thers ty meane of
3.3.3 Ducts
In group 2 medical locations the ducts installed
inside the room must be purposed excl
the power supply of the electrical devices and
their accessories present in the same room; in
practice, ducts that supply power to equipment
located in other rooms cannot pass through these
group 2 medical locations.
y for
The clrcults branching from a medical IT system
‘must necessarily be separated trom the electrical
circuits powered by other systems, and must,
therefore, be installed in separate pipingor ducts
and boxes. The use of shared ducts and koxes is
also allowed provided that the separation is im-
plemented with an insulating separator (fig. 3.13).
The circuits of the Medical iT system can also be
implemented using unipolar cables (cords) of the
type NO7V-K (with the warning not to use navy,
blue or ight blue conductors, since amedical IT
system never has Neutral).
If it is impossible to implement a physical separa-
ton of two electrical systems, and the Medical IT
circuit runs through a duct "shared" with the con-
ductors of another system, double insulation ca~
bles with a non-metallic sheath must be used.
Inaddition, if the leakage current is due toa ca-
pacitive effect, it is recommended that the pro-
tection conductor be separated from the phase
conductors and then inserted in its own protec
tive tube,
In group 2 medical locations where electromedi-
‘cal devices are used in order to monitor and sup-
port vital parameters, such as those of intensive
‘care, resuscitation and similar, the devices should
bbe powered using conductors that are shielded or
inserted in metallic piping asa precaution against
‘lectrical fields, Both the shieldings of the cables.
{as well as the metal piping must be equipoten-
tialised on the nearest node or sub-node.
For radiology and CAT rooms and rooms with
‘equipment that emits ionising radiation, the
power supply conductors shauld nat intarrupt tha
radiation shieldings present.
‘The protection of the ducts against overcurrents
must be implemented using omnipolar automatic,
miniature circuit breakers, Also in Medical T sys-
tems, the circuits branched to the secondary
must be protected with fuses or thermomagnetic
automatic miniature circuit breakers, but not with
RCDs because the RCD would not be effective in
this particular “medical insulation” system.