Vertical mixed flow pumps BQDV, BQTV, BQCV

Application Material options


Vertical pumps BQDV, BQTV, BQCV are intended for pumping Pump main parts are of following constructional materials:
clean service water or slightly polluted surface and river water. Discharge elbow − manganese steel
Max. temperature of a pumped liquid...............................50 °C Impeller vanes − chrome−nickel steel
Values pH ranging ..........................................from 6.5 to 9 pH Impeller hub − chrome steel
Those pumps have been proved competent in fields of nuclear Shaft − high−grade carbon steel
and conventional power industries, water supply branch, water Shaft sleeves − chrome steel
management, industry, agriculture, and so on. Bearings − special rubber

Construction
Pumps are of centrifugal vertical type, with mixed flow impeller.
At the wet end there the shaft is supported on plain bearings
being lubricated with a pumped liquid or with clean water from
an external supply provided there polluted water shall be pump−
ed. Above the branch elbow there the shaft is carried in radial
thrust bearing, that is of rolling−contact type with smaller sizes,
with greater sizes it is of plain pivoted−pad type. Bearing is oil
lubricated and cooled with water being supplied from the pump
discharge side, or from an external supply.
Seal mounted in the discharge elbow is of soft cord−type.
Pumps BQDV are designed for continuous control of the pump
delivery head and capacity through the impeller vanes adjustable
in operation.
Regulating mechanism in the impeller is controlled by a servo−
motor being installed in the pump modified coupling. Regula−
ting device is equipped with limit switches and quick−break
ones and a transmitter of the impeller vanes positions.
Pumps BQTV without possibility of capacity continuous con−
trol within operation. However, there is a regulating mechanism
in the impeller available, so vanes adjusting may be realized too
but only within the pump stillstand after a suction pit previous
drainage.
Pumps BQCV are of pull−out design, that is with possibility of
the pump working parts removal without delivery piping un−
coupling, whereby there a high level of readiness for revision or
repair works on the pump−set may be reached there.
Pumps BQCV are intended principally for nuclear power plants
where seismic resistance is required.
Vertical mixed flow pumps BQDV, BQTV, BQCV

Informatory section through pump 1600−BQDV in workmaship for dry sump

848

840 524.2

300
452

451

461

211
144

711

574
724

524.1
175

382

112
310

230
103

140 141

139

Numbering of positions according to DIN 24 250


103 Spherical insert 230 Impeller 524.2 Stuffing box bush
112 Diffuser 300 Thrust bearing 574 Control rod
139 Suction elbow 310 Plain bearing 711 Discharge pipe
140 Intlet bellmouth 382 Diffuser bearing housing 724 Pipe seal
141 Suction casing 451 Stuffing box housing 840 Pump coupling
144 Discharge branch 452 Gland 848 Coupling spacer
175 Conical adapter 461 Gland packing
211 Shaft 524.1 Shaft sleeve
Vertical mixed flow pumps BQDV, BQTV, BQCV

Informatory selection chart

H [m]
40
ZÁKLADNÍ ŘADA
ZVÝŠENÉ OTÁČKY
SNÍŽENÉ OTÁČKY

30

● ● 1400−36 ● 2400−36
1000−36 1200−36 n 420 1600−36 n 245
800−36 n 590 ● n 370 ● ●
n 740 n 485 ●
1800−36
n 325 2400−36
n 215
20
1400−36 ●

n 365 1800−36 ●
800−36 1200−36

n 590 ● n 420 ● n 290

1000−36 ●
1600−36
15 n 485 n 290
1000−36 ●
n 420 ●
● ● 2400−36
1200−36 n 185
n 365
● ●
1400−36 1800−36
n 290 n 245
10 800−36
n 485
9

5
0,8 0,9 1 1,2 1,4 1,6 1,8 2 3 4 5 6 7 8 9 10 12 14 16 18 20 30
Q [l.s−1]

This chart outlines the entire performance zone of pumps BQDV, BQTV, BQCV.
Big figures in the chart single fields express the discharge branch inner diameter and the pump size together with specific speed.

Pump model key example: 800−36


n 590
800 ........ DN of discharge branch
36 ........... Specific speed ns/10
n 590 ..... Pump speed min −1
Vertical mixed flow pumps BQDV, BQTV, BQCV

Example of the 1400−BQDV pump Size with different angles


of impeller vanes adjustment

H [m] n = 365 min−1

MAX

20
η 88,1
opt
η 88,3

η 87,8

η 86,8
η 85,8
15 hkr 5,2
MIN
5,6 η 84,8
η 83,8

,3
η 82,8 +12°

11
6,6

,3
7,5 η 81,8

10
3
9,
8,4
+3° +9°
+6°

10
−3° 0°

3 4 5 6 7 8 9 10
Q [l.s−1]
Vertical mixed flow pumps BQDV, BQTV, BQCV

Workmanship for wet sump

MOTOR

F 1

E
2

DN
3

C
MIN.
B

G
H1

D ~ 1,4 DN
H

Dimensions
Pump
model A B C ∅D N E F ∅G H H1

BQDV
800− BQTV 700 720 880 1120 800 2240 880 1220 600
shall be specified
individually

BQDV
1000− BQTV 875 900 1100 1400 1000 2800 1100 1520 750
BQDV
1200− 1050 1080 1320 1680 1200 3360 1320 1820 900
BQTV
1400− BQDV 1220 1200 1400 1960 1400 3500 1500 2100 1050
BQTV

Dimensions given above are informatory ones. More accurate and detailed information may be reached with individual particular offers or order jobs after
former technical clearing of business.
Discharge branch flange connecting dimensions DN are intended for PN 6.
1 ...... water supply from pump discharge size for bearing cooling;
2 ...... water drain from bearing cooling − connection consists of pipe union DN 3/4“;
3 ...... water drain from seal − connection consists of pipe union DN 1“
Vertical mixed flow pumps BQDV, BQTV, BQCV

Workmanship for dry sump

MOTOR

F
1

E
2

DN
3

C
MIN.

B
G
H1

S A
∅R

Dimensions
Pump
model A B C DN E F ∅G H1 P R ∅S V

BQDV
1400− BQTV 865 1200 1400 1400 3500 1500 2100 3390 2030x2510 1220 1980
shall be specified
individually

BQDV
1600− BQTV 975 1475 1500 1600 3750 1700 2300 3870 2320x2870 1400 2260
BQDV
1800− 1085 1535 1700 1800 4200 1900 2500 4350 2610x3230 1560 2540
BQTV
2400− BQDV 1460 2200 2250 2400 5620 2550 3450 5800 3480x4300 2040 3390
BQTV

Dimensions given above are informatory ones. More accurate and detailed information may be reached with individual particular offers or order jobs after
former technical clearing of business.
Discharge branch flange connecting dimensions DN are intended for PN 6.
1 ...... water supply from pump discharge size for bearing cooling;
2 ...... water drain from bearing cooling − connection consists of pipe union DN 3/4“;
3 ...... water drain from seal − connection consists of pipe union DN 1 1/2“
Vertical mixed flow pumps BQDV, BQTV, BQCV

Workmanship for dry sump

MOTOR

N
3
F1

M
DN
U

MIN.

K
H1

S
∅R

Dimensions
Pump
model DN F F1 H1 K M N P R ∅S ∅U V

BQDV
shall be specified

1600− BQTV 1600 2700 670 3200 1500 1850 3200 1900x2350 1150 1900 1750
individually

BQDV
1800− BQTV 1800 2550 750 3600 1650 2100 3560 2140x2650 1300 2140 1960
BQDV
2400− 2400 3400 1000 4800 2200 2800 4760 2850x3530 1720 2850 2600
BQTV

Dimensions given above are informatory ones. More accurate and detailed information may be reached with individual particular offers or order jobs after
former technical clearing of business.
Discharge branch flange connecting dimensions DN are intended for PN 6.
3 ...... water drain from seal − connection consists of pipe union DN 1 1/2“