You are on page 1of 14

Discussion on articles published in the

Magazine of Concrete Research


Volume 12, Number 36 : November 1960

The workability of concrete*


by L. J. Murdock, M.Sc., Ph.D., M.LC.E.

Contribution by T. N. W. Akroyd, LL.B., loose bulk density of a single-size closely graded aggre-
M.Sc.(Tech.), A.M.LC.E., A.M.I.Struct.E. gate must depend on three properties: a surface effect
(Constructional Services Limited) due to roughness and angularity, the specific gravity
Dr Murdock's interesting paper describes what is of the aggregate, and the manner in which the aggre-
undoubtedly a further important step in the develop- gate is compacted. If the aggregate is compacted into
ment of concrete mix design. a mould in a uniform manner, a factor can be derived
The problem in mix design is that of knowing what which will be a measure of the surface effect, that is the
aggregate grading and aggregate/cement ratio are re- roughness and angUlarity. This, of course, is
quired with a given water/cement ratio to produce the Shergold's (2) test. If, however, the test is made in a
required workability. It is clear that the water in con- different manner, a different measure of angularity will
crete which will affect workability is the free water, be obtained. This fact appears, at one time, not to
that is the water which is not used up in filling the have been fully appreciated by Dr Murdock who has
pores in the concrete or in mixing with the cement suggested that the angularity index can be determined
powder. Singh in his paper(1) took cognizance of the by using the compacting factor apparatus. (3)
water/cement ratio necessary to give a cement paste of I have had a number of tests carried out in which
standard consistence in the manner now adopted by angularity factors were measured by these twu dif-
Dr Murdock but, even though these facts were known, ferent methods, and the results are given in Table I.
there was still a missing link, namely, the influence of From this Table, it appears that the angularity fac-
aggregate grading and aggregate shape. Dr Murdock's tors measured by the two methods are not inter-
paper supplies this link and deals with two important changeable. Furthermore, there seems to be no signi-
concepts, namely particle size and particle shape. Al- ficant relation between the two, although there is a
though I agree with Dr Murdock that the use of speci- relation between the percentage voids determined by
fic surface places too much emphasis on the smaller these two methods, as is shown in Figure I. The rela-
particle sizes, it is still possible to determine a relation tion previously obtained by Kaplan (4) is also shown
between workability and specific surface as was done in this Figure. Whilst these do not agree, it is clearly
by Singh in his paper. possible to use the compacting factor apparatus as
The surface index proposed by Dr Murdock gives long as a correction is applied to the voids ratio before
due weight to the sand sizes which, in normal con- the angularity index is calculated.
creting practice, appear to be important. It is a little From a limited number of tests, it appears that the
difficult to attach physical significance to the constant angularity may be determined by compacting the dry
added to the summation of surface indices in Table 1 aggregate in the compacting factor mould by vibrating
of Dr Murdock's paper. The historical derivation of it on a vibrating table. This result might be expected
this constant explains its presence, but there seems since the method proposed by Shergold ensures that
little reason why the actual value of the revised surface the maximum bulk density is obtained. The reproduc-
index should not be used without this constant. ibility of the angularity index appears to be better
With regard to the particle shape, it is clear that the when the compacting factor method is used than when
the Shergold method is used or when the results are
obtained by vibrating. Incidentally the determination
*Pages 135-144 of Magazine No. 36. of the angularity factor on each of the single.sizes of

79
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Magazine of Concrete Research: Vol. 13, No. 38 : July 1961

TABLE I Contribution by B. P. Hughes, Ph.D., B.Sc.


(John Laing & Son Ltd)
Angularity index fa'
I should like to refer to the very interesting paper
determined by
by Dr Murdock on the workability of concrete. The
Compacting
relation for the calculation of compacting factors
Material Size B.S. 812 factor
method apparatus should prove most useful because of its ready and
simple application to mix design. There are one or
Slightly rounded i-i in. 1'44 2·24 two items, however, which appear to require some
flint gravel i-1'\' in. 1·87 -
clarification.
Irregular flint i-i in. 1·91 2·77 Dr Murdock states on page 136 that" . . . all
gravel A
attempts to include the surface area coefficient of
Irregular flint *i-1 in. 2·08 3·04
gravel B 2·47 3'14
cement in assessments of workability have failed. For
i-f. in.
this reason, the surface area coefficient of the cement
Angular granite i-I in. 2·62 HO
has previously been neglected, although this appeared
Crystalline i-i in. 2·53 3·95 illogical". I entirely agree that the cement should be
limestone
considered together with the aggregate. This has been
,\- in.-No. 7 2'47 3-44 done in Figure II, which shows a relation 1 obtained
No.7-No. 14 2·47 3·38
a few years ago at the University of Birmingham (5).
Quartz sand No. 14-No. 25 2·25 3·15
No. 25-No. 52 1-62 2·56 The degree of scatter appears directly comparable
No. 52-No. 100* 1·84 - with that for Dr Murdock's relation. In my notation,
a, b, c and ware the specific volumes (gross apparent
·Proctor compaction mould used. volume per unit volume of concrete) of the coarse
aggregate, fine aggregate, cement and water respec-
5 tively(6), whilst rx.aGa and rx.bGb are forms of surface area
coefficient of the coarse and fine aggregate respec-
-0 tively. The value of 3,000 indicates a surface area
-5 50
E expected of particles between B.S. sieve Nos. 200 and
vi

:/:V-~
o:i
5 -- I- -- - - -

-0
.~

~
I 1·0 0 -----,-- ._-
>- 0
>- /relatlon established

~
V
:3'":::>
by Kaplan
/'
._-
"«z 35
-/
---
0·9 5

~ 2"/

0·9 0
. I!f

.1ii.~~
/e
e
30 35 40 45 50 55 60
.

AN G U LA RITY -% voids by compacting factor apparatus
. ft.'" 'i"V III!!

J'<
Figure I: Relation between angularity (as percentage voids) 0·8 5 - - .' oft
measured by the British Standard method and measured by the o'" ~.

}.
>- e
compacting factor apparatus. u
P-
«
~

"z 0·8 o

sand is somewhat tedious and in normal practice I


>-
u
ip·f!J
doubt whether it would be carried out. The results
that we have obtained, however, appear to give a
«0..
:;:
8 0·7 5
j -
I
~ ~,
somewhat higher value for Thames Valley sand (ex d% ¢ A

/
A

Ham River) than that obtained by Dr Murdock.


One drawback with the use of the surface and angu- o· 7 0
V Coarse aggregate: Ham River

V
Fine aggregate: o Ham River • others
larity index is that theoretically one needs to know the Grading of fine aggregate:
values of Is and fa before the mix can be designed, o -!6--1OO
0'6 5 " 7-100,14-100,25-100 or 52-100
whereas in fact they are only known afterwards. This " 7-14 w"h 52-100
is overcome by means of the usual engineering guess- o 7-52,14-52,25-52,7-25 or 14-25
Nominal aggregate/cement ratio:
estimate but it does give weight to a criticism of 1 I 41:3 .0'1:4t 01:6 Q 1:7t -0- 1:9
0'60
Dr Murdock's method, that it is like other methods -2 10 12
of mix design such as the Road Note 4 method: it is (c I e-0·04[w((aOla G a +- hOlh G h -1-3 ,000cj---()'00028] x10 6

very good as long as one is skilled at mix design in


Figure II: Alternative relation/or compacting factor suggested
the first place ! by Dr Hughes.

80

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Discussion
46 2·0
Note: Talbot used Tyler sieves

1·8
'"
<{
I-

'"0 <2
I-
I: <{ 1·6
~ '"
I-
~
sand 23 Z

0
0
~''i-_-=>'=l=--.£'--::t==______t~-=--~(NO. 200-No. 28) w
I: 1·4
w
> U
w ;;
"
<(
I-
w
I-
<{
1·2
Z sand 3 :?;
w
U (No. 200-No. 4)
'"
W
1·0

---
0..

0·8
0 1
-- 2
SAND/CEMENT RATIO
SAND/CEMENT RATIO (by absolute volume)
(b)
(a)

Figure Ill: Curves for the same basic consistence.

400, i.e. a little coarse but not unreasonable for this (1) The water required to give a critical consistence
application. e is the specific volume of the aggregate for the cement alone (equal to a water/cement
passing B.S. sieve No. 120. Different types of coarse ratio of around 0·25 as above).
aggregate give slightly different curves, so that a (2) The addition of saturated, surface-dry sand to the
further factor for the particle shape of the coarse cement paste stiffens the mixture as the result of
aggregate, • different from the angularity factor, (1.(1> a " boundary effect". This is the normal effect of
must be introduced to obtain a single curve. This reducing the bulk density of a granular material
agrees with Dr Murdock's item (2) on .page 135. by increasing the boundary surfaces. If the bulk
The point I wish to emphasize is the complex nature density of the cement is reduced, the voids are in-
of the workability relation. Introduce enough arbitrary creased so that more water must be added to
parameters and it is usually possible to obtain a restore the original consistence and eliminate air
reasonably accurate mean relation for almost any- voids.
thing. This in no way detracts from the ingenious way (3) Further addition of sand eventually reduces the
in which Dr Murdock has made his assumptions in spacing between the sand grains to little more than
order to obtain a relation which is quickly and easily the particle size of the cement. Distribution of
applied, but let us not forget that many other basic cement between the sand becomes restricted and
assumptions can be made to obtain just as accurate a further effect, that of " particle interference",
a relation. occurs when more sand is added. Further water
I strongly endorse the view, given on page 138, must therefore be added to make good these
" that workability should be assessed on the basis of additional voids in the cement.
the volume of the constituents of the concrete". I The foregoing effects are illustrated in Figure lIJa
have never understood why greater use of absolute which has been taken from Weymouth's paper(8).
volumes has not been made in Britain. This concept Curve w/c represents the reduction in voids due to the
is also extremely advantageous for other properties reduction in the volume of cement paste, per unit
of concrete besides workability. volume of mortar, as the sand is added. The difference
The simple Vicat test which" simplifies the problem between this curve and the appropriate curve B is the
of determining the water content available for lubrica- "boundary surface" effect while the difference be-
tion of the mix" (page 139) is usefully applied but is tween the actual curve and curve B is the " particle
a little misleading to the reader. The implication is that interference" effect.
the water requirement of the cement is constant at Figure IlIa can be replotted in the form shown as
around 0·25 for all aggregate contents. This is not Figure IIIb. It is now evident that the total" lubrica-
true, of course. tion " requirement of the cement varies approximately
Talbot and Richart(7) and Weymouth(8) showed linearly with b/e over the practical range for sand 3,
that there are three factors to consider when adding a normal well graded sand. Sand 23 is much finer so
aggregate to cement paste, for a given" basic" con- that well designed mixes require a smaller proportion
sistence. for a given total aggregate/cement ratio (i.e. A,,). Sand

81

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Magazine of Concrete Research.' Vol. 13, No. 38 .' July 1961
36 is a coarse sand normally considered too harsh for the compacting factor and those obtained experi-
the leaner mixes. It is for these reasons that the factor mentally at the Building Research Station would be
of 0·25 is satisfactory in Dr Murdock's relation on expected, but it is difficult to reconcile the range of
page 140. calculated compacting factors in the series of mixes
Table 5 (page 141) omits those results where segre- A to I (0·7-7 to 0'95+) with the fairly uniform values
gation was recorded. Would Dr Murdock please indi- obtained experimentaily. This'leads on to the last point
cate in what sense the term is used here? Is it segrega- raised by Dr Murdock which infers that some mixes
tion of the constituents before compaction, as judged may have been of different workability although the
by visual examination, or is it segregation during com- compacting factors were very similar. It is agreed that
paction, due to a deficiency of fines, as referred to the compacting factor is not an absolute measure of
later on page 141 ? that rather intangible term" workability", and that
Concerning the comparison with Newman and mixes having the same compacting factor may have
Teychenne's results; the two mixes, Band 1, which differences in properties, such as the ease of trowelling,
give poor agreement have the lowest coarse aggregate which are included in the term" workability". How-
(i-is in.) contents. I would be very interested to know ever, the workability of the mixes A to I did not vary
if the tests at Southall included grossly over-sanded to the extent suggested by a variation in compacting
mixes. Only some of the 300 trial mixes referred to factor of from 0·77 to 0·95+ as calculated from
on page 141 appear to be given in Research and Dr Murdock's formula. Furthermore the data ab-
Application. If reasonably well designed mixes are stracted in Table 6 were originally given in a paper by
assumed in Figure 4, then sand contents would be Mr A. 1. Newman and the present writer(9), and in-
extremely low at Av values of around 2. This would cluded the results of Vebe tests, which show little
further reinforce the effect noted at the top of page correlation with Dr Murdock's calculated compacting
139. factors; in fact, for the mixes which gave calculated
compactinp factors of 0·77 and 0·95+, the results of
the Vebe tests were almost identical at 15·7 and 15·0
Contribution by D. C. T~ychenne, B.Sc.(Eng.) respectively.
(Building Research Station) Since the publication of the paper referred to in the
It has long been accepted that the physical charac- previous paragraph, a further programme on the use
teristics of the aggregate such as its maximum size, of surface area in mix design has been carried out at
grading, particle shape, surface texture and absorption the Building Research Station, the results of which
affect the workability of concrete. Dr Murdock has have not yet been published. In this programme, dry
made a very interesting attempt to develop a method aggregates were used but the compacting factor was
of mix design which takes into account most of these not measured until 10 min after mixing. This measured
factors without having to carry out difficult and compacting factor is plotted in Figures IV and V
lengthy tests on the aggregates. against that calculated from Dr Murdock's formula.
Dr Murdock's equation 5 for calculating the com- The values of the surface index U;) were calculated
pacting factor of a concrete mix undoubtedly gives for the 10 different gradings used, the angularity index
good correlation with the experimental data obtained (fa) was assumed to be 1·9 and the aggregate/cement
at Southall, but this correlation is not obtained when ratio by volume (Av) was calculated on the basis of an
this equation is applied to the results of tests made at average specific gravity of 2·54 for the irregular river
the Building Research Station as shown in Table 6 of sand and gravel used. The calculations for Figure IV
the paper and, in respect of more recent data, in were based on the total water/cement ratios, and those
Figures IV and V below. In the present note, answers for Figure V on the water/cement ratio modified to
are given to the questions raised by Dr Murdock con- allow for the full absorption of the aggregate. Neither
cerning the data obtained at the Building Research of these sets of data agrees well with the measured
Station and given in Table 6. values and perhaps the adoption in calculation of an
The water/cement ratio stated is the total water/ intermediate value for water/cement ratio which only
cement ratio based on dry aggregates and the com- allows for some of the absorption would give closer
pacting factor test was carried out immediately after agreement between the measured and calculated
mixing. There is likely to be little difference in the values. When the total water/cement ratios are used,
angularity of the aggregates since it is believed that the a considerable number of the calculated compacting
same type of river sand and gravel was used at both factors are greater than 1. In both Figures IV and V,
laboratories. The use of a different cement should not there is a scatter of about 0·175 in the calculated values
have a great effect and any such effect should appear for a given practical compacting factor. The difference
as a constant difference for the various mixes con- in the values of the calculated compacting factors
sidered. shown in Figures IV and V shows the importance of
As a result of these different conditions of test, a accurate definition and calculation of the water/cement
consistent difference between the calculated values of ratio.

82

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Discussion

0·70 o· 75 0·80 0·85 0·90 0·95 1·00 1·05 1·10 1·15 1· 20 1'25,
CALCULATED COMPACTING FACTOR BASED UPON TOTAL WATER/CEMENT RATIO

Figure IV: Comparison between compacting factors measured at the Building Research Station
and values calculat'!d according to Dr Murdock's formula, on the basis of total water/cement ratio.

1·00

0·95
'"0
f-
U
«
~

0·90
"z
;::
u
«0-
0·85
L
0
U
-'
«
u 0·80
;::
u +
«
'"
0- 0·75
+
0

0'70~--~~--~----~----~~---L-----L-----L----~----~----~--~

0·50 0·55 0·60 0·65 0·70 0·75 0·80 0·85 0·90 0·95 1·00 1·05

CALCULATED COMPACTING FACTOR BASED UPON MODIFIED WATER/CEMENT RATIO

Figure V: Comparison between compacting factors measured at the Building Research Station and
values calculated according to Dr Murdock's formula, on the basis ()( water/cement ratio modified
to allow for the full absorption of the aggregate.

It is considered that the large difference between the values of the surface index (j~) which have been ob-
experimental results obtained at the Building Research tained from the criterion of" best fit " for a given set
Station and the calculated compacting factors, as of data should not be more generally us,d.
shown in Table 6 of the paper and in Figures IV and V, In the outline of mix design procedure, Dr Murdock
are due to the fact that Dr Murdock's values of the has not explained how the suggested val.ues of j~ for
" surface index" do not reflect the relative importance the different maximum sizes of aggregate were ob-
of the different size fractions in the grading of the tained. The procedure also implies that.is should be
aggregate. As the result of the computer analysis, he constant irrespective of the aggregate/cement ratio;
has removed the emphasis from the importance of the although it is generally recognized that leaner mixes
finer sizes in mix design, and it is now difficult to require a higher sand content, which would increase
associate the true surface area of a graded aggregate the over-all specific surface, and it would appear that
with his surface index (is). From the evidence in Table the surface index f.. should also be increased in a
6 and in Figures IV and V, it is suggested that the similar way.

83

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


MaKazine of Concrete Research: Vol. 13, No. 38 : July 196/

Contribution by K. Newman, B.Sc.(Eng.), tence of the film (which is a function of water/cement


A.M.I.C.E. ratio w/c); and adversely affected by the angular shape
(University of London: Imperial College and rough surface texture a, and the interference ip ,
of Science and Technology) between large particles of the aggregates or,
Dr Murdock is to be congratulated on this real
·. P w/c
attempt to produce a simple relation between mix work a b llity ex - . -
SVlpa
characteristics and the workability of concrete. The
replacement of current British mill. design methods by It is interesting to compare this general relation with
a single standard procedure covering all types of the function for compacting factor,
cement and sizes and types of aggregate is long over-
w/c - 0·25
due. Although, in my view, Dr Murdock's approach
is correct in principle, several limitations are made j,!a(A v - 2)
apparent by the conclusions drawn. Dr Murdock's factor for paste consistence is
First, it must be pointed out that, by using Dr w/c - 0'25, which takes into account the water/cement
Murdock's procedure, one is designing concrete mixes ratio required to " wet" the cement. The increase in
for the compacting factor apparatus. Consequently the workability with paste content is expressed as the in-
resultant concrete may not necessarily be suitable for verse of Av - 2. Both relations indicate that work-
the job in hand. As long as workability is defined only ability varies inversely with angular shape and rough
in terms of the compacting factor test, then such surface texture of the aggregate. There remains the
anomalies as an apparent improvement in workability surface index Is to be compared with specific surface s,
with an increase in the fineness of sand will arise. voids ratio v and particle interference ip •
If the properties of fresh concrete are to be des- It must be emphasized that the surface indices.is are
cribed completely, the definition of workability and based on results obtained using the compacting factor
methods of testing must be a measure of not only how test to assess workability. The compacting factor test
much work is required to compact the concrete and is a measure of density, and its use places undue
remove air voids (compactability), but also the ease emphasis on those grading characteristics which help
with which the concrete can flow into formwork to improve the density of concrete when it is acted
between steel bars and be remoulded (mobility), and on by the small forces applied by the test. When the
its ability to remain a stable homogeneous mass during maximum size of aggregate in a mix is increased, say
handling and compaction without segregation of the from! to 1t in., there is a slight reduction in the sur-
constituents (stability). A single test method to assess face area of the aggregate. Of more significance, how-
this composite property has yet to be devised. How- ever, is the increase in bulk density and decrease in
ever, compactability, which is determined by the voids ratio of graded coarse aggregates obtained as
amount of internal work required to compact concrete the maximum particle size increases. Thus, for the
fully, can be measured indirectly by the compact- same over-all specific surface, a greater weight is ob-
ing factor test, the relative mobility can be assessed tained in the compacting factor cylinder with 1tin.
by means of a remoulding test (10), and stability by a aggregate. However, the increase in compacting factor
segregation or cohesion test(ll). does not necessarily mean an increase in the compact-
Such an approach may seem too complex to many ability of the mix.
who regard workability as being defined only in terms Moreover, the surface index suggests that an im-
of compactability(12). However, compactability and provement in workability can be obtained by using
compacting factor measurements alone will not com- finer sand. Concrete mixes which are dry, or have a
pletely differentiate between mixes, as an estimation low cement or sand content, tend to be harsh and
of mobility and stability will depend on a visual unworkable. With these mixes, an increase in the per-
appreciation of concrete. centage of fine material can improve mobility by help-
The effect on fresh concrete of varying the mix pro- ing to fill the voids and decrease particle interference
portions can more easily be understood if concrete is during handling. The resulting increase in density of
regarded as a mixture of large particles surrounded by the uncompacted concrete produces an increase in the
a lubricating film. In concrete the lubricating film is compacting factor value. However, when dry harsh
mortar, and in mortar the lubricating film is cement mixes are vibrated, the greater surface area of fine
paste. The capacity of larger particles for movement particles of sand becomes effective, increasing the
through the matrix without interference will depend amount of effort required to compact the mix. With
on the thickness and consistence of the lubricating rich, workable mixes, the compacting factor is not so
film. It has been shown (13) that, in general terms, work- sensitive to changes in the sand grading and large
ability is improved by an increase in the thickness of alterations in Is values would have little effect.
the lubricating film (which is a function of the paste The surface index, therefore, would appear to be a
content by volume p, the surface area .1', and the voids combination of specific surface, voids ratio and par-
ratio v, of the combined aggregates) and the consis- ticle interference and might be termed the" effective

84

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Discussion

immobile water factor Wi defined by Powers(16), varies


consistence of water----:::~-:::::=-'='___ from about 0·30 for rapid-hardening Portland cement
100 to 0·25 for ordinary Portland cement down to less than
0·20 for high alumina cement. The use of such values
of x in the factor w/c - x provides a satisfactory
explanation of the variations in workability reported
with different cements(15,17l. It is surprising that Dr
w
t-
Murdock did not emphasize this point.
<
'"- 50
As the workability of concrete is affected by the
w
u consistence of cement paste and not the water content
zw
t;; by volume, it is pointless to try to include the specific
;;;
Z surface of cement with the characteristics of the aggre-
o
u gate. The specific surface of cement is only of im-
portance in that it affects the consistence of the cement
paste.
0,20 0'30 0,40 0'50 0'60 0,70 o'so The stumbling block in any mix design method is
WATER/CEMENT RATIO (by weight)
the choice of the optimum proportions of sand and
coarse aggregate to satisfy the requirements of work-
Figure VI: Relation between consistence of neat cement paste
and water/cement ratio for different cements. ability.It is a pity that Dr Murdock has rather avoided
the issue by simply suggesting certain, apparently arbi-
trary, values of surface indexf, for different maximum
size aggregates. Do these values apply to lean, rich or
average cement content mixes? It is well known that
specific surface" for the compacting factor test. The the optimum sand content decreases as the cement
surface index values will not apply to dry mixes de- content increases.
signed for vibration, or mixes where there is no coarse Furthermore, how does Dr Murdock define segre-
aggregate particle interference, such as mortars. This gation? In the latest edition of his book (IS), lower
is further supported by Cusens's evidence(14) that, limits are given for j~ to prevent segregation occurring.
below a value of 0,80, the compacting factor test does How were these values determined? For large values
not give a true indication of the amount of work of.r. and lean mixes, there could be insufficient paste
required to compact the concrete fully. to fill the voids in the combined aggregates. and com-
Nevertheless, despite the limitations of the.r. values, plete compaction could prove impossible. It would be
Dr Murdock's approach is fundamentally correct. The useful if Dr Murdock could suggest some upper limits
compacting factor test will probably be used to define to values off;.
workability, by itself, for some time yet and his pro- I realize that there cannot be a definite answer to
cedure is a great improvement on current methods of these questions because assessment of the properties
design. Therefore, one or two comments on the use of of concrete by the compacting factor test alone will
the equation for compacting factor are appropriate. not provide them. Limits to f; values depend as much
High water/cement ratios, in conjunction with high on the requirements of mobility and stability as on
cement contents, in equation 5 can produce compact- compactability. Other tests are required to express the
ing factor values greater than 1. This is due not so properties of concrete completely and give an indica-
much to an error in the equation as to certain limita- tion of the nature of the deficiency of an unsatisfactory
tions in the factor w/c - 0·25. Figure VI (which has mIx.
been adapted from Figure 4 of reference 15) suggests Finally, concerning the comparison with Newman
that workability is related not to the water content by and Teychenm:'s results, it would be interesting to
volume but to the consistence of the cement paste. know how the weight of the fully compacted concrete
Above water/cement ratios of about 0·75-0·80, all was found when calculating the author's test values
cement pastes have a consistence equivalent to that of of compacting factor. It has been shown(19) that com-
water. Therefore, the factor w/c - 0·25 can never have pacting factor values vary considerably depending on
a value greater than about 0,50-0,55. If this upper assumptions made when calculating the theoretical
limit is applied, equation 5 will not produce compact- wet density of concrete. Do I understand from the
ing factors greater than 1. However, the straight cen- paper, that, whilst Newman and Teychenne used a
tral part of the curves in Figure VI does indicate that total water/cement ratio of 0·55 (corresponding to an
workability is directly related to water content over a effective water/cement ratio of about 0·47), Dr
certain range of water/cement ratios. Murdock used an effective water/cement ratio of 0·55 ?
The water/cement ratio values at zero consistence If so, Dr Murdock's test method should produce higher
indicate the amount of water required to " wet" the compacting factor values, which is the case, at least
cement particles. This value, which is related to the with mixes D, I and K. In addition, recent work at

R5
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Magazine of Concrete Research.' Vol. 13, No. 38 .' July 1961
Imperial College has shown that, for complete satura-
tion to occur, air-dry aggregates must be completely
immersed in water. Addition of the absorbed water I·O,------,-----r----,----,-- -------v:-i-,-0,-----::1
0
only, before mixing, does not guarantee saturation. , ,'
Admittedly the effect on workability is small com-
pared with the effect on strength.
These criticisms are not intended in any way to
detract from the value of the paper. An approach
similar to Dr Murdock's is required if a single design "
Z
I-
procedure covering all concrete mixes is to be de-
veloped. By extending the compacting factor relation
..
U
«
1:
0-7

o
to include the properties of mobility and stability of U

a mix, the workability of concrete will at last be able 0-6~---+---r-,h-,--+--- - - a~tCI"~ - - - f - - -


to be related completely to the mix characteristics. Ii> 6
O' 5'--_----1._ _- ' -_ _--"-_ _-'--_ _"'-'-7_._-'-_----'
o 0-1 0-2 0·) O-~ 0-5 0·6 0'7
10(w/c-O -25 )//,1. (A,-2)

Contribution by W. E. Murphy, B.Sc.(Eng.) Figure VII: Relation between compacting factor and
10 (W/C - O'25)!fs/a(A v - 2) for the first series of C & C A
(Cement and Concrete Association) tests.
Dr Murdock has developed a very interesting and
useful formula relating the compacting factor of fresh
concrete to the properties of the aggregates, the mix
proportions and the water/cement ratio. This formula adopted should be the highest water/cement ratio that
has been examined in connexion with a few mixes will prevent complete penetration of the Vicat plunger
made at the laboratories of the C & C A at Wexham into a neat cement-water paste. This seems equivalent
Springs in the course of other investigations. The first to stating that the figure to be used is the standard
series of mixes contained i in. maximum size irregular consistence of the cement as determined in accordance
gravel, natural sand and a uniform consignment of with B.S. 12:1958. The standard consistence of the
ordinary Portland cement. The series consisted of four cement used in this series of tests was 0·28 and Figure
sets of four mixes, the different sets having aggregate/ VIII shows that the points obtained on plotting the
cement ratios of 3, 4t, 6 and 7t by weight respectively. values of compacting factor obtained to a base of
The water/cement ratios of the four mixes of each 1O(w/c-0'28)/lsliA v -2) lie more closely about a
richness were varied to give a range of workability. single straight line. This offers some evidence that
The gradings of the sand and the coarse aggregate Dr Murdock's formula can be generalized by stating
were maintained constant, but the sand fraction of the that the compacting factor is a function of .
total aggregate was varied as considered necessary for
each mix. lO(w/c - sJ
Ish(Av - 2)··············· . (4a)
The aggregates were soaked in the mixing water for
24 h before the cement was added; the partially com- where Sc is the standard consistence of the cement.
pacted weight for the compacting factor test was deter- The mixes described above made possible an .exam-
mined at times of 3 and 60 min after mixing. Assuming ination of the results obtamed on applying formula 4
that the compacting factor decreases approximately to mixes of various richnesses. A further series of test
linearly in respect to the logarithm of the time after results has been examined to assess the result of apply-
mixing, the average of the two test results was regarded ing the formula to mixes containing aggregates of
as the workability at a time of 13t min after mixing. differing maximum size. The mixes were made with
Figure VII shows the graph obtained when the 16 different water/cement ratios to cover a range of
values of compacting factor obtained are plotted workability, there being a total of 46 mixes. All the
against 1O(w/c-0·25)1!s!a(A v -2). From formula 4 of mixes were made with an aggregate/cement ratio of
Dr Murdock's paper, the points would be expected to 6·0 by weight.
lie close to a single straight line. In fact, it isevident The aggregate for each batch was covered with the
that they are scattered to a considerable extent, there mixing water for 15 min; the partially compacted
being a distinct tendency for the compacting factor of weight for the compacting factor test was measured 3,
a lean mix to be higher, for a given value of 15 and 30 min after mixing and the average of the
1O(w/c-0'25)lfs[a(A v -2), than that of a rich mix. three values was regarded as the workability 11 min
Dr Murdock has suggested that the formula could after mixing.
be improved by varying the constant deducted from The standard consistence of the cement used in this
the water/cement ratio according to the characteristics investigation was again 0·28 and so, if formula 4a is
of the cement. He suggests that the figure to be assumed to apply, the values of compacting factor ob-

86

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Discussion

1·0

- - - - - - -0·02
0·9
l"~;y'.~/"i=JJ.--- -0·04

o'"
>-
~ o·s

"z
>-
~ 0·7
""
~

:E -- - ----" Aggregate
o I Max. % sand
U

TO
I size
I
in. 30 40 50
0·6 - 0·6
I I
" •
G 3 It ~
[] -It ! []
• ~

0·5
0 0·1 0·2 0·3 0·4
A
V
0·5
6
7,
0·6 0·7 0·1 0·2 0·3 0·4 0·5
$

0·6
••
o·sL-_---L_ _----1.._ _---'--_ _- ' - _ . L . - . L . - . L . - - ' - - - ' - - _ - : : '
o 0·7
I O(wlc-'!· 28)/1,/. (A ,-2) I 0(wlc-'!·28)//,1. (A,-2)

Figure VIII: Relation between compacting factor and Figure IX: Relation between compacting factor and
10 (W/C - O·28)/lsfa(A y - 2) for the first series of C & C A W(w/c - O·28)lfsfa(Ay - 2) for the second series ofC & C A
tests. tests.

characteristics are not known; in such cases, it would


tained would once more be expected to be related to
appear logical to assume that the cement has a stan-
1O(w/c-0·28)If.Ia(A y-2). The graph obtained on plot-
dard consistence of about 0·29, this probably being
ting the compacting factor against this function is
the best estimate of the average value for British
shown in Figure IX. It was found that the scatter
ordinary and rapid-hardening Portland cements. This
obtained was not significantly different from that
suggests that it should be assumed that the compacting
resulting from plotting the compacting factor to a base
factor is a function of
of 1O(w/c-0·25)/f;j~(Ay-2). This is as expected, since
the series did not contain any rich mixes. lO(w/c - 0·29)
---'--'--------'-. . . . . . . . . . . . . . (4 b )
Whether formula 4 or 4a is assumed to apply, a Isfa(A y - 2)
large proportion of results showed poor correlation Ten of the series of mixes of different richness were
where mixes made with aggregate of i in. maximum repeated with a more rounded aggregate and another
size containing 30 % sand were concerned; regardless ordinary Portland cement, the standard consistence of
of the formula used, 5 of the 6 measured values were which was not determined. It was found that this was
below the general run of points. In these mixes, 70 % a case where formula 4b applied more closely than
of the aggregate consisted of single-sized i to is in. the formula 4 of the paper.
material and it would appear to be possible that the The modification of formula 4 to account for the
relation between compacting factor and specific sur- setting characteristics of the cement would be expected
face often does not apply very accurately when there to affect the constants of 0·74 and 0·67 in Dr
is an excess of any given size. Murdock's formula 5. Owing to differences in testing
Further evidence of this is obtained on applying technique, the compacting factor results obtained in
Dr Murdock's formula 5 to mix 145 of Table 10 of the tests made at Wexham appeared to be about 0·04
his reference 11. This mix contained, comparatively, a higher than would be obtained by Dr Murdock when
very high proportion (36 %) of aggregate between the testing similar mixes. In spite of this, however, the
No. 14 and No. 25 sieve sizes. When Dr Murdock's constant 0·74 of formula 5 did not appear to be
formula 5 is applied to the data given, the calculated affected by the standard consistence of the cement or
values of compacting factor are found to be 0·77,0·84 the testing technique. The additive constant of 0·67,
and 0·90 corresponding to the three values of water/ however, did appear to depend on the standard con-
cement ratio, in contrast to the actual values of 0·72, sistence of the cement and analysis of the results
0·78 and 0·82. It is possible that this discrepancy may indicated that, if Dr Murdock's testing technique is
be due to limitations of the compacting factor test as used, the compacting factor is given by the formula
a means of determining workability rather than to a
fault in Dr Murdock's formula. cf = 0·74 (l?(W/C - sc) + (l·67s c + 0.25») .... (5a)
From formula 4a it would appear that the com- fs/a(Ay - 2)
pacting factor cannot be related to the mix propor- Formula 5 is a particular case of formula 5a. If
tions unless the standard consistence of the cement is formula 4b is applicable to cement of average stan-
determined. In many cases, however, the cement dard consistence, the best estimate of the compacting

87

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Magazine of Concrete Research: Vol. 13, No. 38 :."July 1961
TAB LEI I : Values of surface index.

Surface index for particles between Example of calculation for R.R.L. Grading
Sieve sizes sieve sizes indicated No. I, I i in. maximum size
between which
particles lie Dr Murdock's values Alternative values Percentage of particles
Is Is' within sieve range Is Is'
3 in.-U in. 0·8 - - - -
Ii in.-! in. 1·3 I 50 65 50
t in.-l in. 2·3 3 14 32 42
I in.-{. in. 4·3 5 12 52 60
l. in.-No. 7 7·3 7 6 44 42
No.7-No. 14 10·3 9 6 62 54
No. l4-No. 25 12·3 II 5 61 55
No. 25-No. 52 12·3 12 4 49 48
No. 52-No. 100 10·3 10 3 31 30
Passing No. 100 5·3 5 - - -
Total 396 381
x 10- 3 = X 10- 3 =

0·396 0·381

factor of a mix having a cement of unknown standard adding a constant of 330 to the sum of the component
consistence would appear to be given by the formula indices. The scatter of the results plotted in Figure I
of the paper, however, appears to be such that the
lO(W/C - 0'29)
c1 = 0·7
( 4.
. FIa(Av - 2)
+ 0·73 ) .......... (5b) surface indices could be represented by a series of
simple integers. As an example of a possible alternative
set of values, the surface indices of the gradings used
In connexion with the use of the information given
in the series of tests mentioned above were calculated
in the paper for the design of concrete mixes, Dr
using the second set of values quoted in Table II. From
Murdock suggests that the angularity index of the
the results of the tests on all the 62 mixes discussed in
aggregate may be assessed approximately from the
this contribution, it appeared that the measure of
examples he quotes or, more exactly, may be deter-
agreement between calculated and actual values of
mined by tests. If values are taken from Table 2 or
compacting factor was not significantly affected by
3 of the paper, the subsequent error in compacting
using these alternative vaJues of surface index.
factor may be 0·08 or more since, for example, the
Dr Murdock has suggested values for the desirable
angularity indices of crushed limestones tested at
surface index of combined aggregate depending upon
Wexham have ranged up to 2·65 compared with the
the maximum size and the expected variation in grad-
author's value of 2·05 for Mendip limestone. If tests
ing of the component materials. The optimum value
are made, it would appear to be unnecessary to test
would also be expected to depend on the workability
each half-size present in the material to be used and
of the concrete and the richness of the mix as well as
it would be of interest if Dr Murdock could give some
the handling conditions. In view of this it would be
guidance as to the number of sizes that should be
interesting to have Dr Murdock's views on the follow-
tested to assess the over-all angularity index of a
ing procedure. First the water/cement ratio is deter-
graded material.
mined from considerations of strength and durability
Perhaps one of the most interesting parts of the
and, if the required compacting factor is less than 0'84,
paper is that dealing with the calculation of surface
one of the following empirical formulae is used to
index, since the figures quoted can be used in any
determine the' optimum value of surface index.
method of mix design which necessitates the deter-
For aggregate of It in. maximum size:
mination of the proportions in which to combine
available aggregates to give a grading equivalent to f; = 0·25cJw/c + 0·40 ... , ................ (6)
that assumed in the course of the design procedure. For' aggregate of! in. maximum size:
Dr Murdock has implied that some improvement in f;· = 0·25cfw/c + 0·45 .................... (7)
his method of design may be possible if the given
For aggregate of ~ in. maximum size:
values are modified in the light of further experimental
evidence. In view of this, it would be interesting if he /, =', 0·25cJw/c + 0·55 .................... (8)
could give some guidance on how his figures were ob- If the required compacting factor is greater than
tained. It is apparent, as indicated in Table II, that the 0'84, the values of surface index obtained from the
values he quotes for the various single sizes are effec- above formulae would probably only be suitable if
tively 0'8, 1'3, 2·3 ... 5·3 and that the arithmetic has the aggregate grading could be expected to be partic-
been simplified by reducing eaCh value by 3·3 and ularly uniform and conditions were such as not to

88
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Discussion
encourage segregation. Under less favourable condi- angularity indices which can be obtained with crushed
tions it would be advisable to increase the values of limestones. Whilst it will be evident that much further
surface index by up to (cI12 - 0·42), the amount of information is now needed on the angularity of aggre-
the increase depending on the conditions in any gates, I suggest for the moment that one or two tests
particular case. on, say, the coarsest and finest sizes of coarse aggregate
should be sufficient.
I also agree with Mr Akroyd that the angularity
Reply by the author determination is tedious if done on all the single sizes
It is gratifying to find that several contributors to of sand. I suggest that a fair approximation might be
the discussion have indicated a considerable measure obtained by taking, say, two or perhaps three sizes
of agreement with the new approach which I put only.
forward. In my reply 1 will deal as fully as possible Sand supplied in the Thames Valley is apt to contain
with the many points they have raised. angular particles owing to the inclusion of crushed
I agree with Mr Akroyd that a relation can be estab- material returned from the crushers which deal with
lished between workability and specific surface, but oversize material for which there is no demand. In the
this breaks down when mixes are used in which the tests described in my paper, a great deal of trouble was
maximum size of aggregate is varied, or the proportion taken to obtain sand which did nat contain crushed
of fine aggregate passing a No. 100 sieve is varied, and particles. In practice, the presence of varying quan-
is true for one particle shape only. The increase in tities of crushed particles can affect the workability
specific surface with increase in angularity does not quite substantially; in fact, inspection of the suggested
appear to be related to the decrease in compacting formula and the comparative range in values for sur-
factor which occurs. In my opinion, the intermediate face indices and angularity indices would appear to
sizes provide more resistance to mobility in the con- suggest that changes in angularity are likely to be of
crete than the finer sizes; if the specific surface is greater importance than changes in grading.
regarded as the index of grading, this effect is not I do not understand Mr Akroyd's reference to the
accounted for. The values obtained for the surface values or.!' and fa only being known after the mix has
index seem to be in keeping with my view. been designed. It is usual to do a sieve analysis of
As Mr Akroyd says, it is difficult to attach physical aggregates to be used in concrete before designing the
significance to the constant added to the summation mix, and tests could be done for j~ at the same time.
of indices in Table 1, except that its effect is to reduce An alternative method of dealing with the question of
the influence of aggregate grading in the relation I angularity is to make up a trial mix and measure its
have established. Further research may suggest a re- compacting factor. With the other variables already
finement of the values I have obtained. From the known, a value for fa can then be calculated and used
analyses I have made with a number of combinations to determine the influence of variations in mix propor-
of values of surface indices, and from the compara- tions and grading from those used in the trial mix.
tively small improvement obtained by taking the com- Dr Hughes has presented interesting data which,
puter values, compared with those used in the original allowing for the difference in approach, do not appear
analysis, it does not seem that the actual values are to contradict the evidence produced in my paper. The
very critical, provided they follow the general form of main object of my paper was to establish the dominant
the curves given in Figure 1. factors influencing workability and to explain their
Mr Akroyd comments on the method of measuring interrelation in as simple and logical a manner as
particle shape or angularity. He is quite correct in possible. By doing so, I hope that, while I have estab-
stating that the method adopted was that suggested by lished a mathematical relation for use with the com-
Shergold and that a different value is obtained by the pacting factor, the basic principles put forward may,
compacting factor apparatus. Unfortunately, there with suitable adjustment, be applied with other
was an error in early copies of Concrete Materials and methods of assessing workability. I think this is where
Practice regarding this point; later copies contain a the approach I have made differs from that suggested
correction slip. Since the compacting factor method is by Dr Hughes, who, in his published paper u» includes
less variable, I think it may be more acceptable, pro- the following sentence: " Unfortunately, the relations
vided a correction is made. I suggest this might be: obtained for the workability of concrete were too
V = 0'7Va + 5·5 complicated for general application to mix design".
Reference is made to Talbot and Richart (7) and
where V is the percentage voids by Shergold's method
Weymouth'sIS) work on cement mortars. The curves in
Va is the percentage voids by the compacting Figure IlIa suggest to me that the boundary effect
factor method chiefly influences mixes with sand/cement ratios richer
This gives good agreement with the relations estab- than 2. With the addition of more sand, particle inter-
lished by Akroyd and Kaplan. ference occurs. In my paper, however, I have not
Mr Murphy has indicated the range in values of attempted to deal with very rich mixes and, in fact,

89
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.
Magazine of Concrete Research.' Vol. f3, No. 38 .' July f96f

the richest mix for which I made tests was I: 3t Whilst absorptions at 24 h were generally of the same
cement: total aggregate. order as were obtained by Mr Newman, it will be noted
Dr Hughes and Mr Newman refer to the question that the rate of absorption changes with particle size.
of segregation, to which reference was made in Table The rate of absorption also varies between different
5. This was in all cases associated with a surface index samples of aggregate obtained at different times.
of 0·50 or less, and resulted from a deficiency of fines. I think the scatter which Mr Teychenne has obtained
Reference is made to this point again towards the end is attributable mainly to the following.
of this reply. (1) The change in rate of absorption with particle size
The tests at Southall included a few mixes which affects the average rate of absorption according to
might be regarded as grossly over-sanded, the max- the combined grading of the aggregate, so that the
imum sand content used being 73 %. There was a effective water/cement ratio is also affected.
tendency to underestimate the compacting factor for (2) The rate of absorption of water by the aggregate
these over-sanded mixes. All the trial mixes ~eferred to in the presence of cement paste may be affected by
on page 141 are given in Research and Application, both the water/cement ratio and the mix propor-
since there are three different water/cement ratios for tions.
each mix number. (3) Some gradings as, for instance, gap gradings with
The fact that Mr Teychenne, in the tests made at fine sand are sensitive to quite small changes in
Building Research Station, has not obtained good water/cement ratio. Likewise, the richer the mix,
correlation with my approach is not surprising, in view the smaller the change in water/cement ratio
of the method adopted in making the tests. My con- needed to alter the workability from low to high.
fidence in my approach was considerably enhanced by Figures IV and V suggest that there is greater
the fact that correlation with the data given in Road scatter for the richer mixes.
Note No.4 was as good as I had obtained with tests In order to overcome this difficulty of absorption of
at Southall. In my paper, only two examples are given water by the aggregate, I consider it essential to begin
in Figures 2 and 3, but the correlation was equally mixing with a saturated aggregate. In my tests, I added
good for other mix proportions and water/cement sufficient water to bring the aggregate to a saturated,
ratios included in Road Note No.4. In his contribu- surface-dry condition half-an-hour before adding the
tion, Mr Murphy has also obtained satisfactory agree- cement, as is stated in the paper. This was a practical
ment with my formula in tests made at the Cement and compromise arising from the evidence available when
Concrete Association. the tests were done, which suggested that the absorp-
The reason for the scatter and the discrepancy be- tion by the aggregate would be almost complete in
tween the results Mr Teychenne has obtained and all that time. The effective water/cement ratio may then
these other results lies, I think, in his use of dry aggre- be taken as the added water. Mr Newman's comment
gate without preliminary soaking, followed by mea- that air-dry aggregates must be completely immersed
surement of the compacting factor 10 min after mixing. to obtain complete saturation is worth noting.
As a result, the effective water/cement ratio, in so far I cannot agree with Mr Teychenne that the difference
as workability is concerned, is somewhere intermed- between the Building Research Station results and
iate between the total water/cement ratio and that mine is due to the fact that the values of the surface
modified to allow for complete absorption by the index do not reflect the relative importance of different
aggregate. size fractions in the grading of the aggregate. As in-
Mr Newman has shown (19) that Thames Valley dicated in my reply to Mr Akroyd, I consider that the
aggregate absorbs in 10 min roughly 60 to 80 % of the surface index provides a compromise between the in-
maximum absorption capacity at 24 h. He further fluences of surface area, and other factors such as
states that" from the strength results, it is apparent frictional resistance and particle interference. My ap-
that the coating of cement paste. slows down the rate proach is, of course, empirical and further research
of absorption in concrete mixes". I share his view on may sort out the relative influences of these other
this. factors.
In tests on one batch of Thames Valley aggregate, I Mr Newman comments on the limitations of the
have obtained the following values for the absorption compacting factor apparatus in providing a measure
of four different gradings, expressed as a percentage of of workability. He mentions mobility and stability.
the absorption capacity at 24 h. One might add ease of finishing (as, for instance, in
roadwork) and possibly other desirable properties. I
Particle size 10 mill 30 min
3' 3'
have used the compacting factor as a measure because
:{ 111'-8 111 . 71 89 it has seemed to me the most useful and practicable
3' 3'
If 111'-16 111. 96 97 single test providing a guide to workability for the
-& in.-No.
7 83 92 type of concrete mix widely used in practice. I agree
No.7-No. 100 (fairly well with him that a single test method giving a better
graded) 82 91 assessment of all the desirable properties will be a

90

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Discussion
most useful advance. Maybe the relation I have estab- think another explanation under (1) below may fit the
lished will, with suitable modification of constants, be case. A number of the mixes in Table 6 of my paper
adaptable to other forms of test. might also be regarded as coming within this category.
I agree with Mr Newman that the surface index may It is well known in the soil mechanics field that single-
not apply to dry harsh mixes designed specifically for size sands become " quick" with a small change in
vibratory methods of compaction. In view of the water content, when loaded or vibrated. I think some
amount of testing involved, it was necessary for me to concrete mixes are analogous, with two results.
restrict my attention to those concrete mixes in general (1) The variation in compacting factor which can
use. I believe that 90 to 95 /~ of the concrete produced occur with a change in effective water/cement
in this country comes within the range of mixes quoted ratio of only 0·01-0·02 is such that, even under test
in the paper, and within a compacting factor range of conditions, it is difficult to obtain reliable results.
0·8 to 0·95+. I agree that high water/cement ratios, (2) Control of workability of such mixes is, in prac-
in conjunction with high cement contents, in equation tice, extremely difficult. They are, in fact, only
5 produce a calculated compacting factor greater than suitable for dry concrete, and then need heavy
I. I had taken the view that the straight-line relation vibration to bring them to a " quick" or mobile
did not hold for compacting factors above about 0·95, condition.
as indicated by the dotted lines in Figures 2 and 3, Referring to the method of obtaining values from
which should eventually become tangential to the line the computer analysis I can only say that, the analysis
for a compacting factor of unity. having been fitted to a suitable programme, the in-
The compacting factor was calculated on the basis formation was fed into the computer and the values
of saturated aggregates. indicated by the crosses in Figure 1 came out. As in-
Mr Newman is correct in assuming that I used an dicated in my reply to Mr Akroyd, the individual
effective water/cement ratio of 0·55, whereas A. J. values do not appear to me to be critical.
Newman and Teychenne(9) used a total water/cement Messrs Teychenne, Newman and Murphy ask for
ratio of 0·55. However, I believe their compacting information on the suggested target values for Is for
factor tests were made immediately after mixing, so the different maximum sizes of aggregate. These are a
that the absorption by the aggregate may have been compromise, since it will be evident that, in theory,
quite small. At that stage it would, in addition, be the lower the value of Is the greater will be the com-
varying rapidly. pacting fa.ctor for any given mix. On the other hand,
Messrs Newman and Murphy refer to the consis- lack of fines seriously increases the risk of segregation
tence of the cement and Mr Newman has emphasized and honeycombing. My observations suggested that
the difference between ordinary Portland, rapid- the risk became serious below about.l~ = 0·5 for a
hardening and high alumina cements. Mr Murphy has ! in. max. diameter mix, and rather less for a mix of
given most useful evidence of the influence of the 1t in. max. size below roughly j~ = 0·45. It is also
cement consistence on workability. My original tests necessary to provide a margin which will allow for the
had indicated values for what he has termed Sc varying variations in grading, particularly of the sand, which
between 0·23 and 0·265 for ordinary Portland cement. inevitably occur in practice. I have therefore selected
With these values, the error in assuming 0·25 in a a value in each case which I feel to be about the best
formula intended for practical use did not appear compromise. I have suggested a maximum value for
likely to be serious. However, I have since obtained Is of about 0·8 for i in. maximum sized aggregate.
values up to 0·29 and, as Mr Murphy has shown, this I have no evidence WIthin the range of mixes tested,
variation can be quite significant. The question of the i.e. 1 : 3t to 1 : 8 by weight, that there is a need to change
best cement consistence value to adopt as an average the surface i·ndex to provide more sand in leaner
when no actual value is available appears to be a mixes. Within this range, the influence of mix propor-
matter which requires further investigation. As Mr tions on sand content is, I think, of minor significance
Murphy states, this may result in some modification compared with the provision which needs to be made
of the constant of 0·67 in the formula. in practice for variations in grading. However, Mr
The tests in Figure 3 appear to give a reasonable Murphy has made an interesting suggestion for the
correlation, except for the i in. maximum grading determination of the optimum value for IS" The for-
with only 30 % sand. It seems to me this would give mulae 6, 7 and 8 he gives would appear to give values
a value ofj~ of only a little over 0·60 and, whilst I have of the same order as those I have suggested in my
little evidence of i in. maximum size aggregates, I paper, although he does qualify them in the following
would suspect that there are insufficient fines to fill paragraph. Any detrimental effect resulting from a
the voids in the i in.--& in. material. As will be noted slight excess of fines is far less than that resulting from
in the paper, I have suggested that the desirable value a deficiency so that, when in doubt, I would prefer to
for Is is 0·70 when a i in. maximum size aggregate is take a somewhat higher figure for Is, rather than aim
used. The suggestion that an excess of any given size at a minimum. Further investigation of this question
may upset the relation is possibly true, although I is necessary.

91

Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.


Magazine of Concrete Research Vol. 13, No. 38 : July 1961

REFERENCES 11. TOURNON, G. Apparatus and experimental studies on the


1. SINGH, B. G. Specific surface of aggregates applied to mix segregation of concretes. RILEM Bulletin. No. 25. December
proportioning. Journal of the American Concrete Institute. 1955. pp. 9-26.
Vol. 30, No.8. February 1959. pp. 893-901. 12. GLANVILLE, w. H., COLLINS, A. R. and MATTHEWS, D. D. The
2. SHERGOLD, F. A. The percentage voids in compacted gravel grading of aggregates and the workability of concrete. 2nd
as a measure of its angularity. Magazine of Concrete edition. London, H.M.S.O., 1947. pp. 28. Road Research
Research. Vol. 5, No. 13. August 1953. pp. 3-10. Technical Paper No.5.
3. MURDOCK, L. J. Concrete materials and practice. London, 13. NEWMAN, K. The use of workability tests for concrete mix
Edward Arnold (Publishers) Ltd, 1960. pp. vii, 392. design and quality control. Imperial College, London,
4. KAPLAN, M. F. The effects of the properties of coarse November 1960. pp. 31. Concrete Structures and Tech-
aggregates on the workability of concrete. Magazine of nology Research Report CSTR 6.
Concrete Research. Vol. 10, No. 29. August 1958. pp. 63-74. 14. CUSENS, A. R. The measurement of the workability of dry
5. HUGHES, B. P. Concrete mix design. Thesis presented to the concrete mixes. Magazine of Concrete Research. Vol. 8,
University of Birmingham for the degree of Ph.D. 1956-57. No. 22. March 1956. pp. 23-30.
6. HUGHES, B. P. Rational concrete mix design. Proceedings of
15. NEWMAN, K. The design of concrete mixes with high alumina
the Institution of Civil Engineers. Vol. 17. November 1960. cement. The Reinforced Concrete Review. Vol. 5, No.5.
pp.315-332. March 1960. pp. 269-301.
7. TALBOT, A. N. and RICHART, F. E. The strength of concrete,
16. POWERS, T. c. The bleeding ofPortland cement paste, mortar
its relation to the cement, aggregates, and water. University
and concrete. Chicago, Portland Cemeut Association, 1939.
of Illinois Engineering Experiment Station, October 1923.
Bulletin No.2. pp. 40-58.
Bulletin 137. pp. 118.
8. WEYMOUTH, C. A. G. A study of fine aggregate in freshly 17. ERNTROY, H. c. and SHACKLOCK, B. w. Design of high

mixed mortars and concretes. Proceedings of the American strength concrete mixes. Proceedings of a Symposium on
Society jor Testing Materials. Vol. 38, Part II. 1938. mix design and quality control of concrete, London, May
pp. 354-372. 1954. London, Cement and Concrete Association, 1955.
9. NEWMAN, A. J. and TEYCHENNE, D. c. A classification of pp.55-73.
natural. sand and its use in mix design. Proceedings of a 18. MURDOCK, L. J. Concrete materials and practice. 3rd edition.
Symposium on mix design and quality control of concrete, London, Edward Arnold (Publishers) Ltd, 1960. pp.
May 1954. London, Cement and Concrete Association, 89-115.
1955. pr. 175-194. 19. NEWMAN, K. The effect of water absorption by aggregates
10. POWERS, T. c. Studies of workability of concrete. Journal on the water/cement ratio of concrete. Magazine of
of the American Concrete Institute. Vol. 3. February 1932. Concrete Research. Vol. 11, No. 33. November 1959.
pp.419-448. pp. 135-142.

92
Downloaded by [] on [12/09/16]. Copyright © ICE Publishing, all rights reserved.

You might also like