Professional Documents
Culture Documents
Contribution by T. N. W. Akroyd, LL.B., loose bulk density of a single-size closely graded aggre-
M.Sc.(Tech.), A.M.LC.E., A.M.I.Struct.E. gate must depend on three properties: a surface effect
(Constructional Services Limited) due to roughness and angularity, the specific gravity
Dr Murdock's interesting paper describes what is of the aggregate, and the manner in which the aggre-
undoubtedly a further important step in the develop- gate is compacted. If the aggregate is compacted into
ment of concrete mix design. a mould in a uniform manner, a factor can be derived
The problem in mix design is that of knowing what which will be a measure of the surface effect, that is the
aggregate grading and aggregate/cement ratio are re- roughness and angUlarity. This, of course, is
quired with a given water/cement ratio to produce the Shergold's (2) test. If, however, the test is made in a
required workability. It is clear that the water in con- different manner, a different measure of angularity will
crete which will affect workability is the free water, be obtained. This fact appears, at one time, not to
that is the water which is not used up in filling the have been fully appreciated by Dr Murdock who has
pores in the concrete or in mixing with the cement suggested that the angularity index can be determined
powder. Singh in his paper(1) took cognizance of the by using the compacting factor apparatus. (3)
water/cement ratio necessary to give a cement paste of I have had a number of tests carried out in which
standard consistence in the manner now adopted by angularity factors were measured by these twu dif-
Dr Murdock but, even though these facts were known, ferent methods, and the results are given in Table I.
there was still a missing link, namely, the influence of From this Table, it appears that the angularity fac-
aggregate grading and aggregate shape. Dr Murdock's tors measured by the two methods are not inter-
paper supplies this link and deals with two important changeable. Furthermore, there seems to be no signi-
concepts, namely particle size and particle shape. Al- ficant relation between the two, although there is a
though I agree with Dr Murdock that the use of speci- relation between the percentage voids determined by
fic surface places too much emphasis on the smaller these two methods, as is shown in Figure I. The rela-
particle sizes, it is still possible to determine a relation tion previously obtained by Kaplan (4) is also shown
between workability and specific surface as was done in this Figure. Whilst these do not agree, it is clearly
by Singh in his paper. possible to use the compacting factor apparatus as
The surface index proposed by Dr Murdock gives long as a correction is applied to the voids ratio before
due weight to the sand sizes which, in normal con- the angularity index is calculated.
creting practice, appear to be important. It is a little From a limited number of tests, it appears that the
difficult to attach physical significance to the constant angularity may be determined by compacting the dry
added to the summation of surface indices in Table 1 aggregate in the compacting factor mould by vibrating
of Dr Murdock's paper. The historical derivation of it on a vibrating table. This result might be expected
this constant explains its presence, but there seems since the method proposed by Shergold ensures that
little reason why the actual value of the revised surface the maximum bulk density is obtained. The reproduc-
index should not be used without this constant. ibility of the angularity index appears to be better
With regard to the particle shape, it is clear that the when the compacting factor method is used than when
the Shergold method is used or when the results are
obtained by vibrating. Incidentally the determination
*Pages 135-144 of Magazine No. 36. of the angularity factor on each of the single.sizes of
79
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Magazine of Concrete Research: Vol. 13, No. 38 : July 1961
:/:V-~
o:i
5 -- I- -- - - -
-0
.~
~
I 1·0 0 -----,-- ._-
>- 0
>- /relatlon established
~
V
:3'":::>
by Kaplan
/'
._-
"«z 35
-/
---
0·9 5
~ 2"/
0·9 0
. I!f
.1ii.~~
/e
e
30 35 40 45 50 55 60
.
l£
AN G U LA RITY -% voids by compacting factor apparatus
. ft.'" 'i"V III!!
J'<
Figure I: Relation between angularity (as percentage voids) 0·8 5 - - .' oft
measured by the British Standard method and measured by the o'" ~.
}.
>- e
compacting factor apparatus. u
P-
«
~
"z 0·8 o
/
A
V
Fine aggregate: o Ham River • others
larity index is that theoretically one needs to know the Grading of fine aggregate:
values of Is and fa before the mix can be designed, o -!6--1OO
0'6 5 " 7-100,14-100,25-100 or 52-100
whereas in fact they are only known afterwards. This " 7-14 w"h 52-100
is overcome by means of the usual engineering guess- o 7-52,14-52,25-52,7-25 or 14-25
Nominal aggregate/cement ratio:
estimate but it does give weight to a criticism of 1 I 41:3 .0'1:4t 01:6 Q 1:7t -0- 1:9
0'60
Dr Murdock's method, that it is like other methods -2 10 12
of mix design such as the Road Note 4 method: it is (c I e-0·04[w((aOla G a +- hOlh G h -1-3 ,000cj---()'00028] x10 6
80
1·8
'"
<{
I-
'"0 <2
I-
I: <{ 1·6
~ '"
I-
~
sand 23 Z
0
0
~''i-_-=>'=l=--.£'--::t==______t~-=--~(NO. 200-No. 28) w
I: 1·4
w
> U
w ;;
"
<(
I-
w
I-
<{
1·2
Z sand 3 :?;
w
U (No. 200-No. 4)
'"
W
1·0
---
0..
0·8
0 1
-- 2
SAND/CEMENT RATIO
SAND/CEMENT RATIO (by absolute volume)
(b)
(a)
400, i.e. a little coarse but not unreasonable for this (1) The water required to give a critical consistence
application. e is the specific volume of the aggregate for the cement alone (equal to a water/cement
passing B.S. sieve No. 120. Different types of coarse ratio of around 0·25 as above).
aggregate give slightly different curves, so that a (2) The addition of saturated, surface-dry sand to the
further factor for the particle shape of the coarse cement paste stiffens the mixture as the result of
aggregate, • different from the angularity factor, (1.(1> a " boundary effect". This is the normal effect of
must be introduced to obtain a single curve. This reducing the bulk density of a granular material
agrees with Dr Murdock's item (2) on .page 135. by increasing the boundary surfaces. If the bulk
The point I wish to emphasize is the complex nature density of the cement is reduced, the voids are in-
of the workability relation. Introduce enough arbitrary creased so that more water must be added to
parameters and it is usually possible to obtain a restore the original consistence and eliminate air
reasonably accurate mean relation for almost any- voids.
thing. This in no way detracts from the ingenious way (3) Further addition of sand eventually reduces the
in which Dr Murdock has made his assumptions in spacing between the sand grains to little more than
order to obtain a relation which is quickly and easily the particle size of the cement. Distribution of
applied, but let us not forget that many other basic cement between the sand becomes restricted and
assumptions can be made to obtain just as accurate a further effect, that of " particle interference",
a relation. occurs when more sand is added. Further water
I strongly endorse the view, given on page 138, must therefore be added to make good these
" that workability should be assessed on the basis of additional voids in the cement.
the volume of the constituents of the concrete". I The foregoing effects are illustrated in Figure lIJa
have never understood why greater use of absolute which has been taken from Weymouth's paper(8).
volumes has not been made in Britain. This concept Curve w/c represents the reduction in voids due to the
is also extremely advantageous for other properties reduction in the volume of cement paste, per unit
of concrete besides workability. volume of mortar, as the sand is added. The difference
The simple Vicat test which" simplifies the problem between this curve and the appropriate curve B is the
of determining the water content available for lubrica- "boundary surface" effect while the difference be-
tion of the mix" (page 139) is usefully applied but is tween the actual curve and curve B is the " particle
a little misleading to the reader. The implication is that interference" effect.
the water requirement of the cement is constant at Figure IlIa can be replotted in the form shown as
around 0·25 for all aggregate contents. This is not Figure IIIb. It is now evident that the total" lubrica-
true, of course. tion " requirement of the cement varies approximately
Talbot and Richart(7) and Weymouth(8) showed linearly with b/e over the practical range for sand 3,
that there are three factors to consider when adding a normal well graded sand. Sand 23 is much finer so
aggregate to cement paste, for a given" basic" con- that well designed mixes require a smaller proportion
sistence. for a given total aggregate/cement ratio (i.e. A,,). Sand
81
82
0·70 o· 75 0·80 0·85 0·90 0·95 1·00 1·05 1·10 1·15 1· 20 1'25,
CALCULATED COMPACTING FACTOR BASED UPON TOTAL WATER/CEMENT RATIO
Figure IV: Comparison between compacting factors measured at the Building Research Station
and values calculat'!d according to Dr Murdock's formula, on the basis of total water/cement ratio.
1·00
0·95
'"0
f-
U
«
~
0·90
"z
;::
u
«0-
0·85
L
0
U
-'
«
u 0·80
;::
u +
«
'"
0- 0·75
+
0
0'70~--~~--~----~----~~---L-----L-----L----~----~----~--~
0·50 0·55 0·60 0·65 0·70 0·75 0·80 0·85 0·90 0·95 1·00 1·05
Figure V: Comparison between compacting factors measured at the Building Research Station and
values calculated according to Dr Murdock's formula, on the basis ()( water/cement ratio modified
to allow for the full absorption of the aggregate.
It is considered that the large difference between the values of the surface index (j~) which have been ob-
experimental results obtained at the Building Research tained from the criterion of" best fit " for a given set
Station and the calculated compacting factors, as of data should not be more generally us,d.
shown in Table 6 of the paper and in Figures IV and V, In the outline of mix design procedure, Dr Murdock
are due to the fact that Dr Murdock's values of the has not explained how the suggested val.ues of j~ for
" surface index" do not reflect the relative importance the different maximum sizes of aggregate were ob-
of the different size fractions in the grading of the tained. The procedure also implies that.is should be
aggregate. As the result of the computer analysis, he constant irrespective of the aggregate/cement ratio;
has removed the emphasis from the importance of the although it is generally recognized that leaner mixes
finer sizes in mix design, and it is now difficult to require a higher sand content, which would increase
associate the true surface area of a graded aggregate the over-all specific surface, and it would appear that
with his surface index (is). From the evidence in Table the surface index f.. should also be increased in a
6 and in Figures IV and V, it is suggested that the similar way.
83
84
R5
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Magazine of Concrete Research.' Vol. 13, No. 38 .' July 1961
Imperial College has shown that, for complete satura-
tion to occur, air-dry aggregates must be completely
immersed in water. Addition of the absorbed water I·O,------,-----r----,----,-- -------v:-i-,-0,-----::1
0
only, before mixing, does not guarantee saturation. , ,'
Admittedly the effect on workability is small com-
pared with the effect on strength.
These criticisms are not intended in any way to
detract from the value of the paper. An approach
similar to Dr Murdock's is required if a single design "
Z
I-
procedure covering all concrete mixes is to be de-
veloped. By extending the compacting factor relation
..
U
«
1:
0-7
o
to include the properties of mobility and stability of U
Contribution by W. E. Murphy, B.Sc.(Eng.) Figure VII: Relation between compacting factor and
10 (W/C - O'25)!fs/a(A v - 2) for the first series of C & C A
(Cement and Concrete Association) tests.
Dr Murdock has developed a very interesting and
useful formula relating the compacting factor of fresh
concrete to the properties of the aggregates, the mix
proportions and the water/cement ratio. This formula adopted should be the highest water/cement ratio that
has been examined in connexion with a few mixes will prevent complete penetration of the Vicat plunger
made at the laboratories of the C & C A at Wexham into a neat cement-water paste. This seems equivalent
Springs in the course of other investigations. The first to stating that the figure to be used is the standard
series of mixes contained i in. maximum size irregular consistence of the cement as determined in accordance
gravel, natural sand and a uniform consignment of with B.S. 12:1958. The standard consistence of the
ordinary Portland cement. The series consisted of four cement used in this series of tests was 0·28 and Figure
sets of four mixes, the different sets having aggregate/ VIII shows that the points obtained on plotting the
cement ratios of 3, 4t, 6 and 7t by weight respectively. values of compacting factor obtained to a base of
The water/cement ratios of the four mixes of each 1O(w/c-0'28)/lsliA v -2) lie more closely about a
richness were varied to give a range of workability. single straight line. This offers some evidence that
The gradings of the sand and the coarse aggregate Dr Murdock's formula can be generalized by stating
were maintained constant, but the sand fraction of the that the compacting factor is a function of .
total aggregate was varied as considered necessary for
each mix. lO(w/c - sJ
Ish(Av - 2)··············· . (4a)
The aggregates were soaked in the mixing water for
24 h before the cement was added; the partially com- where Sc is the standard consistence of the cement.
pacted weight for the compacting factor test was deter- The mixes described above made possible an .exam-
mined at times of 3 and 60 min after mixing. Assuming ination of the results obtamed on applying formula 4
that the compacting factor decreases approximately to mixes of various richnesses. A further series of test
linearly in respect to the logarithm of the time after results has been examined to assess the result of apply-
mixing, the average of the two test results was regarded ing the formula to mixes containing aggregates of
as the workability at a time of 13t min after mixing. differing maximum size. The mixes were made with
Figure VII shows the graph obtained when the 16 different water/cement ratios to cover a range of
values of compacting factor obtained are plotted workability, there being a total of 46 mixes. All the
against 1O(w/c-0·25)1!s!a(A v -2). From formula 4 of mixes were made with an aggregate/cement ratio of
Dr Murdock's paper, the points would be expected to 6·0 by weight.
lie close to a single straight line. In fact, it isevident The aggregate for each batch was covered with the
that they are scattered to a considerable extent, there mixing water for 15 min; the partially compacted
being a distinct tendency for the compacting factor of weight for the compacting factor test was measured 3,
a lean mix to be higher, for a given value of 15 and 30 min after mixing and the average of the
1O(w/c-0'25)lfs[a(A v -2), than that of a rich mix. three values was regarded as the workability 11 min
Dr Murdock has suggested that the formula could after mixing.
be improved by varying the constant deducted from The standard consistence of the cement used in this
the water/cement ratio according to the characteristics investigation was again 0·28 and so, if formula 4a is
of the cement. He suggests that the figure to be assumed to apply, the values of compacting factor ob-
86
1·0
- - - - - - -0·02
0·9
l"~;y'.~/"i=JJ.--- -0·04
o'"
>-
~ o·s
"z
>-
~ 0·7
""
~
:E -- - ----" Aggregate
o I Max. % sand
U
TO
I size
I
in. 30 40 50
0·6 - 0·6
I I
" •
G 3 It ~
[] -It ! []
• ~
0·5
0 0·1 0·2 0·3 0·4
A
V
0·5
6
7,
0·6 0·7 0·1 0·2 0·3 0·4 0·5
$
0·6
••
o·sL-_---L_ _----1.._ _---'--_ _- ' - _ . L . - . L . - . L . - - ' - - - ' - - _ - : : '
o 0·7
I O(wlc-'!· 28)/1,/. (A ,-2) I 0(wlc-'!·28)//,1. (A,-2)
Figure VIII: Relation between compacting factor and Figure IX: Relation between compacting factor and
10 (W/C - O·28)/lsfa(A y - 2) for the first series of C & C A W(w/c - O·28)lfsfa(Ay - 2) for the second series ofC & C A
tests. tests.
87
Surface index for particles between Example of calculation for R.R.L. Grading
Sieve sizes sieve sizes indicated No. I, I i in. maximum size
between which
particles lie Dr Murdock's values Alternative values Percentage of particles
Is Is' within sieve range Is Is'
3 in.-U in. 0·8 - - - -
Ii in.-! in. 1·3 I 50 65 50
t in.-l in. 2·3 3 14 32 42
I in.-{. in. 4·3 5 12 52 60
l. in.-No. 7 7·3 7 6 44 42
No.7-No. 14 10·3 9 6 62 54
No. l4-No. 25 12·3 II 5 61 55
No. 25-No. 52 12·3 12 4 49 48
No. 52-No. 100 10·3 10 3 31 30
Passing No. 100 5·3 5 - - -
Total 396 381
x 10- 3 = X 10- 3 =
0·396 0·381
factor of a mix having a cement of unknown standard adding a constant of 330 to the sum of the component
consistence would appear to be given by the formula indices. The scatter of the results plotted in Figure I
of the paper, however, appears to be such that the
lO(W/C - 0'29)
c1 = 0·7
( 4.
. FIa(Av - 2)
+ 0·73 ) .......... (5b) surface indices could be represented by a series of
simple integers. As an example of a possible alternative
set of values, the surface indices of the gradings used
In connexion with the use of the information given
in the series of tests mentioned above were calculated
in the paper for the design of concrete mixes, Dr
using the second set of values quoted in Table II. From
Murdock suggests that the angularity index of the
the results of the tests on all the 62 mixes discussed in
aggregate may be assessed approximately from the
this contribution, it appeared that the measure of
examples he quotes or, more exactly, may be deter-
agreement between calculated and actual values of
mined by tests. If values are taken from Table 2 or
compacting factor was not significantly affected by
3 of the paper, the subsequent error in compacting
using these alternative vaJues of surface index.
factor may be 0·08 or more since, for example, the
Dr Murdock has suggested values for the desirable
angularity indices of crushed limestones tested at
surface index of combined aggregate depending upon
Wexham have ranged up to 2·65 compared with the
the maximum size and the expected variation in grad-
author's value of 2·05 for Mendip limestone. If tests
ing of the component materials. The optimum value
are made, it would appear to be unnecessary to test
would also be expected to depend on the workability
each half-size present in the material to be used and
of the concrete and the richness of the mix as well as
it would be of interest if Dr Murdock could give some
the handling conditions. In view of this it would be
guidance as to the number of sizes that should be
interesting to have Dr Murdock's views on the follow-
tested to assess the over-all angularity index of a
ing procedure. First the water/cement ratio is deter-
graded material.
mined from considerations of strength and durability
Perhaps one of the most interesting parts of the
and, if the required compacting factor is less than 0'84,
paper is that dealing with the calculation of surface
one of the following empirical formulae is used to
index, since the figures quoted can be used in any
determine the' optimum value of surface index.
method of mix design which necessitates the deter-
For aggregate of It in. maximum size:
mination of the proportions in which to combine
available aggregates to give a grading equivalent to f; = 0·25cJw/c + 0·40 ... , ................ (6)
that assumed in the course of the design procedure. For' aggregate of! in. maximum size:
Dr Murdock has implied that some improvement in f;· = 0·25cfw/c + 0·45 .................... (7)
his method of design may be possible if the given
For aggregate of ~ in. maximum size:
values are modified in the light of further experimental
evidence. In view of this, it would be interesting if he /, =', 0·25cJw/c + 0·55 .................... (8)
could give some guidance on how his figures were ob- If the required compacting factor is greater than
tained. It is apparent, as indicated in Table II, that the 0'84, the values of surface index obtained from the
values he quotes for the various single sizes are effec- above formulae would probably only be suitable if
tively 0'8, 1'3, 2·3 ... 5·3 and that the arithmetic has the aggregate grading could be expected to be partic-
been simplified by reducing eaCh value by 3·3 and ularly uniform and conditions were such as not to
88
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Discussion
encourage segregation. Under less favourable condi- angularity indices which can be obtained with crushed
tions it would be advisable to increase the values of limestones. Whilst it will be evident that much further
surface index by up to (cI12 - 0·42), the amount of information is now needed on the angularity of aggre-
the increase depending on the conditions in any gates, I suggest for the moment that one or two tests
particular case. on, say, the coarsest and finest sizes of coarse aggregate
should be sufficient.
I also agree with Mr Akroyd that the angularity
Reply by the author determination is tedious if done on all the single sizes
It is gratifying to find that several contributors to of sand. I suggest that a fair approximation might be
the discussion have indicated a considerable measure obtained by taking, say, two or perhaps three sizes
of agreement with the new approach which I put only.
forward. In my reply 1 will deal as fully as possible Sand supplied in the Thames Valley is apt to contain
with the many points they have raised. angular particles owing to the inclusion of crushed
I agree with Mr Akroyd that a relation can be estab- material returned from the crushers which deal with
lished between workability and specific surface, but oversize material for which there is no demand. In the
this breaks down when mixes are used in which the tests described in my paper, a great deal of trouble was
maximum size of aggregate is varied, or the proportion taken to obtain sand which did nat contain crushed
of fine aggregate passing a No. 100 sieve is varied, and particles. In practice, the presence of varying quan-
is true for one particle shape only. The increase in tities of crushed particles can affect the workability
specific surface with increase in angularity does not quite substantially; in fact, inspection of the suggested
appear to be related to the decrease in compacting formula and the comparative range in values for sur-
factor which occurs. In my opinion, the intermediate face indices and angularity indices would appear to
sizes provide more resistance to mobility in the con- suggest that changes in angularity are likely to be of
crete than the finer sizes; if the specific surface is greater importance than changes in grading.
regarded as the index of grading, this effect is not I do not understand Mr Akroyd's reference to the
accounted for. The values obtained for the surface values or.!' and fa only being known after the mix has
index seem to be in keeping with my view. been designed. It is usual to do a sieve analysis of
As Mr Akroyd says, it is difficult to attach physical aggregates to be used in concrete before designing the
significance to the constant added to the summation mix, and tests could be done for j~ at the same time.
of indices in Table 1, except that its effect is to reduce An alternative method of dealing with the question of
the influence of aggregate grading in the relation I angularity is to make up a trial mix and measure its
have established. Further research may suggest a re- compacting factor. With the other variables already
finement of the values I have obtained. From the known, a value for fa can then be calculated and used
analyses I have made with a number of combinations to determine the influence of variations in mix propor-
of values of surface indices, and from the compara- tions and grading from those used in the trial mix.
tively small improvement obtained by taking the com- Dr Hughes has presented interesting data which,
puter values, compared with those used in the original allowing for the difference in approach, do not appear
analysis, it does not seem that the actual values are to contradict the evidence produced in my paper. The
very critical, provided they follow the general form of main object of my paper was to establish the dominant
the curves given in Figure 1. factors influencing workability and to explain their
Mr Akroyd comments on the method of measuring interrelation in as simple and logical a manner as
particle shape or angularity. He is quite correct in possible. By doing so, I hope that, while I have estab-
stating that the method adopted was that suggested by lished a mathematical relation for use with the com-
Shergold and that a different value is obtained by the pacting factor, the basic principles put forward may,
compacting factor apparatus. Unfortunately, there with suitable adjustment, be applied with other
was an error in early copies of Concrete Materials and methods of assessing workability. I think this is where
Practice regarding this point; later copies contain a the approach I have made differs from that suggested
correction slip. Since the compacting factor method is by Dr Hughes, who, in his published paper u» includes
less variable, I think it may be more acceptable, pro- the following sentence: " Unfortunately, the relations
vided a correction is made. I suggest this might be: obtained for the workability of concrete were too
V = 0'7Va + 5·5 complicated for general application to mix design".
Reference is made to Talbot and Richart (7) and
where V is the percentage voids by Shergold's method
Weymouth'sIS) work on cement mortars. The curves in
Va is the percentage voids by the compacting Figure IlIa suggest to me that the boundary effect
factor method chiefly influences mixes with sand/cement ratios richer
This gives good agreement with the relations estab- than 2. With the addition of more sand, particle inter-
lished by Akroyd and Kaplan. ference occurs. In my paper, however, I have not
Mr Murphy has indicated the range in values of attempted to deal with very rich mixes and, in fact,
89
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Magazine of Concrete Research.' Vol. f3, No. 38 .' July f96f
the richest mix for which I made tests was I: 3t Whilst absorptions at 24 h were generally of the same
cement: total aggregate. order as were obtained by Mr Newman, it will be noted
Dr Hughes and Mr Newman refer to the question that the rate of absorption changes with particle size.
of segregation, to which reference was made in Table The rate of absorption also varies between different
5. This was in all cases associated with a surface index samples of aggregate obtained at different times.
of 0·50 or less, and resulted from a deficiency of fines. I think the scatter which Mr Teychenne has obtained
Reference is made to this point again towards the end is attributable mainly to the following.
of this reply. (1) The change in rate of absorption with particle size
The tests at Southall included a few mixes which affects the average rate of absorption according to
might be regarded as grossly over-sanded, the max- the combined grading of the aggregate, so that the
imum sand content used being 73 %. There was a effective water/cement ratio is also affected.
tendency to underestimate the compacting factor for (2) The rate of absorption of water by the aggregate
these over-sanded mixes. All the trial mixes ~eferred to in the presence of cement paste may be affected by
on page 141 are given in Research and Application, both the water/cement ratio and the mix propor-
since there are three different water/cement ratios for tions.
each mix number. (3) Some gradings as, for instance, gap gradings with
The fact that Mr Teychenne, in the tests made at fine sand are sensitive to quite small changes in
Building Research Station, has not obtained good water/cement ratio. Likewise, the richer the mix,
correlation with my approach is not surprising, in view the smaller the change in water/cement ratio
of the method adopted in making the tests. My con- needed to alter the workability from low to high.
fidence in my approach was considerably enhanced by Figures IV and V suggest that there is greater
the fact that correlation with the data given in Road scatter for the richer mixes.
Note No.4 was as good as I had obtained with tests In order to overcome this difficulty of absorption of
at Southall. In my paper, only two examples are given water by the aggregate, I consider it essential to begin
in Figures 2 and 3, but the correlation was equally mixing with a saturated aggregate. In my tests, I added
good for other mix proportions and water/cement sufficient water to bring the aggregate to a saturated,
ratios included in Road Note No.4. In his contribu- surface-dry condition half-an-hour before adding the
tion, Mr Murphy has also obtained satisfactory agree- cement, as is stated in the paper. This was a practical
ment with my formula in tests made at the Cement and compromise arising from the evidence available when
Concrete Association. the tests were done, which suggested that the absorp-
The reason for the scatter and the discrepancy be- tion by the aggregate would be almost complete in
tween the results Mr Teychenne has obtained and all that time. The effective water/cement ratio may then
these other results lies, I think, in his use of dry aggre- be taken as the added water. Mr Newman's comment
gate without preliminary soaking, followed by mea- that air-dry aggregates must be completely immersed
surement of the compacting factor 10 min after mixing. to obtain complete saturation is worth noting.
As a result, the effective water/cement ratio, in so far I cannot agree with Mr Teychenne that the difference
as workability is concerned, is somewhere intermed- between the Building Research Station results and
iate between the total water/cement ratio and that mine is due to the fact that the values of the surface
modified to allow for complete absorption by the index do not reflect the relative importance of different
aggregate. size fractions in the grading of the aggregate. As in-
Mr Newman has shown (19) that Thames Valley dicated in my reply to Mr Akroyd, I consider that the
aggregate absorbs in 10 min roughly 60 to 80 % of the surface index provides a compromise between the in-
maximum absorption capacity at 24 h. He further fluences of surface area, and other factors such as
states that" from the strength results, it is apparent frictional resistance and particle interference. My ap-
that the coating of cement paste. slows down the rate proach is, of course, empirical and further research
of absorption in concrete mixes". I share his view on may sort out the relative influences of these other
this. factors.
In tests on one batch of Thames Valley aggregate, I Mr Newman comments on the limitations of the
have obtained the following values for the absorption compacting factor apparatus in providing a measure
of four different gradings, expressed as a percentage of of workability. He mentions mobility and stability.
the absorption capacity at 24 h. One might add ease of finishing (as, for instance, in
roadwork) and possibly other desirable properties. I
Particle size 10 mill 30 min
3' 3'
have used the compacting factor as a measure because
:{ 111'-8 111 . 71 89 it has seemed to me the most useful and practicable
3' 3'
If 111'-16 111. 96 97 single test providing a guide to workability for the
-& in.-No.
7 83 92 type of concrete mix widely used in practice. I agree
No.7-No. 100 (fairly well with him that a single test method giving a better
graded) 82 91 assessment of all the desirable properties will be a
90
91
mixed mortars and concretes. Proceedings of the American strength concrete mixes. Proceedings of a Symposium on
Society jor Testing Materials. Vol. 38, Part II. 1938. mix design and quality control of concrete, London, May
pp. 354-372. 1954. London, Cement and Concrete Association, 1955.
9. NEWMAN, A. J. and TEYCHENNE, D. c. A classification of pp.55-73.
natural. sand and its use in mix design. Proceedings of a 18. MURDOCK, L. J. Concrete materials and practice. 3rd edition.
Symposium on mix design and quality control of concrete, London, Edward Arnold (Publishers) Ltd, 1960. pp.
May 1954. London, Cement and Concrete Association, 89-115.
1955. pr. 175-194. 19. NEWMAN, K. The effect of water absorption by aggregates
10. POWERS, T. c. Studies of workability of concrete. Journal on the water/cement ratio of concrete. Magazine of
of the American Concrete Institute. Vol. 3. February 1932. Concrete Research. Vol. 11, No. 33. November 1959.
pp.419-448. pp. 135-142.
92
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.