NUMERICAL THREE BREAKER BTS 2000 STATION TO STATION BUS TRANSFER SCHEME (BTS - STS-1 OBA<=>OBC)
NUMERICAL THREE BREAKER BTS 2000 STATION TO STATION BUS TRANSFER SCHEME (BTS - STS-2 OBA<=>OBC)
REV. A
C C
E E
The reproduction, transmission, or use of this document or its
comments is not permitted without express written authority.
Offenders will be liable for damages. All rights including rights
created by patent, grant or registration of a utility model, or
design, are reserved
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
COVER SHEET ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 1 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
NO CONTACT
TERMINAL IN BTS PANEL
INDEX TABLE NC CONTACT
B SHEET NO. SHEET DESCRIPTION REV. NO. TERMINAL IN GRP / TRANSFORMER PROTECTION PANEL B
12 TRIP/CLOSE CIRCUIT B
ABBREVIATIONS:
IP - CONTACT INPUT
R - CONTACT OUTPUT
TB - TERMINAL BLOCK
E C - CONTACTOR E
3 B THIRD ISSUE 16-12-2022
A A
D T&C T&C D
OBA BUS TIE-2 OBC BUS OBB BUS TIE-2 OBD BUS
TIE-1 (NC BKR) TIE-1 (NC BKR)
E NOTES:- E
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
SINGLE LINE DIAGRAM & BUS TRANSFER DETAILS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 3 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
A A
C C
REV. A
NOTES: ABOVE TABLE TO BE CONSIDERED AS GENERAL APPLICABILITY TABLE FOR STS-1 AND STS-2 SCHEME.
D D
NOTES:
2. FURTHER, THE BUS A IS CONNECTED TO THE BUS B THROUGH NORMALLY OPEN BUS COUPLER BREAKER.
3. FAST BUS TRANSFER (FBT) PANEL SHALL FACILITATE TRANSFER OF SUPPLY TO OTHER BUS SECTION THROUGH BUSCOUPLER, IN CASE OF LOSS OF SUPPLY IN
ONE BUS SECTION. IN CASE OF PROBLEM IN ST-1 OR OUTAGE OF NORMAL INCOMER BREAKER, THE BUSCOUPLER BREAKER SHALL BE CLOSED THROUGH FAS
BUST TRANSFER LOGIC.
E E
4. THE BUS TRANSFER SYSTEM IS BASICALLY A THREE BREAKER BUS TRANSFER SYSTEM OPERATING BETWEEN NORMALLY CLOSED INCOMER BREAKERS AND THE
NORMALLY OPEN BUS COUPLER BREAKER
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BUS TRANSFER DETAILS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 4 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
BTS READY
(REFER NOTE 1)
A A
TRANSFER COMMAND
(REFER NOTE 4)
NOTES:
BLOCK LOGIC DIAGRAM
C 1) BTS READY: CHECKS ALL PERMISSIVE CONDITIONS FOR BTS READINESS C
2) TRANSFER DIRECTION SELECTION: SELECTS THE TRANSFER DIRECTION BASED ON THE CURRENT BREAKER CONFIGURATION.
- MANUAL TRANSFER: TRANSFER DIRECTION IS SELECTED BY OPERATOR USING BTS 2000 HMI INTERFACE. DEPENDING ON THE
CURRENT BREAKER CONFIGURATION, APPROPRIATE TRANSFER DIRECTIONS ARE MADE AVAILABLE TO THE OPERATOR FOR CHOICE.
- PROTECTIVE TRANSFER / AUTO TRANSFER: TRANSFER DIRECTION IS AUTOMATICALLY DETERMINED BY BTS 2000 FROM PRE-FED
SOFTWARE SETTINGS AS PER BREAKER CONFIGURATION, TYPE OF FAULT AND TYPE OF BUS TRANSFER INITIATION (PROTECTIVE /
AUTO).
3) TRANSFER MODE COMBINATION: SELECTS THE COMBINATION OF TRANSFER MODES (FAST / SLOW / MOMENTARY PARALLELING) FOR
BUS TRANSFER.
D -MANUAL TRANSFER: TRANSFER MODE COMBINATION IS SELECTED BY OPERATOR USING BTS 2000 HMI INTERFACE.
D
-PROTECTIVE TRANSFER / AUTO TRANSFER: TRANSFER MODE COMBINATION IS AUTOMATICALLY DETERMINED BY BTS 2000 FROM
PRE-FED SOFTWARE SETTINGS AS PER TYPE OF FAULT AND TYPE OF BUS TRANSFER INITIATION (PROTECTIVE / AUTO).
5) TRANSFER INITIATE: UPON INITIATION, A TRANSFER IS PERMITTED AS PER THE TRANSFER CYCLE TIME WINDOW (5.0 s). IF TRANSFER
DOES NOT TAKE PLACE DURING THIS PERIOD, BTS IS AUTOMATICALLY BLOCKED ON A TRANSFER FAILURE CONDITION.
6) TRANSFER PROCESSING: PROCESSES THE TRANSFER INITIATION REQUEST BASED ON THE CHOICE OF THE TRANSFER MODE
COMBINATION TO GENERATE AND SEQUENCE BREAKER OPERATION COMMANDS.
7) DETECT THE FAILURE OF BREAKER OPERATION (IF ANY) AND TAKE FEASIBLE BACKUP CORRECTIVE ACTION.
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BLOCK LOGIC DIAGRAM ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 5 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
DC SUPPLY ON
BTS SERVICE SELECTION => BTS IN (REFER NOTE 1)
BREAKER CONFIGURATION OK (REFER NOTE 2)
BREAKER TRIP CIRCUITS HEALTHY (REFER NOTE 3) BTS TRIP OLD SOURCE BREAKER
A READY A
BREAKER CLOSE CIRCUITS HEALTHY (REFER NOTE 4) FAST ®
NEW SOURCE HEALTHY (REFER NOTE 5) INPHASE ® CHECK
CLOSE NEW SOURCE BREAKER
SLOW FAST Y
PERMISSIBLE INTERLOCKS OK TRANSFER CLOSING SUPPLY
(NOTE 11) CONTROL (NOTE 15)
BTS BLOCKED (REFER NOTE 6)
TRANSFER FAILURE
FAST ® TRIP NEW SOURCE BREAKER
SLOW N
INTERNAL SELF TEST FAILURE
FLIP-FLOP
AUTO/PROTECTIVE TRANSFER
BREAKER FAILURE SET
CHECK
TRANSFER FAILURE Y
RESET FAST OLD SOURCE
BREAKER
B OPERATOR RESET
TRIP ? B
CHECK
INPHASE Y
TRANSFER
I/C-1 75S: BREAKER IN SERVICE
(NOTE 12)
Y TRIP TRANSFER BUS
I/C-1 86: MAIN LOCKOUT MOTORS
I/C-1 LINE PT 75S: PT IN SERVICE N
CHECK
I/C-1 LINE PT 98: PT FUSE FAILURE SLOW Y TRANSFER OK
TRANSFER
BUS A PT 75S: PT IN SERVICE
(NOTE 13)
BUS A PT 98: PT FUSE FAILURE
CHECK
TIE-1 BREAKER 75S: BREAKER IN SERVICE
SLOW NEW SOURCE Y
N
C N BREAKER C
TIE-1 BREAKER 86: MAIN LOCKOUT CLOSE ?
BUS B PT 75S: PT IN SERVICE CHECK
MOMENTARY
BUS B PT 98: PT FUSE FAILURE
MOMENTARY PARALLELING
Y N
PARALLELING TRANSFER
I/C-2 LINE PT 75S: PT IN SERVICE
(NOTE 14)
I/C-2 LINE PT 98: PT FUSE FAILURE
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BLOCK LOGIC DIAGRAM ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 6 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
220VDC 220VDC
SOURCE I SOURCE II
A A
XCTB-1 XCTB-2 XCTB-3 XCTB-4
+VE -VE +VE -VE
J1 J2 J3 J4 S4 (16A)
A1 B1 A2 B2
SOURCE I
MCB1
OFF
PHASE (6A)
SOURCE II
H1 H3 1
1 2 2 K1
B X-CTB1/1 1 1 1
T B
F1
S1 S2 S3 (4A)
B K3
2 2 2
220VDCPOSITIVE BUS
H5 T T
1 H7 1 H11
DS1 TH1 F3 F5
P DOOR THERMOSTAT (2A) (2A)
SKT1 SWITCH 30-85° C B B
230 VAC, 50 Hz , 1F 2 2 TO 9/B1 K7TO 9/A1 K9
C H9 H13 C
SWITCH-SOCKET BTS 2000 POWER SCHEME
N SUPPLY CIRCUIT K8 CONTROL CIRCUIT
TO 9/D1 TO 9/E1 K10
B B
F4 F6
(2A) (2A)
P P T T
LIGHTING HEATER 220VDC SUPPLY SWITCHING AND PROTECTION CIRCUIT SCHEME BTS 2000 POWER SCHEME
A.C. SUPPLY SWITCHING AND PROTECTION CIRCUIT SWITCH SOCKET (COMMON PER PANEL)
CIRCUIT CIRCUIT MAIN CIRCUIT SUPPLY CIRCUIT CONTROL CIRCUIT
E E
A.C. CIRCUIT: SUPPLY, PROTECTION AND DISTRIBUTION 220VDC CIRCUIT: SUPPLY, PROTECTION AND DISTRIBUTION
NOTES:
1) A.C. CIRCUIT AND D.C. CIRCUIT (D.C. SUPPLY SWITCHING AND PROTECTION) ARE COMMON FOR ALL SCHEMES PER PANEL.
* SWITCHING TO BE INCORPORATED BY CUSTOMER. SELECTOR SWITCH, MCBs, DIODE SCHEME ETC. CAN BE USED.
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
AC / DC CIRCUIT ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 7 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
XA1
A X-1 X-3 X-5 A
14C/1 1 TV1
I/C-1 LN PT R-Y
1 Relay 1.1 1 Relay 2.1 BUS A 1 Relay 3.1 2
SPARE 15C/1 12C/2 TRIP I/C-1
2 Relay 1.1 2 MOTOR TRIP 2 RJ45 PORT 14C/2 3 TV2
3 Relay 1.2 3 Relay 2.2 3 BUS A PT R-Y
SPARE 13B/10 AUTO FAST BUS 4
4 Relay 1.2 4 TRANSFER 4 TX1 14C/3 5 TV3
5 Relay 1.3 5 SUCCESSFUL 5 BUS B PT R-Y
Relay 2.3 Relay 3.2 6
12C/4 CLOSE I/C-1
6 SPARE 6 Relay 2.4 BUS B 6
15C/3
7 Relay 1.3 7 MOTOR TRIP 7 TX2
8 Relay 1.4 8 Relay 2.5 8 XA2
SPARE TEST MODE
9 9B/9 9 Relay 2.5 9 Relay 3.3
SELECTION 12C/6 TRIP TIE-1 14C/4 1 TV4
I/C-2 LN PT R-Y
10 Relay 1.4 10 10 2
B 11 Relay 1.5 11 Relay 2.6 11 B
BTS IN/OUT SPARE 3 TV5
12 SPARE 9B/3 12 Relay 2.6 12 SPARE
SELECTION 4
13 Relay 1.5 13 13 Relay 3.4
12C/8 CLOSE TIE-1 5 TV6
14 Relay 1.5 RELAY 14 Relay 2.7 14 SPARE
6
SPARE
WATCHDOG FAIL/
13D/8 15 13B/6 15 BTS NOT READY 15
INTERNAL
16 Relay 1.5 DIAGNOSTIC 16 Relay 2.8 16
Relay 2.9 CLOSING Relay 3.5
17 17 17 XA3
9B/4 SUPPLY 13C/2 TRIP I/C-2
18 18 CONTROL 18
1 TCVD
TCVD INPUT
2
3
C 4 C
5
6
7
8
X-6 9
X-2 X-4
10
1 Power BTS 2000 1 Relay 2.10 SPARE 13C/4 1 Relay 3.6
9C/2
2 POWER SUPPLY 2 Relay 2.11 SPARE
CLOSE I/C-2 11
Supply
3 Input 1.1 3 Relay 2.12 SPARE 12
I/C-1 TRIP
12C/2
4 Input 1.1 CKT. MONITOR 4 COMMON
5 Input 1.2 I/C-1 CLOSE 11D/1 5 Input 3.1 I/C-1 NO 10D/1 5 Input 3.1
D
12C/4
6 Input 1.2 CKT. MONITOR 11D/2 6 Input 3.2 10D/2 6 Input 3.2
ST-1 FAILURE FO PORT XA4 D
I/C-1 NC ST-2 FAILURE (LC CONNECTOR TYPE)
7 Input 1.3 TIE-1 TRIP 11D/3 7 Input 3.3 9D/9 7 Input 3.3 1
12C/6 TIE-1 NO READY FOR TEST TRANSFER CT INPUT
8 Input 1.3 CKT. MONITOR 11D/4 8 Input 3.4 Input 3.4 2 TA1 5
TIE-1 NC 10D/3 8
9 Input 1.4 9
I/C- 1 BKR READY TX3 3 1
TIE-1 CLOSE 11D/5 Input 3.5 I/C-2 NO 10D/5 9 Input 3.5
12C/8 I/C-1 LINE PT READY 4
10 Input 1.4 CKT. MONITOR 11D/6 10 Input 3.6 10D/6 10 Input 3.6
I/C-2 NC TIE-1 BREAKER READY TA2 5 CT INPUT
11 Input 1.5 11 COMMON 11 5
I/C-2 TRIP COMMON TX4
13C/1
12 Input 1.5 CKT. MONITOR 12 Input 3.7 6 1
11D/7
TIE-2 NO 10D/7 12 Input 3.7
I/C-2 LINE PT READY 7
13 Input 1.6 I/C-2 CLOSE 13 Input 3.8 10D/8 13 Input 3.8
13C/4 SPARE I/C- 2 BKR READY
Input 1.6 CKT. MONITOR Input 3.9 8 TA3 5 CT INPUT
14 14 SPARE 10D/9 14 Input 3.9
15 Input 1.7 15 Input 3.10
BUS A PT READY 9 1
SPARE 10D/10 15 Input 3.10
SPARE BUS B PT READY 10
16 Input 1.7 16 Input 3.11 16 Input 3.11
SPARE SPARE
E 17 Input 1.8 17 Input 3.12 11 TA4 5 CT INPUT
E
SPARE SPARE 17 Input 3.12
18 Input 1.8 18 COMMON
SPARE 12 1
18 COMMON
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BTS-2000 INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 8 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
A A
K9 (+VE) 220VDC SCHEME CONTROL CIRCUIT
FROM 7/C10 TO 10/A1
ITB/1 ITB/1
BTS IN/OUT BTS 2000
SERVICE
SELECTION NO NC NO NC MAIN
TOGGLE SWITCH MODULE
9/C9 12/B2 9/C9 12/B8
TEST X3/9
12/B4 13/B2 MODE
BTS 2000
SELECT
MAIN 12/B6 13/B4 R-2.5a R-2.5b
MODULE
CLOSING 15/B1 15/B3
B BTS 2000 K9A X3/17 B
SUPPLY X3/8 X3/10
MAIN CONTROL
MODULE C4: 2NO+4NC C5: 2NO+4NC
K7
FROM 7/C9 BTS SERVICE R-2.9
X3/12
IN/OUT K15 K15
SELECTION X3/18 K15
BTS 2000 R-2.6 13
MAIN
MODULE TEST MODE C4
X3/13
X2/1 SELECT
14
POWER K17
SUPPLY 13
C TEST MODE C
X2/2 NO NC C5
15/B1 12/A3
SELECT
15/B3 12/A7 14
K19
13/A3
NO BTS 2000
K13 MAIN
K8 12/A2
FROM 7/D9 C2: 2NO+3NC MODULE
12/A4 READY X6/7
K11 FOR TEST
12/A6 TRANSFER
IP-
12/A9 A1 A1 A1 A1 A1
3.3
D NO NC D
13/A8 C1 C2 C3 C4 C5 X6/11
13/B7 12/B4
13/A4
A2 A2 A2 12/B8 A2 A2
13/B8
13/B4
C1: 7NO ITB/3
C3: 2NO+3NC
K10 K10
1) THE 'BTS READY TO TRANSFER' CONTACT OUTPUT CLOSES WHEN THE BUS TRANSFER DIRECTION IS MANUALLY SELECTED, AND ALL SYSTEM CONDITIONS, INCLUDING PERMISSIVE INTERLOCKS, ARE OK.
2) WHEN THE TEST MODE IS NOT SELECTED, A 'BTS READY TO TRANSFER' CONDITION ILLUMINATES WITH LIVE SOFTKEY ON HMI. A MANUAL TRANSFER GETS INITIATED ON PRESSING LIVE SOFTKEY.
3) WHEN THE TEST MODE IS SELECTED, TEST MODE RELAYS C4 AND C5 PICKUP AND A 'BTS READY TO TRANSFER' CONDITION ILLUMINATES WITH TEST SOFTKEY.
THE RELAY INTRODUCE A HIGH IMPEDANCE IN THE BREAKER TRIPPING / CLOSING CIRCUITS THUS ENSURING THAT THEY WILL NOT OPERATE DURING A TEST TRANSFER.
A TEST TRANSFER GETS INITIATED ON PRESSING BY TEST SOFTKEY. A TEST TRANSFER CHECKS ALL SYSTEM CONDITIONS AND CONDUCTS A FICTITIOUS BUS TRANSFER TO PROVIDE THE OPERATOR
A FEEDBACK OF THE ANTICIPATED OPERATIONS OF THE BUS TRANSFER SYSTEM IF A MANUAL BUS TRANSFER IS CONDUCTED FOR THE SELECTED TRANSFER DIRECTION AND TRANSFER MODE COMBINATION UNDER THE CURRENT SYSTEM CONDITIONS.
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
CONTROL INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 9 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
A A
X-TB1/1 X-TB1/3
TB1/45 TB1/45
REV. B TB2/53 TB1/39 TB1/43 TB1/39 TB2/53 TB2/27 TB2/27
ST-1 ST-2
B FAILURE FAILURE B
86: 98: 86: 98: 86: 98: 98:
LOCKOUT FUSE LOCKOUT FUSE LOCKOUT FUSE FUSE
RELAY FAIL RELAY RELAY FAIL RELAY RELAY FAIL RELAY FAIL RELAY
TB1/46 TB1/46
TB2/54 TB1/40 TB1/44 TB1/40 TB2/54 TB2/28 TB2/28
REV. B
X-TB1/2 X-TB1/4
TB2/47 TB1/35 TB1/37 TB1/35 TB2/47 TB1/33 TB1/33
75S: 75S: 75S: 75S: 75S: 75S: 75S:
BKR IN PT IN BKR IN PT IN BKR IN PT IN PT IN
C SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE C
I/C-1 BREAKER READY I/C-1 LINE PT READY TIE-1 BREAKER READY I/C-2 LINE PT READY I/C- 2 BREAKER READY BUS A PT READY BUS B PT READY
ST-1 ST-2
E FAILURE FAILURE PERMISSIVE INTERLOCK OK E
NOTES:
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
SOURCE FAILURE & PERMISSIVE INTERLOCKS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 10 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
A A
K9 (+VE) 220VDC SCHEME CONTROL CIRCUIT TO 13/A1
FROM 11/A10
IP- I/C-1 NC X4/6 TIE-1 NO X4/7 TIE-1 NC X4/8 I/C-2 NO X4/9 I/C-2 NC X4/10 IP-
D CONTACT CONTACT CONTACT CONTACT CONTACT D
2.1 2.7
IP- IP- IP- IP- IP-
X4/11 2.2 2.3 2.4 2.5 2.6 X4/18
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
BREAKER NO /NC CONTACT ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 11 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
K55 K85
K63 K77
21 31
C3
ITB/5 C3 ITB/6 9-D4
9-D4
32
BTS 2000 K55 BTS 2000 22 BTS 2000 K77 BTS 2000
MAIN MAIN MAIN MAIN K87
K65
C MODULE MODULE MODULE MODULE C
I/C-1 CLOSE COIL TIE-1 TRIP COIL TIE-1 TRIP TIE-1 CLOSE
I/C-1 TRIP COIL X2/3 X2/5 X5/5 I/C-1 CLOSE X5/9 TIE-1 CLOSE COIL X2/9 X5/13
MONITORING
X5/1 I/C-1 TRIP MONITORING MONITORING X2/7 MONITORING
IP- IP- IP- R-3.3 IP-
R-3.1 R-3.2 R-3.4
1.1 1.2 1.3 1.4
I/C-1 TRIP CIRCUIT I/C-1 CLOSE CIRCUIT TIE-1 TRIP CIRCUIT WITH TIE-1 CLOSE CIRCUIT
WITH COIL MONITORING WITH COIL MONITORING COIL MONITORING WITH COIL MONITORING
E NOTES: E
1) ALL BREAKER TRIP / CLOSE AS WELL AS MOTOR TRIP CIRCUITS GET DISABLED WHEN BTS IS IN OUT CONDITION BY THE BTS IN/OUT SELECTION RELAY C1,C2.
2) ON PICKUP, THE TEST MODE RELAYS INTRODUCE A HIGH IMPEDANCE IN THE BREAKER TRIPPING / CLOSING CIRCUITS THUS ENSURING THAT THEY WILL NOT OPERATE DURING A TEST TRANSFER.
3) ALL BREAKER CLOSE CIRCUITS GET MOMENTARILY DISCONNECTED BY THE CLOSING SUPPLY CONTROL RELAY C3 AT THE END OF EACH TRANSFER CYCLE. THIS ENABLES THE DROPOUT OF THE ANTI
PUMPING RELAYS WITH LOW DROPOUT CHARACTERISTICS.
4) BTS OUT (NC) CONTACT OF RELAY C2 PROVIDED AS EXTRA FOR FSTSRE USE IN CLOSING CIRCUITS IF REQUIRED.
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TRIP / CLOSE CIRCUITS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 12 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
(+VE) 220VDC (+VE) 220VDC
FROM SWGR. FROM SWGR.
REV. B TB1/15
TB1/53 X-TB1/45
TB1/57
A A
X-TB1/39 K113 X-TB1/42
61
K95 C2 K103
63 BTS 2000 BTS 2000
53 9/D3 X-TB1/67 X-TB1/69 X-TB1/71 X-TB1/73
MAIN MAIN
BTS IN C1 C1 BTS IN MODULE K117 K121 K125 MODULE K129
62
SELECTION 9/D3
K115
9/D3 SELECTION BTS MAIN X3/14 73 AUTO X-3/3
MODULE 13
FAST BUS
64 NOT TRANSFER
54 X-TB1/46 C3 C1 TRANSFER
K97 K105 READY R 2.7 CYCLE BTS IN 9/D3 SUCCESSFUL R 2.2
9-D4
OVER
31 PCB1/17 TB1/16 61 PCB1/21 X3/15 14 74 X-3/4
32 PCB1/19 62 PCB1/23
K107
K99
TRANSFER CYCLE AUTO FAST BUS
61 BTS NOT READY BTS IN
OVER TRANSFER
ITB/7 C3
9-D4 SUCCESSFUL
K99 62
BTS 2000 BTS 2000
MAIN MAIN K109
C MODULE MODULE C
I/C-2 TRIP COIL X5/17 I/C-2 TRIP I/C-2 CLOSE COIL X6/1 I/C-2 CLOSE
X2/11 X2/13
MONITORING MONITORING
IP- IP-
R-3.5 R-3.6 X-TB1/75 X-TB1/77 X-TB1/79
1.5 1.6
K133 K137 K141
X2/12 X5/18 X2/14 X6/2
43 43 RELAY X1/15
WATCHDOG
BUS A BUS B FAIL/
C6 C7
K111 MOTOR 15/D1 MOTOR INTERNAL R 1.5
K101 15/D3
TRIP TRIP DIAGNOSTIC
44
44 X1/16
X-TB1/40 X-TB1/43
K135 K139 K143
D TB1/49 TB1/16 X-TB1/76 X-TB1/78 X-TB1/80 D
REV. B
TC CC
RELAY
BUS A BUS B
WATCHDOG FAIL/
MOTOR TRIP MOTOR TRIP
INTERNAL DIAGNOSTIC
I/C-2 TRIP CIRCUIT WITH COIL I/C-2 CLOSE CIRCUIT WITH COIL
MONITORING MONITORING ALARM / ANNUNCIATION/D.C.S
E NOTES: E
1) ALL BREAKER TRIP / CLOSE AS WELL AS MOTOR TRIP CIRCUITS GET DISABLED WHEN BTS IS IN OUT CONDITION BY THE BTS IN/OUT SELECTION RELAY C1,C2.
2) ON PICKUP, THE TEST MODE RELAYS INTRODUCE A HIGH IMPEDANCE IN THE BREAKER TRIPPING / CLOSING CIRCUITS THUS ENSURING THAT THEY WILL NOT OPERATE DURING A TEST TRANSFER.
3) ALL BREAKER CLOSE CIRCUITS GET MOMENTARILY DISCONNECTED BY THE CLOSING SUPPLY CONTROL RELAY C3 AT THE END OF EACH TRANSFER CYCLE. THIS ENABLES THE DROPOUT OF THE ANTI
PUMPING RELAYS WITH LOW DROPOUT CHARACTERISTICS.
4) BTS OUT (NC) CONTACT OF RELAY C2 PROVIDED AS EXTRA FOR FSTSRE USE IN CLOSING CIRCUITS IF REQUIRED.
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TRIP / CLOSE CIRCUITS/ALARM / ANNUNC. ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC B
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 13 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
A A
TB1/16 TB2/25 TB2/25 TB1/16 ??? ???
B B
BTS 2000 H15 BTS 2000 H19 BTS 2000 H23 BTS 2000 H27 BTS 2000 H31 BTS 2000 H35
MAIN MAIN MAIN MAIN MAIN MAIN
MODULE MODULE MODULE MODULE MODULE MODULE
I/C-1 XA-1/1 BUS A XA-1/3 BUS B XA-1/5 I/C-2 XA-2/1 SPARE PT XA-2/3 SPARE PT XA-2/5
LINE PT PT PT LINE PT
D D
TB1/19 TB2/26 TB2/26 TB1/19 ??? ???
E E
NOTES:
1) BTS 2000 PT INPUTS PROVIDE INBUILT GALVANIC ISOLATION AND NO SEPARATE ISOLATION PTs ARE REQUIRED.
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
PT INPUT ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 14OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
14 44 14 24 34 14 24 34
B B
K159 K163 K167 K171 K175 K179
X-MTB1/2 X-MTB1/4 X-MTB1/6 X-MTB1/8 X-MTB1/10 X-MTB1/12
K145 K151
71 PCB1/25 71 PCB1/29
TEST MODE C4 RES7 TEST MODE C5 RES8
RELAY 9/D9 (5Kk /9W) RELAY 9/D9 (5Kk /9W)
BUS A BUS A BUS A BUS B BUS B BUS B
72 PCB1/27 72 PCB1/31 MOTOR #1 TRIP MOTOR #2 TRIP MOTOR #3 TRIP MOTOR #1 TRIP MOTOR #2 TRIP MOTOR #3 TRIP
K147 K153
BTS 2000 BTS 2000
C MAIN MAIN C
MODULE MODULE
BUS A X-3/1 BUS B X-3/6
MOTOR TRIP MOTOR TRIP
MOTOR FEEDER DETAILS
R-2.1 R-2.4 SCHEME BUS MOTOR NO. MOTOR FD SWGR TB
NO NO #1 CW#C TB1/46-49
OBA
X-3/2 15/B5 X-3/7 15/B8 STS-1 #2 MDBFP TB1/46-49
OBA<=>OBC #1 CW#C TB1/46-49
15/B6 15/B9 OBC
#2 MDBFP TB1/46-49
K149 15/B7 K155 15/B10
D 13/D6 13/D7 STS-2 OBB #1 CW#D TB1/46-49 D
A1 A1
OBB<=>OBD OBD #1 CW#D TB1/46-49
C6: 4 NO C7: 4 NO
C6 C7
A2 A2
REV. A
K10 K10
FROM 11/E10 (-VE) 220VDC SCHEME CONTROL CIRCUIT END
E E
BUS A MOTOR TRIP BUS B MOTOR TRIP
BUS A MOTOR TRIP CONTACTS BUS B MOTOR TRIP CONTACTS
RELAY RELAY
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
MOTOR TRIP CONTACTS ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC A
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 15 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
A A
24
BREAKER READY
23
I/C-2
52b 22 BREAKER BTS OUT I/L 46
NC CONTACT
21 45
52a 20 SPARE 44
NO CONTACT 43
B 19 B
CLOSE COMMAND
I/C-1
18 42
BREAKER BTS OUT I/L
17 SPARE 41
SPARE 16 40
TRIP COMMAND
15 39
CLOSE COMMAND
14 38
BREAKER READY
SPARE 13 37
12 52b 36
TRIP COMMAND
C 11
NC CONTACT 35 C
10 52a 34
SPARE BREAKER READY
10 9 TIE-1
NO CONTACT 33
SPARE
9 8
BREAKER 32
52b BTS OUT I/L
8
NC CONTACT 7 31
SPARE
7 52a 6 SPARE 30
NO CONTACT 5 29
SOURCE 2 -VE 6 CLOSE COMMAND
220VDC
SOURCE 2 +VE 5 PROTECTIVE 4 28
SUPPLY
D SOURCE 1 -VE 4
TRANSFER ST-2 FAILURE
3 SPARE 27 D
INPUTS
2 26
SOURCE 1 +VE 3 TRIP COMMAND
ST-1 FAILURE 1 25
230VAC, N 2
50 Hz,
1 PH AC
P 1
SUPPLY X-TB1 X-TB1
X-CTB
E E
NOTES:
1. ALL TB'S OF THE PANEL WILL BE SUITABLE FOR RING TYPE LUG.
STUD TYPE TERMINAL BLOCK CSTSB4
* REFER GENERAL APPLICABILITY TABLE ON SHEET NO. 04 OF 17 FOR SCHEME SPECIFIC
DISCONNECTING TYPE TERMINAL BLOCK CDTTS NOMENCLATURE
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TERMINAL BLOCK INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 16 OF 17
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10
73 8
I/C-2 LINE
52 MOTOR #1 TRIP
BTS IN 72 7
PT READY 51 SELECTION
71
BUS A 6
OBA BUS PT
50 MOTOR TRIP MOTOR #3 TRIP
TRANSFER 70 5
READY 49
CYCLE OVER
69 4
D 48 MOTOR #2 TRIP D
I/C-1 LINE
68 3
PT READY 47 BTS NOT READY
67 2
MOTOR #1 TRIP
1
XTB1 XTB1 X-MTB1
E E
STUD TYPE TERMINAL BLOCK CSTSB4
GEN. TOL. : PROJECT : 2X500 MW TPS AT DVC, ANDAL DESCRIPTION: INITIALS NAME AARTECH SOLONICS LTD.
F MAT. : CUSTOMER : DAMODAR VALLEY CORPORATION
TERMINAL BLOCK INTERFACE ALL DIMNS.
DRN. VRS VINAY
35-A/36 Sector-B, Industrial Area, F
GEMC No. : 511687725937901 ARE IN MM. Mandideep, Dist. Raisen (M.P.)
SPEC. : CHD. ROK RAJEND
GEMC Gen Dt. : 02/12/2022 TITLE : UNLESS INDIA-462046
SCALE : NTS BUS TRANSFER SYSTEM (BTS) PANEL OTHERWISE REV.
CLIENT : DSTPS DVC ANDAL APPD. NMT NITISHA DRG.NO.: BT 22-23 09 SC 0
SPECIFIED.
THIRD ANGLE PROJECTION REF.DRG.NO. : BLOCK LOGIC DIAGRAM & SCHEMATIC DRAWING DATE: 16/12/2022 ASL. W.O.: 07 SH.: 17 OF 17
01 02 03 04 05 06 07 08 09 10