YHW-3003RY×3 Technical parameters

Hot water Temperature (T1): t1 = 37℃


Cold water Temperature (T2) : t2 = 32℃
Wet Bulb Temperature (WB): τ= 29.5℃
Atmospheric pressure : P = 9.94×104Pa
Tower Water Flow: Q =924m3/h
Products : Cross-flow Cooling Tower
Dimensions : L9650mm×W5550mm×H6100mm
Motor Power : 15kW×3
Power supply : 400V / 3Φ / 50Hz
Fan diameter : Φ3000 mm×3
Air Flow : 229320m3/h×3
Drive : Belt transfer, anti-water
Dry Weight : 3600kg×3
Operating Weight : 10820kg×3
Inlet Pipe: 6-DN200mm(PN1.0MPa)
Outlet Pipe: 3-DN300mm(PN1.0MPa)
Overflow Pipe: 3-DN80mm
Water make-up Pipe : 3-DN40mm
Quick water make-up Pipe: 3-DN40mm
Drain Pipe : 3-DN80mm
Cooling Tower distribution
Pooling water distribution system, with patent nozzle
system :
Film: PVC film sheet
Drift loss: ≤0.001%
Evaporation loss: 0.83%
Pump Head: 6mH2O
Anti-corrosion: HDGS structural components, SS304 fasteners
Color: RAL7047

Compilation: Proofreading: