You are on page 1of 5

ANSWER / SOLUTION

The answer / solution to the problem / question documented in this article.

ASP WARNINGS

1 Bulk configuration install failed. Configuration installation failed when the user try to save configuration.
Should use the latest FM, where encrypted config file is sent

2 Config corrupted and settings in SF loaded. Config in dataflash corrupted and config loaded from serial flash.

3 Config corrupted and defaults loaded Config in dataflash corrupted

4 PID Lamp Failed to Switch ON PID sensor is faulty

5 Pump failure 1. 4R+ sensor not installed properly and leaks will be there
2. Filter is not present at the inlet

6 Toxic 1 Sensor reflex test is failed CO sensor contact issue or sensor failure

7 Toxic 2 Sensor reflex test is failed H2S sensor contact issue or sensor failure

8 Toxic 1 channel digital pot failure CO digipot write failed

9 Toxic 2 channel digital pot failure H2S digipot write failed

10 Stuck at fault for sensor1 O2 sensor contact issue or sensor damaged

11 Stuck at fault for sensor2 CO sensor contact issue or sensor damaged

12 Stuck at fault for sensor3 H2S sensor contact issue or sensor damaged

13 Stuck at fault for sensor4 LEL sensor contact issue or sensor damaged

14 Stuck at fault for sensor5 RAE sensor contact issue or sensor damaged

15 LEL protection activated 1. LEL flood test


2. LEL gas reading > 100%LEL
3. O2 readings < 5%vol

16 O2 warmup failed. Sensor contact issue or sensor failure

17 AS1 Signal Failed Sensor conact issue

18 Rae Eeprom Checksum Failed RAE EEPROM corrupted.

19 CSTACK crossed 87 percentage Stack exeeded 87%

20 CSTACK crossed 75 percentage Stack exeeded 75%


23 Battery EEPROM corrupted Battery EEPROM data not written properly

24 Rae Eeprom Wrong part number Bad sensor. Should replace the sensor

25 Invalid RTC Power failure to RTC. Should set the time again

ASP - ERRORS

26 Error was caused by a fatal assertion Many failures. Need to read ASP devicelog for routecasuse

27 Watchdog is reset Software bug : watchdog reset

28 Failed Clock initialization Crystal Issue

29 Watchdog is reset LVD reset

30 Failed bootloading Not Used

31 sensor make exceeded max configured Invalid sensor Make is set.

32 Sensor configuration not valid Baseline and Sensitivity might be not in limits

33 Communication b/w ASP & ICM failure Software bug

34 Failed RAM integrity test RAM test failed

35 Failed ROM integrity test ROM test failed

36 External ADC Failure 1. Connection issue. Can restart and test

37 RL78 ADC failure Internal ADC failure

38 All sensors stuck at fault and not running If all sensors failed with stuck at fault

39 Task Monitoring Test failed Software bug

40 Data flash Test failed 24 hr test : configuration file in data flash is corrupted

41 I2C Error RAE sensor not installed

42 Supply voltage test failed Controller supply voltage failure. Controller supply should be with in 1.6
to 3.6 V

43 Serial flash test failed Configuration file in serial flash is corrupted

ICM - WARNINGS

129 ICAP: max file size error Wrong configuration file

130 ICAP: File Corrupt Wrong configuration file


131 ICAP: File Open Failed Wrong configuration file

132 ICAP: Max chunk size for comm Wrong configuration file

133 ICAP: File CRC failure Wrong configuration file

134 ICAP: write to flash failure Dataflash hardware failure

135 ICAP: read from flash failure Dataflash hardware failure

136 ICAP: Command time out FW issue

137 ICAP: user config file transfer abort FW issue

138 ICAP: factory config file transfer abort FW issue

139 ICAP: user config file install fail FW issue

140 ICAP: factory config file install fail Configuration file corrupted

141 SELF_TEST: Event log CRC Failure Serial flash Memory corruption

142 SELF_TEST: Bump log CRC Failure Serial flash Memory corruption

143 BLE: Flash Init Failure BLE module connection issue or wrong firmware loaded

144 BLE: Rx Over run error BLE FW error

145 BLE: UART Not ready BLE FW error

146 BLE: UART No Data BLE FW error

147 NFC: Tap NA

148 NFC: Config Install Failure NA

149 NFC: Tag Read Failure NA

150 IR: Rx Over run error Wrong data from Fleet manager

151 IR: UART Not Ready Wrong data from Fleet manager

152 IR: UART No Data Wrong data from Fleet manager

153 statck overflow Firmware error

154 DBG: UART Not Ready Firmware error

155 DBG: UART No Data Firmware error

156 No valid sensor installed on device Sensors not installed. Configuration issue
157 FW image CRC fail Wrong Firmware file received

158 ASP FW image bank earse failure Firmware update error

159 ASP FW file transfer failure Firmware update error

160 ASP FW upgrade failure Firmware update error

161 FW upgrade failure Firmware update error

162 - NFC: NA
165

166 FLASH erase failure: Dataflash hardware failure

167 DBG: Debug port Rx over run error FW issue

ICM - ERRORS

180 Assert Failure FW issue

181 Version Mis Match FW issue

182 critical low battery Low battery

183 overflow fault handling queue memory overflow

184 Version Mis Match Wrong Firmware file received

185 Junk data received on IPC RX always FW error

186 Unknown command error Wrong command sent

187 No response from ASP Communication error from ASP

188 No broadcast data received from ASP Communication error from ASP

189 ROM test failure memory corruption

190 RAM test failure memory corruption

191 Start up issue FW error

192 DBG task did not respond to prod signal Operating system failure

193 ICM task did not respond to prod signal Operating system failure

194 LOG task did not respond to prod signal Operating system failure
195 BLE task did not respond to prod signal Operating system failure

196 IR task did not respond to prod signal Operating system failure

197 IPC task did not respond to prod signal Operating system failure

198 SEH task did not respond to prod signal Operating system failure

199 WDT task did not respond to prod signal Operating system failure