AMERICAN BUREAU OF SHIPPING Customer Name ABB GENERATORS LTD. Purchase Order No ‘Attending Office Nanjing Report Number NJ2691804 First Visit Date 18-Aug-2014 Last Visit Date 23-Oct-2014 Certification OF: (One (1) AC Generator 4 Quantity: One(1) Manufacturer: ABB GENERATORS LTD. ‘Survey Location: Equipment Data Manufacturer Number(S. No.) Medel Number Destination Vessel (Class Number Builder/Shipyard Builder ID / Hull No. Purchaser Name Design Details, Design State ‘ABS Reviewing Orgerization CN Shanghai ESD Drawing Number AFP 5804000 Additional Data ABS Stamping + NJ2691804-A & Serial No. Generator Duty Main Rated Voltage 480V Rated Power 1825.6 KW Rated Frequency 60 He Number of Phase Three Rated Speed 1800 rpm Rated Power Factor (AC Generator) 08 Cass of Insulation (Stator Windings) 4 ‘Type of Enclosure Ipaa This is to Certify that the undersigned surveyor(s) to this Bureau did, at the request of the customer, carry out the following survey and report as follows: ‘Traceability of materials used on ths project has been verified. The principal data has been verified in accordance with the applicable Rulas/spectications and approved plans, and confirmed to be within acceptable tolerances. All testing (pressure/loadioperationaletc has been carried out as applicable and vented in accordance with the applicable Rulesispectications. Testing machines are maintained ina satisfactory condition and records of thelr recheck or calibration dates confirmed Al parts of the machinerylequipment satisfactorily complied witn tne approved drawings. Amendments, it any verified to be rectified and considered satisfactory, ‘Subject to satisfactory installation, testing and trials after instalation onboard the vessel ‘Asbestos-ftee deciaration veifed and supporting documentation reviewed Final markings for identification confirmed. Customer Name ABB GENERATORS LTD. Purchase Order No Attending Office Nanjing Report Number NJ2691804 Fest Visit Date 18-Aug-2014 Last Visit Date. 23-Oct-2014 ‘A Particulars of rated condition Rated output : 2282 KVA Rated voltage : 480 V Rated current : 2744.8 A ‘Ambient Temp. Max: 50.6 Rated Power Factor 0.8 ‘Type of winding connection : ¥ B. The Details of material for Generator Shaft pis see ABS report NX2599616-A & NX2613622-A, ©. The folowing tests were carried out as Routine Test, Examined and all found satisfactory (Type test refer to 01798451). For details, refer to manufacturer's report as attached. 1. Viswal inspection 2 Insulation resistance measurement 3. Winding resistance measurement 4 Air gap measurement 5 Dielectric strength test 6. Running balance test 7. Voltage regulation test 8. Bearing check afer test 9, Over-current test 10. Over speed test Surveyor(s) to The American Bureau of Shipping Attending Surveyors. Zhou Yu Electronically Signed on 23-Oct-2014 Reviewed By Wang, Ya0 Electronically Signed on 29-Oct-2014, CN Jiujiang Staton

You might also like