You are on page 1of 6

A real-life application of an efficient energy

management method for a local energy system in


presence of energy storage systems

D. Menniti, A. Pinnarelli. N . Sorrentino, P. Vizza, A. Burgio, G. Brusco, M. Motta


Dept. of Mechanical, Energy and Management Engineering,
University of Calabria
Rende, Italy

Abstract— In the last years, the use of energy storage systems, transmission lines, to reduce the power imbalances between
to allow greater renewable sources integration especially for local expected and measured power profiles and the corresponding
energy systems, is significantly increasing. Opportune energy imbalance charges.
management methods have to be implemented for an efficient use
of those energy storage systems. In this paper, an efficient energy In the last years, the role of energy storage systems (ESSs) is
management method, proposed by the authors in a previous significantly increased. The ESSs, as well known, are useful to
paper, is briefly discussed and a real-life application, realized in enable greater renewable sources integration considering their
the Campus of University of Calabria, is presented. The proposed intermittent nature. Their role is to compensate the power flows
energy management method is used in order to reduce power for the time lag existing between RES plants production and load
peaks on the grid, to reduce the energy exchanged with the grid consumption. The ESSs can provide several services, in the
and the power imbalances. actual and next future scenario of National Electricity Systems,
including load leveling, load following, firm capacity, operating
Keywords— Energy management, nanoGrid, photovoltaic, reserves (regulation, contingency spinning reserve), black-start
storage system. and end-use applications (backup power, UPS, power quality).
I. INTRODUCTION The ESSs are suitable solution to increase the reliability of
National Electricity System.
In the last years, with the increase of energy produced by
renewable energy sources (RESs) and the corresponding issues To reach the aforementioned functionalities, an ESS has to
concerning the electric grid (hereinafter referred to as grid), be opportunely managed. To face the problems linked to the
there was the necessity of new solutions to optimize the use of uncertainties of RESs, load and market price, in literature,
the energy produced from RESs. It needs to solve the related several ESS energy management methods with different aims
technical problems on the grid and, at the same time, to have been presented [4-6].
maximize economic revenues for both producers and the so- In [7], the authors propose an energy management method to
called prosumer (producer and consumer at same time) and to make more efficient the use of ESSs both to minimize the energy
minimize the costs for the consumers. exchanged and the power peaks on the grid. Two different
For this purpose, in literature, several energy management approaches can be used: a real-time and a predictive approach.
methods have been proposed: they are utilized to minimize the The use of the last approach implies the implementation of
exchange of energy with the grid, to reduce the power peaks on opportune PV production and load demand forecast models.
the grid or to reduce power imbalances. Using the forecast models, illustrated by the authors in [7], the
ESS is opportunely managed. A feature of the implemented
Referring to the economic aspects, power flows from several method is its multi-periodicity. Indeed, it can manage the power
RESs could be managed within a micro-grid [1] or among users flows for more than one day, obtaining better results compared
belonging to a same local energy system [2-4]. Generally, when to the case in which the data of a one day is used. In [8] the
local energy systems are considered, the energy management authors utilize the predictive approach through a cloud-based
method aims to minimize the energy exchange with the grid, in architecture in a real-life application showing the results.
order to maximize the economic revenues for the sale of energy
produced by renewable plants inside the local energy system and The real-time approach presumes that the power produced
to minimize the costs for the purchased energy from outside. by RESs and absorbed by loads is measured instantly, in this
way power flows are managed only considering the real-time
In addition, through more efficient energy management state of the system, as consequence the possible subsequent
methods, it is possible to reduce the power peaks on the grid, system conditions are not considered. The numerical results
with the aim to reduce congestion on distribution and show that using the predictive approach the energy exchanged
This work was financed by the Italian Ministry of Economic
Development (MISE) and the Ministry of Education, University and Research
(MIUR), through the National Operational Program for Business and
Competitiveness 2014-2020, PON F/050159/01-03/X32.

978-1-5386-5186-5/18/$31.00 ©2018 IEEE

Authorized licensed use limited to: Pontificia Universidad Javeriana. Downloaded on February 13,2023 at 02:56:22 UTC from IEEE Xplore. Restrictions apply.
with the grid can be reduced of about 2% while the power peaks Between the objectives that the OF can assume, there are the
up to 70%; the use of real-time approach instead is strongly minimization of exchanged energy with the grid, minimization
dependent on the current state of the system, Storage State of of peak power or of the exchanged energy with the grid in a
Charge, loads power, RES power. Although both methods and defined time interval, or other functionalities.
concerning numerical results are reported, in the current paper
the experimental results related to the use of the real-time Some of the constraints to which the method is subject are as
approach are reported; the results concerning the predictive follows:
approach are reported in [8]. = + ∗ (3)
Differently to other energy management methods proposed (4)
in literature, the proposed one allows the management of ESS in ≤ ≤
a very economical way, implementing the optimization software ≤ ≤ (5)
in an embedded device, with the possibility to configure
different functionalities; such software also uses forecast models = (6)
that are implemented using free weather data.
The equation (2) is utilized to calculate the power exchanged
In this paper, starting from the simulation results obtained
using the PV production and the load demand data of a build in with the grid ; the constrains (3) to (6) concern the operation
the University of Calabria, experimental tests are carried out of storage. In (3) the variation of the stored energy (between two
utilizing the real-time approach in a real-life application, time intervals) is calculated, in (4) the stored energy is limited
realized in the Campus of the same University. between a minimum and maximum value (depending on the
storage capacity); in (5) the storage charge and discharge power
II. EFFICIENT ENERGY MANAGEMENT METHODS DESCRIPTION are limited; in (6) the initial state of charge is defined.
Considering a local energy system, two approaches can be Once the load demand and PV production profile forecasts
used to implement an efficient energy management method: a for each single user are obtained, the difference between the two
real-time and a predictive approach. According to the profiles is calculated. This difference represents the input of the
applications, both approaches have been presented, but only the method, which solves the OF, taking into account the constraints
real-time approach is utilized and tested. concerning the ESS and the load demand. The method returns
A. Predictive approach the storage power exchange profile and as consequence the
power profile exchanged with the grid.
The implemented predictive approach [7] is used to manage
the power flows between different sources, loads and ESSs; it B. Real time approach
can be utilized for more than one day; every day is divided in The real-time approach considers the measured power
more time intervals (t); such time intervals are the same of that produced by RESs and the power absorbed by loads; starting
utilized in the forecasting model; in the specific case it is the from these two measures, the ESS is managed to inject or absorb
hour. a specific amount of energy, according to a prefixed goal and
The variables utilized in the model are described below for considering the system constrains. In particular, the same
the time interval t and the day d: is the load power; is equations, utilized in the predictive approach, can be utilized in
the real time approach, only considering real time interval.
the power produced by PV system; is the power exchanged
with storage system; is the energy stored in the battery To compare the two approaches many tests have been carried
out, considering the test facility of University of Calabria. It is
system. Moreover, and are the minimum and
observed that, although both approaches can be utilized for
maximum storage capacity, and are the minimum different goals, an approach is more powerful than the other one
and maximum power of the storage system and is the for a specific goal. In particular, for the minimization of power
initial battery state of charge. imbalances the real-time approach is preferable, vice-versa for
the energy exchange minimization with the grid, the predictive
The Objective Function (OF) of the method is defined in (1)
approach is preferred, while for power peak minimization, both
and it can have different goals for the energy exchange
approaches could be utilized. In the following, two cases are
optimization:
illustrated: the method considering as goals the minimization of
grid power peak and minimization of power imbalances.

: min ( ) (1) C. Minimization of grid power peak


In this case it is assumed the prosumer have a limited
maximum power equal to _ . This may be due to several
reasons, for example, the prosumer has a contract with the
distribution system operator for reduced power, or the
with: distribution network is sized for a limited power. In fact, such
= − − (2) type of management allows to reduce the problems concerning
the congestion, or limitations on interface devices; indeed the
loads power or the generation power can be greater than the

Authorized licensed use limited to: Pontificia Universidad Javeriana. Downloaded on February 13,2023 at 02:56:22 UTC from IEEE Xplore. Restrictions apply.
contract power or than the electrical capacity of the line, so the where  follows  . As stated in (2), the authors assume that
storage system and an opportune management method are the power delivered/absorbed by the storage during the time
necessary. It is worth to underline that such constrain influences interval  is a constant value.
both power injection and absorption; the energy management On the other hand, the choice of Δt1 and Δt2 evidently is a
method (both predictive and real time approaches) is completed crucial point; indeed, the lengths of  and  strongly
with the following equation: influence the storage operation and the goodness of the
| |≤ _ (7) imbalance compensation as well.
According to the explanations reported above, the proposed
The OF (1), anyway, is implemented to minimize the entire real time approach sets the time periods equal each other,  =
energy exchange with the grid.  =  , and it sets the power of the storage as:
In [7] some numerical results show that the power peaks can 0, =0
be reduced up to 70%. ()=
( − 1) − ( − 1) + ( − 1), >0
D. Power imbalances minimization
Let us consider a prosumer with a PV plant and a storage where i is an index over time periods.
system. In this case, the storage system operates with the goal
to reduce the power imbalances at the point of delivery (POD). III. REAL-LIFE APPLICATION UNICAL CAMPUS
In this case a real-time approach has to be utilized. So, let To demonstrate the effectiveness of the proposed energy
us consider a reference value for the power at the POD, namely management method, the real time approach is tested in a real
Pr(t) and the corresponding measured power, namely Pm(t); the life application (in the following referred as test facility),
imbalance in the time interval  is then: realized in a build of University of Calabria (Unical) Campus,
 while the predictive approach has already been tested in [8].
( ) = ( )− ( ) (8)
Since the storage operates in order to eliminate or mitigate this The test facility, as illustrated in Fig. 1, consists of three DC
imbalance, the power delivered/absorbed by it, namely Pb(t), nanogrid for Home Application (nGfHA), opportunely
fulfils the following equation: interconnected; two photovoltaic plants (PV and PVNG) with
 rated power of 4.5 kW for each one; a storage system (BES) with
( ) = ( ) = ∗  (9) a capacity of 22 kWh and a Stirling engine µ-CHP plant (SE)
with an electric rated power of 1 kWe and a thermal rated power
of 14 kWt.

Fig. 1 Test facility in Campus of University of Calabria

An nGfHA is a small power DC nanogrid for household where different generation sources can be interconnected, both
application. It is realized through a DC voltage bus (DC-bus) dispatchable and not-dispatchable sources, an inverter for non-

Authorized licensed use limited to: Pontificia Universidad Javeriana. Downloaded on February 13,2023 at 02:56:22 UTC from IEEE Xplore. Restrictions apply.
interruptible loads and storage system. Such system is connected carried out; however, this forecast is not equal to the real-time
to the grid using a bidirectional inverter (indicated in the PV production and for this reason, it is necessary to compensate
following as PEI), which is able to absorb or deliver power this difference by using the BES of Nanogrid-1. The real time
according to the needs. Moreover, it can provide ancillary approach is utilized, so the power is measured every second
services to the grid. Each nGfHA is controlled by a DC bus instantly and it is compensated.
signaling control logic (DBS) to guarantee safe operation both
in grid-connected that in islanded mode as proposed by the The power imbalance compensation is performed using the
authors [9]. Thanks to the DBS logic, depending on the voltage proposed energy management method operating in real-time
measured on the DC bus, the functions that the nGfHA must approach. So, instantaneously, the power generated by the PV
perform are established. Moreover, every nGfHA can receive an plants is measured and compared with the expected power, this
external signal requiring to deliver or absorb a given power. The difference represents the power that the BES has to exchange
principal characteristic of DBS is that the DC bus voltage is the (supplied or stored) in the test facility. The test-facility also
only information carrier implementing the control strategy in a supplies several loads, so the load demand profile forecast has
decentralized and distributed manner. In this way power flows also to be valuated. Such load profile will be subtracted from the
can be managed according to the logics described above. estimated production profile. It is worth to underline that the
load prediction will be different from the real one also, as
The system set-up is described below: starting from the LV consequence, it could also be a cause of power imbalances.
distribution grid connection, immediately after the energy Therefore, it is necessary to compensate both the power
counter, we have: a first AC line suppling some no-essential imbalances due to the real PV production plants and to the real
loads; another AC line to which the PV plant is connected by a load demand.
conventional inverter; and other three AC lines to which the
three nanogrids are connected, connect in turn to the common Two tests will be carried out: in the first, there will be a lower
DC bus. The first one, the Nanogrid 2 (see Figure 1) connects power output than the expected one and a second test in which
the PVNG plant, while the other two Nanogrid are: the nanogrid, there is a power output greater than the expected power. The
named Nanogrid 1, controls the storage system BES and the power imbalances reduction is carried out using a real-time
inverter which supplies some essential loads; the other nanogrid, approach: every time interval the produced PV power is
named Nanogrid 3, controls an inverter for other essential loads measured and it is compared with the forecasted one; from this
and the SE. difference the power which the storage system have to supply is
obtained.
The three nGfHAs work independently of each other,
appropriately managing the converters that interface the As case study the day 16 October 2017 is considered, for this
different sources and the loads. In order to work independently day at 16.00 the forecasted PV power is about 4910 W, the
of each other, without effective communication between the power absorbed by non-essential loads (named AC-Loads) is
different subsystems, the DBS logic is used, regulating the about 300 W and the power absorbed by essential loads (named
power flow by measuring the voltage on the common DC bus. AC Critical-Loads) is about 470 W, as consequence the
Each nGfHA regulates the voltage on the DC bus to an forecasted power to exchange with the grid is equal to 4140 W.
appropriate value, according to the PV and µ-CHP production After that, the power really produced by the PV plants is
power or required power by any loads and based on the equal to 3836 W, while the power actually absorbed by external
availability of storage system (depending on the state of charge) AC-Loads is equal to 699 W and the power absorbed by AC
or if it operates in grid connection or islanded mode. Critical-Loads is equal to 470 W. As consequence, there is a
The three nGfHAs work trying to minimize the amount of power about 1480 W to be balanced in real-time; it represents
energy absorbed by the grid, maximizing the local use of energy the possible imbalance measured at the POD, if there was no an
produced by renewable sources plants. opportune compensation. To reduce such imbalance, the storage
system supplies exactly this power (1477 W) reducing the
The Nanogrid 2, which is interfaced both with the PV plant imbalances.
and the grid, maximize the power produced by the PV plant; the
generated power is delivered to the grid or to the DC bus. The In Figure 2 the experimental results are reported as illustrated
Nanogrid 1 allows to exchange power with the DC-bus charging by the implemented user-friendly interface: the power
exchanged with the grid, for the three phases, is respectively
or discharging the storage system and suppling any the essential
loads. At the end, the Nanogrid 3 allows to supply SE for the equal to 2944 W, 940 W and 246 W, reaching a total power equal
start-up and to withdraw the power produced by the same to 4130 W, which is almost equal to the forecasted power. Figure
generator; this energy is then supplied on the DC bus and it is 3 shows the grid voltage and the voltage for critical loads
available for other nanogrids and to feed local both essential and produced by the Nanogrid 1 and 2 (UPS): it has a frequency
non-essential loads. equal to 50 Hz and a RMS value of 230 V. The DC bus voltage
is measured; it is utilized to communicate the different operating
IV. EXPERIMENTAL RESULTS states of the three nanogrid: in the observed case the DC bus
voltage is regulated to 355 V which corresponds to the system
Several tests have been carried out. In the first test, the configuration when storage system supplies power. At the end,
production forecast of both PV plants for a specific time is the storage current is shown, it can be observed it is about 6.5 A.

Authorized licensed use limited to: Pontificia Universidad Javeriana. Downloaded on February 13,2023 at 02:56:22 UTC from IEEE Xplore. Restrictions apply.
Figure 2 Power imbalance minimization in case of power deficit

than that contracted one or in any case greater than that which
the PEI can exchange with the grid. In this test the loads absorb
a power equal to 4500 W, divided respectively into 1290 W of
AC Critical-Loads, 2150 W of home automation loads
(representing other non-essential AC loads), and 1074 W AC-
Loads on the 1st phase. The two PV plants produce a power equal
to 987 W for PVNG and 354 W for every phase for PV; as
consequence on the 1st phase the PV plants produce a power of
1341 W. Each phase has a maximum power limit about 2 kW,
while in the actual case the power grid has to supply a power
equal to 3170 W (see Figure 4). For this reason, in order to avoid
the grid disconnection (due to the contract breach), the BES has
to supply the power difference. In the above illustrated case the
BES has to supply a power equal to 1100 W. Suppling this
power, in addition to supplying the loads, the Nanogrid 2 will
deliver a power to the network of 791 W, while at the POD on
phase 1 a power about 2000 W is absorbed.
Figure 3 Power imbalance reduction test - Acquisition
This could be managed according the aforementioned two
approaches, the real-time and the predictive one. The use of the
Similar considerations can be made when a surplus of power real time approach assumes that the power is measured instantly
compared to the programmed one is considered; in this case the and it depends on the current state of the system (as seen by the
BES has to absorb the surplus power. This is possible only if the reported results), while the utilize of the predictive approach
state of charge of the storage system is lower than a defined assumes that load and generation power forecast methods are
threshold (equal to 98%). utilized and they have a high reliability. So to obtain good
results, both methods have to be utilized.
As further test, it was supposed to have the necessity to
supply a set of loads that absorb an instantaneous power greater

Authorized licensed use limited to: Pontificia Universidad Javeriana. Downloaded on February 13,2023 at 02:56:22 UTC from IEEE Xplore. Restrictions apply.
Figure 4 Minimization of grid power peak

V. CONCLUSIONS [4] G. Belli, G. Brusco, A. Burgio, M. Motta, D. Menniti, A. Pinnarelli, and


N. Sorrentino, “An energy management model for energetic communities
In this paper, an efficient energy management method, of Smart Homes: the Power Cloud,” In Networking, Sensing and Control
proposed by the authors in a previous paper, based on a real-time (ICNSC), 2017 IEEE 14th International Conference on, pp. 158-162,
IEEE, May 2017.
approach is applied in the real-life application of Unical Campus
[5] S. Teleke, M. E. Baran, S. Bhattacharya, and A. Q. Huang, “Rule-based
test facility. After a brief summary to illustrate the proposed control of battery energy storage for dispatching intermittent renewable
efficient energy management method, the test-facility is sources,” IEEE Trans. Sustain. Energy, vol. 1, no. 3, pp. 117–124, 2010.
described and some experimental results are discussed. The [6] N. Jayasekara, P. Wolfs, and M. A. S. Masoum, “An optimal management
application of proposed real-time approach on a real-life case strategy for distributed storages in distribution networks with high
emphasizes some feature that the use of only simulation method penetrations of PV”, Electr. Power Syst. Res., vol. 116, pp. 147–157,
does not considers perfectly: such as the BES and power 2014.
converter dynamics and the uncertainty of load demand due to [7] G. Belli, A. Burgio, D. Menniti, A. Pinnarelli, N. Sorrentino, P. Vizza, “A
the real behavior of end-users. multiperiodal management method at user level for storage systems using
artificial neural network forecasts”, Trans. Environ. Electr. Eng., vol. 1,
no. 4, pp. 29, Nov. 2016.
REFERENCES
[8] G. Brusco, A. Burgio, D. Menniti, A. Pinnarelli, N. Sorrentino, and L.
[1] A. Mohamed and O. Mohammed, “Real-time energy management scheme Scarcello, “An Energy Box in a Cloud-Based Architecture for
for hybrid renewable energy systems in smart grid applications,” Electr. Autonomous Demand Response of Prosumers and Prosumages,”
Power Syst. Res., vol. 96, pp. 133–143, 2013. Electronics, vol. 6, no. 4, p. 98, 2017.
[2] M. Marzband, M. Ghadimi, A. Sumper, and J. L. Domínguez-García, [9] G. Barone, G. Brusco, A. Burgio, D. Menniti, A. Pinnarelli, and N.
“Experimental validation of a real-time energy management system using Sorrentino, “A power management and control strategy with grid-
multi-period gravitational search algorithm for microgrids in islanded ancillary services for a microgrid based on DC bus,” Int. Rev. Electr. Eng.,
mode,” Applied energy, vol. 128, pp. 164-174, 2014. vol. 9, no. 4, pp. 792–802, 2014.
[3] R. Missaoui, H. Joumaa, S. Ploix, and S. Bacha, “Managing energy smart
homes according to energy prices: analysis of a building energy
management system,” Energy and Buildings, vol. 71, pp. 155-167. 2014.

Authorized licensed use limited to: Pontificia Universidad Javeriana. Downloaded on February 13,2023 at 02:56:22 UTC from IEEE Xplore. Restrictions apply.

You might also like