7COLEGIO SACO OLIVEROS IIEE LEVAN OBSERV-Model
7COLEGIO SACO OLIVEROS IIEE LEVAN OBSERV-Model
EMPOTRADO 3F,220V,60Hz
2x25A
2x20A Sens=30mA
C-4 CL=AC
2-1x4mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P TOMACORRIENTE OFICINA,RECEPCION
2x25A
2x20A Sens=30mA
C-5 CL=AC
2-1x4mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P ALUMBRADO OFICINA,RECEPCION
2x25A
2x16A Sens=30mA
C-6 CL=AC
2-1x2.5mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P PANEL DE ALARMA CONTRA INCENDIO
C-7
C-8
C-9
Cu 2x20mm-Puesta a tierra
Cu 2x20mm-Puesta a tierra
LEYENDA
ALTURA (m.) CAJA (mm.)
Cu 2x20mm-Puesta a tierra
GRAFICO DEFINICION SNPT. eje RECEPTORA
Cu 2x20mm-Puesta a tierra
EMPOTRADO 3F,220V,60Hz
2Sa,b
3x25A
3-1x4mm² THW+1x4mm² /TW 3x32A C-1 3-1x4mm² NH80 +1x4mm² /T NH-80- 20mmØ PVC-P a tablero TD-4.1;4.2
25mm Ø PVC-P
2x25A
2x20A Sens=30mA
C-2 CL=AC
2-1x4mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P ALUMBRADO AULAS
2x25A n
2x20A Sens=30mA
C-3 CL=AC
2-1x4mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P TOMACORRIENTES
2x25A
2x25A Sens=30mA
C-4 CL=AC
2-1x4mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P TOMACORRIENTES VENTILADOR AULA
Cu 2x20mm-Puesta a tierra
C-3
Cu 2x20mm-Puesta a tierra
C-3
Cu 2x20mm-Puesta a tierra
2x25A
2x20A Sens=30mA
2-1x4mm² THW+1x4mm² /TW 2x32A C-1 CL=AC
2-1x2.5mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P ALUMBRADO
25mm Ø PVC-P
2x25A
2x40A
Sens=30mA 2-1x4mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P
0. 0
ESC=1/25
C-2 CL=AC TOMACORRIENTES REFRIGERADORA
2x25A
2x16A Sens=30mA
C-3 CL=AC
2-1x2.5mm² NH80 +1x2.5mm² /T NH-80- 20mmØ PVC-P TOMACORRIENTES COCINA
conductor de Conector de bronce
cobre electrolitico
viene de tablero Ø 16mm (Ver detalle)
Varilla de cobre
electrolitico de
2.40m x Ø 16mm
RESIST.< 25 OHM.
DETALLE DEL POZO A TIERRA
ESC. 1/25
PROPIETARIO :
PROFESIONAL:
INSTALACIONES ELECTRICAS
DIAGRAMA UNIFILAR,CUADRO DE CARGAS, LEYENDA