Professional Documents
Culture Documents
UFAD Mini-Conference
U.S. Green Building Council – Colorado Chapter
Denver, CO
September 18, 2009
Reheat
Higher heating discharge temperatures reduces air flow
Higher plenum supply temperature and reduced airflow
lowers reheat
Plenum air to fan coil increases reheat
Energy modeling of UFAD systems
Goal/Significance
1. Develop a version of the whole-building energy simulation program,
EnergyPlus, capable of modeling UFAD systems
2. Develop practical design tool to estimate cooling airflow quantities for
UFAD systems
These are the first validated UFAD energy simulation program and
cooling airflow design tool
Project details
CBE, UC San Diego, Lawrence Berkeley National Lab, JCI/York
Sponsor: California Energy Commission PIER Program
Project start: November 1, 2002
First phase complete: December 31, 2006
http://www.cbe.berkeley.edu/research/briefs-ufadmodel.htm
Improved UFAD module included with EnergyPlus v3.1
released in April 2009
Heat transfer in overhead system
Simplified illustration of distribution of room heat gains for multi-story
overhead building at steady state
Room air
extraction
~90%
Total system (RCLR)
heat gain
100%
Overhead System
Q × RCLR
CFM =
1.08 × ∆T
Where:
Q= total heat gains to room, including lights (Btu/hr)
CFM = total room airflow (ft3/min)
∆T = temperature difference between the room setpoint
temperature and the supply air temperature (°F)
RCLR = ratio of room cooling load to total system heat gain
Q × RCLR
CFM =
1.1× ( Btu / hr ⋅ cfm ⋅ ° F ) × ∆T
Overhead UFAD
Supply Temp: 55°F Supply Temp: 65°F
Space Heat Load: 17,297 Btu/hr Space Heat Load: 17,297 Btu/hr
RAT
Height
Ceiling
∆Troom
Temperature
at head height
∆Toz
Ankle (4 in.)
Temperature
Room air stratification
Heat transfer in UFAD environment
From To
Through
Total system Room air Ceiling-slab ceiling
heat gain extraction radiation
Perimeter 100% 60-70%
Ceiling-floor AHU
zone (RCLR) radiation
Through Through
slab floor
65°F
To From
Q × RCLR
CFM =
1.1× ( Btu / hr ⋅ cfm ⋅ ° F ) × ∆T
Overhead UFAD
Supply Temp: 55°F Supply Temp: 65°F
Space Heat Load: 17,297 Btu/hr Space Heat Load: 17,297 Btu/hr
Standard Overhead
Load Calculation
100
80
Height (inches)
60
40
3 W/sf
65°F SAT
2.8°F ΔToz
0.54 cfm/sf
20 0.9 diffuser/WS
(Original design)
0
66 68 70 72 74 76 78 80
Temperature (°F)
Predicted plenum inlet temperature
Cooling load = 3.0 W/ft2
68
P lenum Inlet T emperature (°F )
66 Average diffuser
discharge = 67°F
64
62
60
Average diffuser
58 discharge = 65°F
56
54
52
50
0.0 0.5 1.0 1.5 2.0 2.5 3.0
2
A irflow (c fm/ft )
80
Height (inches)
60
40 3 W/sf
Both profiles are
65°F SAT controlled to
2.8°F ΔToz
0.54 cfm/sf
Toz,avg = 74°F
0.9 diffuser/WS
20
(Original design)
0
66 68 70 72 74 76 78 80
Temperature (°F)
Cooling airflow design calculations
Must account for impact of thermal decay in plenum
To
Room air
extraction Room air
75% extraction
Total system 60% AHU
cooling load
100%
Perimeter Interior
zone zone
From
Heat gain into supply plenum 20% Heat gain into supply plenum 35%
Energy modeling of UFAD systems
Why this work is important Supported by CEC/PIER
BERG Program
Can UFAD systems save energy
…and if so, how much? 45
Objectives 40
35
Quantify energy and demand Total HVAC
EUI, kBtu/sf/yr
13.6
30
Isolate impact of UFAD system
25
Approach 20 Lighting
15.9
Compare energy performance of UFAD 15
Modular software
structure that allows
for upgrades and
modifications
Return plenum
Upper zone
Stratification height
Temperature
Room air stratification modeled as two Plenum Diffuser
inlet SAT
zones separated at stratification height, h
What are the UFAD module inputs and outputs?
Inputs Outputs
Supply Conditions Supply Plenum
Supply Plenum
Temperature
Configuration Room Occupied Zone
Air Temperature Temperature
Room Conditions Room Upper Zone
Temperature
Thermostat Setting / Height
Heat Sources Return Plenum
Temperature
Diffusers
Surface Temperatures
Type (Swirl or VA)
Airflow Rate
Number
UFAD module development and validation
2+ Year Effort
Theoretical Work
hs=0 hs=1/8D
Bench-Scale
Testing and hs=1/4 D hs=1/2 D
Validation
(Salt Tanks)
Heat Source Cooling Vent
Interior zone full-scale testing and validation
Test chamber cross section
Energy model of test chamber
Return
Plenum
Room
Supply
Plenum
EnergyPlus validation – Temperature profile
Roof
Interior zone,
measured data vs.
Return
full scale test
plenum
chamber simulation Ceiling
Closely simulates
air and surface
temperatures in
Layer
room and supply Room
Interface
plenum
Measured
Simulated
Raised floor
Supply
plenum Slab
Whole-building prototype
Three story, six zones per floor (incl. service core @ 15%)
20,000 ft2 floorplates, 1.5 aspect ratio
One model for both UFAD and OH systems
Simulated UFAD system
Early morning, system off
System startup
Warm-up
Occupants arrive
Solar peaking, east perimeter zone
Mid morning
Late morning
Mid day
Mid afternoon
Occupants leave
Occupants left
System off
Prototype baseline design parameters
14 0.5
0.7
Site Annual HVAC EUI (kBtu/sf/yr)
12 2.9
3.2 0.4
0.4 0.6 0.5 0.4
10 0.6 0.4 2.5
2.6 0.6 0.6 2.0 2.1
8 2.8 3.3 4.3 1.8
0.4 2.2 2.1
0.3 Aux
0.4 0.3
1.8 6 3.9 3.6
6 3.4 1.7 1.9 2.2 4.0
3.8 Fan
Chiller
4 3.0
2.9 2.4
2.0 5.4 5.4 5.2 4.9
Boiler
6.2
4.4 4.5 4.8
2
3.1 3.4 3.8 4.3
2.6 2.2 2.6
1.4 1.3 1.6 1.9
0
UFAD 57
UFAD 60
UFAD 63
UFAD 57
UFAD 60
UFAD 63
UFAD 57
UFAD 60
UFAD 63
OH BC 1
OH BC 2
OH BC 1
OH BC 2
OH BC 1
San Francisco Los Angeles OH BC 2
Sacramento
Impact of stratification
Sacramento
16 60
Aux
14 55
Site Annual HVAC EUI (kBtu/sf/yr)
http://www.eere.energy.gov/buildings/energyplus
Fred Bauman
fbauman@berkeley.edu
CBE website
www.cbe.berkeley.edu
EnergyPlus website
http://www.eere.energy.gov/buildings/energyplus