You are on page 1of 9

Research Article

Advances in Mechanical Engineering


2017, Vol. 9(8) 1–9
Ó The Author(s) 2017
Experimental investigation on DOI: 10.1177/1687814017714980
journals.sagepub.com/home/ade
frictional multiplier of steam-water
two-phase flow in internally ribbed
enhanced tubes

Weishu Wang1,2, Weihui Xu1, Bingchao Zhao1 and Qincheng Bi2

Abstract
The frictional multiplier of steam-water two-phase flow in four-head internally ribbed tubes was experimentally
investigated under two test conditions—adiabatic and heated. The internally ribbed tube has the following dimensions:
outside diameter 28.6 mm, wall thickness 5.8 mm, and hydraulic diameter 15.24 mm. The test tube, 2000 mm in length,
was vertically installed and uniformly heated electrically. A wide range of experimental parameters were considered.
The pressure range was 9–31 MPa, mass flux range was 600–1800 kg/(m2 s), and steam quality range was 0–1 in subcriti-
cal pressure region. In this study, the effects of pressure, mass flux, and steam quality on the frictional multiplier
were analyzed. The corresponding empirical correlations were presented. The variation in pressure drop between the
adiabatic tube and heated tube was determined. The experimental results demonstrated that the characteristics of the
frictional pressure drop in the internally ribbed tube under heated and adiabatic conditions are dissimilar. The two-phase
frictional multiplier in the heated tube is higher than that in the adiabatic tube. With the decrease in the pressure
or increase in the steam quality, the two-phase frictional multiplier increases gradually. However, the single-phase fric-
tional factor in the heated tube is smaller than that in the adiabatic tube in the subcritical and supercritical pressure
region.

Keywords
Steam-water two-phase flow, internally ribbed enhanced tube, frictional multiplier

Date received: 10 November 2016; accepted: 17 May 2017

Academic Editor: Oronzio Manca

Introduction (DNB).7,8 The internally ribbed tube is widely used in


the water walls of modern supercritical boilers such as
The performance and efficiency of a thermal system supercritical circulating fluidized bed (CFB) boilers and
can be significantly enhanced if the dimensions of the supercritical pressure W-shape flame boilers. The
heat exchangers are reduced according to ‘‘optimum’’
heat transfer enhancement techniques for fixed heat 1
North China University of Water Resources and Electric Power,
duty. Because the ribbed channel can be used as a pas- Zhengzhou, China
sive heat transfer enhancement tool, a series of ribbed 2
State Key Laboratory of Multiphase Flow in Power Engineering, Xi’an
channels are generally utilized in industrial devices such Jiaotong University, Xi’an, China
as the heat exchangers of chemical engineering systems,
Corresponding author:
refrigerators, and micro-coolers of electronic sys- Weishu Wang, North China University of Water Resources and Electric
tems.1–6 Various types of ribbed tubes are widely used Power, Zhengzhou 450045, China.
in boilers to delay the departure from nucleate boiling Email: wangweishu@ncwu.edu.cn

Creative Commons CC-BY: This article is distributed under the terms of the Creative Commons Attribution 4.0 License
(http://www.creativecommons.org/licenses/by/4.0/) which permits any use, reproduction and distribution of the work without
further permission provided the original work is attributed as specified on the SAGE and Open Access pages (https://us.sagepub.com/en-us/nam/
open-access-at-sage).
2 Advances in Mechanical Engineering

turbulence in the proximity of the tube wall surface is actual industrial operating conditions. Therefore, it is
enhanced to reduce the thermal boundary layer thick- necessary to further enrich the corresponding database
ness by a chaotic mixing of fluid in the internally ribbed of pressure drop of two-phase flow within ribbed tubes.
tube, which has been reviewed by Mohsen et al.9 and In this study, the frictional pressure drop characteristics
Kareem et al.;10 in this manner, the heat transfer is of steam-water two-phase flow are studied under heated
enhanced. It is evident that frictional pressure drop in and adiabatic conditions. The system parameters taken
internally ribbed tubes is significantly higher than that into consideration in this study adequately cover the
in smooth tubes. range of the operational parameters of supercritical
Accurate predictions of frictional pressure drop of pressure boiler. The results are likely to provide a set of
single-phase and two-phase flows are crucial for the meaningful references for the design of large capacity
effective design of thermal-exchange equipment for heat exchanger.
industrial purposes because the pressure drop deter-
mines the power input in a fixed-flow system. In addi-
tion, the pressure drop also determines the mass flux, Experimental setup and method
flow distribution, and critical heat transfer (CHF) in a
fixed pressure drop system. Although considerable The experiments were carried out on a high-pressure
research has been conducted, such as those by steam-water two-phase flow test loop capable of attain-
Bergles,11 Guo et al.,12 Srinivasan et al.,13 Zdaniuk ing pressures of up to 40 MPa at Xi’an Jiaotong
et al.,8 and Taklifi et al.,14 and numerous empirical cor- University. The test loop is suitable for undertaking
relations have been proposed in the past decades, these experimental research on two-phase flows, single-phase
study results are ineffective for achieving the purpose. flows, and heat transfer in large steam boilers, nuclear
For example, there is negligible information on certain reactors, and heat exchangers. The schematic diagram
effects of flow pattern and condition parameters on of the test loop is shown in Figure 1. The test section
frictional pressure drop of steam-water two-phase flow. was a stainless steel tube, which was seamless, cold
With the development of enhanced heat transfer tech- drawn, and annealed. The experimental system incor-
nology, the prediction of two-phase flow frictional porated a series of stainless steel tubes, which together
pressure drop in ribbed flow channel has become highly were used as a resistance heater and through which the
critical. Compared with the smooth channel, heat water flowed. With the resistance heater, the local heat
transfer is higher in the ribbed channel; this is accom- input was determined, and a point heat transfer coeffi-
panied by a higher two-phase flow frictional pressure cient could be calculated. Feed water was boosted from
drop. For a ribbed tube, numerous factors such as tube the tank by a high-pressure plunger pump and heated
diameter, rib parameters, inner surface configuration, by a regenerative heat exchanger and main pre-heater
rib structure, and flow pattern affect the prediction of to obtain the required test parameters. Fluids from the
two-phase flow frictional pressure drop. Over the past test section flowed through the regenerator and con-
years, predictions of two-phase frictional pressure drop denser and then returned to the tank. The bypass was
in micro-fin channels15–17 and small diameter tubes18 used to regulate mass, velocities, and pressures in the
have been proposed. A few investigations have been experiment. The test section and main pre-heater were
conducted on the internally ribbed tubes used in large directly heated by alternating current, with these mod-
capacity boilers. Chen et al.,19 Cheng and Chen,20 and ules themselves functioning as resistance elements. The
Yang et al.4 reported the flow boiling and steam-water heated tubes were enclosed with insulation. In this
two-phase frictional pressure drop in an internally experiment, the overall heated capacity was 840 kW, of
ribbed tube. Kolar21 experimentally investigated the which 180 kW was used for heating the test section.
frictional pressure drop of triangular internally ribbed Two electrical terminal bars, which were constructed
tube and determined that the two-phase frictional pres- from copper plate, were drilled and reamed to fit the
sure drop is in direct proportion to the numerical value tube dimension and finally soldered in place.
of (e/d)0.63, where e is the rib height and d is the equiva- The test tube was a 28.6 mm 3 5.8 mm four-rib
lent inside diameter of the tube. Ackerman22 deter- internally ribbed tube of hydraulic diameter 15.24 mm.
mined that the frictional pressure drop in the adiabatic The rib was in the form of a helix on the inner surface.
ribbed tube is 25% higher than that in the smooth tube. Specifications of the test tube are presented in Table 1.
A few research studies23–26 have also demonstrated that The heated length was 2000 mm, measured between the
the structure of the internally ribbed tube has a signifi- terminal bars. The outer wall temperature of the heated
cant impact on the frictional pressure drop. test tube was measured by 96 thermocouples of F3 mm
The frictional pressure drop correlations of intern- NiCr–NiSi (precision of 0.4 K) connected at 14 cross
ally ribbed tubes vary among the diverse rib types. sections along the length of the test section to identify
Moreover, a number of these correlations were devel- variations in the outer tube wall temperature. These
oped under adiabatic conditions, which differ from thermocouples were calibrated in a water thermostat
Wang et al. 3

Figure 1. Schematic diagram of the test loop.


1: water tank; 2: filter; 3: high-pressure plunger pump; 4: mass flowmeter; 5: orifice flowmeter; 6: heat exchanger; 7: pre-heater; 8: test section—
vertical; 9: test section—horizontal; 10: condenser; 11: inlet of cooling water; 12: outlet of cooling water; 13: rotermeter;14: bypass.

Table 1. Specifications of the four-head internally ribbed tube. These pressure transducers were calibrated by the
national authoritative quality inspection department.
Specifications Value Tolerance The mass flow rate was measured by an orifice meter
Outside diameter (mm) 28.6 6 0.15 calibrated by the weighing method. The measuring
Major inside diameter (mm) 15.84 6 0.15 accuracy of the orifice meter was 0.25%. The symbols
Minimum wall thickness (mm) 5.8 + 20%, 20% P and DP represent pressure and differential pressure
Number of ribs 4 – measuring points, respectively. The heated test section
Rib width (circumferential), mm 4.8 6 0.6
was mounted vertically and enclosed with 50 mm thick
Rib width (longitudinal), mm 8.3 6 1.04
Rib height (mm) 0.85 6 0.3 insulation.
Rib side angle (°) 54 + 15, 210 The experiments were performed as per the follow-
Lead (mm) 86.19 6 12.7 ing procedure. The pressure, mass flux, and heat flux
were first maintained constant. Then, the heating pow-
ers of the pre-heaters were increased gradually, which
increased the inlet enthalpy of the test section continu-
system before being used. The adiabatic test section ously. By means of the above operation, parameters
was 2000 mm in length. The electrical heating power including wall temperature and heat transfer character-
was defined as the product of the effective values of the istics of the working fluid were measured under various
voltage and current. operating conditions. The pressure, fluid temperature,
Figures 2 and 3 illustrate the structures of the test mass flux, wall temperature, and electrical input
tubes of the heated test section and adiabatic test sec- were acquired automatically and recorded by an
tion, respectively. The fluid pressure of the test section IMP3595 distributed data acquisition board connected
was measured by the Rosemount 3051 capacitance-type with all the sensors used in the experiments. The
pressure transmitter. ST3000/S900 differential pressure parameter ranges of this study were as follows: the
transducers were used to measure the pressure drop of pressure ranged from 9 to 31 MPa, mass flux varied
the test section. Furthermore, the measuring accuracy from 600 to 1800 kg/(m2 s), and steam quality varied
of the differential pressure transducers was 0.25%. from 0 to 1.
4 Advances in Mechanical Engineering

Figure 2. Test section and thermocouple arrangement for the heated tube.

equations (2) and (4), respectively. The acceleration


pressure drops in the heated tube and adiabatic tube
are calculated using equations (3) and (5), respectively.
For the heated tube test section
" #
Figure 3. Test section and thermocouple arrangement for the rl  g  L  sin a 1 + xo  (rl =rg  1)
adiabatic tube. DPg =  ln
(xo  xi )  (rl =rg  1) 1 + xi  (rl =rg  1)

Date reduction of two-phase frictional ð2Þ


pressure drop where rl is the density of the liquid phase, rg is the den-
sity of the gas phase, xo is the steam quality of the out-
With regard to steam-water two-phase frictional pres-
let, xi is the steam quality of the inlet, and a is the angle
sure drop, the main influencing factors are pressure,
of the tube
steam quality, mass flux, heat flux, tube diameter, flow
direction, and geometrical features of the inner surface !
of the tube. The total pressure drop is obtained as 2 1 1
DPa = G  ðx0  xi Þ   ð3Þ
follows rg rl
DP = DPTPf + DPg + DPa ð1Þ For the adiabatic tube test section
where DP is the total pressure drop, DPTPf is the two- DPg = rl  g  L  sin a ð4Þ
phase frictional pressure drop, DPg is the gravitational
pressure drop, and DPa is the acceleration pressure DPa = 0 ð5Þ
drop. The total pressure drop can be calculated from
The two-phase frictional pressure drop is given by
the measured data is DP = P1 2 P2.
As represented by equation (1), the two-phase fric-
DPTP = f2l0  DPl0 ð6Þ
tional pressure drop is calculated as the total pressure
drop minus the gravitational pressure drop and accel- where DPl0 is the single-phase saturated-water frictional
eration pressure drop. The total pressure drop is pressure drop and is obtained by the Blasius correla-
obtained from the experiment, and the gravitational tion;27 the coefficient f2l0 is defined as the two-phase
pressure drop and acceleration pressure drop are calcu- frictional multiplier.
lated by the homogeneous flow model used in this The steam quality at the axial location z of the
study. Specifically, the gravitational pressure drops in test section is calculated using the thermal balance
the heated tube and adiabatic tube are calculated using equation
Wang et al. 5

Table 2. Uncertainties in measured and calculated parameters.

Variables Uncertainty (%)

Pressure (MPa) 1.11


Differential pressure (kPa) 0.75
Electrically heated power (kW) 6.25
Fluid temperature (°C) 0.4
Steam quality 7.63

P
pDl (Ll  Lsc )ql + pDn Ln qn + pdzql
x= ð7Þ
Aflow  G  Hfg
where Dn, Ln, and qn are the inside diameter, heated
length, and heat flux, respectively, of the nth pre-hea-
ter. Lsc is the sub-cooled length within Ll, which can be Figure 4. Effects of pressure on two-phase frictional multiplier
calculated by in heated tube.

Aflow  GCp DTsub


Lsc = ð8Þ
pDl  ql 1500 kg/m2 s and constant heat flux of 500 kW/m2 in
the internally ribbed heated tube. The ordinate repre-
where DTsub is the temperature variation between the
sents the two-phase frictional multiplier, and the
saturated fluid temperature and inlet fluid temperature
abscissa represents the steam quality. Considering the
of the first pre-heater. In the experiments, the heat
example of a pressure of 9 MPa, it is observed in
absorption efficiency was calibrated, and the system
Figure 4 that the two-phase frictional multiplier
heat balance was ensured to be maximized. Thus, the
increased with increasing steam quality within a certain
steam quality in this study is considered an equilibrium
range of steam quality. This phenomenon demonstrates
steam quality. The heat absorption efficiency of the test
that the frictional pressure drop in the steam phase was
section is estimated from the enthalpy alteration of
higher than that in the liquid phase. However, when
single-phase water and input electric power and is
the steam quality reached a certain value (approxi-
given by
mately 0.7), the rate of increase reduced.
DH As illustrated in Figure 4, the pressure significantly
h= ð9Þ impacted the two-phase frictional multiplier, which
QE
decreased with increasing pressure. However, the
wherein DH and QE are calculated as follows decreasing trend was gradual until the near-critical
pressure region was reached. The two-phase frictional
1 2 multiplier was approximately equal to 1 within the
DH = pd GCp (to  ti ) ð10Þ
4 whole steam-quality region, indicating that the two-
QE = UI ð11Þ phase frictional pressure drop was similar to that of the
single-phase frictional pressure drop when the pressure
The estimated uncertainties in the measured and cal- approached the near-critical value.
culated parameters are delineated in Table 2.
Effects of mass flux on f2l0
Experimental results and discussion
Figure 5 displays the variations in two-phase frictional
It is generally considered that the steam quality, pres- multiplier with steam quality and mass flux at a pres-
sure, and mass flux influence f2l0 . Therefore, the effects sure of 16 MPa and heat flux of 300 kW/m2 in the
of these parameters on the two-phase frictional multi- heated test section. From Figure 5, it is observed that
plier in the heated and adiabatic tubes are discussed in the mass flux had negligible effect on two-phase fric-
this article. tional multiplier in the range of the test parameters. In
the low steam-quality region, the frictional multiplier
converged to a line, indicating that the frictional multi-
Effects of steam quality and pressure on f2l0 plier is insensitive to mass flux. With the increase in the
Figure 4 illustrates the experimental data of the two- mass flux, the frictional multiplier in the high steam-
phase frictional multiplier plotted against steam quality quality region increases marginally. A local hump
and system pressure at constant mass flux of appeared in the proximity of steam quality of
6 Advances in Mechanical Engineering

Figure 7. Variation of single-phase frictional factor with


Figure 5. Effects of mass flux on two-phase frictional multiplier Reynolds number.
in heated tube.
the difference of frictional multiplier between the two
pressures increases with increasing steam quality.
Second, as can be observed from Figure 6, when
P = 21 MPa, the frictional multiplier of both adiabatic
and heated tubes gradually increase with the increase in
the steam quality. And there is little difference between
the frictional multiplier of adiabatic tube and heated
tube. It is meant that the two-phase frictional pressure
drop is equal to the single-phase frictional pressure
drop when the pressure is around critical
pressure. While P = 13 MPa, the frictional multiplier
of the heating tube is always bigger than the adiabatic
tube under the same steam quality. And the frictional
multiplier in the adiabatic tube keeps increasing. But
the frictional multiplier in the heated tube increases
first and then remains a certain value (steam quality of
0.7–1). This phenomenon can be explained as follows:
Figure 6. Frictional multiplier difference in heated and
adiabatic tubes.
(1) the inside wall of the internally ribbed tube encom-
passes liquid water because of the liquid-phase centrifu-
approximately 0.6 under the high mass fluxes of 1650 gal force flowing in the internally ribbed tube at lower
and 1800 kg/(m2 s). It could be owing to flow regime steam quality, which leads to the increase in the fric-
variations in this region. This concept of flow pattern tional multiplier when the steam quality is less than 0.7.
variation in these regions was derived from a compari- (2) When the steam quality is bigger than 0.7, the fluid
son of the study results presented by Taklifi et al.14 and flowing at a higher speed could rupture the liquid mem-
Hewitt and Roberts.28 From the figure, it could be pre- brane in the proximity of the internal wall when the
dicted that the shift to annular flow regimes occurs at a steam quality exceeded a certain value in the heated
point within the range of x = 0.5–0.8. tube compared with the adiabatic tube; simultaneously,
the flow pattern of the higher speed fluid in the high
steam-quality region shifts to a mist flow at a lower
Two-phase frictional multiplier in heated and pressure. The two reasons together lead to the frictional
adiabatic tubes multiplier in the heated tube to increase first and then
Figure 6 illustrates the difference of two-phase fric- remain a certain value.
tional multiplier between the heated test tube and adia- It is observed in Figure 6 that in the two-phase flow
batic test tube at mass flux of 1200 kg/(m2 s) and region, the frictional multiplier of the heated tube is
pressures of 13 and 21 MPa. First, the effects of operat- higher than that of the adiabatic tube. However, in the
ing pressure on pressure drop are remarkable. The two- single-phase flow region, the frictional factor in the
phase frictional multiplier decreases with increasing heated tube is smaller than that in the adiabatic tube,
pressure under the same steam quality; furthermore, which is illustrated in Figure 7. The phenomenon might
Wang et al. 7

be a result of the enhancement of flow disturbance on quality and pressure; the others factors may be ignored.
the wall surface in the two-phase flow region. In the Now, it is feasible to fit the formulas of two-phase fric-
single-phase flow region, the friction factor f was a tional multiplier under heated and adiabatic conditions
function of only the Reynolds number, as follows.
Re = (r  u  d=m), which is associated with the dynamic The formula of two-phase frictional multiplier f2l0 is
viscosity m; m decreased with the increase in the liquid fitted to the case of the adiabatic internally ribbed tube.
temperature at similar pressure and mass flux. As the Just as in equation (14), rl =rg considers the effect of
inner-wall temperature of the heated tube was higher pressure on f2l0 . Based on the experimental results of
than that of the adiabatic tube, the dynamic viscosity this study as discussed above, the function f (x, P) can
of the heated tube was smaller, Reynolds number of be simplified to f(x), which is a unary function with
the heated tube was higher, and friction factor f of the steam quality x. Referring to Chisholm29 method, we
heated tube was smaller than the respective values of assume f (x) = ½a + bx + cx2 + dx3  and correlate the
the adiabatic tube. function using polynomial fitting; the coefficients a, b,
c, and d could be obtained based on 531 and 474 data
points for the adiabatic and heated tubes, respectively.
Correlations of two-phase frictional pressure drop Based on the multivariate linear regression analysis,
As described before, the two-phase frictional pressure we obtain the following correlation for adiabatic intern-
drop was calculated by equation (6). The two-phase ally ribbed tube
frictional multiplier could be correlated as follows
f (x) = 0:002 + 0:52x + 0:03x2  0:22x3 ð16Þ
f2l0 = DPTP =DPl0 ð12aÞ
The corresponding application conditions are the
where pressure range 9–21.5 MPa and mass flux range 400–
1800 kg/(m2 s). The comparison between predicted two-
DPTP = fTP  (l=d)  (G2 =rh ) ð12bÞ phase multiplier and experimental data is displayed in
Figure 8. The average error of equation (16) is 5.4%
DPl0 = f  (l=d)  (G2 =rl ) ð12cÞ
with a standard deviation of 16.9%. In all, 32.2% of
where the test data lie within the 6 10% error band, and the
entire set of test data lie within the 6 40% error band.
rh = rl =(1 + x  (rl =rg  1)) ð12dÞ Fitting the formula of two-phase f2l0 in the heated
internally ribbed tube yields
Combining equations (12a)–(12d) yields
f (x) = 0:05 + 0:36x + 0:36x2  0:42x3 ð17Þ
f2l0 = ( fTP =f )  (1 + x(rl =rg  1)) ð13Þ
The corresponding application conditions are the
By introducing a correction factor k, equation (13) pressure range of 9–21.5 MPa, mass flux range 400–
can be expressed as follows 1800 kg/(m2 s), and heat flux range 300–600 kW/m2.

f2l0 = (1 + k  x(rl =rg  1)) ð14Þ

Based on the experimental results in Figures 4–6, we


found that the two-phase frictional multiplier is related
to steam quality x, operating pressure P, and mass flux
G. Meanwhile, the function f (x, P, G, . . . ) is introduced,
which also is related to steam quality x, operating pres-
sure P, and mass flux G. Then, equation (14) can be
rewritten as follows

f2l0 = 1 + f (x, P, G, . . . )  (rl =rg  1) ð15Þ

Therefore, the purpose of the experimental study is


to obtain the function f (x, P, G, . . . ). From Figure 5, it
can be observed that the mass fluxes have negligible
effect on the two-phase frictional multiplier f2l0 , and
therefore, the function f (x, P, G, . . . ) can be simplified
to the form f (x, P). This implies that the critical factors Figure 8. Comparison between experimental and calculated
affecting the two-phase frictional multiplier are steam two-phase multiplier using equation (16) for adiabatic tube.
8 Advances in Mechanical Engineering

Funding
The author(s) disclosed receipt of the following financial sup-
port for the research, authorship, and/or publication of this
article: This work was supported by the Program for
Innovative Research Team (in Science and Technology) at
University of Henan Province (No. 16IRTSTHN017), Plan
for Scientific Innovation Talent of Henan Province (No.
154100510011), and National Natural Science Foundation of
China (No. 51406026).

References
1. Popov IA, Gortyshov YF and Olimpiev VV. Industrial
applications of heat transfer enhancement: the modern
state of the problem (a review). Therm Eng 2012; 59:
1–12.
Figure 9. Comparison between experimental and calculated 2. Wang QW, Zeng M, Ma T, et al. Recent development
two-phase multiplier using equation (17) for heated tube. and application of several high-efficiency surface heat
exchangers for energy conversion and utilization. Appl
Figure 9 presents the experimentally obtained values of Energ 2014; 135: 748–777.
3. Wang JG, Li HX, Guo B, et al. Investigation of forced
the two-phase multiplier plotted against those obtained
convection heat transfer of supercritical pressure water in
by equation (17). The predictions of equation (17) are a vertically upward internally-ribbed tube. Nucl Eng Des
satisfactory, with an average error of 4.7% and a stan- 2009; 239: 1956–1964.
dard deviation of 11.1%. In all, 53.8% of the test data 4. Yang D, Pan J, Zhou CQ, et al. Experimental investiga-
lie within the 6 10% error band, and the entire set of tion on heat transfer and frictional characteristics of ver-
test data lie within the 6 30% error band. tical upward rifled tube in supercritical CFB boiler. Exp
Therm Fluid Sci 2011; 35: 291–300.
5. Zhu XJ, Wang WS, Xu WH, et al. A study of the hydro-
Conclusion dynamic characteristics of a vertical water wall in a
2953t/h ultra-supercritical pressure boiler. Int J Heat
1. The single-phase frictional factor f in the heated
Mass Tran 2015; 86: 404–414.
tube was lower than that in the adiabatic tube, 6. Xu WG, Wang SY, Zhang QH, et al. Experimental and
while the two-phase frictional multiplier was numerical studies of heat transfer and friction factor of
higher in the heated tube than in the adiabatic therminol liquid phase heat transfer fluid in a ribbed
tube. The values based on the diverse pressure tube. Appl Therm Eng 2016; 95: 165–177.
ranges can be calculated according to correla- 7. Shen Z, Yang D, Mao KY, et al. Heat transfer charac-
tions expressed by equations (16) and (17). teristics of water flowing in a vertical upward rifled tube
2. The pressure significantly affected the two-phase with low mass flux. Exp Therm Fluid Sci 2016; 70:
frictional multiplier. Two-phase frictional multi- 341–353.
plier f2l0 decreased with increasing pressure, and 8. Zdaniuk GJ, Chamra LM and Mago PJ. Experimental
the rate of decrease reduced until the near- determination of heat transfer and friction in helically-
critical pressure region was reached. Steam qual- finned tubes. Exp Therm Fluid Sci 2008; 32: 761–775.
9. Mohsen S, Mofid G and Domiri D. Review of heat
ity affected the two-phase frictional multiplier in
transfer enhancement methods: focus on passive methods
a more complicated manner. With increasing
using swirl flow devices. Renew Sust Energ Rev 2015; 49:
steam quality, f2l0 increased; however, the 444–469.
increase gradient reduced correspondingly. 10. Kareem ZS, Mohd Jaafar MN, Lazim TM, et al. Passive
3. The effect of mass flux on f and f2l0 was weak; heat transfer enhancement review in corrugation. Exp
however, the effect of mass flux on f2l0 in the Therm Fluid Sci 2015; 68: 2–38.
higher steam-quality region was more apparent 11. Bergles AE. Heat transfer enhancement—the maturing of
than in the lower steam-quality region. With an second generation heat transfer technology. Heat Trans-
increase in the mass flux, the two-phase fric- fer Eng 1997; 18: 47–55.
tional multiplier decreased accordingly. 12. Guo LJ, Feng ZP and Chen XJ. An experimental investi-
gation of the frictional pressure drop of steam-water two-
phase flow in helical coils. Int J Heat Mass Tran 2001; 44:
Declaration of conflicting interests 2601–2610.
The author(s) declared no potential conflicts of interest with 13. Srinivasan PS, Nandapurkar SS and Holland FA. Pres-
respect to the research, authorship, and/or publication of this sure drop and heat transfer in coils. Chem Eng 1968; 218:
article. 113–119.
Wang et al. 9

14. Taklifi A, Hanafizadeh P, Behabadi MAA, et al. Experi- Atomic Energy Research Establishment Report M2159.
mental investigation on heat transfer and pressure drop London: HMSO, 1969.
of supercritical water flows in an inclined rifled tube. J 29. Chisholm D. Two-phase flow in pipelines and heat exchan-
Supercrit Fluid 2016; 107: 209–218. gers. London: George Godwin, 1983.
15. Hu HT, Ding GL and Wang KK. Measurement and cor-
relation of frictional two-phase pressure drop of R410A/ Appendix 1
POE oil mixture flow boiling in a 7 mm straight micro-fin
tube. Appl Therm Eng 2008; 28: 1272–1283. Notation
16. Qu WL and Siu-Ho A. Measurement and prediction of A area (m2)
pressure drop in a two-phase micro-pin-fin heat sink. Int
C(x) regression of coefficient
J Heat Mass Tran 2009; 52: 5173–5184.
17. Saisorn S and Wongwises S. Flow pattern, void friction
Cp specific heat at constant pressure
and pressure drop of two-phase air–water flow in a hori- (J/(kg°C))
zontal circular micro-channel. Exp Therm Fluid Sci 2008; D equivalent diameter of the tube (m)
32: 748–760. Dpj average diameter (m)
18. Hu HT, Ding GL, Huang XC, et al. Pressure drop dur- Erib height (m)
ing horizontal flow boiling of R410A/oil mixture in 5 mm F single-phase frictional pressure drop
and 3 mm smooth tubes. Appl Therm Eng 2009; 29: factor
3353–3365. fTP two-phase frictional pressure drop factor
19. Chen TK, Chen XZ and Chen XJ. Boiling heat transfer G mass flux (kg/(m2 s))
and frictional pressure drop in internally-ribbed tubes: heat I heating current (A)
transfer: second international symposium, vol. 1. New
K correction factor
York: Hemisphere Publishing Corporation, 1992,
pp.621–629.
L length (m)
20. Cheng L and Chen T. Flow boiling heat transfer in a ver- P pressure (MPa)
tical spirally internally-ribbed tube. Heat Mass Transfer Q heat flux (kW/(m2 s))
2001; 37: 229–236. Re Reynolds number
21. Kolar V. Heat transfer in turbulent flow of fluids through T temperature (°C)
smooth and rough tubes. Int J Heat Mass Tran 1965; 8: U heating voltage (V)
639–653. X steam quality
22. Ackerman JW. Pseudo-boiling heat transfer to supercriti-
cal pressure water in smooth and ribbed tubes. J Heat DP differential pressure (MPa)
Transf 1970; 92: 490–498. DPTPf two-phase frictional pressure drop (MPa)
23. Chen LX and Chen TK. Study of vapor liquid two-phase DPl0 single-phase saturated-water frictional
frictional pressure drop in a vertical heated spirally pressure drop (MPa)
internally-ribbed tube. Chem Eng Sci 2007; 62: 783–792. m dynamic viscosity (N s/m2)
24. Xiong DJ, Wang MH and Zhu CG. Flow Characteristics n kinematic viscosity (m2/s)
of the two phase water and steam flow within a f2l0 two-phase frictional multiplier
quadruple-lead ribbed tube. Power Eng 1983; 3: 20–26. r density of fluid (kg/m3)
25. Chen TK, Chen XZ and Chen XJ. Research on frictional
pressure drop of high pressure steam-water two-phase
flow in ribbed tubes. Power Eng 1989; 9: 10–15. Subscripts
26. Zheng JX, Chen TK and Luo YS. Investigation on the 1 first cross section
characteristics of internally rifled tubes two-phase flow
2 second cross section
friction pressure losses in sub-critical and near critical
pressure region. Power Eng 1995; 15: 56–63.
o outlet
27. Blasius H. Das Ahnlichkeitsgesetz bei Reibungsvorgan- i inlet
gen in Flussigkeiten. Forschg Arb Ing Wes 1913; 134: g gas phase
1–41. l liquid phase
28. Hewitt GF and Roberts DW. Studies of two-phase flow
patterns by simultaneous x-ray and flash photography.

You might also like