AMERICAN BUREAU OF SHIPPING
Customer Name ABB GENERATORS LTD. Purchase Order No,
Attending Office Nanjing Report Number NJ2691804
First Visit Date 18-Aug-2014 Last Visit Date 23-01-2014
Certification OF: ‘One (1) AC Generator 3 Quantity: One(1)
‘Manufacturer ABB GENERATORS LTD.
‘Survey Location:
Equipment Data
Manufacturer Number(S. No.)
‘Model Number
Destination Vessel (Class Number)
BullderiShipyara NDING LTD.
Buller 1D / Hull No.
Purchaser tame . itd 0.
Design Detail \P
Das State Design Apprveeeviowed
‘A8S Reviewng Oraerizaton Gn Shanghai ESD
Crewe Nerber sae seosooo
Additional Data
ABS Stamping +¥ NJ2691804-A 8 Serial No
Generator Duty Main
Rate Voltage 480
Rated Power 1825.6kW
Rated Frequency 60 Hz
Number of Phase Thee
Rated Speed 1800 rpm
Rated Power Factor (AC Generator) 08
Class of Insulation (Stator Windings) H
Type of Enclosure Pa
This is to Certify that the undersigned surveyor(s) to this Bureau did, at the request of the customer, carry out
the following survey and report as follows.
Traceability of materials used on ths project has been verified.
‘The principal data has been verified in accordance with the applicable Rules/speciications and approved plans, and
Confirmed to be within acceptable tolerances.
Alltesting (pressurelload/operationavetc,) has been carted out a
applicable Rules/specifications
pplicable and verified in accordance with the
Testing machines are maintained in a satisfactory condition and records oftheir recheck or calibration dates,
‘confirmed.
All part of the machinerylequipment satisfactorily compli with the approved drawings. Amendments, ifany,
verified to be rected and considered satisfactory.
‘Subject to satsfaciory installation, testing and trials after installation onboard the vessel
‘Asbestos-free declaration verified and supporting documentation reviewed
Final markings for identification confirmed.Customer Name ABB GENERATORS LTD. Purchase Order No
Attending Offce Nanjing Report Number NJ2691804
First Visit Date 18-Aug-2014 Last Visit Date 23-Oct-2014
A Particulars of rated condition
Rated output : 2282 KVA
Rated voliage: 480
Rated current 2744.8 8
‘Ambient Temp. Max:: 50.
Rated Power Factor 0.8
‘Type of winding connection: Y
B. The Details of material for Generator Shaft pls see ABS report NX2598816-A 8 NX2613622-A,
C. The following tests were carried out as Routine Test, Examined and all found satisfactory. (Type test refer to WO1788451), For deta,
refer to manufacturers report as attached
1. Visual inspection
2. Insulation resistance measurement
3. Winding resistance measurement
4 Airgap measurement
5. Dielectric strength test
6 Running balance test
7. Voltage regulation test
8. Bearing check after test
9. Over-curent test
10. Over speed test
Surveyoris) to The American Bureau of Shipping
Attending Surveyors
Zhou vu Electronically Signed on 23-Oct-2014
Roviewed By
Wang, Yao Electronically Signed on 23-Oct-2014, CN Jiujiang Station