YHW-3401RZ×4 Technical parameters

Hot water Temperature (T1): t1 = 37℃


Cold water Temperature (T2) : t2 = 32℃
Wet Bulb Temperature (WB): τ= 29.5℃
Atmospheric pressure : P = 9.94×104Pa
Tower Water Flow: Q =1328m3/h
Products : Cross-flow Cooling Tower
Dimensions : L14450mm×W6550mm×H5310mm
Motor Power : 15kW×4
Power supply : 400V / 3Φ / 50Hz
Fan diameter : Φ3400 mm×4
Air Flow : 233280m3/h×4
Drive : Belt transfer, anti-water
Dry Weight : 4220kg×4
Operating Weight : 13070kg×4
Inlet Pipe: 8-DN200mm(PN1.0MPa)
Outlet Pipe: 4-DN300mm(PN1.0MPa)
Overflow Pipe: 4-DN80mm
Water make-up Pipe : 4-DN40mm
Quick water make-up Pipe: 4-DN40mm
Drain Pipe : 4-DN80mm
Cooling Tower distribution
Pooling water distribution system, with patent nozzle
system :
Film: PVC film sheet
Drift loss: ≤0.001%
Evaporation loss: 0.83%
Pump Head: 5.2mH2O
Anti-corrosion: HDGS structural components, SS304 fasteners
Color: RAL7047

Compilation: Proofreading: