41m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 41 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 2nd Floor, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 350 Amp
TAG NAME: DISTRIBUTION PANEL 6 FROM: MDP‐1‐B22F
CODE: ARMAK‐EPDP‐B22F‐20171011‐06 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐6‐B22F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.1°C 29.1°C to 33.1°C 22.0°C 0.95 2.63m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 42 of 71
INSPECTION ITEM #2
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.1°C 29.1°C to 33.1°C 22.0°C 0.95 2.63m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

INSPECTION ITEM #3
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

Page 43 of 71
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.1°C 29.1°C to 33.1°C 22.0°C 0.95 2.63m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: SOME MACHINES WERE NOT ENERGIZE DURING THE SURVEY. THIS PANEL HAS NO CRITICAL 
                                           SPOT ON ITS PRE‐THERMAL SCANNING SURVEY. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 44 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 
09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 1ST FLOOR MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: LIGHTING PANEL B2GF FROM: ‐
CODE: ARMAK‐EPLP‐B21F‐20190328‐06 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.2‐GF‐LP REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.1°C 30.1°C to 33.1°C 22.0°C 0.95 1.30m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 45 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 3RD FLOOR MAIN BREAKER RATING: 3 Phase, 75Amp
TAG NAME: LIGHTING PANEL FROM: ‐
CODE: ARMAK‐EPLP‐B23F‐20190328‐07 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.2 3F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
PRE‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00097.JPG FILE NAME:  IR_00121.IS2

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


37.9°C 28.0°C to 38.2°C 22.0°C 0.95 1.17m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 46 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 2ND FLOOR, PILLOW PACK MAIN BREAKER RATING: 3 Phase, 75 Amp
TAG NAME: FACILITIES PANEL FROM: ‐
CODE: ARMAK‐EPFP‐B21F‐20190328‐06 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: FAC 1 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


31.3°C 30.5°C to 33.7°C 22.0°C 0.95 1.41m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 47 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 
09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 1ST FLOOR MAIN BREAKER RATING: 3 Phase, 200 Amp
TAG NAME: FACILITIES PANEL FROM: ‐
CODE: ARMAK‐EPFP‐B22F‐20190328‐05 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: BLDG.2‐GF‐FAC REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


32.7°C 29.9°C to 42.3°C 22.0°C 0.95 0.33m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: POSSIBLE UNDERATED CIRCUIT BREAKER DUE TO HIGH LOAD OR SMALL SIZE CABLE.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
CHECK LOADING, REPLACE BY HIGHIER CIRCUIT BREAKER, CHANGE AND INCREASE THE CABLE SIZE.

Page 48 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 2, 1ST FLOOR, FIRE PUMP MAIN BREAKER RATING: 3 Phase, 60Amp
TAG NAME: FACILITIES PANEL FROM: BLDG.2 FAC
CODE: ARMAK‐EPFP‐B21F‐20200724‐07 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: FAC 3 REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


29.3°C 26.3°C to 29.3°C 22.0°C 0.95 0.94m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 49 of 71
BUILDING 3

Page 50 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 2ND FLOOR, PACKAGIN MAIN BREAKER RATING: 3 Phase, 400 Amp
TAG NAME: MAIN DISTRIBUTION PANEL B3 FROM: SG‐5‐600A
CODE: ARMAK‐EPMP‐B32F‐20190328‐05 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MFG‐E‐B32F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


32.6°C 30.4°C to 33.4°C 22.0°C 0.95 1.50m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Page 51 of 71
INSPECTION ITEM #2
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.2°C 30.5°C to 33.2°C 22.0°C 0.95 1.50m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEMS: NORMAL, WITH NEGLIGIBLE HIGH SPOT CLOSE TO AMBIENT TEPERATURE.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 52 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 2ND FLOOR, PACKAGING MAIN BREAKER RATING: 3 Phase, 100 Amp
TAG NAME: DISTRIBUTION PANEL 1 FROM: ‐
CODE: ARMAK‐EPDP‐B32F‐20180831‐07 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐1‐B32F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00110.JPG FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.3°C 30.2°C to 33.1°C 22.0°C 0.95 1.05m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 53 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 2ND FLOOR, PACKAGING MAIN BREAKER RATING: 3 Phase, 160 Amp
TAG NAME: DISTRIBUTION PANEL 2 FROM: ‐
CODE: ARMAK‐EPDP‐B31F‐20180426‐04 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐2‐B32F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


39.3°C 30.1°C to 39.3°C 22.0°C 0.95 0.45m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: DENERGIZED PANEL DURING THERMAL IMAGE SURVEY. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 54 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG 3, 2ND FLOOR ‐ COMPRESSOR MAIN BREAKER RATING: 3 Phase, 500Amp
TAG NAME: PANEL BOX ‐ COMPRESSOR FROM: ‐
CODE: ARMAK‐EPFP‐B32F‐20180207‐08 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB‐B32F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (DEC, 2020) POST‐THERMAL IMAGE SURVEY (JAN 6, 2021)

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

Page 55 of 71
HI Temp. Range Temp. Range Background Emissivity Distance DATE
31.1°C 31.8°C to 37.1°C 22.0°C 0.95 1.24m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: TEMPERATURE INCREASE COMPARE TO POST‐THERMAL SURVEY. POSSIBLE INCREASE OF LOAD.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
CONTINUE TO MONITOR THIS PANEL , Check actual load and its MCB rating 

Page 56 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 3RD FLOOR SPARE MAIN BREAKER RATING: 3 Phase, 250Amp
TAG NAME: PANEL BOX 3RD FLOOR FROM: ‐
CODE: ARMAK‐EPDP‐B33F‐20180720‐14 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB1‐B33F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 12, 2021)

DENERGIZED

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: DENERGIZED PANEL DURING THERMAL IMAGE SURVEY. 

Other Recommendation

Page 57 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR MAIN BREAKER RATING: 3 Phase, 250Amp
TAG NAME: PANEL BOARD 1 ‐ CORE MAKER FROM: DP‐5‐B22F
CODE: ARMAK‐EPMP‐B31F‐20180426‐06 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: PB1‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

Page 58 of 71
HI Temp. Range Temp. Range Background Emissivity Distance DATE
45.3°C 30.5°C to 45.3°C 22.0°C 0.95 1.66m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEMS: 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
CONTINUE TO MONITOR THIS PANEL , Check actual load and its MCB rating 

Page 59 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR, CORE MAKER 1 MAIN BREAKER RATING: 3 Phase, 160Amp
TAG NAME: DISTRIBUTION  PANEL 2, PANEL CORE FROM: PB1‐B31F
CODE: ARMAK‐EPMP‐B31F‐20180426‐06 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP2‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


32.6°C 29.8°C to 32.6°C 22.0°C 0.95 1.17m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 60 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR, CORE MAKER 2 MAIN BREAKER RATING: 3 Phase, 250Amp
TAG NAME: DISTRIBUTION  PANEL 3 FROM: PB1‐B31F
CODE: ARMAK‐EPDP‐B31F‐20181106‐10 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP3‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


33.6°C 29.8°C to 33.6°C 22.0°C 0.95 0.94m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEMS: NORMAL, WITH NEGLIGIBLE HIGH SPOT CLOSE TO AMBIENT TEPERATURE.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 61 of 71
POST-Thermographic APC INDUSTRIAL SERVICES, OPC.
Inspection for Semi-
Unit 2D Tower B Suntrust Adriatico Garden M. 
Adriatico St.., Brgy 720 Zone 78 Malate Manila 
Philippines
Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐
6325050, 09062510088, 09178865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR ‐ FORKLIFT AREA MAIN BREAKER RATING: 3 Phase, 160Amp
TAG NAME: ELECTRICAL PANEL B3 FACILITIES FROM: ‐
CODE: ARMAK‐EPFP‐B31F‐20160223‐09 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: ETP‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

DENERGIZED

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: DENERGIZED PANEL DURING THERMAL IMAGE SURVEY. 

Other Recommendation

Page 62 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR ‐ FORKLIFT AREA MAIN BREAKER RATING: 3 Phase, 160Amp
TAG NAME: DISTRIBUTION PANEL B3 FORKLIFT FROM: ‐
CODE: ARMAK‐EPFP‐B31F‐20160223‐10 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


58.2°C 29.8°C to 58.2°C 22.0°C 0.95 0.38-2.02m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: HOT SPOT FROM PREVIOUS INSPECTION NOT FOUND POSSBILE IT IS ALREADY RECTIFIED.
NEW HOT SPOT FOUND. POSSIBLE UNDERRATED CB.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
RECHECK THE LOAD OF THIS CIRCUIT BREAKER.
PROVIDE SEPARATE AUXILARY CONNECTION TO SEPARATE 2 CABLES IN SINGLE TERMINATION , Re check load computation

Page 63 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR ‐ FORKLIFT AREA MAIN BREAKER RATING: 3 Phase, 175Amp
TAG NAME: DISTRIBUTION PANEL B3 FORKLIFT FROM: ETP‐B31F
CODE: ARMAK‐EPFP‐B31F‐20160223‐11 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: DP‐M‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.2°C 29.8°C to 34.2°C 22.0°C 0.95 1.41m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 64 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR ‐ FORKLIFT AREA MAIN BREAKER RATING: 3 Phase, 75Amp
TAG NAME: LIGHTING PANEL ‐ B3 FROM: ETP‐B31F
CODE: ARMAK‐EPLP‐B31F‐20150831‐08 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: LP‐B31F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


36.2°C 30.2°C to 36.2°C 22.0°C 0.95 1.20m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: SIGNIFICANT CHANGE WAS FOUND AFTER PM. TEMPERATURE IS NOW CLOSE TO AMBIENT.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
CONTINUE TO MONITOR.

Page 65 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR ‐ FORKLIFT AREA MAIN BREAKER RATING: 3 Phase, 300Amp
TAG NAME: MANUAL TRANSFER FROM: ‐
CODE: ARMAK‐EPFP‐B31F‐20160223‐12 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: MTS REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  IR_00135.JPG FILE NAME:  IR_00166.IS2

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


34.2°C 29.8°C to 34.2°C 22.0°C 0.95 1.65m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 66 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 1ST FLOOR ‐ FORKLIFT AREA MAIN BREAKER RATING: 3 Phase, 300Amp
TAG NAME: DISTRIBUTION PANEL B3 FACILITIES FROM: ETP‐B31F
CODE: ARMAK‐EPFP‐B31F‐20160223‐13 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: ECB (DP‐M‐B31F) REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


35.0°C 30.0°C to 35.0°C 22.0°C 0.95 1.17m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: NORMAL, L1 AND L2 ARE USED FOR 1 PHASE SUPPLY.

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.

Page 67 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 2ND FLOOR MAIN BREAKER RATING:
TAG NAME: LIGHTING PANEL FROM:
CODE: ARMAK‐EPLP‐B32F‐20150831‐09 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: LP‐B32F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (DEC 26, 2020) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


58.7°C 31.3°C to 58.7°C 22.0°C 0.95 0.44-1.10m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: THE MCB WITH HOT SPOT. OLD CB WERE USED. POSSBILE LOADING ISSUE.
NO PRE‐THERMAL SURVEY. HOT SPOT TEMPERATURE DECREASES. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
RECOMMEND TO REPALCE WHOLE PANEL NEW CB  SET.

Page 68 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 3RD FLOOR MAIN BREAKER RATING:
TAG NAME: LIGHTING PANEL FROM:
CODE: ARMAK‐EPLP‐B33F‐20150831‐10 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: LP‐B33F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


37.3°C 30.8°C to 37.3°C 22.0°C 0.95 0.42-1.11m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: THE MCB WITH HOT SPOT. OLD CB WERE USED. POSSBILE LOADING ISSUE.
NO PRE‐THERMAL SURVEY.  SLIGHTLT DECREASE THE HOT SPOT TEMPERATURE

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
CONSIDER TO REPLACE THE WHOLE PANEL WITH THE NEW CB.

Page 69 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 4TH FLOOR MAIN BREAKER RATING:
TAG NAME: LIGHTING PANEL FROM:
CODE: ARMAK‐EPLP‐B34F‐20150831‐11 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: LP‐B34F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


47.4°C 31.°7 to 47.4°C 22.0°C 0.95 0.47-93m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: THE MCB WITH HOT SPOT. OLD CB WERE USED. POSSBILE LOADING ISSUE.
NO PRE‐THERMAL SURVEY. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
CONSIDER TO REPLACE THE WHOLE PANEL WITH THE NEW CB.

Page 70 of 71
APC INDUSTRIAL SERVICES, OPC.
POST-Thermographic Unit 2D Tower B Suntrust Adriatico Garden M. 

Inspection for Semi- Adriatico St.., Brgy 720 Zone 78 Malate Manila 


Philippines

Annual Electrical Telephone No.: 632‐79141257, Mobile No.: 0917‐


6325050, 0906‐2510088, 0917‐8865414

Preventive Maintenance
LOCATION: BLDG. 3, 5TH FLOOR MAIN BREAKER RATING:
TAG NAME: LIGHTING PANEL FROM:
CODE: ARMAK‐EPLP‐B35F‐20150831‐12 REF. PRE‐SURVEY : Pre‐Survey Electrical PM 112420.pdf
OLD CODE: LP‐B35F REF. PM REPORTS : Post‐Survey Electrical PM 010621.pdf

INSPECTION ITEM #1
POST‐THERMAL IMAGE SURVEY (JAN 6, 2021) ACTUAL PHOTO AND IDENTIFICATION

FILE NAME:  FILE NAME: 

POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021) POST‐THERMAL IMAGE SURVEY (JUNE 25, 2021)

FILE NAME:  FILE NAME: 

HI Temp. Range Temp. Range Background Emissivity Distance DATE


39.3°C 30.7°C to 39.3°C 22.0°C 0.95 0.47-93m 25-Jun-21

Problem Classification NORMAL MINOR IMPORTANT SERIOUS CRITICAL NOTE: See page 2

Overall Findings
INSPECTION ITEM#1: THE MCB WITH HOT SPOT. OLD CB WERE USED. POSSBILE LOADING ISSUE. TWO CABLE ARE 
TERMATED TO THIS CB. NO PRE‐THERMAL SURVEY. 

Other Recommendation
REPEAT THE PERIODIC INSPECTION PROGRAM.
STRONGLY RECOMMEND TO UPGRADE OLD PANEL AND RE WIRE ALL LOAD TO ENSURE SAFE OPERATION .

Page 71 of 71