Professional Documents
Culture Documents
Abstract
The frictional multiplier of steam-water two-phase flow in four-head internally ribbed tubes was experimentally
investigated under two test conditions—adiabatic and heated. The internally ribbed tube has the following dimensions:
outside diameter 28.6 mm, wall thickness 5.8 mm, and hydraulic diameter 15.24 mm. The test tube, 2000 mm in length,
was vertically installed and uniformly heated electrically. A wide range of experimental parameters were considered.
The pressure range was 9–31 MPa, mass flux range was 600–1800 kg/(m2 s), and steam quality range was 0–1 in subcriti-
cal pressure region. In this study, the effects of pressure, mass flux, and steam quality on the frictional multiplier
were analyzed. The corresponding empirical correlations were presented. The variation in pressure drop between the
adiabatic tube and heated tube was determined. The experimental results demonstrated that the characteristics of the
frictional pressure drop in the internally ribbed tube under heated and adiabatic conditions are dissimilar. The two-phase
frictional multiplier in the heated tube is higher than that in the adiabatic tube. With the decrease in the pressure
or increase in the steam quality, the two-phase frictional multiplier increases gradually. However, the single-phase fric-
tional factor in the heated tube is smaller than that in the adiabatic tube in the subcritical and supercritical pressure
region.
Keywords
Steam-water two-phase flow, internally ribbed enhanced tube, frictional multiplier
Creative Commons CC-BY: This article is distributed under the terms of the Creative Commons Attribution 4.0 License
(http://www.creativecommons.org/licenses/by/4.0/) which permits any use, reproduction and distribution of the work without
further permission provided the original work is attributed as specified on the SAGE and Open Access pages (https://us.sagepub.com/en-us/nam/
open-access-at-sage).
2 Advances in Mechanical Engineering
turbulence in the proximity of the tube wall surface is actual industrial operating conditions. Therefore, it is
enhanced to reduce the thermal boundary layer thick- necessary to further enrich the corresponding database
ness by a chaotic mixing of fluid in the internally ribbed of pressure drop of two-phase flow within ribbed tubes.
tube, which has been reviewed by Mohsen et al.9 and In this study, the frictional pressure drop characteristics
Kareem et al.;10 in this manner, the heat transfer is of steam-water two-phase flow are studied under heated
enhanced. It is evident that frictional pressure drop in and adiabatic conditions. The system parameters taken
internally ribbed tubes is significantly higher than that into consideration in this study adequately cover the
in smooth tubes. range of the operational parameters of supercritical
Accurate predictions of frictional pressure drop of pressure boiler. The results are likely to provide a set of
single-phase and two-phase flows are crucial for the meaningful references for the design of large capacity
effective design of thermal-exchange equipment for heat exchanger.
industrial purposes because the pressure drop deter-
mines the power input in a fixed-flow system. In addi-
tion, the pressure drop also determines the mass flux, Experimental setup and method
flow distribution, and critical heat transfer (CHF) in a
fixed pressure drop system. Although considerable The experiments were carried out on a high-pressure
research has been conducted, such as those by steam-water two-phase flow test loop capable of attain-
Bergles,11 Guo et al.,12 Srinivasan et al.,13 Zdaniuk ing pressures of up to 40 MPa at Xi’an Jiaotong
et al.,8 and Taklifi et al.,14 and numerous empirical cor- University. The test loop is suitable for undertaking
relations have been proposed in the past decades, these experimental research on two-phase flows, single-phase
study results are ineffective for achieving the purpose. flows, and heat transfer in large steam boilers, nuclear
For example, there is negligible information on certain reactors, and heat exchangers. The schematic diagram
effects of flow pattern and condition parameters on of the test loop is shown in Figure 1. The test section
frictional pressure drop of steam-water two-phase flow. was a stainless steel tube, which was seamless, cold
With the development of enhanced heat transfer tech- drawn, and annealed. The experimental system incor-
nology, the prediction of two-phase flow frictional porated a series of stainless steel tubes, which together
pressure drop in ribbed flow channel has become highly were used as a resistance heater and through which the
critical. Compared with the smooth channel, heat water flowed. With the resistance heater, the local heat
transfer is higher in the ribbed channel; this is accom- input was determined, and a point heat transfer coeffi-
panied by a higher two-phase flow frictional pressure cient could be calculated. Feed water was boosted from
drop. For a ribbed tube, numerous factors such as tube the tank by a high-pressure plunger pump and heated
diameter, rib parameters, inner surface configuration, by a regenerative heat exchanger and main pre-heater
rib structure, and flow pattern affect the prediction of to obtain the required test parameters. Fluids from the
two-phase flow frictional pressure drop. Over the past test section flowed through the regenerator and con-
years, predictions of two-phase frictional pressure drop denser and then returned to the tank. The bypass was
in micro-fin channels15–17 and small diameter tubes18 used to regulate mass, velocities, and pressures in the
have been proposed. A few investigations have been experiment. The test section and main pre-heater were
conducted on the internally ribbed tubes used in large directly heated by alternating current, with these mod-
capacity boilers. Chen et al.,19 Cheng and Chen,20 and ules themselves functioning as resistance elements. The
Yang et al.4 reported the flow boiling and steam-water heated tubes were enclosed with insulation. In this
two-phase frictional pressure drop in an internally experiment, the overall heated capacity was 840 kW, of
ribbed tube. Kolar21 experimentally investigated the which 180 kW was used for heating the test section.
frictional pressure drop of triangular internally ribbed Two electrical terminal bars, which were constructed
tube and determined that the two-phase frictional pres- from copper plate, were drilled and reamed to fit the
sure drop is in direct proportion to the numerical value tube dimension and finally soldered in place.
of (e/d)0.63, where e is the rib height and d is the equiva- The test tube was a 28.6 mm 3 5.8 mm four-rib
lent inside diameter of the tube. Ackerman22 deter- internally ribbed tube of hydraulic diameter 15.24 mm.
mined that the frictional pressure drop in the adiabatic The rib was in the form of a helix on the inner surface.
ribbed tube is 25% higher than that in the smooth tube. Specifications of the test tube are presented in Table 1.
A few research studies23–26 have also demonstrated that The heated length was 2000 mm, measured between the
the structure of the internally ribbed tube has a signifi- terminal bars. The outer wall temperature of the heated
cant impact on the frictional pressure drop. test tube was measured by 96 thermocouples of F3 mm
The frictional pressure drop correlations of intern- NiCr–NiSi (precision of 0.4 K) connected at 14 cross
ally ribbed tubes vary among the diverse rib types. sections along the length of the test section to identify
Moreover, a number of these correlations were devel- variations in the outer tube wall temperature. These
oped under adiabatic conditions, which differ from thermocouples were calibrated in a water thermostat
Wang et al. 3
Table 1. Specifications of the four-head internally ribbed tube. These pressure transducers were calibrated by the
national authoritative quality inspection department.
Specifications Value Tolerance The mass flow rate was measured by an orifice meter
Outside diameter (mm) 28.6 6 0.15 calibrated by the weighing method. The measuring
Major inside diameter (mm) 15.84 6 0.15 accuracy of the orifice meter was 0.25%. The symbols
Minimum wall thickness (mm) 5.8 + 20%, 20% P and DP represent pressure and differential pressure
Number of ribs 4 – measuring points, respectively. The heated test section
Rib width (circumferential), mm 4.8 6 0.6
was mounted vertically and enclosed with 50 mm thick
Rib width (longitudinal), mm 8.3 6 1.04
Rib height (mm) 0.85 6 0.3 insulation.
Rib side angle (°) 54 + 15, 210 The experiments were performed as per the follow-
Lead (mm) 86.19 6 12.7 ing procedure. The pressure, mass flux, and heat flux
were first maintained constant. Then, the heating pow-
ers of the pre-heaters were increased gradually, which
increased the inlet enthalpy of the test section continu-
system before being used. The adiabatic test section ously. By means of the above operation, parameters
was 2000 mm in length. The electrical heating power including wall temperature and heat transfer character-
was defined as the product of the effective values of the istics of the working fluid were measured under various
voltage and current. operating conditions. The pressure, fluid temperature,
Figures 2 and 3 illustrate the structures of the test mass flux, wall temperature, and electrical input
tubes of the heated test section and adiabatic test sec- were acquired automatically and recorded by an
tion, respectively. The fluid pressure of the test section IMP3595 distributed data acquisition board connected
was measured by the Rosemount 3051 capacitance-type with all the sensors used in the experiments. The
pressure transmitter. ST3000/S900 differential pressure parameter ranges of this study were as follows: the
transducers were used to measure the pressure drop of pressure ranged from 9 to 31 MPa, mass flux varied
the test section. Furthermore, the measuring accuracy from 600 to 1800 kg/(m2 s), and steam quality varied
of the differential pressure transducers was 0.25%. from 0 to 1.
4 Advances in Mechanical Engineering
Figure 2. Test section and thermocouple arrangement for the heated tube.
P
pDl (Ll Lsc )ql + pDn Ln qn + pdzql
x= ð7Þ
Aflow G Hfg
where Dn, Ln, and qn are the inside diameter, heated
length, and heat flux, respectively, of the nth pre-hea-
ter. Lsc is the sub-cooled length within Ll, which can be Figure 4. Effects of pressure on two-phase frictional multiplier
calculated by in heated tube.
be a result of the enhancement of flow disturbance on quality and pressure; the others factors may be ignored.
the wall surface in the two-phase flow region. In the Now, it is feasible to fit the formulas of two-phase fric-
single-phase flow region, the friction factor f was a tional multiplier under heated and adiabatic conditions
function of only the Reynolds number, as follows.
Re = (r u d=m), which is associated with the dynamic The formula of two-phase frictional multiplier f2l0 is
viscosity m; m decreased with the increase in the liquid fitted to the case of the adiabatic internally ribbed tube.
temperature at similar pressure and mass flux. As the Just as in equation (14), rl =rg considers the effect of
inner-wall temperature of the heated tube was higher pressure on f2l0 . Based on the experimental results of
than that of the adiabatic tube, the dynamic viscosity this study as discussed above, the function f (x, P) can
of the heated tube was smaller, Reynolds number of be simplified to f(x), which is a unary function with
the heated tube was higher, and friction factor f of the steam quality x. Referring to Chisholm29 method, we
heated tube was smaller than the respective values of assume f (x) = ½a + bx + cx2 + dx3 and correlate the
the adiabatic tube. function using polynomial fitting; the coefficients a, b,
c, and d could be obtained based on 531 and 474 data
points for the adiabatic and heated tubes, respectively.
Correlations of two-phase frictional pressure drop Based on the multivariate linear regression analysis,
As described before, the two-phase frictional pressure we obtain the following correlation for adiabatic intern-
drop was calculated by equation (6). The two-phase ally ribbed tube
frictional multiplier could be correlated as follows
f (x) = 0:002 + 0:52x + 0:03x2 0:22x3 ð16Þ
f2l0 = DPTP =DPl0 ð12aÞ
The corresponding application conditions are the
where pressure range 9–21.5 MPa and mass flux range 400–
1800 kg/(m2 s). The comparison between predicted two-
DPTP = fTP (l=d) (G2 =rh ) ð12bÞ phase multiplier and experimental data is displayed in
Figure 8. The average error of equation (16) is 5.4%
DPl0 = f (l=d) (G2 =rl ) ð12cÞ
with a standard deviation of 16.9%. In all, 32.2% of
where the test data lie within the 6 10% error band, and the
entire set of test data lie within the 6 40% error band.
rh = rl =(1 + x (rl =rg 1)) ð12dÞ Fitting the formula of two-phase f2l0 in the heated
internally ribbed tube yields
Combining equations (12a)–(12d) yields
f (x) = 0:05 + 0:36x + 0:36x2 0:42x3 ð17Þ
f2l0 = ( fTP =f ) (1 + x(rl =rg 1)) ð13Þ
The corresponding application conditions are the
By introducing a correction factor k, equation (13) pressure range of 9–21.5 MPa, mass flux range 400–
can be expressed as follows 1800 kg/(m2 s), and heat flux range 300–600 kW/m2.
Funding
The author(s) disclosed receipt of the following financial sup-
port for the research, authorship, and/or publication of this
article: This work was supported by the Program for
Innovative Research Team (in Science and Technology) at
University of Henan Province (No. 16IRTSTHN017), Plan
for Scientific Innovation Talent of Henan Province (No.
154100510011), and National Natural Science Foundation of
China (No. 51406026).
References
1. Popov IA, Gortyshov YF and Olimpiev VV. Industrial
applications of heat transfer enhancement: the modern
state of the problem (a review). Therm Eng 2012; 59:
1–12.
Figure 9. Comparison between experimental and calculated 2. Wang QW, Zeng M, Ma T, et al. Recent development
two-phase multiplier using equation (17) for heated tube. and application of several high-efficiency surface heat
exchangers for energy conversion and utilization. Appl
Figure 9 presents the experimentally obtained values of Energ 2014; 135: 748–777.
3. Wang JG, Li HX, Guo B, et al. Investigation of forced
the two-phase multiplier plotted against those obtained
convection heat transfer of supercritical pressure water in
by equation (17). The predictions of equation (17) are a vertically upward internally-ribbed tube. Nucl Eng Des
satisfactory, with an average error of 4.7% and a stan- 2009; 239: 1956–1964.
dard deviation of 11.1%. In all, 53.8% of the test data 4. Yang D, Pan J, Zhou CQ, et al. Experimental investiga-
lie within the 6 10% error band, and the entire set of tion on heat transfer and frictional characteristics of ver-
test data lie within the 6 30% error band. tical upward rifled tube in supercritical CFB boiler. Exp
Therm Fluid Sci 2011; 35: 291–300.
5. Zhu XJ, Wang WS, Xu WH, et al. A study of the hydro-
Conclusion dynamic characteristics of a vertical water wall in a
2953t/h ultra-supercritical pressure boiler. Int J Heat
1. The single-phase frictional factor f in the heated
Mass Tran 2015; 86: 404–414.
tube was lower than that in the adiabatic tube, 6. Xu WG, Wang SY, Zhang QH, et al. Experimental and
while the two-phase frictional multiplier was numerical studies of heat transfer and friction factor of
higher in the heated tube than in the adiabatic therminol liquid phase heat transfer fluid in a ribbed
tube. The values based on the diverse pressure tube. Appl Therm Eng 2016; 95: 165–177.
ranges can be calculated according to correla- 7. Shen Z, Yang D, Mao KY, et al. Heat transfer charac-
tions expressed by equations (16) and (17). teristics of water flowing in a vertical upward rifled tube
2. The pressure significantly affected the two-phase with low mass flux. Exp Therm Fluid Sci 2016; 70:
frictional multiplier. Two-phase frictional multi- 341–353.
plier f2l0 decreased with increasing pressure, and 8. Zdaniuk GJ, Chamra LM and Mago PJ. Experimental
the rate of decrease reduced until the near- determination of heat transfer and friction in helically-
critical pressure region was reached. Steam qual- finned tubes. Exp Therm Fluid Sci 2008; 32: 761–775.
9. Mohsen S, Mofid G and Domiri D. Review of heat
ity affected the two-phase frictional multiplier in
transfer enhancement methods: focus on passive methods
a more complicated manner. With increasing
using swirl flow devices. Renew Sust Energ Rev 2015; 49:
steam quality, f2l0 increased; however, the 444–469.
increase gradient reduced correspondingly. 10. Kareem ZS, Mohd Jaafar MN, Lazim TM, et al. Passive
3. The effect of mass flux on f and f2l0 was weak; heat transfer enhancement review in corrugation. Exp
however, the effect of mass flux on f2l0 in the Therm Fluid Sci 2015; 68: 2–38.
higher steam-quality region was more apparent 11. Bergles AE. Heat transfer enhancement—the maturing of
than in the lower steam-quality region. With an second generation heat transfer technology. Heat Trans-
increase in the mass flux, the two-phase fric- fer Eng 1997; 18: 47–55.
tional multiplier decreased accordingly. 12. Guo LJ, Feng ZP and Chen XJ. An experimental investi-
gation of the frictional pressure drop of steam-water two-
phase flow in helical coils. Int J Heat Mass Tran 2001; 44:
Declaration of conflicting interests 2601–2610.
The author(s) declared no potential conflicts of interest with 13. Srinivasan PS, Nandapurkar SS and Holland FA. Pres-
respect to the research, authorship, and/or publication of this sure drop and heat transfer in coils. Chem Eng 1968; 218:
article. 113–119.
Wang et al. 9
14. Taklifi A, Hanafizadeh P, Behabadi MAA, et al. Experi- Atomic Energy Research Establishment Report M2159.
mental investigation on heat transfer and pressure drop London: HMSO, 1969.
of supercritical water flows in an inclined rifled tube. J 29. Chisholm D. Two-phase flow in pipelines and heat exchan-
Supercrit Fluid 2016; 107: 209–218. gers. London: George Godwin, 1983.
15. Hu HT, Ding GL and Wang KK. Measurement and cor-
relation of frictional two-phase pressure drop of R410A/ Appendix 1
POE oil mixture flow boiling in a 7 mm straight micro-fin
tube. Appl Therm Eng 2008; 28: 1272–1283. Notation
16. Qu WL and Siu-Ho A. Measurement and prediction of A area (m2)
pressure drop in a two-phase micro-pin-fin heat sink. Int
C(x) regression of coefficient
J Heat Mass Tran 2009; 52: 5173–5184.
17. Saisorn S and Wongwises S. Flow pattern, void friction
Cp specific heat at constant pressure
and pressure drop of two-phase air–water flow in a hori- (J/(kg°C))
zontal circular micro-channel. Exp Therm Fluid Sci 2008; D equivalent diameter of the tube (m)
32: 748–760. Dpj average diameter (m)
18. Hu HT, Ding GL, Huang XC, et al. Pressure drop dur- Erib height (m)
ing horizontal flow boiling of R410A/oil mixture in 5 mm F single-phase frictional pressure drop
and 3 mm smooth tubes. Appl Therm Eng 2009; 29: factor
3353–3365. fTP two-phase frictional pressure drop factor
19. Chen TK, Chen XZ and Chen XJ. Boiling heat transfer G mass flux (kg/(m2 s))
and frictional pressure drop in internally-ribbed tubes: heat I heating current (A)
transfer: second international symposium, vol. 1. New
K correction factor
York: Hemisphere Publishing Corporation, 1992,
pp.621–629.
L length (m)
20. Cheng L and Chen T. Flow boiling heat transfer in a ver- P pressure (MPa)
tical spirally internally-ribbed tube. Heat Mass Transfer Q heat flux (kW/(m2 s))
2001; 37: 229–236. Re Reynolds number
21. Kolar V. Heat transfer in turbulent flow of fluids through T temperature (°C)
smooth and rough tubes. Int J Heat Mass Tran 1965; 8: U heating voltage (V)
639–653. X steam quality
22. Ackerman JW. Pseudo-boiling heat transfer to supercriti-
cal pressure water in smooth and ribbed tubes. J Heat DP differential pressure (MPa)
Transf 1970; 92: 490–498. DPTPf two-phase frictional pressure drop (MPa)
23. Chen LX and Chen TK. Study of vapor liquid two-phase DPl0 single-phase saturated-water frictional
frictional pressure drop in a vertical heated spirally pressure drop (MPa)
internally-ribbed tube. Chem Eng Sci 2007; 62: 783–792. m dynamic viscosity (N s/m2)
24. Xiong DJ, Wang MH and Zhu CG. Flow Characteristics n kinematic viscosity (m2/s)
of the two phase water and steam flow within a f2l0 two-phase frictional multiplier
quadruple-lead ribbed tube. Power Eng 1983; 3: 20–26. r density of fluid (kg/m3)
25. Chen TK, Chen XZ and Chen XJ. Research on frictional
pressure drop of high pressure steam-water two-phase
flow in ribbed tubes. Power Eng 1989; 9: 10–15. Subscripts
26. Zheng JX, Chen TK and Luo YS. Investigation on the 1 first cross section
characteristics of internally rifled tubes two-phase flow
2 second cross section
friction pressure losses in sub-critical and near critical
pressure region. Power Eng 1995; 15: 56–63.
o outlet
27. Blasius H. Das Ahnlichkeitsgesetz bei Reibungsvorgan- i inlet
gen in Flussigkeiten. Forschg Arb Ing Wes 1913; 134: g gas phase
1–41. l liquid phase
28. Hewitt GF and Roberts DW. Studies of two-phase flow
patterns by simultaneous x-ray and flash photography.