Trouble shooting for Error 40:

It is an error caused by man setting to make that our inverter can not work.

First step: Kindly check if you can see the parameters of P9-08 & P9-10
If you can see the parameters, just change it with: P9-08=0 & P9-10=999 and to see if it works
If you can not see the parameters, that means this parameters are set by others, and also set
password to protection (this man may be your competitors), so we can not unlock password,
then need to change the two IC chips (U16 & U66) on the integrated controllers main board, or
change a new main board if you have problem to find the two chips.

The two chips model:


Position Number Model Qty
U66 24LC08T-I/SN SOIC8(24LC08BT-I/SN Microchip) 1
U16 24LC64T-I/SN SOIC8 1

After this changed, you may need to make adjustment again to make the elevator restart to work.