INDEX
Overview 2-5
Product Data 6 - 26
Wiring Diagrams 27 - 29
Characteristic Curves 30 - 33
Dimensions 34 - 52
Standards & Approvals
Third party certificates (ERDA / CPRI) available for CO range of changeover switches
NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005
Standard. Accredited laboratories have the responsibility of satisfying the criteria of
laboratory accreditation at all times, which are verified during Surveillance and
Reassessment visits by NABL. Further the accredited laboratories should prove their
technical competence by satisfactory participation in recognized Proficiency Testing
Programmes.
The CO range of Changeover switches are tested in E&A’s NABL accredited Switchgear
Testing Lab.
Marking
A CE marking is a European marking of conformity that indicates a product complies
with the essential requirements of the applicable European laws or directives with
respect to safety, health and environment and consumer protection. Generally, this
conformity to the applicable directives is done through self-declaration and is required
on products in the countries of the European Economic Area (EEA) to facilitate trade
among the member countries. The manufacturer or their authorized representative
established in the EEA is responsible for affixing the CE marking to their product. The
CE marking provides a means for a manufacturer to demonstrate that a product
complies with a common set of laws required by all countries in the EEA to allow free
movement of trade within the EEA countries.
E&A’s CO range of Changeover switches conform to the Low voltage directive 73/23/EEC
as amended by directive 93/68/EEC, provided it is used in the application for which it is
made and is installed and maintained in accordance with professional practices with
relevant installation standards and operating instructions.
RoHS Compliance
As a green initiatives, L&T Electrical & Automation (E&A) understands the requirements
of the RoHS directive. The directive restricts the use of hazardous substances in electrical
and electronic equipment and bans electrical equipment containing more than
permitted levels of lead, cadmium, mercury, hexavalent chromium, polybrominated
biphenyl (PBS) and polybrominated diphenyl ether (PBDE) flame retardants.
1
Overview
Basic Function
¾ 03
Superior
¾ Performance 04
Product
¾ Range 05
Changeover Switches
L&T Electrical & Automation (E&A) offers you a unique series of Changeover Switches combining
compactness with high performance & customer convenience, thus, making it a state-of-the-art
product in changeover technology.
The CO range covers ratings from 63 A to 2000 A in 6 frame sizes. These changeover switches are
available in open execution, Sheet steel enclosure, fused version (suitable for DIN type fuse - link),
motorised version & Enclosed ATS version.
Onload Changeover S-D consists of two separate sets of terminals for incoming supplies and a set of
output terminals to connect the common load. Thus, changeover switch ensures continuity of supply to
the load by alternating between normal and alternate supply.
3
Superior Performance
Higher Contact system is of double break, knife type having self wiping action
short-time with electrodynamic compensation. This ensures reliable performance
during normal as well as short circuit fault conditions, offering higher
withstand
short-time withstand rating.
Capacity
Total Factory fitted external shorting links can be easily removed and fitted
on the other side as required at site (125 A to 2000 A). This gives more
flexibility of flexibility at the time of installation. For Frame 1(63A, 100A & 125A),
connection CAT no.s for top and bottom shorting links are available.
Maximum
termination Changeover Switch provides generous terminal capacity in its compact
capacity size, facilitating aluminium termination.
Higher Higher ground clearance between terminals and mounting base plate
ground ensures adequate clearance even after connecting cables. This
clearance eliminates the possibility of phase to ground flash over.
Total
safety Changeover Switch provides complete safety by providing terminal
shrouds, source separator and inter-phase barriers.
4
Product Range
Onload Changeover S-Ds are available from 63 A to 2000 A. The range is covered through 6 frames as
shown below.
IV 400 630
5
Product Data
Manual
¾ Changeover Product Feature 07
Technical
¾ Specifications of
Manual Changeover 11
Motorised
¾ Changeover Product Features 13
Universal
¾ Mounting for
Manual Changeover Range 15
Automatic
¾ Source Transfer Solution 16
ASTS
¾ with AST Controller 17
ASTS
¾ with AuXC 2000 Controller 19
Technical
¾ Specifications of
Motorised Kit 21
Enclosed
¾ ATS 23
Ordering
¾ Information 26
Manual Changeover Product Feature
2 6 4
8
7
9
5
7
1. Mechanism
A single, compact and modular mechanism cassette
operates two Switch-Disconnectors and provides
mechanical interlocking between them.
The use of patented, self interlocked and dual dead center
mechanism in CO range provides higher reliability for
changeover function.
2. Terminal shroud
These shrouds provide complete touch proof design and
prevent accidental touching of live terminals. They are
click fit type. Due to hinge type terminal shrouds, it can be
turned by 90 degree, hence terminals can be inspected
without removing these shrouds.
3. Source separator
Source separator is used to isolate two incoming
supplies and to eliminate possibility of flash over
between two supplies due to accidental falling of
external objects.
7
Manual Changeover Product Feature
4. Inter-phase barriers
Inter-phase barriers are provided for additional
safety to eliminate possibility of inter-phase short-
circuit.
N
O
5. Positive ON / OFF indication of S-Ds
The Changeover S-D indicates true position of contacts.
6. Staggered terminals
The Changeover S-Ds are designed to have staggered
terminal arrangement for top and bottom S-Ds. It
provides clear access to all terminals from the front,
ensuring ease of termination.
All terminal joints can be easily inspected without the
need of removing termination of top S-D.
8
Manual Changeover Product Feature
8. Handle
The Changeover Switch has a unique flip-able operating handle for ratings 250 Amp and
above which enables user to operate the switch with two hands. The handle also offers the
following features:
• Provision for Padlocking in OFF position with three Padlocks of Ø5 to Ø7
• Defeat feature in both ON states and auto restoration of panel door
• IP54 with extended type operating handle
Two hand type flip-able handle One hand type handle Changeover unit
250 A & above rating upto 200 A rating padlockable in OFF state by 3 pad locks
9
Manual Changeover Product Feature
+ =
10
Technical Specifications of Manual Changeover
Frame 1 Frame 2
11
Frame 3 Frame 4 Frame 5 Frame 6
200 A$ 250 A 315 A 400 A 630 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A
IS / IEC 60947-3, EN 60947-3
CO2-200 CO3-250 CO3-315 CO4-400 CO4-630 CO5-630 CO5-800 CO5-1000 CO6-1250 CO6-1600 CO6-2000
4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole
415 415 415 415 415 415 415 415 415 415 415
50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
$
12 12 12 12 12 12 12 12 12 12 12
3 3 3 3 3 3 3 3 3 3 3
200 250 315 400 630 630 800 1000 1250 1600 2000
200 250 315 400 630 630 800 1000 1250 1600 2000
1600 /1250 2000#/1250
#
200 250 315 400 630 630 800 1000 1250
85 132 160 225 315 315 400 450 710 710 710
1600 2000 2520 3200 5040 5040 6400 8000 10000 10000 10000
2000 2500 3150 4000 6300 6300 8000 10000 12500 12500 12500
8 16 18 22 26 35 50 50 50 50 50
18 28 28 35 35 70 85 85 85 85 85
14 32 36 46 55 73.5 105 105 105 105 105
16000 16000 16000 10000 10000 10000 10000 10000 10000 10000 10000
2000 2000 2000 2000 2000 2000 1000 1000 1000 1000 500
1 1 2 3 3
NA NA NA NA NA NA
100 100 100 100 100
12
Motorised Changeover Product Features
4 1
3
7
6
5 2
1. Compact design
No change in H x W x D of motorised changeover
switch and manual changeover switch.
3. Manual override
Manual operation of motorised changeover switch is also
feasible through the manual override feature.
As a safety feature, the control supply of motorised kit (EOM)
is automatically cut off during the insertion of handle.
13
Motorised Changeover Product Features
5. Auxiliary contacts
It consists of two sets of changeover contacts one for each
S-D. It is prewired and prefitted in motorised changeover
switch.
6. Pad locking
Provision for padlocking in OFF position with three
padlocks of Ø5 to Ø7. Padlocking is possible in both auto
and manual mode.
7. Fuse protection
Inbuilt glass fuse of 5 x 20 size protects the motorised
kit (EOM) during abnormalities. Also, spare fuse holder
has been provided for storage of fuse.
14
Universal Mounting for Manual Changeover Range
ON
N
O
ON
ON
ON
N
O
2
ON
ON
ON
N
O
3
ON
ON
ON
N
O
4
ON
ON
15
Automatic Source Transfer System
16
ASTS with AST Controller
Motorised Changeover
AST Controller
No connection
Line2
Nb
L3b
L2b Line1 1. Control supply terminal block
L1b
Na
L3a
L2a Source I & II sensing inputs are to be connected
L1a
E(Earth) for continuous monitoring by AST controller.
C1
NO
1
2. Auxiliary contact Set connection NC
1
C2
Two sets of pre-wired changeover auxiliary NO
2
NC
contacts one for each S-D. Same is used for power 2
ON-1
OFF
ON-II 3. Main terminal connection
E
N
Control inputs to motorised changeover
P
through AST controller
17
SELECTOR SWITCH
OFF
(Electrical Operation
disabled)
O
1 2
AUTO MANUAL
(Control through (Control through
Supply Monitor) Push buttons)
AST CONTROLLER
ON ON
UV UV
OV
BLINK:ASY
ON:REV
SOURCE - I SOURCE - II
(PRIORITY) (BACK-UP)
ON - I OFF ON - II
User Interface
Auto Mode
In auto mode Source-I (priority source) is continuously monitored, in case of Source-I failure
AST controller checks for Source-II (back-up source ). If it is available then AST controller gives
command to motorised changeover to shift on Source-II.
18
ASTS with AuXC 2000 Controller
Motorised Changeover
Modes of Operation:
OFF Mode:
In this mode, the automatic control is disabled and the controller does not take any action. All views of the
measures and the status of the LEDs remain active.
To access the programming/settings menu, it is mandatory to operate in OFF mode.
Pressing the OFF-RESET button resets the retentive alarms, provided the conditions that generated the
alarm have been removed.
Manual Mode:
In this mode, the MCO can be manually controlled by the pressing the MAN key.
Closing/opening operation can be achieved by :
- Selecting the switch position
- Pressing the p
and q
buttons, for a minimum time of 300ms,to confirm the closing or opening operation
The generators can also be controlled manually by moving on the page start/stop groups.
Line 2 selected
Breaker 1 selected
Function selectable Selectable function
Page scroll locked with MAN
with MAN
Page scroll locked
19
AuxC-2000 Controller
Selects the
OFF operating
mode
Selects the
automatic Select the manual
mode. Green operating mode
AUT LED lights
▲ and ▼ keys - Used to scroll through the display pages or to select the list of options
in a menu. Simultaneously pressing ▼ + calls▲ up the Main menu with rotating icons
Front LED
Line 1 voltage status Line 2 voltage status
LED (green) - LED (green) -
indicates that the line indicates that the line
voltage source 1 is within voltage source 2 is within
the programmed limits the programmed limits.
Auto Mode:
The AUT mode is indicated by the green LED for AUT. In automatic mode, the controller automatically
gives command for opening & closing of the MCO. When the priority line voltage is out of bounds for a
time longer than that specified(line presence green LED turns off), the unit disconnects the load from the
priority line and connects it to secondary line considering start-up of generator(if programmed) and
interlock time delay. When the priority line returns within the programmed limits, the controller will
switch back the load on it.
The cycles of automatic operation vary according to the type of application (utility-utility, utility-
generator, generator-generator).
20
Technical Specifications of Motorised Kit
Frame 2
Depth (mm) 94
21
Frame 3 Frame 4 Frame 5 Frame 6
250 & 315 400 & 630 630 to 1000 1250 to 2000
IS/IEC 60947-3, IEC 60947- 3, EN60947-3
50 50 50 50
3 3 3 3
-5 to + 55 -5 to + 55 -5 to + 55 -5 to + 55
2 2 2 2
2 2 2 2
84 84 84 108
94 94 94 118
22
Enclosed Automatic Transfer Switch
Rapid industrialization and urbanization are leading to ever-rising demand for reliable
electricity.
Technological advancement and changing lifestyles have given rise to many applications
which demand 24 X7 uninterruptible power supply. In some industries, power outages
for even short duration may lead to considerable commercial losses.
E&A’s Enclosed Automatic Transfer Switch(ATS) constantly monitors the incoming power
sources and seamlessly switches the load to the ‘back-up’ supply when it senses
variation or abnormality in the main supply. Once main supply is restored, the load is
automatically shifted to the main supply.
Option of priority source selection and swapping gives additional flexibility to suit
different site requirements.
These switches are very convenient to use as one does not have to manually operate the
switch.
The typical applications are in critical processes in various industries and also in growing
residential, commercial & infrastructure segments.
23
Enclosed Automatic Transfer Switch
Range:
125A to 630A,
415V AC
Flexibility
• Priority Source Selection
• Adjustable Time Delay (0.1 sec to 3 hours)
• Suitable for 3-Phase as well as 1-Phase Sources
Performance
• Double-Break Contact System offering High
Short-time withstand (ICW)
• High Mechanical & Electrical Life: Double than
requirement of IS/IEC Standard
• Suitable for Aluminium Termination
Safety
• Protections : UV/OV, Phase Sequence, Single
Phasing, Frequency
• Authorized Access Control through Password
Protection
• Inbuilt Terminal Shrouds, Phase Barriers &
Source Separator
Convenience
• Ample Space for Cable Termination,
No need of Separate Cable Gland Box
• Ease of Generator Control
(ON-OFF Cooling Cycle, Self-Test)
• Cyclic Event Logger : Logs 100 Events
24
Enclosed Automatic Transfer Switch
Phase Sequence Control M02>>P02.05 OFF Select Nominal Voltage M02>>P02.01 400 50-5000 V AC
Undervoltage setting for Line 1 M06>>P06.01 85% L-L
Select Voltage Control Mode M02>>P02.07 L-L L-N
Overvoltage setting for Line 1 M06>>P06.04 110% L-L+L-N
Undervoltage setting for Line 2 M07>>P07.01 85% -1- Line 1
Select Priority Line M05>>P05.02 -1-
Overvoltage setting for Line 2 M07>>P07.04 110% -2- Line 2
Note : Refer AuXC2000- Automatic Transfer Controller Manual for further details and complete settings/programming parameters
25
Ordering Information
CO10630OOOO
63 A CO10630OSOO CX10630OOCO –
CO10630OOOD*
CO11000OOOO
I 100 A CO11000OSOO – – –
CO11000OOOD*
26
+ _ _
Wiring Diagrams
Motorised
¾ Changeover Switch 28
Motorised
¾ Changeover Switch Control
through Supply Monitor - MG73BH 28
Motorised
¾ Changeover Switch Control
through AuXC-2000 29
Wiring Diagrams
Neutral
Push to Push to Push to
ON OFF ON
Source I both Source II
Source
Auxiliary Contact
Power Supply Opening All
Source I Power
Closing 1 Closing 2
Contacts
Spare
Control
Glass
Fuse
5x20 mm
Q2
Source II Power
Motorised
changeover switch
Contacts
DG SUPPLY EB SUPPLY
N2 B2 Y2 R2 N1 B1 Y1 R1
18 16 15
NO NC C
MD21DF
INCOMING
SUPPLY
MONITOR
L3 L2 L1
18 16 15 28 26 25 18 16 15 28 26 25
NO NC C NO NC C NO NC C NO NC C
EB SUPPLY DG SUPPLY
MG73BH MG73BH CONTACTOR CONTACTOR
DG SUPPLY EB SUPPLY
MONITOR MONITOR NC NC NO NO A2 NC NC NO NO A2
N L3 L2 P L1 N L3 L2 P L1
9 8 7 6 5 4 3 2 1
28
Wiring Diagrams
SOURCE 1 SOURCE 2
K2 K1
K1 K2
K1
K2
K1
K2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
L1 L2 L3 N L1 L2 L3 N A1 A2
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Parameter
Programming Connection Setting (Description)
Terminal code
15(INP1) P10.01.01 Line 1 breaker closed (Feedback 1)
Inputs
16(INP2) P10.02.01 Line 2 breaker closed (Feedback 2)
25(OUT4) P11.04.01 Close line 1 contactor/circuit breaker
Outputs 27(OUT5) P11.05.01 Open line 1 / line 2
30(OUT7) P11.07.01 Close line 2 contactor/circuit breaker
Others - P05.07 Changeover pulse
29
Characteristic Curves
HRC Fuse-link
¾ Details 31
Time-Current
¾ Characteristics of Type
HF Fuse-links 32
Cut-off
¾ Current Characteristics of Type
HF Fuse-links 32
Time-Current
¾ Characteristics of Type
HN Fuse-links 33
Cut-off
¾ Current Characteristics of Type
HN Fuse-links 33
HRC Fuse-link Details
Features
• Conform to IEC 60269-2, IS 13703 part 2
• Range: 2 A to 800 A, 415 V, AC 50 Hz
• Type: HF Cylindrical (2 A to 63 A) & HN DIN (63 A to 800 A)
• High breaking capacity: 80 kA for type HF and 100 kA for type HN
Fuse Suitable
Rating Fuse-link
Frame mountable fuse-link
(A) Size
kit type
I 63 CO Frame 1 63 A HF 14 x 51 Cylindrical
31
Characteristic Curves
63 A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
8B
2A
4A
6A
4
2
1000
4
2
100
Pre-arcing Time (seconds)
4
2
10
4
2
1
4
2
0.1
4
2
0.01
4
2 3 4 5 10 2 3 4 5 100 2 3 4 5 1000 2 3 4 5
Symmetrical Current (A)
6A
4A
(asymmetrical Fault Conditions)
1.0 2A
Cut-off Current-ka (peak)
0.1
2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8
0.01 0.1 1.0 10
32
Characteristic Curves
100 A
125 A
160 A
200 A
250 A
315 A
400 A
500 A
630 A
800 A
63 A
80 A
10000
4
2
1000
2
100
4
Pre-arcing Time (seconds)
2
10
4
2
2
0.1
2
0.01
4
2 3 4 5 10 2 3 4 5 100 1 2 3 4 5 1000 2 3 4 5 10000 3 4 5
800 A
630 A
5
500 A
600 A
315 A
250 A
200 A
2 160 A
125 A
100 A
80 A
10 63 A
(Asymmetrical Fault Conditions)
Cut-off Current-ka (peak)
0.1
2 5 2 5 2 5 8
0.1 1 10 100
33
Dimensions
Dimensions
¾ of Open Execution Manual
Changeover Switch 35
Dimensions
¾ of Manual Changeover
Switch in Sheet Steel Enclosure 41
Dimensions
¾ of Manual Fuse
Changeover Switch 44
Dimensions
¾ of Motorised
Changeover Switch 47
Dimensions
¾ of Auto Source Transfer Switch
Controller : AuXC-2000 49
Dimensions
CO1-63/100
Open Execution with Direct Handle Manual Changeover Switch
44 x 140
Cutout Suitable for Mounting In
Distribution Board (Slot for Termination)
4 Nos. Mounting Holes 50.5 74 (Mounting)
44 Suitable for M4 Screws 32 16.5
64.5
Provision of Mounting on
TH35 - 7.5 Rail As Per IS 11039
37 37 37
140
175
A
81.1
68.1
59.1
CO1-100 A 2.5
CO1-63/100/125
Open Execution with Extended Handle Manual Changeover Switch
50.5 74 (Mounting)
4 Nos. Mounting Holes
Suitable for M4 Screw 32
180.4 )(with spreader links)
90.2
163.4
90.2
* Bushes
140.6
Rating Termination
Bolt
A
CO1-63/100/125 M6
75.1
68.1
59.1
34.9
Rating A
5.7
CO1-63 A 2
17.3
16 (Terminal with)
CO1-100/125 A 2.5
CO2-125/160/200
Open Execution with Extended Handle Manual Changeover Switch
7
Panel Door
88
Cubicle to be 241 ± 1
9
190 Mounting
4 Nos. Mounting
Contact Block
267
Holes Suitable
Auxiliary
for M6 Screws
154
120 (Mounting)
E&A
30
A
42
C
E&A
Rating A B C D
CO2-125 22 3 138 121
CO2-160 22 3 138 121
CO2-200 22 3 138 121 44 44 44 M4 Screws
210 for Earthing
(2 Nos.)
CO3-250/315
Open Execution with Extended Handle Manual Changeover Switch
7
Panel Door
113
Maintain Distance Inside of
Cubicle to be 276 ± 1
4 Nos. Mounting
Contact Block
Holes Suitable
Auxiliary
301
for M8 Screws
239 with Accessories
193
159 (Mounting)
138
E&A
B
39
A
54
E&A
36
Dimensions
CO4-400/630
Open Execution with Extended Handle Manual Changeover Switch
7
Panel Door
130
Cubicle to be 290 ± 1
286 (Mounting)
316
4 Nos. Mounting
Contact Block
Holes Suitable
Auxiliary
210
for M8 Screws
151
A
40
58
E&A
202
228
E&A
Rating A
CO4-400 5
CO4-630 6
M12 Bolt 70 70 70
M4 Screws
310 for Earthing
(2 Nos.)
CO5-630/800/1000
Open Execution with Extended Handle Manual Changeover Switch
8
164
Maintain Distance Inside of
12.6
Phase Barrier
Cubicle to be 330 ± 1
380
Terminal
359.8
Holes Suitable
for M8 Screws
182
A
Auxiliary
45
66.7
220 Mounting
Contact
E&A
Block
228
264
50
E&A
Rating A M5 Screws
15
37
Dimensions
CO6-1250/1600
Open Execution with Extended Handle Manual Changeover Switch
with center operation
4 Nos. Mounting Holes
Suitable for M10 Screws 1250A Terminal Arrangement
317.5 (mounting)
Suitable for M10 Hardware
212.5
19
Housing
55
22
Wall
19
D (with Accessories)
22
265 (mounting)
60
NO NC COM
200
10
A
COM NC NO
Maximum:500
105
Minimum:400
105
Maximum:480
Minimum:380
Suitable for M12 Hardware
108.3
540
22
B
Housing
65
26
Wall
325
E
271
26
22
70
C
F
Cat. No. Rating A B C D E F
CO61250OOOO CO6-1250 310 8 56 339 112 87 Tapped Hole Suitable for M5
Screw for Earthing
CO61600OOOO CO6-1600 330 12 54 347 108 85 (25 Sq. mm Cable Lug)
CO6-1250/1600
Open Execution with Extended Handle Manual Changeover Switch
with side operation
540
200
A
COM NC NO
10
Panel
Door
Mounting Holes
Minimum:400
372.9
Maximum:482
Minimum:382
Suitable for
M10 Hardware
325
E
271
38
Dimensions
CO6-2000
Open Execution with Extended Handle Manual Changeover Switch
with center operation
317.5 (mounting) 107
Terminal Arrangement
192.1
Suitable for M12 Hardware
Housing
50
Wall
110
456 (with Accessories)
40
26.5
8.5
265 (mounting)
200
25
420.2
40
85
Maximum:480
540 Suitable for M10 Screws
Minimum:380
15
325
105
271
52.5
83.5
M5 Hardware for Earthing
Lug (25 Sq. mm)
CO6-2000A
Termination of 100 mm Bus Bar
50604
101 Max. Space for
Busbar : 26 mm
Max. Space For Max. Busbar
Busbar : 26mm Thickness: 8 x 2 Nos.
Max. Busbar
Max. Space For
Thickness: 8 X 2 Nos.
Busbar : 38 mm
Max. Busbar
Thickness:12 x 2 Nos.
CK50604
101
>PP-EPDM-FR<
Source 1
Source 2
101
>PP-EPDM-FR<
39
Dimensions
Terminal
Spacer
Busbar
Note: 1. Different configurations of busbars can be used maintaining minimum cross section areas as specified in the table
2. Factory supplied bolt length caters to the copper bus bar termination as per standard. In case of different configurations & cross section areas,
bolt of higher length may be required.
27 20 27 20
09
09
25 92.5 25
25 92.5 25
40
Dimensions
CO1-63/100/125
Manual Changeover Switch In Sheet Steel Enclosure
72.4
224.4
152
D
262 A B
Rating Termination
Bolt
CO1-63/100/125 A M6
A B C D C
CO2-125/160/200
Manual Changeover Switch In Sheet Steel Enclosure
97
340
215.5
243
350 (Mounting)
431
315 Ø5.7
51 213 (Mounting)
41
Dimensions
CO3-250/315
Manual Changeover Switch In Sheet Steel Enclosure
97.4
378.4
281
285
350 (Mounting)
390
570
Ø5.7
4 Nos. Mounting
Holes Suitable
for M8 Screws
110
CO4-400/630
Manual Changeover Switch In Sheet Steel Enclosure
107.4
4 Nos. Mounting
Holes Suitable
for M8 Screws
399.4
292
366
600 (Mounting)
465
732
Ø5.7
42
Dimensions
CO5-800/1000
Manual Changeover Switch In Sheet Steel Enclosure
107.6
445
337.1
348.1
4 Nos. Mounting
Holes Suitable
for M10 Screws
102
510
804
460
Ø5.7
255
Minimum Hinge
Distance 255 mm
402
560
82 346 (Mounting)
43
Dimensions
CO1-63
Fuse Changeover Switch (Suitable for Cylindrical Type Fuse Link)
94.4
68
Bushes
Panel Door 37 37 37
175
123.8
115.6
Rating Termination
Bolt
2
75.1
59.1
CO1-63 A M6
34.9
17.3
5.7
16 (Terminal with)
CO2-125/160/200
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)
7
Neutral
Maintain Distance Inside of
Phase
Barrier Pole
4 Nos. Mounting
Holes Suitable 190 (Mounting)
Contact Block
302
for M6 Screws
255
245
Auxiliary
208 with Accessories
170
120 (Mounting)
112
E&A
30
A
42
C
D
E&A
Rating A B C D
CO2-125 22 3 138 121
CO2-160 22 3 138 121 44 44 44 M4 Screws
CO2-200* 26 5 150 121 210 for Earthing
(2 Nos.)
* Cat no. CO22000OOOO is of Interior CO2-200 suitable for
fuse mounting kit CX22000OODO
All dimensions are in mm
44
Dimensions
CO3-250/315
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)
7
Fuse Phase Barrier Panel Door
* Fuse Link
351
4 Nos. Mounting 235.4 (Mounting)
293
Contact Block
292
Holes Suitable
Auxiliary
277
for M6 Screws
207
159 (Mounting)
E&A
39
A
54
C
E&A
Rating A B C D
CO3-250 29 4.5 182 156
CO3-315 35 5 198 164 M10 Bolt
56 56 56 M4 Screws
260 for Earthing
(2 Nos.)
CO4-400
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)
7
* Fuse Link
Neutral
Maintain Distance Inside of
Phase
Cubicle to be 360 ± 1mm.
Pole
Barrier
386
332
320
298
227
286 (Mounting)
4 Nos. Mounting
Contact Block
151
Holes Suitable
5
Auxiliary
for M8 Screws
42
40
58
E&A
202
228
E&A
M12 Bolt
70 70 70 M4 Screws
310 for Earthing
(2 Nos.)
45
Dimensions
CO5-630/800
Fuse Changeover Switch (Suitable for DIN Type Fuse Link)
Fuse
Phase Barrier
8
* Fuse Link
Cubicle to be 431 ± 1
Barrier
6
459.5
403.6
377
353
263.6
182
A
45
66.7
50
345 (Mounting)
80 80 80
17.5
4 Nos. Mounting
Holes Suitable
for M8 Screws
E&A
* Suitable for
228
264
E&A Make
Rating A Fuse Links
CO5-630 6 E^ A
CO5-800 8
M5 Screws
15
for Earthing
Suitable (2 Nos.)
for 92 92
M16 Bolt 380
46
Dimensions
NOII OFF
J (Mounting)
L
C
D
M
I NO
MANUAL
AUTO
=
R
N A
P
Mounting Earthing
holes E F F F 10.1
Screws
(4 Nos.) (2 Nos.)
125 22 3 138 121 28 44 210 211 120 190 CO2 CX2 240.3 234.3 30 42 112 M6 M4
160 CO2 CX2 22 3 138 121 28 44 210 211 120 190 CO3 CX3 277.2 271.2 39 54 138 M8 M4
200 22 3 138 121 28 44 210 211 120 190 CO4 CX4 293.7 287.7 42 58 151 M8 M4
250 29 4.5 182 156 32 56 260 239 159 235.4 CO5 CX5 330.9 324.9 45 66.7 182 M8 M5
CO3 CX3
315 35 5 198 164 32 56 260 239 159 235.4
400 40 5 228 202 32.3 70 310 329 200 286
CO4 CX4
630 40 6 228 202 32.3 70 310 329 200 286
630 50 6 264 228 - 80 380 351.6 220 345
800 CO5 CX5 50 8 264 228 - 80 380 351.6 220 345
1000 50 8 264 228 - 80 380 351.6 220 345
CO6-1250/1600/2000
Motorised Changeover Switch
540
389
108
271 118
>PP-EPDM-FR<
>PP-EPDM-FR<
Ck50604
Ck50604
101
101
=
347
MANUAL AUTO
250.4
ON
274
OFF II
ON
=
= =
70
All dimensions are in mm
47
Dimensions
Panel Cutout
Motorised Changeover Switch
Panel Cutout
B
=
AUTO
MANUAL
88
ON I
OFF NO II
=
Type A B
CO2 with CX2 95 60
52.5 CO3 with CX3 117.7 79.5
88 CO4 with CX4 143 100
CO5 with CX5 172.5 110
Bezel Assembly
Ø3 x 4
100
Insert this part
into the Bezel
Place Gasket on Bezel
6
Door
100
6 6
Panel Cutout
*Available with standard product.
48
Dimensions
AuXC-2000
Rear Terminal Connections
OUT 1
OUT 2
OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
AuXC-2000
Panel cut-out
49
Dimensions
AST Controller
Panel Cutout & Drill Plan for Flush Mounting
198.6±0.5
186±0.5 A1
Hole
Ø5.5 x 4Nos. AST Controller
65±0.5
230±0.5
100±0.5
A2
50
Enclosed ATS
Overall Dimensions
E C D
B
213
Mounting Holes
B
A 213
RATING(A) A B C D
51
Enclosed ATS
Handle Clamp & IP Cover Mounting
IP Cover Mounting
Insert the IP cover as shown
Click
52
SP 50487 R7