Professional Documents
Culture Documents
Transformer Tertiary Winding Basic Application - PAC Basics
Transformer Tertiary Winding Basic Application - PAC Basics
Open
Wye-Wye Transformer
Voltage Stability
References
Tertiary winding in transformers have been widely used in the transmission and distribution of electricity –
from power transformers up to distribution transformers. In most cases, the role of the tertiary is for
voltage stability and suppression of third harmonic voltages. The discussion will begin with a brief
introduction to wye-wye transformers, their advantages and potential issues associated with their
operation.
尊重您隐私的广告
Wye-wye connected transformers are very common and have been used throughout the electric power
industry for several reasons. The following are the most notable reasons for using wye-wye transformers.
One end of the winding can be placed at low potential to ground (except for ungrounded neutral)
Voltage Stability
The conveniences offered by a wye-wye transformer come with a stability issue to the line-to-neutral
voltage which may become unstable when
Third harmonic currents cannot flow through the primary or secondary windings
Unbalanced loads on a wye-wye transformer with isolated primary neutral presents a voltage stability
issue as illustrated in the above figure. The load current which flows through the neutral of the secondary
side produces a zero-sequence voltage drop which shifts the secondary terminal’s voltage to neutral.
However, the increase in the line-to-neutral voltage is limited to 1.4pu if secondary is effectively
grounded.
The above figure shows a simplified network with generator, power line, and a wye-wye connected
transformer with isolated primary neutral, and the equivalent zero-sequence network. By isolating the
transformer primary neutral, zero-sequence currents are prevented to flow.
Harmonic Distortion
Harmonic Distortion
Image taken from IEEE Std C57.158™-2017
The absence of zero-sequence path for the third harmonic currents to flow results to the distortion
voltages as shown in the above figure.
The figure below shows a zero-sequence network with a source, transmission line , and a three-winding
transformer equivalent circuit.
The presence of a stabilizing winding presents an alternate path with significantly lower zero-sequence
impedance for the harmonic currents to flow.
The following gallery shows pictures of a burned three-winding transformer due to upstream ground
faults.
References
“IEEE Guide for the Application of Tertiary and Stabilizing Windings in Power Transformers,” in IEEE Std
C57.158-2017 , vol., no., pp.1-80, 27 April 2018, doi: 10.1109/IEEESTD.2018.8352755
“Application of Primary Fuses“, Hubbell Power Systems, Inc., 2000, Centralia, MO.
Prev
Email Address
Subscribe