You are on page 1of 17

01 02 03 04 05 06 07 08 09 10

A A

COVER SHEET OF BLOCK LOGIC DIAGRAM AND SCHEMATIC DIAGRAM DRAWINGS


BUS TRANSFER SYSTEM (BTS) PANEL
BLOCK LOGIC DIAGRAM AND SCHEMATIC DIAGRAM
B B

NUMERICAL THREE BREAKER BTS 2000 STATION TO STATION BUS TRANSFER SCHEME (BTS - STS-1 OBA<=>OBC)
NUMERICAL THREE BREAKER BTS 2000 STATION TO STATION BUS TRANSFER SCHEME (BTS - STS-2 OBA<=>OBC)

REV. A

C C

CUSTOMER: DAMODAR VALLEY CORPORATION


GEMC NO.: 511687725937901 DATED :02/12/2022
PROJECT : 2X500 MW TPS AT DVC, ANDAL
D D
END USER: DSTPS DVC ANDAL

E E
The reproduction, transmission, or use of this document or its
comments is not permitted without express written authority.
Offenders will be liable for damages. All rights including rights
created by patent, grant or registration of a utility model, or
design, are reserved
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
COVER SHEET ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 1 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

BUS TRANSFER SYSTEM (BTS) PANEL


A A

BLOCK LOGIC DIAGRAM AND SCHEMATIC DIAGRAM


LEGENDS

NO CONTACT
TERMINAL IN BTS PANEL
INDEX TABLE NC CONTACT
B SHEET NO. SHEET DESCRIPTION REV. NO. TERMINAL IN GRP / TRANSFORMER PROTECTION PANEL B

1 COVER SHEET B PT SYMBOL


TERMINAL IN DCS / ANNUNCIATION PANEL
2 INDEX TABLE & LEGENDS B
X/X
3 SINGLE LINE DIAGRAM A
TERMINAL IN 11 KV BTS MAIN MODULE
RX.X BO CONTACT
4 BUS TRANSFER DETAILS A

5 BLOCK LOGIC DIAGRAM A T B


FUSE X/X

6 BLOCK LOGIC DIAGRAM A


X/X
A1 A2
C 7 A.C. CIRCUIT / D.C. CIRCUIT 0 C CONTACTOR C
IP- BTS MAIN MODULE
8 BTS 2000 INTERFACE 0 X.X BI CONTACT
RESISTOR
9 CONTROL INTERFACE A
X/X
10 SOURCE FAIL & PERMISSIVE INTERLOCKS B 1 2 MCB
11 BREAKER NO/NC CONTACTS A

12 TRIP/CLOSE CIRCUIT B

13 TRIP/CLOSE CIRCUIT, ALARM & ANNNCIATIONS B CONVENTIONS:


14 PT INPUT INTERFACE A
D 1. ALL REFERENCES (RELAY NOS / TERMINAL NOS ETC.) BELONGING TO D
15 MOTOR TRIP CONTACTS A BTS 2000 ARE PREFIXED WITH THE CHARACTER "R" "IP" AND "XA".
2. ALL REFERENCES BELONGING TO THE EXTERNAL TERMINAL BLOCK
16 TERMINAL BLOCK INTERFACE 0 INTERFACE ARE PREFIXED WITH THE CHARACTER "X" AND
17 TERMINAL BLOCK INTERFACE 0 DENOTED AS X-CTB, X-TB1 & X.

ABBREVIATIONS:

IP - CONTACT INPUT
R - CONTACT OUTPUT
TB - TERMINAL BLOCK
E C - CONTACTOR E
3 B THIRD ISSUE 16-12-2022

2 A SECOND ISSUE 08-12-2022

1 0 FIRST ISSUE 05-12-2022

ISSUE NO. REV NO. DESCRIPTION DATE

GEMC NO.:511687725937901 DATED :02/12/2022


GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
INDEX SHEET ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 2 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A A

ST-1 ST-2 ST-1 ST-2


B B

I/C-1 I/C-2 I/C-1 I/C-2


LINE PT LINE PT LINE PT LINE PT
REV. ABTS 2000 BTS 2000
REV. A
C OBA<=>OBC (STS-1) OBB<=>OBD (STS-2) C
BUS TRANSFER SYSTEM BUS TRANSFER SYSTEM
I/C-1 I/C-2 I/C-1 I/C-2
T&C T&C T&C T&C

OBA BUS OBC BUS OBB BUS OBD BUS


PT PT PT PT

D T&C T&C D
OBA BUS TIE-2 OBC BUS OBB BUS TIE-2 OBD BUS
TIE-1 (NC BKR) TIE-1 (NC BKR)

E NOTES:- E

NORMALLY OPEN BREAKER

NORMALLY CLOSED BREAKER

T&C TRIP & CLOSE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
SINGLE LINE DIAGRAM & BUS TRANSFER DETAILS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 3 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A A

BREAKER DESIGNATION P.T. CUBICLE DESIGNATION


PANEL/ SCHEME TRANSFER
RELAY DESIGNATION DETAILS I/C-1 TIE I/C-2 I/C I/C
BUS A PT BUS B PT
BREAKER BREAKER BREAKER LINE PT LINE PT
B B
BUS OBA TO
BTS-STS-1 I/C-1 OBA OBC I/C-2
BUS OBC I/C-1 TIE-1 I/C-2
LINE PT BUS PT BUS PT LINE PT
OBA<=>OBC
BTS AND VICE VERSA
PANEL BUS OBB TO
BTS-STS-2 I/C-1 OBB OBD I/C-2
BUS OBD I/C-1 TIE-1 I/C-2
LINE PT BUS PT BUS PT LINE PT
OBB<=>OBD
AND VICE VERSA

C C
REV. A

NOTES: ABOVE TABLE TO BE CONSIDERED AS GENERAL APPLICABILITY TABLE FOR STS-1 AND STS-2 SCHEME.

D D
NOTES:

1. 2X500 MW TPS AT DVC, ANDAL HAS TWO SOURCE

2. FURTHER, THE BUS A IS CONNECTED TO THE BUS B THROUGH NORMALLY OPEN BUS COUPLER BREAKER.

3. FAST BUS TRANSFER (FBT) PANEL SHALL FACILITATE TRANSFER OF SUPPLY TO OTHER BUS SECTION THROUGH BUSCOUPLER, IN CASE OF LOSS OF SUPPLY IN
ONE BUS SECTION. IN CASE OF PROBLEM IN ST-1 OR OUTAGE OF NORMAL INCOMER BREAKER, THE BUSCOUPLER BREAKER SHALL BE CLOSED THROUGH FAS
BUST TRANSFER LOGIC.
E E
4. THE BUS TRANSFER SYSTEM IS BASICALLY A THREE BREAKER BUS TRANSFER SYSTEM OPERATING BETWEEN NORMALLY CLOSED INCOMER BREAKERS AND THE
NORMALLY OPEN BUS COUPLER BREAKER

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BUS TRANSFER DETAILS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 4 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

BTS READY
(REFER NOTE 1)
A A

TRANSFER DIRECTION TRANSFER


SELECTION PROCESSING
(REFER NOTE 2) BREAKER FAILURE
TRANSFER FAST / BREAKER DETECTION AND
INITIATE END OF
SLOW / TRIP / CLOSE CORRECTIVE ACTION
TRANSFER CYCLE
(REFER NOTE 5) MOMENTARY COMMANDS
TRANSFER MODE PARALLELING (REFER NOTE 7)
COMBINATION
B (REFER NOTE 3) B
(REFER NOTE 6)

TRANSFER COMMAND
(REFER NOTE 4)

NOTES:
BLOCK LOGIC DIAGRAM
C 1) BTS READY: CHECKS ALL PERMISSIVE CONDITIONS FOR BTS READINESS C

2) TRANSFER DIRECTION SELECTION: SELECTS THE TRANSFER DIRECTION BASED ON THE CURRENT BREAKER CONFIGURATION.
- MANUAL TRANSFER: TRANSFER DIRECTION IS SELECTED BY OPERATOR USING BTS 2000 HMI INTERFACE. DEPENDING ON THE
CURRENT BREAKER CONFIGURATION, APPROPRIATE TRANSFER DIRECTIONS ARE MADE AVAILABLE TO THE OPERATOR FOR CHOICE.
- PROTECTIVE TRANSFER / AUTO TRANSFER: TRANSFER DIRECTION IS AUTOMATICALLY DETERMINED BY BTS 2000 FROM PRE-FED
SOFTWARE SETTINGS AS PER BREAKER CONFIGURATION, TYPE OF FAULT AND TYPE OF BUS TRANSFER INITIATION (PROTECTIVE /
AUTO).

3) TRANSFER MODE COMBINATION: SELECTS THE COMBINATION OF TRANSFER MODES (FAST / SLOW / MOMENTARY PARALLELING) FOR
BUS TRANSFER.
D -MANUAL TRANSFER: TRANSFER MODE COMBINATION IS SELECTED BY OPERATOR USING BTS 2000 HMI INTERFACE.
D
-PROTECTIVE TRANSFER / AUTO TRANSFER: TRANSFER MODE COMBINATION IS AUTOMATICALLY DETERMINED BY BTS 2000 FROM
PRE-FED SOFTWARE SETTINGS AS PER TYPE OF FAULT AND TYPE OF BUS TRANSFER INITIATION (PROTECTIVE / AUTO).

4) TRANSFER COMMAND: COMMAND A BUS TRANSFER OPEATION.


-MANUAL TRANSFER: TRANSFER COMMAND IS ISSUED BY OPERATOR USING BTS 2000 HMI INTERFACE.
-PROTECTIVE TRANSFER: TRANSFER COMMAND IS AUTOMATICALLY ISSUED BY BTS 2000 FROM PRE-FED SOFTWARE SETTINGS AS PER
BREAKER CONFIGURATION AND VERIFICATION OF PROTECTIVE TRANSFER INITIATION COMMAND.
-AUTO TRANSFER: TRANSFER COMMAND IS AUTOMATICALLY ISSUED BY BTS 2000 ON SENSING TIME DELAYED BUS UNHEALTHINESS
(UNDER / OVER) (VOLTAGE / FREQUENCY / |df/dt|) AS PER PRE-FED SOFTWARE SETTINGS, BREAKER CONFIGURATION AND TYPE OF
E FAULT. E
REV. A

5) TRANSFER INITIATE: UPON INITIATION, A TRANSFER IS PERMITTED AS PER THE TRANSFER CYCLE TIME WINDOW (5.0 s). IF TRANSFER
DOES NOT TAKE PLACE DURING THIS PERIOD, BTS IS AUTOMATICALLY BLOCKED ON A TRANSFER FAILURE CONDITION.

6) TRANSFER PROCESSING: PROCESSES THE TRANSFER INITIATION REQUEST BASED ON THE CHOICE OF THE TRANSFER MODE
COMBINATION TO GENERATE AND SEQUENCE BREAKER OPERATION COMMANDS.

7) DETECT THE FAILURE OF BREAKER OPERATION (IF ANY) AND TAKE FEASIBLE BACKUP CORRECTIVE ACTION.

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BLOCK LOGIC DIAGRAM ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 5 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

DC SUPPLY ON
BTS SERVICE SELECTION => BTS IN (REFER NOTE 1)
BREAKER CONFIGURATION OK (REFER NOTE 2)
BREAKER TRIP CIRCUITS HEALTHY (REFER NOTE 3) BTS TRIP OLD SOURCE BREAKER
A READY A
BREAKER CLOSE CIRCUITS HEALTHY (REFER NOTE 4) FAST ®
NEW SOURCE HEALTHY (REFER NOTE 5) INPHASE ® CHECK
CLOSE NEW SOURCE BREAKER
SLOW FAST Y
PERMISSIBLE INTERLOCKS OK TRANSFER CLOSING SUPPLY
(NOTE 11) CONTROL (NOTE 15)
BTS BLOCKED (REFER NOTE 6)
TRANSFER FAILURE
FAST ® TRIP NEW SOURCE BREAKER
SLOW N
INTERNAL SELF TEST FAILURE
FLIP-FLOP
AUTO/PROTECTIVE TRANSFER
BREAKER FAILURE SET
CHECK
TRANSFER FAILURE Y
RESET FAST OLD SOURCE
BREAKER
B OPERATOR RESET
TRIP ? B
CHECK
INPHASE Y
TRANSFER
I/C-1 75S: BREAKER IN SERVICE
(NOTE 12)
Y TRIP TRANSFER BUS
I/C-1 86: MAIN LOCKOUT MOTORS
I/C-1 LINE PT 75S: PT IN SERVICE N
CHECK
I/C-1 LINE PT 98: PT FUSE FAILURE SLOW Y TRANSFER OK
TRANSFER
BUS A PT 75S: PT IN SERVICE
(NOTE 13)
BUS A PT 98: PT FUSE FAILURE
CHECK
TIE-1 BREAKER 75S: BREAKER IN SERVICE
SLOW NEW SOURCE Y
N
C N BREAKER C
TIE-1 BREAKER 86: MAIN LOCKOUT CLOSE ?
BUS B PT 75S: PT IN SERVICE CHECK
MOMENTARY
BUS B PT 98: PT FUSE FAILURE
MOMENTARY PARALLELING
Y N
PARALLELING TRANSFER
I/C-2 LINE PT 75S: PT IN SERVICE
(NOTE 14)
I/C-2 LINE PT 98: PT FUSE FAILURE

I/C-2 75S: BREAKER IN SERVICE


NEW SOURCE BREAKER CLOSED
I/C-2 86: MAIN LOCKOUT

TIE-2 CLOSE I/L

TRANSFER MODE BREAKER FAILURE DETECTION


NOTES: IN PERMISSIVE INTERLOCK ALL THE BREAKERS TO BE CONSIDER WHICH IS CONCERNED TO BTS SCHEME.
TRANSFER PROCESSING
D COMBINATIONS AND CORRECTIVE ACTION D
TRANSFER DIRECTION
TRANSFER OLD (TRIPPING) NEW (CLOSING) CHOICE:
BREAKER TRANSFER BUS SOURCE SOURCE MANUAL/
CONFIGURATION DIRECTION PT BKR PT BKR PT
PROTECTIVE/
AUTO NOTES: 7) MANUAL TRANSFER: TRANSFER DIRECTION IS SELECTED BY OPERATOR USING BTS 2000 HMI
1. BTS CAN BE SELECTED IN/OUT OF SERVICE THROUGH BTS 2000 SERVICE INTERFACE. DEPENDING ON THE CURRENT BREAKER CONFIGURATION, APPROPRIATE TRANSFER
I/C-1 OFF
BUS- I/C-1 SELECTION TOGGLE SWITCH. DIRECTIONS ARE MADE AVAILABLE TO THE OPERATOR FOR CHOICE.
TIE-1 ON BUS A => ST-1 BUS A TIE-1 I/C-1 MANUAL
B PT LINE PT 2. BREAKER CONFIGURATION IS ASCERTAINED BY MONITORING THE STATUS TRANSFER MODE COMBINATION
I/C-2 ON
AS WELL AS CONSISTENCY OF THE NO AND NC CONTACTS OF THE FAST, FAST-SLOW, SLOW, MOMENTARY PARALLELING
MANUAL / BREAKERS. CONSISTENCY IMPLIES THAT NO AND NC STATUS FEEDBACK 8) PROTECTIVE TRANSFER: ST-1 TO ST-2, ST-2 TO ST-1.
I/C-1 BUS B
BUS A => ST-2 BUS A I/C-1 TIE-1 PROTECTIVE/ SHOULD BE OPPOSITE TO EACH OTHER. 9) AUTO TRANSFER: DISABLED SETTINGS TO BE FINALISED DURING COMMISSIONING BASED ON SPIN
I/C-1 ON LINE PT PT
AUTO 3. CONTINUITY OF TRIP CIRCUITS OF ALL CLOSED BREAKERS ARE DOWN TRIALS.
TIE-1 OFF
MONITORED BY SENSING THE VOLTAGE DROP ACROSS THE TRIPPING TRANSFER MODE COMBINATION
I/C-2 ON MANUAL /
I/C-2 BUS A CONTACTS. 10) PROTECTIVE/AUTO TRANSFER: FAST-INPHASE-SLOW
BUS B => ST-1 BUS B I/C-2 TIE-1 PROTECTIVE/
LINE PT PT
AUTO 4. CONTINUITY OF CLOSING CIRCUITS OF ALL OPEN BREAKERS ARE TRANSFER PROCESSING: TRANSFER MODE CRITERIA (SETTINGS TO BE FINALISED DURING COMMISSIONING)
E I/C-1 ON MONITORED BY SENSING THE VOLTAGE DROP ACROSS THE CLOSING 11. FAST TRANSFER: |PHASE DIFF.| < 20°, |BUS V| > 80%, ANSI C50.41, TIME WINDOW: 0.1s, MAXIMUM FREQUENCY
DIFF <1.5 Hz. CLOSING DELAY: 0 ms.
E
TIE-1 ON I/C-2
CONTACTS.
BUS B => ST-2 BUS B TIE-1 BUS B I/C-2 MANUAL 12. IN PHASE TRANSFER : |PHASE DIFF.| < 20°, |BUS V| > 70%, TIME WINDOW : 0.7s. df/dt=3 Hz/sec, MAXIMUM
I/C-2 OFF LINE PT 5. NEW SOURCE HEALTHINES IS DETERMINED BY MONITORING THE U/V FREQUENCY DIFF (Δf) <5 Hz
(90%) OF THE PT INPUT OF THE NEW SOURCE (REFER TRANSFER 13. SLOW TRANSFER: |BUS V| < 20%, TIME WINDOW 3s REV. A
I/C-1 I/C-2
MANUAL / DIRECTION). 14. MOM. PARALLELING TRANSFER: |PHASE DIFF| < 20°, |BUS V| > 80%, TIME WINDOW: 0.5s
BUS A+B => ST-2 BUS A+B I/C-1 I/C-2 PROTECTIVE/ 6. BTS IS BLOCKED UNDER CONDITIONS THAT DEMAND OPERATOR 15. CLOSING SUPPLY CONTROL MOMENTARILY DISCONNECTS ALL THE BREAKER CLOSING CIRCUITS AT THE END
LINE PT LINE PT
AUTO OF THE TRANSFER CYCLE TO ENABLE DROPOUT OF THE ANTI PUMPING RELAYS.
ATTENTION AND REQUIRE MANUAL RESET THROUGH BTS 2000 HMI
MANUAL/
INTERFACE.
I/C-2 I/C-1 BREAKER FAILURE DETECTION AND CORRECTIVE ACTION
BUS A+B => ST-1 BUS A+B I/C-2 I/C-1 PROTECTIVE/
LINE PT LINE PT 16. DURING BREAKER FAILURE DETECTION, BREAKER OPERATION IS CHECKED BY MONITORING THE TIME DELAY
AUTO
BETWEEN A TRIP/CLOSE COMMAND AND ITS RESPECTIVE STATUS CHANGEOVER. IF THIS TIME DELAY EXCEEDS A
PREFED TIME MARGIN SETTING; THEN THE BREAKER FAILURE CORRECTIVE ACTION LOGIC IS INVOKED.
* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC NOMENCLATURE 17. IF A BREAKER TRIPPING FAILURE RESULTS IN A PERMANENT PARALLELING CONDITION, THEN A TRIP COMMAND
IS ISSUED TO THE NEWLY CLOSED NEW SOURCE BREAKER.

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BLOCK LOGIC DIAGRAM ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 6 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

220VDC 220VDC
SOURCE I SOURCE II
A A
XCTB-1 XCTB-2 XCTB-3 XCTB-4
+VE -VE +VE -VE

J1 J2 J3 J4 S4 (16A)
A1 B1 A2 B2
SOURCE I
MCB1
OFF
PHASE (6A)
SOURCE II

H1 H3 1
1 2 2 K1
B X-CTB1/1 1 1 1
T B
F1
S1 S2 S3 (4A)
B K3
2 2 2

220VDCPOSITIVE BUS
H5 T T
1 H7 1 H11
DS1 TH1 F3 F5
P DOOR THERMOSTAT (2A) (2A)
SKT1 SWITCH 30-85° C B B
230 VAC, 50 Hz , 1F 2 2 TO 9/B1 K7TO 9/A1 K9
C H9 H13 C
SWITCH-SOCKET BTS 2000 POWER SCHEME
N SUPPLY CIRCUIT K8 CONTROL CIRCUIT
TO 9/D1 TO 9/E1 K10
B B
F4 F6
(2A) (2A)
P P T T

IL1 HTC1 220VDCNEGATIVE BUS


ENCL. HEATER
LIGHT (80W)
K4
B
F2
D H2 H4 N N
(4A) D
3 4
T
MCB1
X-CTB1/2 (6A) K2
NEUTRAL

LIGHTING HEATER 220VDC SUPPLY SWITCHING AND PROTECTION CIRCUIT SCHEME BTS 2000 POWER SCHEME
A.C. SUPPLY SWITCHING AND PROTECTION CIRCUIT SWITCH SOCKET (COMMON PER PANEL)
CIRCUIT CIRCUIT MAIN CIRCUIT SUPPLY CIRCUIT CONTROL CIRCUIT
E E
A.C. CIRCUIT: SUPPLY, PROTECTION AND DISTRIBUTION 220VDC CIRCUIT: SUPPLY, PROTECTION AND DISTRIBUTION

NOTES:

1) A.C. CIRCUIT AND D.C. CIRCUIT (D.C. SUPPLY SWITCHING AND PROTECTION) ARE COMMON FOR ALL SCHEMES PER PANEL.

* SWITCHING TO BE INCORPORATED BY CUSTOMER. SELECTOR SWITCH, MCBs, DIODE SCHEME ETC. CAN BE USED.

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
AC / DC CIRCUIT ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 7 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

XA1
A X-1 X-3 X-5 A
14C/1 1 TV1
I/C-1 LN PT R-Y
1 Relay 1.1 1 Relay 2.1 BUS A 1 Relay 3.1 2
SPARE 15C/1 12C/2 TRIP I/C-1
2 Relay 1.1 2 MOTOR TRIP 2 RJ45 PORT 14C/2 3 TV2
3 Relay 1.2 3 Relay 2.2 3 BUS A PT R-Y
SPARE 13B/10 AUTO FAST BUS 4
4 Relay 1.2 4 TRANSFER 4 TX1 14C/3 5 TV3
5 Relay 1.3 5 SUCCESSFUL 5 BUS B PT R-Y
Relay 2.3 Relay 3.2 6
12C/4 CLOSE I/C-1
6 SPARE 6 Relay 2.4 BUS B 6
15C/3
7 Relay 1.3 7 MOTOR TRIP 7 TX2
8 Relay 1.4 8 Relay 2.5 8 XA2
SPARE TEST MODE
9 9B/9 9 Relay 2.5 9 Relay 3.3
SELECTION 12C/6 TRIP TIE-1 14C/4 1 TV4
I/C-2 LN PT R-Y
10 Relay 1.4 10 10 2
B 11 Relay 1.5 11 Relay 2.6 11 B
BTS IN/OUT SPARE 3 TV5
12 SPARE 9B/3 12 Relay 2.6 12 SPARE
SELECTION 4
13 Relay 1.5 13 13 Relay 3.4
12C/8 CLOSE TIE-1 5 TV6
14 Relay 1.5 RELAY 14 Relay 2.7 14 SPARE
6
SPARE
WATCHDOG FAIL/
13D/8 15 13B/6 15 BTS NOT READY 15
INTERNAL
16 Relay 1.5 DIAGNOSTIC 16 Relay 2.8 16
Relay 2.9 CLOSING Relay 3.5
17 17 17 XA3
9B/4 SUPPLY 13C/2 TRIP I/C-2
18 18 CONTROL 18
1 TCVD
TCVD INPUT
2
3
C 4 C
5
6
7
8
X-6 9
X-2 X-4
10
1 Power BTS 2000 1 Relay 2.10 SPARE 13C/4 1 Relay 3.6
9C/2
2 POWER SUPPLY 2 Relay 2.11 SPARE
CLOSE I/C-2 11
Supply
3 Input 1.1 3 Relay 2.12 SPARE 12
I/C-1 TRIP
12C/2
4 Input 1.1 CKT. MONITOR 4 COMMON
5 Input 1.2 I/C-1 CLOSE 11D/1 5 Input 3.1 I/C-1 NO 10D/1 5 Input 3.1
D
12C/4
6 Input 1.2 CKT. MONITOR 11D/2 6 Input 3.2 10D/2 6 Input 3.2
ST-1 FAILURE FO PORT XA4 D
I/C-1 NC ST-2 FAILURE (LC CONNECTOR TYPE)
7 Input 1.3 TIE-1 TRIP 11D/3 7 Input 3.3 9D/9 7 Input 3.3 1
12C/6 TIE-1 NO READY FOR TEST TRANSFER CT INPUT
8 Input 1.3 CKT. MONITOR 11D/4 8 Input 3.4 Input 3.4 2 TA1 5
TIE-1 NC 10D/3 8
9 Input 1.4 9
I/C- 1 BKR READY TX3 3 1
TIE-1 CLOSE 11D/5 Input 3.5 I/C-2 NO 10D/5 9 Input 3.5
12C/8 I/C-1 LINE PT READY 4
10 Input 1.4 CKT. MONITOR 11D/6 10 Input 3.6 10D/6 10 Input 3.6
I/C-2 NC TIE-1 BREAKER READY TA2 5 CT INPUT
11 Input 1.5 11 COMMON 11 5
I/C-2 TRIP COMMON TX4
13C/1
12 Input 1.5 CKT. MONITOR 12 Input 3.7 6 1
11D/7
TIE-2 NO 10D/7 12 Input 3.7
I/C-2 LINE PT READY 7
13 Input 1.6 I/C-2 CLOSE 13 Input 3.8 10D/8 13 Input 3.8
13C/4 SPARE I/C- 2 BKR READY
Input 1.6 CKT. MONITOR Input 3.9 8 TA3 5 CT INPUT
14 14 SPARE 10D/9 14 Input 3.9
15 Input 1.7 15 Input 3.10
BUS A PT READY 9 1
SPARE 10D/10 15 Input 3.10
SPARE BUS B PT READY 10
16 Input 1.7 16 Input 3.11 16 Input 3.11
SPARE SPARE
E 17 Input 1.8 17 Input 3.12 11 TA4 5 CT INPUT
E
SPARE SPARE 17 Input 3.12
18 Input 1.8 18 COMMON
SPARE 12 1
18 COMMON

TV-INPUT VOLTAGE TRANSFORMERS(VT TYPE)


TA-INPUT CURRENT TRANSFORMERS
(CT1 TYPE - 1A OR 5A)
* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC TCVD-150mA CURRENT INPUT
NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BTS-2000 INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 8 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A A
K9 (+VE) 220VDC SCHEME CONTROL CIRCUIT
FROM 7/C10 TO 10/A1

ITB/1 ITB/1
BTS IN/OUT BTS 2000
SERVICE
SELECTION NO NC NO NC MAIN
TOGGLE SWITCH MODULE
9/C9 12/B2 9/C9 12/B8
TEST X3/9
12/B4 13/B2 MODE
BTS 2000
SELECT
MAIN 12/B6 13/B4 R-2.5a R-2.5b
MODULE
CLOSING 15/B1 15/B3
B BTS 2000 K9A X3/17 B
SUPPLY X3/8 X3/10
MAIN CONTROL
MODULE C4: 2NO+4NC C5: 2NO+4NC
K7
FROM 7/C9 BTS SERVICE R-2.9
X3/12
IN/OUT K15 K15
SELECTION X3/18 K15
BTS 2000 R-2.6 13
MAIN
MODULE TEST MODE C4
X3/13
X2/1 SELECT
14
POWER K17
SUPPLY 13
C TEST MODE C
X2/2 NO NC C5
15/B1 12/A3
SELECT
15/B3 12/A7 14
K19
13/A3
NO BTS 2000
K13 MAIN
K8 12/A2
FROM 7/D9 C2: 2NO+3NC MODULE
12/A4 READY X6/7
K11 FOR TEST
12/A6 TRANSFER
IP-
12/A9 A1 A1 A1 A1 A1
3.3
D NO NC D
13/A8 C1 C2 C3 C4 C5 X6/11
13/B7 12/B4
13/A4
A2 A2 A2 12/B8 A2 A2
13/B8
13/B4
C1: 7NO ITB/3
C3: 2NO+3NC
K10 K10

FROM 7/C10 (-VE) 220VDC SCHEME CONTROL CIRCUIT TO 10/E1

CLOSING SUPPLY TEST MODE


BTS 2000 POWER SUPPLY BTS IN/OUT SELECTION BTS 2000 TEST TRANSFER INTERFACE
CONTROL SELECTION
E NOTE:
E

1) THE 'BTS READY TO TRANSFER' CONTACT OUTPUT CLOSES WHEN THE BUS TRANSFER DIRECTION IS MANUALLY SELECTED, AND ALL SYSTEM CONDITIONS, INCLUDING PERMISSIVE INTERLOCKS, ARE OK.

2) WHEN THE TEST MODE IS NOT SELECTED, A 'BTS READY TO TRANSFER' CONDITION ILLUMINATES WITH LIVE SOFTKEY ON HMI. A MANUAL TRANSFER GETS INITIATED ON PRESSING LIVE SOFTKEY.

3) WHEN THE TEST MODE IS SELECTED, TEST MODE RELAYS C4 AND C5 PICKUP AND A 'BTS READY TO TRANSFER' CONDITION ILLUMINATES WITH TEST SOFTKEY.
THE RELAY INTRODUCE A HIGH IMPEDANCE IN THE BREAKER TRIPPING / CLOSING CIRCUITS THUS ENSURING THAT THEY WILL NOT OPERATE DURING A TEST TRANSFER.
A TEST TRANSFER GETS INITIATED ON PRESSING BY TEST SOFTKEY. A TEST TRANSFER CHECKS ALL SYSTEM CONDITIONS AND CONDUCTS A FICTITIOUS BUS TRANSFER TO PROVIDE THE OPERATOR
A FEEDBACK OF THE ANTICIPATED OPERATIONS OF THE BUS TRANSFER SYSTEM IF A MANUAL BUS TRANSFER IS CONDUCTED FOR THE SELECTED TRANSFER DIRECTION AND TRANSFER MODE COMBINATION UNDER THE CURRENT SYSTEM CONDITIONS.

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
CONTROL INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 9 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A A

K9 (+VE) 220VDC SCHEME CONTROL CIRCUIT K9


TO 11/A1

X-TB1/1 X-TB1/3

X-TB1/9 X-TB1/47 X-TB1/23 X-TB1/51 X-TB1/37 X-TB1/49 X-TB1/53

TB1/45 TB1/45
REV. B TB2/53 TB1/39 TB1/43 TB1/39 TB2/53 TB2/27 TB2/27
ST-1 ST-2
B FAILURE FAILURE B
86: 98: 86: 98: 86: 98: 98:
LOCKOUT FUSE LOCKOUT FUSE LOCKOUT FUSE FUSE
RELAY FAIL RELAY RELAY FAIL RELAY RELAY FAIL RELAY FAIL RELAY
TB1/46 TB1/46
TB2/54 TB1/40 TB1/44 TB1/40 TB2/54 TB2/28 TB2/28
REV. B

X-TB1/2 X-TB1/4
TB2/47 TB1/35 TB1/37 TB1/35 TB2/47 TB1/33 TB1/33
75S: 75S: 75S: 75S: 75S: 75S: 75S:
BKR IN PT IN BKR IN PT IN BKR IN PT IN PT IN
C SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE C

TB2/48 TB1/36 TB1/38 TB1/36 TB2/48 TB1/34 TB1/34

X-TB1/10 X-TB1/48 X-TB1/24 X-TB1/52 X-TB1/38 X-TB1/50 X-TB1/54

BTS 2000 BTS 2000 K31


MAIN K21 MAIN I/C-2 X6/12
MODULE MODULE K23 K25 K27 K29 LINE PT K33 K35 K37
D ST-1 X6/5 ST-2 X6/6 I/C-1 X6/8 I/C-1 X6/9 TIE-1 X6/10
READY IP- I/C-2 X6/13 BUS A X6/14 BUS B X6/15
D
FAILURE FAILURE BREAKER LINE PT BREAKER 3.7 BREAKER PT PT
READY READY READY READY READY READY
IP- IP- IP- IP- IP- IP- IP- IP-
3.1 3.2 3.4 3.5 3.6 X6/18 3.8 3.9 3.10

X6/11 X6/11 X6/11 X6/11 X6/11 X6/18 X6/18 X6/18


ITB-3
K10 K10
(-VE) 220VDC SCHEME CONTROL CIRCUIT TO 11/E1

I/C-1 BREAKER READY I/C-1 LINE PT READY TIE-1 BREAKER READY I/C-2 LINE PT READY I/C- 2 BREAKER READY BUS A PT READY BUS B PT READY
ST-1 ST-2
E FAILURE FAILURE PERMISSIVE INTERLOCK OK E

NOTES:

1) SWITCHGEAR INTERFACING SHALL BE COMPLETED DURING COMMISSIONING.

* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC


NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
SOURCE FAILURE & PERMISSIVE INTERLOCKS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 10 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A A
K9 (+VE) 220VDC SCHEME CONTROL CIRCUIT TO 13/A1
FROM 11/A10

X-TB1/5 X-TB1/7 X-TB1/19 X-TB1/21 X-TB1/33 X-TB1/35 X-TB1/81

TB2/19 TB2/21 TB2/19 TB2/21 TB2/19 TB2/21 TB2/19

TIE-1 52a: TIE-1 52b: TIE-2 52a:


I/C-1 52a: I/C-1 52b: I/C-2 52a: I/C-2 52b:
NO NC NO
NO NC NO NC
B CONTACT CONTACT
CONTACT CONTACT
CONTACT CONTACT
CONTACT B

TB2/20 TB2/22 TB2/20 TB2/22 TB2/20 TB2/22 TB2/20

X-TB1/6 X-TB1/8 X-TB1/20 X-TB1/22 X-TB1/34 XT-B1/36 X-TB1/82

C K39 K41 K43 K45 K47 K49 K181


C

BTS 2000 BTS 2000


MAIN MAIN
MODULE BTS 2000 BTS 2000 BTS 2000 BTS 2000 BTS 2000 MODULE
I/C-1 NO X4/5 MAIN MAIN MAIN MAIN MAIN TIE-2 NO X4/12
CONTACT MODULE MODULE MODULE MODULE MODULE CONTACT

IP- I/C-1 NC X4/6 TIE-1 NO X4/7 TIE-1 NC X4/8 I/C-2 NO X4/9 I/C-2 NC X4/10 IP-
D CONTACT CONTACT CONTACT CONTACT CONTACT D
2.1 2.7
IP- IP- IP- IP- IP-
X4/11 2.2 2.3 2.4 2.5 2.6 X4/18

X4/11 X4/11 X4/11 X4/11 X4/11


ITB/4 ITB/4
10 TO 13/E1
FROM 11/E10 (-VE) 220VDC SCHEME CONTROL CIRCUIT

I/C-1 NO I/C-1 NC TIE-1 NO TIE-1 NC I/C-2 NO I/C-2 NC TIE-2 NO


CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT CONTACT
E E
NOTES:
1) BREAKER NO / NC CONTACTS ARE MONITORED FOR EVALUATING THE STATUS OF THE BREAKER OPERATIONS.
2) THE TRIP / CLOSE OPERATION TIMINGS AND BREAKER FAILURE DETECTION OF THE BREAKERS ARE ASCERTAINED BY MONITORING THE TIME DIFFERENCE
BETWEEN BREAKER OPERATION SIGNAL (TRIP / CLOSE) AND RESPECTIVE CHANGE IN STATUS OF BREAKER CONTACT

* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC


NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BREAKER NO /NC CONTACT ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 11 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

(+VE) 220VDC (+VE) 220VDC (+VE) 220VDC (+VE) 220VDC


FROM SWGR.
TB1/15
FROM SWGR.
REV. B
FROM SWGR. REV. B TB1/15 FROM SWGR.
REV. B
A TB1/53 X-TB1/17 TB1/57 TB1/52 X-TB1/31 TB1/57 A
K69 K91
X-TB1/11 X-TB1/14 X-TB1/25 31 X-TB1/28
21
C2 C2 K81
K51 K59 K73 9/D3
13 9/D3 23 33 43
BTS IN BTS IN BTS IN C1 32 C1 BTS IN
C1 22 C1
9/D3
K93 9/D3
SELECTION 9/D3 9/D3 SELECTION SELECTION SELECTION
K71 X-TB1/32
14 X-TB1/18 24 34 44
K53 K61 K75 K83

21 PCB1/1 TB1/16 31 PCB1/5 61 PCB1/9


TB1/16 21 PCB1/13
B TEST MODE C4 RES3 TEST MODE C5 RES4 B
RES1 TEST MODE C4 RES2
TEST MODE C4 BTS OUT I/L
9/D7 (5Kk /9W) 9/D8 (5Kk /9W)
RELAY (5Kk /9W) BTS OUT I/L RELAY 9/D7 (5Kk /9W) 9/D7 RELAY
RELAY
22 PCB1/3 32 PCB1/7 62 PCB1/11 22 PCB1/15

K55 K85
K63 K77
21 31
C3
ITB/5 C3 ITB/6 9-D4
9-D4
32
BTS 2000 K55 BTS 2000 22 BTS 2000 K77 BTS 2000
MAIN MAIN MAIN MAIN K87
K65
C MODULE MODULE MODULE MODULE C
I/C-1 CLOSE COIL TIE-1 TRIP COIL TIE-1 TRIP TIE-1 CLOSE
I/C-1 TRIP COIL X2/3 X2/5 X5/5 I/C-1 CLOSE X5/9 TIE-1 CLOSE COIL X2/9 X5/13
MONITORING
X5/1 I/C-1 TRIP MONITORING MONITORING X2/7 MONITORING
IP- IP- IP- R-3.3 IP-
R-3.1 R-3.2 R-3.4
1.1 1.2 1.3 1.4

X2/4 X5/2 X2/6 X5/6 X2/8 X5/10 X2/10 X5/14

K57 K79 K89


K67
X-TB1/12 X-TB1/26 X-TB1/29
X-TB1/15
D TB1/49 TB1/49 TB1/16 D
TB1/16
REV. B REV. B REV. B
TC CC TC CC

I/C-1 TRIP CIRCUIT I/C-1 CLOSE CIRCUIT TIE-1 TRIP CIRCUIT WITH TIE-1 CLOSE CIRCUIT
WITH COIL MONITORING WITH COIL MONITORING COIL MONITORING WITH COIL MONITORING
E NOTES: E
1) ALL BREAKER TRIP / CLOSE AS WELL AS MOTOR TRIP CIRCUITS GET DISABLED WHEN BTS IS IN OUT CONDITION BY THE BTS IN/OUT SELECTION RELAY C1,C2.
2) ON PICKUP, THE TEST MODE RELAYS INTRODUCE A HIGH IMPEDANCE IN THE BREAKER TRIPPING / CLOSING CIRCUITS THUS ENSURING THAT THEY WILL NOT OPERATE DURING A TEST TRANSFER.
3) ALL BREAKER CLOSE CIRCUITS GET MOMENTARILY DISCONNECTED BY THE CLOSING SUPPLY CONTROL RELAY C3 AT THE END OF EACH TRANSFER CYCLE. THIS ENABLES THE DROPOUT OF THE ANTI
PUMPING RELAYS WITH LOW DROPOUT CHARACTERISTICS.
4) BTS OUT (NC) CONTACT OF RELAY C2 PROVIDED AS EXTRA FOR FSTSRE USE IN CLOSING CIRCUITS IF REQUIRED.

* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC


NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TRIP / CLOSE CIRCUITS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 12 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
(+VE) 220VDC (+VE) 220VDC
FROM SWGR. FROM SWGR.
REV. B TB1/15
TB1/53 X-TB1/45
TB1/57
A A
X-TB1/39 K113 X-TB1/42
61
K95 C2 K103
63 BTS 2000 BTS 2000
53 9/D3 X-TB1/67 X-TB1/69 X-TB1/71 X-TB1/73
MAIN MAIN
BTS IN C1 C1 BTS IN MODULE K117 K121 K125 MODULE K129
62
SELECTION 9/D3
K115
9/D3 SELECTION BTS MAIN X3/14 73 AUTO X-3/3
MODULE 13
FAST BUS
64 NOT TRANSFER
54 X-TB1/46 C3 C1 TRANSFER
K97 K105 READY R 2.7 CYCLE BTS IN 9/D3 SUCCESSFUL R 2.2
9-D4
OVER
31 PCB1/17 TB1/16 61 PCB1/21 X3/15 14 74 X-3/4

TEST MODE RES6 K119 K123 K127 K131


B TEST MODE C5 RES5 C5
B
RELAY 9/D8 (5Kk /9W) BTS OUT I/L RELAY 9/D8 (5Kk /9W) X-TB1/68 X-TB1/70 X-TB1/72 X-TB1/74

32 PCB1/19 62 PCB1/23
K107
K99
TRANSFER CYCLE AUTO FAST BUS
61 BTS NOT READY BTS IN
OVER TRANSFER
ITB/7 C3
9-D4 SUCCESSFUL
K99 62
BTS 2000 BTS 2000
MAIN MAIN K109
C MODULE MODULE C
I/C-2 TRIP COIL X5/17 I/C-2 TRIP I/C-2 CLOSE COIL X6/1 I/C-2 CLOSE
X2/11 X2/13
MONITORING MONITORING
IP- IP-
R-3.5 R-3.6 X-TB1/75 X-TB1/77 X-TB1/79
1.5 1.6
K133 K137 K141
X2/12 X5/18 X2/14 X6/2
43 43 RELAY X1/15
WATCHDOG
BUS A BUS B FAIL/
C6 C7
K111 MOTOR 15/D1 MOTOR INTERNAL R 1.5
K101 15/D3
TRIP TRIP DIAGNOSTIC
44
44 X1/16
X-TB1/40 X-TB1/43
K135 K139 K143
D TB1/49 TB1/16 X-TB1/76 X-TB1/78 X-TB1/80 D
REV. B

TC CC
RELAY
BUS A BUS B
WATCHDOG FAIL/
MOTOR TRIP MOTOR TRIP
INTERNAL DIAGNOSTIC

I/C-2 TRIP CIRCUIT WITH COIL I/C-2 CLOSE CIRCUIT WITH COIL
MONITORING MONITORING ALARM / ANNUNCIATION/D.C.S
E NOTES: E
1) ALL BREAKER TRIP / CLOSE AS WELL AS MOTOR TRIP CIRCUITS GET DISABLED WHEN BTS IS IN OUT CONDITION BY THE BTS IN/OUT SELECTION RELAY C1,C2.
2) ON PICKUP, THE TEST MODE RELAYS INTRODUCE A HIGH IMPEDANCE IN THE BREAKER TRIPPING / CLOSING CIRCUITS THUS ENSURING THAT THEY WILL NOT OPERATE DURING A TEST TRANSFER.
3) ALL BREAKER CLOSE CIRCUITS GET MOMENTARILY DISCONNECTED BY THE CLOSING SUPPLY CONTROL RELAY C3 AT THE END OF EACH TRANSFER CYCLE. THIS ENABLES THE DROPOUT OF THE ANTI
PUMPING RELAYS WITH LOW DROPOUT CHARACTERISTICS.
4) BTS OUT (NC) CONTACT OF RELAY C2 PROVIDED AS EXTRA FOR FSTSRE USE IN CLOSING CIRCUITS IF REQUIRED.

* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC


NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TRIP / CLOSE CIRCUITS/ALARM / ANNUNC. ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 13 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

R-PHASE R-PHASE R-PHASE R-PHASE R-PHASE R-PHASE

A A
TB1/16 TB2/25 TB2/25 TB1/16 ??? ???

X-TB1/55 X-TB1/57 X-TB1/59 X-TB1/61 X-TB1/63 X-TB1/65

B B
BTS 2000 H15 BTS 2000 H19 BTS 2000 H23 BTS 2000 H27 BTS 2000 H31 BTS 2000 H35
MAIN MAIN MAIN MAIN MAIN MAIN
MODULE MODULE MODULE MODULE MODULE MODULE
I/C-1 XA-1/1 BUS A XA-1/3 BUS B XA-1/5 I/C-2 XA-2/1 SPARE PT XA-2/3 SPARE PT XA-2/5
LINE PT PT PT LINE PT

TV1 TV2 TV3 TV4 TV5 TV6

XA-1/2 XA-1/4 XA-1/6 XA-2/2 XA-2/4 XA-2/5

H17 H21 H25 H29 H33 H37


C C

X-TB1/56 X-TB1/58 X-TB1/60 X-TB1/62 X-TB1/64 X-TB1/66

D D
TB1/19 TB2/26 TB2/26 TB1/19 ??? ???

Y-PHASE Y-PHASE Y-PHASE Y-PHASE Y-PHASE Y-PHASE

I/C-1 LINE PT BUS A PT BUS B PT I/C-2 LINE PT SPARE PT SPARE PT

E E
NOTES:

1) BTS 2000 PT INPUTS PROVIDE INBUILT GALVANIC ISOLATION AND NO SEPARATE ISOLATION PTs ARE REQUIRED.

* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC


NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
PT INPUT ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 14OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A (+VE) 220VDC SCHEME CONTROL CIRCUIT A


K9 K9
FROM 11/A10 END
ITB/2

X-MTB1/1 X-MTB1/3 X-MTB1/5 X-MTB1/7 X-MTB1/9 X-MTB1/11


K157 K161 K165 K169 K173 K177
13 43 13 23 33 13 23 33
BTS IN C2 BTS IN C2 C6 C6 C6 C7 C7 C7
SELECTION 9/D3 SELECTION 9/D3 15/D1 15/D1 15/D1 15/D3 15/D3 15/D3

14 44 14 24 34 14 24 34
B B
K159 K163 K167 K171 K175 K179
X-MTB1/2 X-MTB1/4 X-MTB1/6 X-MTB1/8 X-MTB1/10 X-MTB1/12
K145 K151

71 PCB1/25 71 PCB1/29
TEST MODE C4 RES7 TEST MODE C5 RES8
RELAY 9/D9 (5Kk /9W) RELAY 9/D9 (5Kk /9W)
BUS A BUS A BUS A BUS B BUS B BUS B
72 PCB1/27 72 PCB1/31 MOTOR #1 TRIP MOTOR #2 TRIP MOTOR #3 TRIP MOTOR #1 TRIP MOTOR #2 TRIP MOTOR #3 TRIP

K147 K153
BTS 2000 BTS 2000
C MAIN MAIN C
MODULE MODULE
BUS A X-3/1 BUS B X-3/6
MOTOR TRIP MOTOR TRIP
MOTOR FEEDER DETAILS
R-2.1 R-2.4 SCHEME BUS MOTOR NO. MOTOR FD SWGR TB
NO NO #1 CW#C TB1/46-49
OBA
X-3/2 15/B5 X-3/7 15/B8 STS-1 #2 MDBFP TB1/46-49
OBA<=>OBC #1 CW#C TB1/46-49
15/B6 15/B9 OBC
#2 MDBFP TB1/46-49
K149 15/B7 K155 15/B10
D 13/D6 13/D7 STS-2 OBB #1 CW#D TB1/46-49 D
A1 A1
OBB<=>OBD OBD #1 CW#D TB1/46-49
C6: 4 NO C7: 4 NO
C6 C7
A2 A2

REV. A
K10 K10
FROM 11/E10 (-VE) 220VDC SCHEME CONTROL CIRCUIT END

E E
BUS A MOTOR TRIP BUS B MOTOR TRIP
BUS A MOTOR TRIP CONTACTS BUS B MOTOR TRIP CONTACTS
RELAY RELAY

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
MOTOR TRIP CONTACTS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 15 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

A A

24
BREAKER READY
23
I/C-2
52b 22 BREAKER BTS OUT I/L 46
NC CONTACT
21 45
52a 20 SPARE 44
NO CONTACT 43
B 19 B
CLOSE COMMAND
I/C-1
18 42
BREAKER BTS OUT I/L
17 SPARE 41
SPARE 16 40
TRIP COMMAND
15 39
CLOSE COMMAND
14 38
BREAKER READY
SPARE 13 37
12 52b 36
TRIP COMMAND
C 11
NC CONTACT 35 C
10 52a 34
SPARE BREAKER READY
10 9 TIE-1
NO CONTACT 33
SPARE
9 8
BREAKER 32
52b BTS OUT I/L
8
NC CONTACT 7 31
SPARE
7 52a 6 SPARE 30
NO CONTACT 5 29
SOURCE 2 -VE 6 CLOSE COMMAND
220VDC
SOURCE 2 +VE 5 PROTECTIVE 4 28
SUPPLY
D SOURCE 1 -VE 4
TRANSFER ST-2 FAILURE
3 SPARE 27 D
INPUTS
2 26
SOURCE 1 +VE 3 TRIP COMMAND
ST-1 FAILURE 1 25
230VAC, N 2
50 Hz,
1 PH AC
P 1
SUPPLY X-TB1 X-TB1
X-CTB

X-CTB INTERFACE X-TB1 INTERFACE

E E
NOTES:

1. ALL TB'S OF THE PANEL WILL BE SUITABLE FOR RING TYPE LUG.
STUD TYPE TERMINAL BLOCK CSTSB4
* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC
DISCONNECTING TYPE TERMINAL BLOCK CDTTS NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TERMINAL BLOCK INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 16 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10

BTS INTERNAL CKT TB. 7


6
A A
5
4
3
2
1
SPARE
PT INPUTS 66 ITB
SPARE PT 86
65 SPARE
85 SPARE
SPARE
20
64
B SPARE PT
84 19 B
63 SPARE
TIE-2 NO 83 SPARE
18
62
I/C-2 LINE PT
CONTACT
82 17
61 TIE-2 NO
81 SPARE
16
60 ALARM /
BUS B PT ANNUNCIATION IN RELAY 80 15
59 D.C.S. WATCHDOG FAIL/
79 14
58 INTERNAL DIAGNOSTIC SPARE
BUS A PT
78 13
57 OBC BUS
MOTOR TRIP 77 BUS B 12
C 56 MOTOR TRIP MOTOR #3 TRIP
C
I/C-1 LINE PT BUS -A 76 11
55 MOTOR TRIP
PT 75 10
54 MOTOR #2 TRIP
READINESS BUS- B PT READY AUTO FAST BUS TRANSFER 74 9
53 SUCCESSFUL
--

73 8
I/C-2 LINE
52 MOTOR #1 TRIP
BTS IN 72 7
PT READY 51 SELECTION
71
BUS A 6
OBA BUS PT
50 MOTOR TRIP MOTOR #3 TRIP
TRANSFER 70 5
READY 49
CYCLE OVER
69 4
D 48 MOTOR #2 TRIP D
I/C-1 LINE
68 3
PT READY 47 BTS NOT READY
67 2
MOTOR #1 TRIP
1
XTB1 XTB1 X-MTB1

X-TB1 & X-MTB1 INTERFACE

E E
STUD TYPE TERMINAL BLOCK CSTSB4

DISCONNECTING TYPE TERMINAL BLOCK CDTTS

* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC


NOMENCLATURE

GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TERMINAL BLOCK INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 17 OF 17
01 02 03 04 05 06 07 08 09 10