SEISMIC RESTRAINTS
Multi-Directional Bracing For Electrical Conduit,
Cable Tray And Mechanical Piping Systems

OSHPD Pre-Approved System

SYSTEMS THAT MAKE SENSE


INTRODUCTION
INTRODUCTION
What is Seismic Bracing?
Seismic forces are exerted on a building and its contents during an earthquake. These forces act
horizontally upon the structure itself, as well as the piping, cable trays, ductwork, and other building
systems within. Typical supports for piping, trays, and other equipment are designed for the gravity,
or vertical, loads but do not take into account the horizontal loading caused by earthquakes. Seismic
restraints (i.e. braces) resist the horizontal forces and keep the systems in place and secure. The main
purpose of seismic bracing is safety- to minimize the loss of life due to an earthquake.

Seismic Bracing Requirements


The rules and requirements for the seismic restraints are published in the model building codes: The
Uniform Building Code (International Conference of Building Officials), National Building Code
(Building Officials and Code Administrators) and the Standard Building Code (Southern Building Code
Congress International). Each code is similar in nature, and has a chapter on structural forces which
defines the level of seismic force must be used in the design of seismic restraints.
The amount of seismic force (as determined by the building code) is given as a percent of the
components’ weight, or g-force. If the horizontal force is determined to be 50 percent of the piping
weight, for example, the seismic force is .5g.
The seismic "g-value" can vary greatly depending on the nature of the project. Critical buildings in a
high seismic zone have larger g-value requirements than warehouses in zone 1.
Factors that govern the seismic g-values used for design:
• Seismic Zone • Soil Type
• Building Type • Distance from known faults
• Elevation within building • Anchorage Type
• System being braced
The design professional should use these factors and the applicable building code requirements to
determine the proper g-values to be used for the project.

While this manual has been developed under the requirements of the 2001 California Building Code,
this manual may also be used under other building codes as the California Building Code requires more
stringent seismic design criteria.
This brochure contains seismic bracing details that can be used for seismic bracing projects up
to 1.0g (ASD) or 1.4g. The brace spacing charts, required details, and rod loads must be determined
for the specific g-value for the project and shall be submitted to the engineer of record prior to
construction. The determination of the seismic force level shall also be submitted to the engineer of
record and to OSHPD for hospital projects in the state of California prior to construction. However,
the seismic force level need not be submitted to the engineer of record or OSHPD if included in the
original construction documents. This brochure contains charts for a variety of g values, however
custom charts can be created to reflect different g-values as required for the project. Contact B-Line
Engineering at 618-654-2184 with your requirements.
A copy of the complete Seismic Restraints Manual shall be on the jobsite for the duration of the
project.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 i of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 1

TABLE OF CONTENTS

General Information & Notes ................................ 1 - 11

Single Pipe/Conduit Bracing Selection ....... 12 - 16

Trapeze Bracing Selection .................................... 17 - 20

Trapeze Members ........................................................ 21 - 22

Structural Attachment Selection ................................. 23


Concrete .......................................................................... 24 - 33
Wood ................................................................................. 34 - 37
Steel .............................................................................................. 38

Hanger Rod Attachments &


Approved Components ....................................................... 39
Concrete .......................................................................... 40 - 46
Wood ............................................................................................ 47
Steel ................................................................................... 48 - 56

Approved Components
Rod Stiffeners ................................................................ 57 - 58
Adjustable Hinge .......................................................... 59 - 60
Hardware ......................................................................... 61 - 62

Pipe Hangers/Clamps .............................................. 63 - 71

Anchoring Components .......................................... 72 - 78

Metric Conversion Charts .................................. 79


Seismic Map ....................................................... 80

Appendix 1
Additional Support Spacing Charts For
Single Pipe/Conduit Applications (.15g, .30g,
.45g, .50g, .75g and 1.00g) ................... 82 - 106

Appendix 2
Additional Support Spacing Charts For
Trapeze Applications (.15g, .30g, .45g, .50g,
.75g and 1.00g) .................................. 108 - 145

Appendix 3
Proof Test Instructions For Concrete
Anchors (IR26-6) ........................................... 146

Appendix 4
Calculating Your Seismic Force Level .... 147 - 155

Appendix 5 (Beyond the scope of OSHPD)


Additional Engineering Approvals ................... 156

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 ii of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 2

GENERAL INFORMATION

B-LINE SEISMIC RESTRAINT SYSTEMS are designed to resist seismic loading while minimizing
installation time and providing superior performance. On the following pages, several methods of seismic
bracing are illustrated. The choice of brace design should be governed by the system requirements and location
of supports.
Actual applications may vary and are not strictly limited to the combinations of fittings and supports shown.
Any changes to the depicted designs should be in accordance with standard engineering practices and be
approved by OSHPD (California Office of Statewide Health Planning & Development) if necessary.
For additional information on hangers, channels, fittings, and hardware shown, see the latest B-Line Strut
Systems Catalog or Pipe Hangers and Supports Catalog.

Seismic restraints are designed to resist the horizontal seismic force in two primary directions: Transverse
(perpendicular) and Longitudinal (parallel) to the run. The braces are attached to the building with a structure
attachment (for concrete, steel, wood, etc.) of various anchor sizes. Typically, the stronger the structure
attachment, the greater the brace spacing allowed.

The following steps detail how to use the brochure:


Step 1: Select the bracing details for single pipe hangers or trapeze supports.

Step 2: Obtain required force level (%g) from applicable code for local jurisdiction or from the structural
engineer of record.
Example: 2001 California Building Code
As defined in the 2001 California Building Code, Chapter 16A, Section 1632A, the seismic horizontal
force, Fp, may be calculated using the following formula:

apCaIp h
Fp = (1 + 3 • x )Wp
Rp hr

Except that: Fp shall not be less than 0.7 Ca Ip Wp and need not be more than 4 Ca Ip Wp.

Where:
Fp = Seismic Force Level
ap = Amplification Factor (Table 16A-O)
Rp = Component Response Modification Factor (Table 16A-O)
= 3.0 for electrical, mechanical and plumbing equipment and associated
conduit, ductwork and piping utilizing deeply embedded anchors. (Table 16A-O)
= 1.5 for installations using concrete anchors with an embedment-to-diameter
ratio less than 8.
i.e. a 1/2" diameter concrete anchor with an embedment of less than 4" inches.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 1 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 3

GENERAL INFORMATION
Ip = Importance Factor (Table 16A-K)
= 1.5 for Essential facilities such as Hospitals, Fire Stations, Police Stations,
Aviation Control Towers, etc. consult Table 16A-K in CBC for a detailed listing.
= 1.0 for most other occupancies
Ca = Seismic Coefficient. This is a cumulation of several factors:
Zone, Soil Properties, and distance from known fault.
(Table 16A-I, Table 16A-J, Table 16A-Q, Table 16A-S, and Table 16A-U)
hx = Element or component attachment elevation with respect to grade.
Note: hx shall not be taken less than 0.0
hr = Structure Roof Elevation with respect to grade.

Special Note: This manual is based on allowable stress design (ASD), where as the seismic force level
(%g or Fp) for non-structural components provided in building codes are based on strength design. For
use in this manual, the seismic force level (Fp) from the building code are converted to allowable stress
design by dividing the result by 1.4.

Example: If the building code yields, (Fp) = 1.4g, this value is converted to allowable stress design (ASD)
as used in this catalog as follows: Fp=1.4g/1.4=1.0 g

Strength Design to Allowable Stress Design Conversions

.21g from building code = .15g (ASD)


.42g from building code = .30g (ASD)
.63g from building code = .45g (ASD)
.70g from building code = .50g (ASD)
1.05g from building code = .75g (ASD)
1.40g from building code = 1.00g (ASD)

Example One, Deeply Embedded Anchors:


Cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical center in California.
The cable tray is actually suspended from the bottom of the 2nd floor, which has an elevation of 20 feet
above grade. Location of the surgical center is in seismic zone 4 with a rock soil profile.

apCaIp h
Fp = (1 + 3 • x )Wp
Rp hr

ap = 1.0 from Table 16A-O

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 2 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 4

GENERAL INFORMATION
Ca = .40Na from Table 16A-Q, which is combination of Zone and Soil profile
Zone 4 = .40, from Table 16A-I
Rock Soil Profile = SB, from Table 16A-J
Seismic Source Type = B, for faults other than Type A & C (Table 16A-U)
Near Source Factor (Na) = 1.0, for 5 km from known seismic source (Table 16A-S)
Ip = 1.5 from Table 16A-K, Occupancies having surgery and emergency treatment areas.
Rp = 3.0 from Table 16A-O for deep embedded anchors
hx = 20 feet
hr = 40 feet
(1.0)(0.40(1.0))(1.5) 20
Fp = (1 + 3 • )Wp = 0.50Wp = 0.50g
3.0 40

Check if value falls within limits:

Fp shall not be taken less than, 0.7CaIpWp = 0.7(.40)(1.5)Wp = .42g


Fp shall not be greater than, 4.0CaIpWp = 4.0(.40)(1.5)Wp = 2.4g

2.4g > .5 > 0.42g Therefore allowing the use of 0.50g

To convert this Fp from a strength design to an Allowable Stress Design (ASD) used in this catalog
divide by 1.4.
0.50g
Fp = = 0.36g (ASD)
1.4

0.36g is the Allowable Stress Design Seismic Load Factor determined from 2001 California
Building Code.

Special Note: A table for .36g (ASD) is not available in this catalog. When seismic force levels (%g or
Fp) falls between catalog table values (i.e.: .15g, .3g, .45g, etc.) the seismic force level shall be rounded
up to the next highest cataloged force level.

Example: If Fp = .36g (ASD), then use catalog tables for .45g (ASD).

Example Two, Shallow Embedded Anchors:


Special Note: Installations using concrete anchors installed with an embedment length-to-diameter
ratio of less than 8, also referred to as shallow embedment anchors, have an adjusted Component
Response Factor. The adjusted factor Rp = 1.5.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 3 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 5

GENERAL INFORMATION
Cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical center in California.
The cable tray is actually suspended from the 2nd floor, which has an elevation of 20 feet above
grade. Location of the surgical center is in seismic zone 4 with a rock soil profile, shallow
embedment anchors are used for brace locations.
apCaIp h
Fp = (1 + 3 • x )Wp
Rp hr

ap = 1.0 from Table 16A-O


Ca = .40Na from Table 16A-Q, which is combination of Zone and Soil profile
Zone 4 = .40 from Table 16A-I
Rock Soil Profile = SB from Table 16A-J
Seismic Source Type = B for faults other than Type A & C (Table 16A-U)
Near Source Factor (Na) = 1.0 for 5 km from known seismic source (Table 16A-S)

Ip = 1.5 from Table 16A-K, Occupancies having surgery and emergency treatment areas.
Rp = 1.5 adjusted for Shallow Embedment Anchors
hx = 20 feet
hr = 40 feet
(1.0)(0.40(1.0))(1.5) 20
Fp = (1 + 3 • )Wp = 1.0Wp = 1.0g
1.5 40

Check if value falls within limits:


Fp shall not be taken less than, 0.7CaIpWp = 0.7(.40)(1.5)Wp = .42g
Fp shall not be greater than, 4.0CaIpWp = 4.0(.40)(1.5)Wp = 2.4g

2.4g > 1.0g > 0.42g Therefore allowing the use of 1.0g

To convert this Fp from a strength design to an Allowable Stress Design (ASD) used in this catalog
divide by 1.4.
1.0g
Fp = = 0.71g (ASD)
1.4

0.71g is the Allowable Stress Design Seismic Load Factor determined from 2001 California
Building Code for shallow embedment anchors.

Special Note: A table for .71g (ASD) is not available in this catalog. When seismic force levels (%g or
Fp) falls between catalog table values (i.e.: .15g, .3g, .45g, etc.) the seismic force level shall be rounded
up to the next highest cataloged force level.

Example: If Fp = .71g (ASD), then use catalog tables for .75g (ASD).

Note: For other Code examples see Appendix 4

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 4 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 6

GENERAL INFORMATION

Step 3: With required force level (%g), obtain the transverse and longitudinal brace spacing from
Appendix 1 (single pipe) or Appendix 2 (trapeze hanger). The following notes shall be followed:
a) Break the length of pipe into separate straight runs, which are considered to be a single straight
section between any bends in the pipe except where the bend is at an offset of less than the
maximum offset length as defined below.

Table 1 - Steel Pipe or Conduit Table 2 - Copper Tubing


Nominal Max. Offset Length (ft) Nominal Max. Offset Length (ft)
Pipe Tubing
Size 0.15g 0.3g 0.5g 0.75g 1.0g Size 0.15g 0.3g 0.5g 0.75g 1.0g
5 4 4 4 4 3 12 4 4 4 4 4
6 6 6 6 6 5
8 10 10 10 9 7
10 10 10 10 10 9

Note: The tabulated values represent pipe and tubing with moment and shear transfering joints.
Therefore, for use of these tables pipes shall have welded, brazed, or UL Listed grooved joints. Pipe and
tube sizes not listed above or joined as reqiuired shall be limited to a maximum offset length of 2 ft.

Maximum Offset Length (ft.)

b) Brace each straight run in the transverse direction at both ends. Where several short runs occur,
see note e) on the following page.

Straight Run

Transverse bracing at both ends of the pipe run

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 5 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 7

GENERAL INFORMATION

c) Check the required spacing for transverse bracing (Appendixes 1 & 2) and compare it to the
length of the straight run. If the length of the straight run is greater than the allowable distance
for transverse bracing add transverse braces until the spacing does not exceed the allowable
transverse brace distance.

Straight Run

Additional Transverse Braces

d) Each straight run must have at least one longitudinal brace. Add longitudinal braces so that the
spacing does not exceed the allowable longitudinal brace spacing in Appendixes 1 & 2.

Straight Run
Longitudinal Brace (Transverse brace
for the adjacent run)
Longitudinal Brace
Longitudinal Brace (Transverse brace for
the adjacent run)

24” (610mm) Max. 24” (610mm) Max.

Note: A transverse brace may dually act as a longitudinal brace for an adjacent run when it is
located within 24” of the adjacent straight run. However, Appendixes 1 & 2 shall be reviewed to
use the stronger of the longitudinal or transverse brace requirements, i.e. anchor and other
component sizes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 6 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 8

GENERAL INFORMATION

e) In many cases, several short runs occur one after the other. Based on previous requirements,
each straight run requires a longitudinal brace when the adjacent short runs exceed the maximum
offset length (ft.). When the adjacent short runs do not exceed the maximum offset length (ft.) the
longitudinal braces can act as transverse braces as long as the allowable transverse brace spacing
(Appendixes 1 & 2) is not exceeded.

In the following layout, transverse braces are used as longitudinal braces when the straight runs
are less than the maximum offset length (ft.). When a straight run exceeds the maximum offset
length (ft.) additional braces are required.

First Transverse Brace Second Transverse Brace

Longitudinal
brace
Two braces may
be required. Short run less
than the maximum
Straight run offset length (ft.)
exceeding the
maximum offset Longitudinal
length (ft.) brace

Multiple offsets can be treated as a single run when the


total offset is less than the maximum offset length (ft.).

Plan or Elevation

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 7 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 9

GENERAL INFORMATION
f) When a flexible connection or swing joint is used, such as at a pipe drop to mechanical
equipment, the pipe may cantilever at a length equal to or less than half the allowable transverse
brace spacing (Appendixes 1 & 2). When greater than half the allowable transverse brace
spacing, support to the floor is required as shown below.
Transverse brace at the
Straight Run
end of horizontal run

Requires a flexible connection or


swing joint between equipment. Allowable Transverse Brace Spacing
2

Mechanical equipment.
If < 6 ft.
Support to Floor
Is Required.
Floor

Step 4: Note the structure connection type (brace anchor requirements) from the Appendix,
and select the brace anchorage detail to suit (pages 23 thru 38).
Step 5: Note the hanger rod load from the Appendix, and select a rod attachment to structure
to suit (pages 39 thru 56).
Step 6: Check if rod stiffeners are required (pages 57 & 58) to prevent the hanger rod from
buckling.

Seismic restraints may typically be omitted from the following installations:


(Verify with structural engineer of record for site specific project.)

1. Fuel piping less than 1 inch (25 mm) inside diameter.


2. All other piping less than 21/2 inches (63 mm) inside diameter, except medical gas including
vacuum piping.
3. All piping suspended by individual hangers 12 inches (305 mm) or less in length from the top of
the pipe to the bottom of the support for the hanger; where rod hangers are not subject to
bending moments. (To eliminate bending moment flexible connections may be used such as the
B752 on page 49 or B446 & B446C on page 56)
4. All electrical conduit less than 21/2 inches (63 mm) trade size.
5. All rectangular air handling ducts less than 6 sq. ft. (.56 m2) in cross sectional area.
6. All round air handling ducts less than 28 inches (711 mm) in diameter.
7. All ducts suspended by hangers 12 inches (305 mm) or less in length from the top of the duct to
the bottom of the support for the hanger; where rod hangers are not subject to bending
moments. (To eliminate bending moment flexible connections may be used such as the B752 on
page 49 or B446 & B446C on page 56)

NOTE: Reference building code enforced by local authority having


jurisdiction for specific requirements.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 8 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 10

GENERAL NOTES FOR SEISMIC BRACING

GENERAL NOTES FOR SEISMIC BRACING


A) The seismic restraint assemblies shown in this pre-approval document are designed to resist
vertical loading simultaneously with seismic loading (transverse & longitudinal loading). Design
recommendations shown are for single standard weight steel pipes filled with water. Contents
other than water shall be evaluated by the user. Pipes of other approved materials shall be
supported in accordance with their approved installation standards. Details not shown in this
pre-approval shall be submitted to OSHPD for approval before installation if necessary.

B) This bracing system is limited to the pipe sizes and support details shown. Special
consideration must be given for pipe material and connections, insulation, thermal movement,
vibration, and building seismic joints.

C) Transverse and longitudinal braces shall be no more than 45° above or below the centerline of
the pipe, duct, or tray.

D) All channel and pipe clamp nuts and bolts shall be tightened to the following torques:
1/4"-20 to 6 ft.-lbs. (8 N•m)
3/8"-16 to 19 ft.-lbs. (26 N•m)
1/2"-13 to 50 ft.-lbs. (68 N•m)
5/8"-11 to 65 ft.-lbs. (88 N•m)
3/4"-10 to 75 ft.-lbs. (101 N•m)

E) The transverse and longitudinal bracing spacing listed in Appendix 1 & 2 is based on ductile
piping (steel, copper, etc.) with ductile connections (welded, brazed, etc.) and has the following
limitations:

1) Transverse bracing shall not exceed 40’-0” (12.2 m).


Longitudinal bracing shall not exceed 80’-0” (24.4 m).

2) Fuel piping shall have transverse bracing 20'-0" (6.1 m) o.c. maximum and
longitudinal bracing 40'-0" (12.2 m) o.c. maximum.

3) Non-ductile piping, and piping with non-ductile connections shall have transverse
bracing 20'-0" (6.1 m) o.c. maximum and longitudinal bracing 40'-0" (12.2 m) o.c.
maximum or 1/2 of the calculated brace spacing indicated in Appendix 1 or 2,
whichever is more restrictive.

F) Transverse bracing for one pipe section may also act as longitudinal bracing for the pipe
section connected to it, if the bracing is installed within 24 inches (609 mm) of the elbow or tee
of similar size. Figures 2 and 4 do not serve as adequate longitudinal braces.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 9 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 11

GENERAL NOTES FOR SEISMIC BRACING

G) Branch lines of a smaller diameter shall not be used to brace main lines.

H) Where rod stiffeners are required a minimum of two hanger rod stiffener assemblies shall be
installed. (Part number SC-228 or SC-UB)

I) It is important to check anchorage details against the applicable building code requirements.
Seismic design forces may increase substantially when anchors are considered “shallow”
(embedded less than 8 times the anchor diameter).

J) When bracing trapeze type hangers, the bracing shall be attached directly to the trapeze hanger
assembly and piping secured to the trapeze assembly with pipe straps.

K) A rigid piping system shall not be braced to different parts of a building that may respond
differently during an earthquake. Example: Solid concrete wall and a roof (metal deck filled with
lightweight concrete). Special care should be taken to avoid bracing rigid pipe on both sides of
a building seismic joint without allowing for pipe and building movement.

L) The pre-approval document is based on British Units (Inches & Pounds) and values noted in
parenthesis (Metric or S.I. Units) are equivalent values. In case of conflicts, British Units will be
the standards for evaluating the proper application of pre-approvals.

M) The designer of the structure shall determine the adequacy of the support structure to carry the
load of the piping and equipment. Engineer of record for a site specific project shall verify that
the structure can support the connection loads of the hanger rod and the bracing attachments.
This pre-approval document is not intended for the seismic design of the piping itself. The
dynamic properties of the building structure and piping should be considered when selecting
the type of piping to be installed.

N) Seismic bracing shall not limit the expansion and contraction of the piping system. Always
consider thermal movements when selecting brace locations and materials. The design for
thermal movements is beyond the scope of OSHPD pre-approval.

P) No portion of this pre-approval shall be taken out of context and used in other systems,
design or purpose.

Q) On transverse bracing, the pipe insulation material may be part of the brace assembly (i.e) in
the load path. In this case the insulating material shall be capable of withstanding the lateral
forces without damage and shall include a pipe shield for hangers or a pipe saddle for rollers.
For longitudinal bracing, clamping must be applied directly to the pipe with any insulation
being installed directly over the hanger and brace assembly. In these applications the
mechanical engineer of record shall be contacted for insulating recommendations.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 10 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 12

B-LINE CHANNEL BRACES

The following B-Line channels may be used as brace members for


Figures 1 - 11 using the following structure connection types:

Maximum Maximum Channel Channel


Material
Channel Structure Brace Height Width
Thickness
Type* Connection Length
Type** (m) (mm) (mm) (mm)

B54 IV 4’-10” (1.47) 13/16” (20.6) 1 5/8” (41.3) 14 Ga. (1.9)

B52 IV 4’-8” (1.42) 13/16” (20.6) 1 5/8” (41.3) 12 Ga. (2.6)

B42 V 5’-10” (1.78) 1” (25.4) 1 5/8” (41.3) 12 Ga. (2.6)

B32 V 8’-0” (2.44) 13/8” (34.9) 1 5/8” (41.3) 12 Ga. (2.6)

B24 IV 9’-7” (2.92) 15/8” (41.3) 1 5/8” (41.3) 14 Ga. (1.9)

B22 V 9’-5” (2.74) 15/8” (41.3) 1 5/8” (41.3) 12 Ga. (2.6)

B22A V 10’-10” (3.30) 31/4” (82.5) 1 5/8” (41.3) 12 Ga. (2.6)

B11 IV 11’-7” (3.53) 31/4” ( 82.5) 1 5/8” (41.3) 12 Ga. (2.6)

*Slotted channel (SH) versions of all the above types may also be used for brace members.
See page 21 for channel details.
**The Structure Connection Type is the brace anchorage requirement.
See pages 23 - 38 for brace attachment details.

Note: Do not exceed the maximum brace length or maximum structure connection
type for the channels listed.

Commentary:

Appendix 1 & 2 list the allowable structure connection type (I, II, III, IV, or V) for each brace spacing listed. The
structure connection type limits the amount of axial load (in tension or compression) which is applied to the
brace member. The axial load is listed for each structure connection detail on pages 23 - 38, and is as follows:

Structure Connection Type Maximum Axial Load in Brace Member

I ....................................... 175 lbs. (0.78 kN)


II ...................................... 300 lbs. (1.33 kN)
III ...................................... 450 lbs. (2.00 kN)
IV ...................................... 675 lbs. (3.00 kN)
V ...................................... 975 lbs. (4.33 kN)

The B-Line channel brace member must have a capacity greater than the value listed in the above table for the
maximum recommended brace length.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 11 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 13

SINGLE PIPE/CONDUIT BRACING

Single Rod Hanger Pipe Bracing


1) Layout piping run and determine size and location of piping.

2) Select vertical supports (single rod pipe hangers).

a) Select type of hanger dependent on type of pipe, thermal expansion and contraction, etc.

b) Determine maximum spacing of hanger rods and minimum hanger rod diameter.
(Appendix 1)

c) Select hanger rod connection to the structure based on structure type, rod size and hanger
rod load from Appendix 1. Refer to section on hanger rod attachment for
details (pages 39 thru 56)

d) Engineer of record for a site specific project shall verify that the structure can support
the connection loads.

3) Select lateral bracing (transverse and longitudinal bracing).

a) Select bracing details (transverse & longitudinal) from Figures 1 thru 8.

b) Determine maximum spacing for transverse and longitudinal braces. (Appendix 1)

c) Determine the type of structure connection required. (Appendix 1)


Refer to section on structural attachments for connection details.

d) Determine if rod stiffener is required. (pages 57 & 58)

e) Engineer of record for a site specific project shall verify that the structure can support
the connection loads.

4) Review the design and revise layout where loads exceed the limitations of the hanger rods,
hangers or connection details.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 12 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 14

SINGLE PIPE BRACING


CLEVIS HANGER TRANSVERSE BRACING (Figure 1)
Adjustable Pipe
ATR Pipe Size Clevis Hanger Hinge Sleeve
All Threaded Rod in. (mm) Part No. Part No. Part No.*
(See Page 57 for 1/2" (15) B3100-1/2 N/A N/A
minimum diameter)
3/4" (20) B3100-3/4 N/A N/A
Rod Stiffener 1" (25) B3100-1 B335-2-3/8 B3100PS-1
(See Pages 57 & 58) 11/4" (32) B3100-11/4 B335-2-3/8 B3100PS-11/4
1 (Min.) 11/2" (40) B3100-11/2 B335-2-3/8 B3100PS-11/2
2" (50) B3100-2 B335-2-3/8 B3100PS-2
1 B-Line Channel 21/2" (65) B3100-21/2 B335-2-3/8 B3100PS-21/2
Transverse Brace
3" (80) B3100-3 B335-2-3/8 B3100PS-3
(See page 11)
31/2" (90) B3100-31/2 B335-2-3/8 B3100PS-31/2
B335-2-Bolt Size 4" (100) B3100-4 B335-2-3/8 B3100PS-4
Adjustable Hinge 5" (125) B3100-5 B335-2-1/2 B3100PS-5
(See Page 59) 6" (150) B3100-6 B335-2-1/2 B3100PS-6
B3100PS Pipe Sleeve 8" (200) B3100-8 B335-2-5/8 B3100PS-8
10" (250) B3100-10 B335-2-3/4 B3100PS-10
12" (300) B3100-12 B335-2-3/4 B3100PS-12
B3100 Series Clevis Hanger
(See Page 63) * Not included when ordering standard B3100 Series Clevis Hanger.

Notes: Pipe sleeve required over cross bolt of Clevis Hanger when using the brace connection shown above (Figure 1).
Pipe sleeve is not required when clevis hanger is used in conjunction with the bracing shown in Figure 5 - page 15.
Refer to Note Q) on page 10 for installations requiring insulated pipe.

"J" HANGER TRANSVERSE BRACING (Figure 2)

Rod Stiffener
May Be Required
(See Pages 57 & 58) 1 Min.
Adjustable
Pipe Size "J" Hanger Hinge
1 in. (mm) Part No. Part No.
ATR 1/2" (15) B3690-1/2 N/A
All Threaded Rod 3/4" (20) B3690-3/4 N/A
(See Page 57 for
minimum diameter) 1" (25) B3690-1 B335-2-3/8
B-Line Channel
11/4" (32) B3690-11/4 B335-2-3/8
Transverse Brace
(See page 11) 11/2" (40) B3690-11/2 B335-2-3/8
2" (50) B3690-2 B335-2-3/8
B335-2-Bolt Size 21/2" (65) B3690-21/2 B335-2-1/2
Adjustable Hinge
3" (80) B3690-3 B335-2-1/2
(See Page 59)
31/2" (90) B3690-31/2 B335-2-1/2
4" (100) B3690-4 B335-2-1/2
B3690 Series 5" (125) B3690-5 B335-2-1/2
'J' Hanger 6" (150) B3690-6 B335-2-1/2
(See Page 64)
8" (200) B3690-8 B335-2-1/2

Note: Refer to Note Q) on page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 13 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 15

SINGLE PIPE BRACING


PIPE CLAMP TRANSVERSE BRACING (Figure 3)

ATR Rod Stiffener


All Threaded Rod May Be Required
(See Page 57) (See Pages 57 & 58)

1 (Min.)

B-Line Channel 1
B3200 Series
Adjustable
Transverse Brace
(See page 11)
Weldless Eye Nut
Pipe Size Pipe Clamp * Hinge
in. (mm) Part No. Part No.
11/2" (40) B3144-11/2 B335-2-1/2
2" (50) B3144-2 B335-2-1/2
21/2" (65) B3144-21/2 B335-2-1/2 B335-2-Bolt Size
Adjustable Hinge
3" (80) B3144-3 B335-2-1/2
(See Page 59)
4" (100) B3144-4 B335-2-5/8
5" (125) B3144-5 B335-2-5/8
6" (150) B3144-6 B335-2-3/4
8" (200) B3144-8 B335-2-3/4 B3144 Series
10" (250) B3144-10 B335-2-3/4 Double Bolt Pipe Clamp
(See Page 65)
12" (300) B3144-12 B335-2-3/4

* See note D) on page 9 for clamp torque values. Note: Refer to Note Q) on page 10 for installations requiring insulated pipe.

PIPE ROLLER TRANSVERSE BRACING (Figure 4)


ATR
All Threaded Rod
(See Page 57 for
minimum diameter)

Rod Stiffener
Adjustable
(See Pages 57 & 58)
Pipe Size Pipe Roller Hinge
in. (mm) Part No. Part No.
21/2" (65) B3110-21/2 B335-2-1/2
3" (80) B3110-3 B335-2-1/2
31/2" (90) B3110-21/2 B335-2-1/2
1 (Min.) B-Line Channel 4" (100) B3110-4 B335-2-1/2
Transverse Brace 5" (125) B3110-5 B335-2-5/8
1 (See page 11) 6" (150) B3110-6 B335-2-3/4

B335-2-Bolt Size
Adjustable Hinge
(See Page 59)

B3110 Series
Adjustable Steel Yoke Pipe Roll
(See Page 66)
Note: Refer to Note Q) on page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 14 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 16

SINGLE PIPE BRACING


TRANSVERSE BRACING (Figure 5)

1 (Min.)
B2400 Series
Pipe Strap
1
(See Page 71)

B-Line Channel
Transverse Brace
(See page 11)
3” min.
(76mm)

Channel Nuts & Bolts Not Included (See Pages 61 & 62)

Notes: Install brace within 4" (101mm) of hanger. (Hanger not shown for clarity. See Figure 6 below)
Refer to Note Q) on page 10 for installations requiring insulated pipe

LONGITUDINAL BRACING (Figure 6)


Rod Stiffener May Be Required
(See Pages 63 & 64)

B335V-Bolt Size Pipe Adjustable Riser Adjustable


Adjustable Half Hinge Pipe Size Clamp* Half Hinge Clamp * Half Hinge
(See Page 59) in. (mm) Part No. Part No. Part No. Part No.
1" (25) B3140-1 B335V-1/2 B3373-1 B335V-1/2
11/4" (32) B3140-11/4 B335V-1/2 B3373-11/4 B335V-1/2
B-Line Channel 11/2" (40) B3140-11/2 B335V-1/2 B3373-11/2 B335V-1/2
Longitudinal Brace 2" (50) B3140-2 B335V-1/2 B3373-2 B335V-1/2
(See page 11) 21/2" (65) B3140-21/2 B335V-1/2 B3373-21/2 B335V-1/2
3" (80) B3140-3 B335V-1/2 B3373-3 B335V-1/2
31/2" (90) B3140-31/2 B335V-1/2 B3373-31/2 B335V-1/2
4" (100) B3140-4 B335V-5/8 B3373-4 B335V-1/2
5" (125) B3140-5 B335V-5/8 B3373-5 B335V-1/2
6" (150) B3140-6 B335V-3/4 B3373-6 B335V-1/2
Pipe 4” max. B3140 Pipe Clamp 8" (200) B3140-8 B335V-3/4 B3373-8 B335V-5/8
Hanger (101mm) or B3373 Riser Clamp
10" (250) -- -- B3373-10 B335V-5/8
or Series
Support (See Pages 67 & 69) 12" (300) -- -- B3373-12 B335V-5/8
* See note D) on page 9 for clamp torque values.
Notes: Install brace within 4" (101mm) of hanger.
Refer to Note Q) on page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 15 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 17

SINGLE PIPE BRACING - COPPER TUBING


CLEVIS HANGER TRANSVERSE BRACING (Figure 7)
ATR
All Threaded Rod
(See Page 57 for Copper Adjustable Pipe
minimum diameter) Tubing Size Clevis Hanger Hinge Sleeve
in. (mm) Part No. Part No. Part No.*
Rod Stiffener
1/2" (15) B3104CT-1/2 N/A N/A
(See Pages 57 & 58)
3/4" (20) B3104CT-3/4 N/A N/A
1 (Min.)
1" (25) B3104CT-1 B335-2-3/8 B3104CTPS-1
B-Line Channel
11/4" (32) B3104CT-11/4 B335-2-3/8 B3104CTPS-11/4
1 Transverse Brace
(See page 11) 11/2" (40) B3104CT-11/2 B335-2-3/8 B3104CTPS-11/2
2" (50) B3104CT-2 B335-2-3/8 B3104CTPS-2
21/2" (65) B3104CT-21/2 B335-2-3/8 B3104CTPS-21/2
B335-2-Bolt Size Adjustable Hinge 3" (80) B3104CT-3 B335-2-3/8 B3104CTPS-3
(See Page 59) 31/2" (90) B3104CT-31/2 B335-2-3/8 B3104CTPS-31/2
4" (100) B3104CT-4 B335-2-3/8 B3104CTPS-4
B3104CTPS Pipe Sleeve
* Not included when ordering standard B3104CT Series Clevis Hanger.
B3104CT Series Clevis Hanger
(See Page 68)

Notes: Pipe sleeve required over cross bolt of Clevis Hanger when using the brace connection shown above (Figure 7).
Refer to Note Q) on page 10 for installations requiring insulated pipe.

LONGITUDINAL BRACING (Figure 8)

Rod Stiffener May Be Required


(See Pages 57 & 58)

B335V-Bolt Size
Adjustable Half Hinge Copper Riser Adjustable
(See Page 59) Tubing Size Clamp * Half Hinge
in. (mm) Part No. Part No.
1" (25) B3373CT-1 B335V-1/2
B-Line Channel
11/4" (32) B3373CT-11/4 B335V-1/2
Longitudinal Brace
(See page 11) 11/2" (40) B3373CT-11/2 B335V-1/2
2" (50) B3373CT-2 B335V-1/2
21/2" (65) B3373CT-21/2 B335V-1/2
3" (80) B3373CT-3 B335V-1/2
31/2" (90) B3373CT-31/2 B335V-1/2
4" (100) B3373CT-4 B335V-1/2

Pipe Hanger B3373CT * See note D) on page 9 for clamp torque values.
or Support 4” max.
(101mm) Riser Clamp Series
(See Page 69)

Note: Install brace within 4" (101mm) of hanger.


Refer to Note Q) on page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 16 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 18

TRAPEZE BRACING
Trapeze Assembly Bracing
1). Layout piping and/or conduit runs and determine number, size and location of items to be supported by
the trapeze
2). Determine trapeze support spacing (LT). This is usually determined by the maximum support spacing of
the smallest pipe or conduit on the trapeze.
3). Select trapeze supports.
a). Determine the total vertical load (TL) for each trapeze.
TL = LT x WT
TL = Total vertical load for each trapeze support (lbs.)
LT = Trapeze support spacing (ft.)
WT = Weight of all piping, cable tray, ductwork, conduit, etc. in lbs./ft. supported by the trapeze
b). Determine length of trapeze, making sure sufficient length is added to attach the all threaded rod and
bracing attachments. All channel nuts shall be fully engaged within strut.
(13/16” (20mm) minimum distance from edge of strut to center line of bolt.)
c). Select type of trapeze member (B22, B22AMIG, etc.) by selecting a member with loading greater
than the total load (TL). See Table 4 on page 22 for strut loading data, noting that the trapeze beam
span is the distance between the hanger rods. Also determine whether the applied load is uniform or
concentrated, and follow notes on page 22 accordingly. Variations in pipe sizes (simular to concentrated
load assembly on page 22) shall be treated as a concentrated load, where as same sized pipes evenly
distributed across the span (similar to uniform load assembly on page 22) may be treated as a uniform
load. Uniform loads on page 22 are converted to a concentrated load by a 50% reduction. Do not
exceed the beam span length given by Table 4A on page 22, which limits overloading due to
longitudinal seismic force.
d). Determine hanger rod size from Appendix 2 based on total weight (WT) and trapeze support spacing
(LT). Rod sizes are given for trapeze supports with braces attached and unbraced trapezes.
e). Select a hanger rod connection to structure (pages 39 thru 56) that is greater than the hanger rod loads
listed in Appendix 2.
4). Select transverse and longitudinal bracing.
a). Select bracing detail from Figures 9 - 11.
b). Determine spacing of transverse / longitudinal bracing from Appendix 2 based on total weight (Wt)
and the trapeze support span (Lt). Note the corresponding structure attachment type (Roman numeral
I - V) for each possible brace interval. When supporting multiple pipe sizes, do not exceed the
maximum spacing for the smallest pipe as given in Appendix 1.
Verify that the specific forces do not exceed the capacity of the pipe clamps on pages 70 & 71.
c). Determine if rod stiffener is required (pages 57 & 58).
d). Engineer of record for a site specific project shall verify that the structure can support the
connection loads.
5). Review the design and revise layout where loads exceed the limitations of the hanger rods, strut trapeze
supports, or connection details.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 17 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 19

TRAPEZE BRACING
TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 9)

B-Line Channel
Longitudinal Brace ATR
B335-2-Bolt Size (See page 11)
Adjustable Hinge All Threaded Rod
(See Page 59) (See Page 57)

Rod Stiffener
(See Pages 57 & 58)
B2400
Series 1
Pipe Straps
(See Page 71) 1 (Min.)
B-Line Channel
Transverse Brace B-Line Channel
(See page 11)
Transverse Brace
(See page 11)

B335-2-1/2 Adjustable Hinge B335-2-1/2 Adjustable Hinge


Transverse Brace Longitudinal Brace
(See Page 59) Hex Nut & (See Page 59)
Square Washer
B-Line Channel - Size as Required
B2000 Series (See Page 62)
(See Page 22 - Table 4 & 4A For
Channel Load Data) Pipe Straps
See Note 3b (See Page 70)
on page 17

Notes:

1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent
to the all thread rod, or attached to the all thread rod itself.

2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod.

3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt
or all thread rod.

4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze
support. Either set of braces may be removed to form a longitudinal brace only or a transverse
brace only if desired.

5). Longitudinal braces, when needed, must be installed at both ends of trapeze.

6). The equipment shown on this trapeze support is generic in nature. Any number of pipes,
conduits, ductwork or cable tray may be supported following the system weight and support
spans listed in Appendix 2 - Table 1.

7). Torque all nuts per Note D, page 9.

8). Refer to note Q, page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 18 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 20

TRAPEZE BRACING
TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 10)
B-Line Channel
Longitudinal Brace
(See page 11) ATR
B335-2-Bolt Size
Adjustable Hinge All Threaded Rod
(See Page 59) (See Page 57)

Rod Stiffener
(See Pages 57 & 58)

Cable Tray 1 (Min.)


B-Line Channel
Transverse Brace
(See page 11) B-Line Channel
Transverse Brace
(See page 11)

B335-2-1/2 Adjustable Hinge B335-2-1/2 Adjustable Hinge


Transverse Brace Longitudinal Brace
(See Page 59) Hex Nut &
(See Page 59)
Square Washer
B-Line Channel - Size as Required (See Page 62)
(See Page 22 - Table 4 & 4A For B2000 Series Pipe Straps
Channel Load Data) (See Page 70)

See Note 3b B2400 Series


on page 17
Pipe Straps
(See Page 71)

Notes:

1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent
to the all thread rod, or attached to the all thread rod itself.

2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod.

3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt
or all thread rod.

4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze
support. Either set of braces may be removed to form a longitudinal brace only or a transverse
brace only if desired.

5). Longitudinal braces, when needed, must be installed at both ends of trapeze.

6). The equipment shown on this trapeze support is generic in nature. Any number of pipes,
conduits, ductwork or cable tray may be supported following the system weight and support
spans listed in Appendix 2 - Table 1.

7). Torque all nuts per Note D, page 9.

8). Refer to note Q, page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 19 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 21

TRAPEZE BRACING
TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 11)
B-Line Channel
Longitudinal Brace
(See page 11) ATR
All Threaded Rod
(See Page 57)

Rod Stiffener
(See Pages 57 & 58) B2400 1
Series
Pipe Straps
1 (Min.)
(See Page 71)

B-Line Channel
Transverse Brace
(See page 11)
B-Line Channel -
Size as Required
(See Page 22 -
Table 4 & 4A For
Channel Load Data) B335-2-1/2 Adjustable Hinge
Longitudinal Brace
Hex Nut & (See Page 59)
B2000 Series Square Washer
(See Page 62)
Pipe Straps
See Note 3b (See Page 70)
on page 17

Notes:

1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent
to the all thread rod, or attached to the all thread rod itself.

2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod.

3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt
or all thread rod.

4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze
support. Either set of braces may be removed to form a longitudinal brace only or a transverse
brace only if desired.

5). Longitudinal braces, when needed, must be installed at both ends of trapeze.

6). The equipment shown on this trapeze support is generic in nature. Any number of pipes,
conduits, ductwork or cable tray may be supported following the system weight and support
spans listed in Appendix 2 - Table 2.

7). Torque all nuts per Note D, page 9.

8). Refer to note Q, page 10 for installations requiring insulated pipe.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 20 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 22

APPROVED COMPONENTS
Seismic Approvals: Trapeze Hanger, Longitudinal Brace, Transverse Brace, Threaded Stiffener

Single Channel “A” Channel


15/8" Y
(41mm)
3/8" 3/8"
7/8"
(9mm) (9mm) ‘Hx’
(22mm)

9/32"
Y (7mm) ‘H’
X X
‘H’
X X
‘Hx’
Notes: Y
Standard Lengths: 10 ft. (3.05 m) Y
13/16" 13/16"
& 20 ft. (6.09 m) (20mm) (20mm)
Finishes: Plain, Dura-Green
15/8"
Epoxy, and Pre-Galvanized
(41mm)

Height Dimensions
Channel ‘H’ ‘Hx” B_ _SH
in. (mm) in. (mm)
9/16" (14mm)
x 7/8" (22mm) slots
B54 13/16” (20) 0.3422 (8.7)
13/16” 2" (51mm) on centers.
B52 (20) 0.3366 (8.5)
1" (25mm) from end of channel to center of first slot.
B42 1” (25) 0.4226 (10.7)
B32 13/8” (35) 0.6052 (15.4)
B24 15/8” (41) 0.7304 (18.5)
B22 15/8” (41) 0.7189 (18.2) B_ _SHA
B22A 31/4” (82) 1.6250 (41.3)
9/16" (14mm) x 7/8" (22mm) slots 2" (51mm) on centers.
B12 27/16” (62) 1.1127 (28.2)
B12A 47/8” (124) 2.4375 (61.9)
1" (25mm) from end of channel to center of first slot.
B11 31/4” (82) 1.5112 (38.4) All B12SHA & B11SHA channels are mig welded.
B11A 61/2” (165) 3.2500 (82.5)

Table 3
SECTION PROPERTIES X -X Axis Y - Y Axis
Areas of Moment of Section Radius of Moment of Section Radius of
Channel Weight Section Inertia (I) Modulus (S) Gyration (R) Inertia (I) Modulus (S) Gyration (R)
lbs./ft. kg/m in.2 (cm2) in.4 (cm4) in.3 (cm3) in. (cm) in.4 (cm4) in.3 (cm3) in. (cm)

B54 1.01 (1.51) .299 (1.93) .0263 (1.09) .0560 (0.92) .297 (0.75) .1106 (4.60) .1361 (2.23) .608 (1.55)
B52 1.31 (1.95) .386 (2.49) .0320 (1.33) .0673 (1.10) .288 (0.73) .1404 (5.84) .1728 (2.83) .603 (1.53)
B42 1.47 (2.18) .432 (2.79) .0554 (2.31) .0968 (1.59) .358 (0.91) .1645 (6.85) .2025 (3.32) .617 (1.57)
B32 1.73 (2.58) .510 (3.29) .1252 (5.21) .1626 (2.67) .496 (1.26) .2098 (8.73) .2582 (4.23) .642 (1.63)
B24 1.44 (2.15) .424 (2.74) .1494 (6.22) .1670 (2.74) .594 (1.51) .1857 (7.73) .2286 (3.75) .662 (1.68)
B22 1.90 (2.83) .559 (3.61) .1850 (7.70) .2042 (3.34) .580 (1.47) .2340 (9.74) .2880 (4.72) .653 (1.66)
B22A 3.80 (5.65) 1.118 (7.21) .9379 (39.04) .5772 (9.46) .924 (2.34) .4681 (19.48) .5761 (9.44) .653 (1.66)
B12 2.47 (3.67) .727 (4.69) .5203 (21.65) .3927 (6.43) .852 (2.16) .3306 (13.76) .4068 (6.66) .679 (1.72)
B12A 4.94 (7.35) 1.453 (9.37) 2.8132 (117.09) 1.1541 (18.91) 1.402 (3.56) .6611 (27.52) .8137 (13.33) .679 (1.72)
B11 3.05 (4.54) .897 (5.79) 1.0917 (45.44) .6278 (10.29) 1.112 (2.82) .4271 (17.78) .5256 (8.61) .696 (1.77)
B11A 6.10 (9.08) 1.794 (11.59) 6.2139 (258.64) 1.9120 (31.33) 1.876 (4.76) .8542 (35.55) 1.0513 (17.23) .696 (1.77)

Calculations of section properties are based on metal thicknesses as determined by the AISI Cold-Formed Steel Design Manual.
For channel loading see page 22.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 21 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 23

TRAPEZE BRACING
Typical Trapeze

ATR ATR

Beam Span (BS)


Beam Span (BS)
B-Line Channel
(See below)

Uniform Load Concentrated Load

Table 4

Channel Type & Uniform Beam Load Rating

Beam Span B22SH B22 B22A B12 B12A* B11 B11A*


(BS)
in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN)

12" (305) 2553 (11.35) 2837 (12.62) 8165 (36.32) 5498 (24.45) 3259 (14.49) 4395 (19.54) 4309 (19.16)
24" (610) 1276 (5.68) 1418 (6.31) 4083 (18.16) 2750 (12.23) 3259 (14.49) 4395 (19.54) 4309 (19.16)
36" (914) 851 (3.78) 946 (4.21) 2722 (12.11) 1833 (8.15) 3259 (14.49) 2930 (13.03) 4309 (19.16)
48" (1219) 638 (2.84) 709 (3.15) 2042 (9.08) 1374 (6.11) 3259 (14.49) 2197 (9.77) 4309 (19.16)
60" (1524) 511 (2.27) 568 (2.52) 1633 (7.26) 1100 (4.89) 3231 (14.37) 1758 (7.82) 4309 (19.16)
72" (1829) 426 (1.89) 473 (2.10) 1361 (6.05) 916 (4.07) 2693 (11.98) 1465 (6.51) 4309 (19.16)
84" (2133) 365 (1.62) 405 (1.80) 1167 (5.19) 785 (3.49) 2308 (10.26) 1256 (5.58) 3824 (17.01)
96" (2438) 319 (1.42) 354 (1.57) 1021 (4.54) 687 (3.05) 2019 (8.98) 1011 (4.49) 3346 (14.88)
108" (2743) 284 (1.26) 315 (1.40) 908 (4.04) 611 (2.72) 1795 (7.98) 977 (4.34) 2974 (13.23)
120" (3048) 255 (1.13) 283 (1.26) 817 (3.63) 550 (2.44) 1616 (7.19) 879 (3.91) 2677 (11.91)

• Loads shown in chart have a safety factor of 2.


• Based on uniformly loaded simple span with adequate lateral bracing using an allowable stress of 21,000 psi (144.7 MPa).
• To determine concentrated load capacity at mid-span, multiply the uniform load by 0.5.
• Refer to note 3c) on page 17 for uniform and concentrated load requirements.
• Use 90% of the solid channel loads for corresponding SH and SHA channels.
• Refer to note Q) on page 10 for installations requiring insulated pipe.
* These back to back channels are mig welded.

Table 4A
Structure Channel type and maximum beam span for
Connection longitudinal beam loading
Type B22SH B22 B22A B12 B12A* B11 B11A*
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)

I 176 (4470) 196 (4978) 391 (9931) 276 (7010) 552 (14021) 357 (9068) 714 (18135)
II 103 (2616) 114 (2895) 228 (5791) 161 (4089) 322 (8179) 208 (5283) 416 (10566)
III 68 (1727) 76 (1930) 152 (3861) 107 (2718) 215 (5461) 139 (3530) 278 (7061)
IV 46 (1168) 51 (1295) 101 (2565) 72 (1829) 143 (3632) 93 (2362) 185 (4699)
V 32 (813) 35 (889) 70 (1778) 50 (1270) 99 (2514) 64 (1625) 128 (3251)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 22 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 24

STRUCTURAL ATTACHMENTS
Brace Structural Attachment Selection Procedure
1) Determine structure to be attached to from the following:
A) Concrete
B) Wood Beam
C) Structural Steel
2) Reference structure connection type from Appendix 1 & 2.
3) Choose appropriate structural detail that meets structure connection type. (I, II, III, IV or V) pages 24
thru 38.
4) Determine anchor size. On concrete structure attachments, calculate minimum embedment and minimum
distance between anchors.
General Notes For Concrete Attachments
1) The “minimum embedment” values given on pages 24 - 30 provide the anchor capacity to reach the
design loads shown, but may be considered by the 1997 UBC to be “shallow” anchors (embedment less
that 8 times the anchor diameter). Using “shallow” anchors may increase the design seismic force,
depending on the building code used. As an alternative, consider using the following values to avoid
“shallow anchor” issues:
Anchor Bolt Dia.“8x” Embedment
3/8” 3” (76mm)
1/2” 4” (101mm)
5/8” 5” (127mm)
3/4” 6” (152mm)
2) Size and number of expansion anchors is based on "without special inspection" values given in ICBO
(International Conference of Building Officials) Report No. 4627 dated February 1, 2001, Hilti Kwik Bolt
- II Carbon Steel Allowable Tension and Shear Values.
3) Other anchors may be used providing they are listed in an ICBO ES Evaluation Report, which was tested
in accordance with AC01, including the seismic qualification tests of AC01 Section 5.6. These values
must meet or exceed the values provided in ICBO Report No. 4627, and must be approved by the
structural engineer of record. OSHPD change order is required for California hospitals.
4) For California Essential Facilities, 50% of the expansion type anchor (alternate anchors in a group) shall
be proof tested per Appendix 3. Other projects may have similar requirements, check local codes and
ordinances.
5) Cast in place concrete anchors require special inspection as indicated in the building code for the local
jurisdiction.
6) When slab thickness is less than the minimum allowable, but in excess of the minimum anchor
embedment, a thru bolt approach may be used if approved by the site engineer.
7) When installing drill-in anchors in existing non-prestressed reinforced concrete, use care and caution to
avoid cutting or damaging the existing reinforcing bars. When installing them into existing prestressed
concrete (pre-or post-tensioned), locate the prestressed tendons by using a non-destructive method prior
to installation. Exercise extreme care and caution to avoid cutting or damaging the tendons during
installation. Maintain a minimum clearance of 1 inch (25mm) between the reinforcement and the drilled-in
anchor.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 23 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 25

STRUCTURAL ATTACHMENTS
Concrete Attachments
‘T’
‘F’ Expansion anchors of Detail 1
diameter 'D'. Slab
Minimum embedment 1/2" x 11/4" Hex Head
of anchor in Cap Screws & N225WO Nuts
concrete is 'E'. (See Pages 61 & 62)

Normal Weight Concrete B-Line Channel


Longitudinal or
B-Line Adjustable Hinge 1
Transverse Brace
Longitudinal or Transverse Brace
1 min.
(See Page 59)
Load

Expansion anchors of
Detail 2 diameter 'D'. ‘T’
Metal Deck

‘E’
Light Weight or 1/2" x 11/4" Hex Head
Normal Weight Concrete ‘F’ Cap Screws & N225WO Nuts
B-Line Adjustable Hinge (See Pages 61 & 62)
Longitudinal or Transverse Brace B-Line Channel
(See Page 59) Longitudinal or
1
Transverse Brace
1 min. Load

Light Weight or Normal Weight Concrete Metal Deck


Minimum Minimum Minimum Distance Minimum
Structure Anchor* Embedment of Distance From Edge To Concrete
Connection Load Bolt Anchor in Between Center of Bolt Coverage
Type Dia. 'D' Concrete 'E' ** Anchors ‘F’ ‘T’
lbs. (kN) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)

I 175 (0.78) 3/8" (9.5) 21/4" (57.1) 62/3" (169.3) 61/2" (165.1) 3/4" (19)
II, III 450 (2.00) 5/8" (15.9) 41/2" (114.3) 102/3" (270.9) 11" (279.4) 13/8" (35)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum light weight concrete. ** See important notes on page 23.

Normal Weight Concrete


Minimum Minimum Minimum Distance Minimum
Structure Anchor* Embedment of Distance From Edge To Concrete
Connection Load Bolt Anchor in Between Center of Bolt Coverage
Type Dia. 'D' Concrete 'E' ** Anchors ‘F’ ‘T’
lbs. (kN) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)

I, II 300 (1.33) 3/8" (9) 21/2" (63) 5" (127) 47/8" (124) 3/4" (19)
III 450 (2.00) 1/2" (13) 31/2" (89) 7" (178) 63/4" (171) 11/16" (27)
IV 675 (3.00) 5/8" (16) 4" (101) 8" (203) 81/4" (209) 13/8" (35)
V 975 (4.33) 3/4" (19) 43/4" (120) 91/2" (241) 93/4" (247) 17/16" (36)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum normal weight concrete. ** See important notes on page 23.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 24 of
Structural Engineer S 3913
**SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 26

STRUCTURAL ATTACHMENTS
Concrete Attachments
Detail 3
Slab

‘T’ 'F' ‘X’

Expansion anchors of
diameter 'D'.

Minimum B202 Square Washer Equal Equal B22 Channel


embedment (See Page 62) Distance Distance 15/8" x 15/8"
(41mm) (41mm)

of anchor in
concrete is 'E'. B202 Square Washer
1/2"x 11/4" (41mm) Hex Head
& Hex Nut
(See Page 62) Cap Screws & N225WO Nuts
(See Pages 61 & 62)

B-Line Adjustable Hinge 1


(See Page 59)
1 min.

B-Line Channel
Longitudinal or
Transverse Brace Load

Minimum Minimum Distance Minimum


Structure Anchor* Minimum Distance From Edge To Concrete
Connection Load Bolt Embedment Between Anchors Center of Bolt Coverage
Type Dia. 'D' 'E' ** ‘X’ ‘F’ ‘T’
lbs. (kN) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)

I, II, III, IV 675 (3.00) 3/8" (9) 21/2" (63) 5" (127) 47/8" (124) 3/4" (19)
V 975 (4.33) 1/2" (13) 31/2" (89) 7" (178) 63/4" (171) 11/16" (27)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 23.
Note: 24” (609mm) maximum distance between anchors.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 25 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 1

STRUCTURAL ATTACHMENTS
Concrete Attachments
Detail 4
Metal Deck

'F'

‘X’
‘T’

Expansion anchors
of diameter 'D'.
E
B22 Channel
15/8" (41mm) x 15/8" (41mm) Equal Equal B202 Square Washer
Distance Distance (See Page 62)

1/2" x 11/4" (32mm) Hex Head


B202 Square Washer Cap Screws & N225WO Nuts
& Hex Nut B-Line Adjustable Hinge (See Pages 61 & 62)
(See Page 62)
Longitudinal or Transverse 1
Brace 1 min.
(See Page 59)

B-Line Channel
Longitudinal or
Transverse Brace
Load

Light Weight or Normal Weight Concrete Metal Deck

Minimum Minimum Distance Minimum


Structure Anchor* Minimum Distance From Edge To Concrete
Connection Load Bolt Embedment Between Anchors Center of Bolt Coverage
Type Dia. 'D' 'E' ** ‘X’ ‘F’ ‘T’
lbs. (kN) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)

I, II, III 450 (2.00) 3/8" (9) 21/4" (57) 62/3" (169) 61/2" (165) 3/4" (19)
IV, V 975 (4.33) 5/8" (16) 41/2" (114) 102/3" (271) 11" (279) 13/8" (35)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum light weight or normal weight concrete.
** See important notes on page 23.
Note: 24” (609mm) maximum distance between anchors.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 26 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 2

STRUCTURAL ATTACHMENTS
Concrete Attachments

Detail 5
Slab

B2501 cast in place anchors


of diameter 'D'.
(See Page 75)

Minimum distance from


edge of concrete to center
of bolt is (10 x 'D').

Minimum embedment
1” in concrete.
(25mm)
min. 'E'.

B-Line Adjustable Hinge 1/2" x 11/4" Hex Head


1
Longitudinal or Transverse Brace Cap Screws & N225WO Nuts
(See Page 59) 1 min. (See Pages 61 & 62)

B-Line Channel
Longitudinal or
Transverse Brace Load

Minimum
Structure Cast In Place Minimum Distance
Connection Load Anchor* Embedment Between
Type Dia. 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm) in. (mm)

I, II, III 450 (2.00) 3/8" (9) 3" (76) 41/2" (114)

IV, V 975 (4.33) 1/2" (13) 4" (101) 6" (152)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum normal weight concrete.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 27 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 3

STRUCTURAL ATTACHMENTS
Concrete Attachments
Detail 6
Metal Deck
Minimum distance from
edge of concrete to center
of bolt is (10 x 'D'). B2501 cast in place anchors of
diameter 'D'.
(See Page 75)

1” E
(25mm)
min.

B-Line Adjustable Hinge


1/2" x 11/4" Hex Head
Longitudinal or Transverse 1
Brace Cap Screws & N225WO Nuts
(See Page 59) 1 min. (See Pages 61 & 62)

B-Line Channel
Longitudinal or
Transverse Brace Load

Light Weight Concrete


Minimum
Structure Cast In Place Minimum Distance
Connection Load Anchor* Embedment Between
Type Dia. 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm) in. (mm)

I 175 (0.78) 3/8" (9) 3" (76) 41/2" (114)

II 300 (1.33) 1/2" (13) 4" (101) 6" (152)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum light weight concrete.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

Normal Weight Concrete


Minimum
Structure Cast In Place Minimum Distance
Connection Load Anchor* Embedment Between
Type Dia. 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm) in. (mm)

I, II 300 (1.33) 3/8" (9) 3" (76) 41/2" (114)

I, II 300 (1.33) 1/2" (13) 4" (101) 6" (152)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum normal weight concrete.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 28 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 4

STRUCTURAL ATTACHMENTS
Concrete Attachments

Detail 7
Minimum distance from Slab
edge of concrete to center
of bolt is (10 x 'D').

‘X’

1” B2501 cast in place anchors


(25mm)
of diameter 'D'.
min.
(See Page 75)

Minimum embedment
of anchor in concrete.
'E'.

B202 Square Washer


(See Page 62) Equal Equal
Distance Distance
B22 Channel
15/8" x 15/8"
(41mm) (41mm)

1/2" x 11/4" Hex Head


Cap Screws &
B202 Square Washer 1 N225WO Nuts
& Hex Nut (See Pages 61 & 62)
(See Page 62)
1 min.
B-Line Adjustable Hinge
Longitudinal or Transverse Brace
(See Page 59)

B-Line Channel
Longitudinal or
Transverse Brace Load

Minimum
Structure Cast In Place Minimum Distance
Connection Load Anchor* Embedment Between
Type Dia. 'D' 'E' Anchors ‘X’
lbs. (kN) in. (mm) in. (mm) in. (mm)

I, II, III, IV, V 975 (4.33) 3/8" (9) 3" (76) 41/2" (114)

I, II, III, IV, V 975 (4.33) 1/2" (13) 4" (101) 6" (152)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum normal weight concrete.
Notes: 24” (609mm) maximum distance between anchors.
Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 29 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 5

STRUCTURAL ATTACHMENTS
Concrete Attachments
Minimum distance
from edge of concrete to Detail 8
center of bolt Metal Deck
is (10 x 'D').

‘X’

1”
(25mm)
min.

E
B2501 cast in place
anchors of diameter 'D'.
(See Page 75) Equal Equal B202 Square Washer
Distance Distance (See Page 62)
B22 Channel
B202 Square Washer 15/8" (41mm) x 15/8" (41mm)
& Hex Nut 1/2" x 11/4" Hex Head
(See Page 62)
B-Line Adjustable Hinge Cap Screws & N225WO Nuts
Longitudinal or Transverse Brace 1 (See Pages 61 & 62)
(See Page 59)
1 min.

B-Line Channel
Longitudinal or
Transverse Brace
Load
Light Weight Weight Concrete
Structure Cast In Place Minimum Min. Distance
Connection Load Anchor* Embedment Between
Type Dia. 'D' 'E' Anchors ‘X’
lbs. (kN) in. (mm) in. (mm) in. (mm)

I, II, III 450 (2.00) 3/8" (9) 3" (76) 41/2" (114)

I, II, III 450 (2.00) 1/2" (13) 4" (101) 6" (152)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum light weight concrete.
Notes: 24” (609mm) maximum distance between anchors.
Pre-cast anchors must be accurately secured prior to pouring concrete.

Normal Weight Concrete


Structure Cast In Place Minimum Min. Distance
Connection Load Anchor* Embedment Between
Type Dia. 'D' 'E' Anchors ‘X’
lbs. (kN) in. (mm) in. (mm) in. (mm)

I, II, III, IV 675 (3.00) 3/8" (9) 3" (76) 41/2" (114)

I, II, III, IV 675 (3.00) 1/2" (13) 4" (101) 6" (152)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum normal weight concrete.
Notes: 24” (609mm) maximum distance between anchors.
Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 30 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 6

STRUCTURAL ATTACHMENTS
Concrete Attachments

Detail 9
Slab

Minimum distance from B2500 Spot Insert with


edge of concrete to center N2500 Square Nut of
of bolt is (10 x 'D'). thread size 'D'.
(See Page 76)

1”
(25mm)
min.
Minimum embedment
in concrete 'E'.

B200 Series Square Washer


(See Page 62)

1/2" x 11/4" Hex Head


B-Line Adjustable Hinge
Longitudinal or Transverse Brace 1 Cap Screws & N225WO Nuts
(See Pages 61 & 62)
(See Page 59)

1 min.

B-Line Channel
Longitudinal or
Transverse Brace Load

Minimum
Structure Thread Minimum Distance
Connection Load Size Embedment Between
Type 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm)

I 175 (0.78) 1/2"-13, 5/8"-11, 3/4"-10, 7/8"-9 19/16" (40) 6" (152)

* B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 31 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 7

STRUCTURAL ATTACHMENTS
Concrete Attachments

Minimum distance from B2500 Spot Insert with


edge of concrete to center N2500 Square Nut of thread Detail 10
of bolt is (10 x 'D'). size 'D'. Metal Deck
(See Page 76)
1”
(25mm)
min.

B200 Series Square Washer


(See Page 62)
1/2" x 11/4" Hex Head
B-Line Adjustable Hinge Cap Screws & N225WO Nuts
Longitudinal or Transverse 1
(See Pages 61 & 62)
Brace
(See Page 59) 1 min.
B-Line Channel
Longitudinal or Load
Transverse Brace

Normal Weight Concrete

Minimum
Structure Thread Minimum Distance
Connection Load Size Embedment Between
Type 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm)

I 175 (0.78) 1/2"-13, 5/8"-11, 3/4"-10, 7/8"-9 19/16" (40) 6" (152)

* B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 32 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 8

STRUCTURAL ATTACHMENTS
Concrete Attachments

Detail 11

“L”

B32I-8 or Stronger Concrete Insert


Attached to Concrete Structure
(See Pages 77 & 78)

B633-1/2, B634, Reduce loads by 50% when


B335-2-1/2 or B650-1/2 Adjustable Hinge is mounted within
Adjustable Hinge 2” (51mm) from the end of the insert.
(See Pages 59 & 60)

Use 1/2” diameter bolts and


1/2” channel nuts

B-Line Channel
(Longitudinal or Transverse Brace)

Load

Minimum
Structure Allowable Insert
Connection Load Length
Type “L”
lbs. (kN) in. (mm)

I,II,III,IV,V 975 (4.33) 8" (203)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 33 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 9

STRUCTURAL ATTACHMENTS
Wood Beam Attachments
(Used for Bracing Perpendicular)
Detail 12

B3248-2 x 2 x 1/4 (min.)


Series Square Washer & Wood Beam
Hex Nut Thickness
(See Pages 62 & 74)

Thru bolt of diameter “D”.

Must be above the


neutral axis of wood Adjustable Hinge
(See Page 59)
beam and a minimum
of (4 x ‘D’) from top and
bottom of the beam.
1/2" x 11/4" Hex Head
Cap Screws &
N225WO Nuts
(See Pages 61 & 62)

B-Line Channel
Longitudinal or
Transverse Brace
1
Load

1 min.

11/2” (38mm) 31/2” (89mm)


Structure Allowable Minimum Beam Minimum Beam
Connection Load * Thickness Thickness
Type Bolt Dia ‘D’ Bolt Dia ‘D’
lbs. (kN) in. (mm) in. (mm)

I 175 (0.78) 1/2" (13) 1/2" (13)


II 300 (1.33) 1/2" (13) 1/2" (13)
III 450 (2.00) 3/4" (19) 1/2" (13)
IV 675 (3.00) -- -- 5/8" (16)
V 975 (4.33) -- -- 3/4" (19)

* Based on douglas fir with .51 specific gravity or greater.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 34 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 10

STRUCTURAL ATTACHMENTS

Wood Beam Attachments

(Used for Bracing Perpendicular)


Detail 13

31/2" Min.
Wood Beam
Thickness

Lag Bolt of diameter “D” with


4 x ‘D’ 3” (76.2mm) minimum embedment
minimum

4 x ‘D’ Adjustable Hinge


minimum
(See Page 59)

1/2" x 11/4" Hex Head


Cap Screws &
N225WO Nuts
(See Pages 61 & 62)

B-Line Channel
Longitudinal or
Transverse Brace
1
Load

1 min.

Structure Allowable
Lag Bolt
Connection Load *
Dia ‘D’
Type
lbs. (kN) in. (mm)

I 175 (0.78) 1/2" (13)

* Based on douglas fir with .51 specific gravity or greater.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 35 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 11

STRUCTURAL ATTACHMENTS
Wood Beam Attachments
Detail 14

Used where brace runs parallel to wood beam or where double bolts are required.

Bolt of diameter ‘D’ through wood with


B3248-2x2x1/4 (minimum) series
Square Washer & Hex Nut
(See Pages 62 & 74)

B3060SW Series
(See Page 73)

Angle must be attached to


wood beam above the neutral
1/2" x 11/4" (32mm) axis at a minimum of (4 x ‘D’)
Hex Head Cap Screw from the top and bottom of
with Lock Washer the beam.
& Hex Nut
(See Pages 61 & 62)

1/2" x 11/4" Hex Head


Cap Screws &
N225WO Nuts
Adjustable Hinge (See Pages 61 & 62)
(See Page 59) 1

1 min. B-Line Channel


Longitudinal or Transverse Brace

Load

11/2” (38mm) 31/2” (89mm)


Structure Allowable Minimum Beam Minimum Beam
Connection Load * Thickness Thickness
Type Bolt Dia ‘D’ Bolt Dia ‘D’
lbs. (kN) in. (mm) in. (mm)

I 175 (0.78) 1/2" (13) 1/2" (13)


II 300 (1.33) 5/8" (16) 1/2" (13)
III 450 (2.00) 3/4" (19) 5/8" (16)
IV 675 (3.00) 1" (25) 5/8" (16)

* Based on douglas fir with .51 specific gravity or greater.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 36 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 12

STRUCTURAL ATTACHMENTS

Wood Beam Attachments


Detail 15

Used where brace runs parallel to wood beam or where double bolts are required.
Minimum beam thickness of 31/2” (88.9mm) required.

Lag bolts of diameter ‘D’ with


3” (76.2mm) embedment (min.)

B3060SW Series
(See Page 73)

Angle must be attached to


wood beam above the neutral
1/2" x 11/4" (32mm) axis at a minimum of (4 x ‘D’)
Hex Head Cap Screw from the top and bottom of
with Lock Washer the beam.
& Hex Nut
(See Page 62)

1/2" x 11/4" Hex Head


Cap Screws &
N225WO Nuts
Adjustable Hinge (See Pages 61 & 62)
(See Page 59) 1

1 min. B-Line Channel


Longitudinal or Transverse Brace

Load

Structure Allowable Lag Bolt


Connection Load * Dia ‘D’
Type
lbs. (kN) in. (mm)

I 175 (0.78) 1/2" (12)

* Based on douglas fir with .51 specific gravity or greater.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 37 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 13

STRUCTURAL ATTACHMENTS
Structural Steel
Detail 16
Case 1 Case 2

Bolt Diameter 'D'


ASTM A307 or Better

B-Line B3234
Bevel Washer Lock Washer
When Required Required
B-Line Adjustable Hinge
(See Page 59)

B-Line Adjustable Hinge B-Line Adjustable Hinge


(See Page 59) (See Page 59)

B3248
Case 3 1/4” (6mm) thick Case 4
sized to fit joist

B-Line Adjustable Hinge


(See Page 59)

B-Line Adjustable Hinge


(See Page 59)

Structure Allowable Bolt Diameter


Connection Load ‘D’
Type
lbs. (kN) in. (mm)

I, II, III 450 (2.00) 3/8" (9)

IV, V 975 (4.33) 1/2" (12)

* See Note M) on page 10.


Note: Due to induced torsional load, the structural members in Case 1 & 2 must be
verified by structural site engineer for adequate strength.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 38 of
Structural Engineer S 3913
**SRS2002-OSpg.26-39 (11/02) N 1/3/03 4:43 PM Page 14

HANGER ROD ATTACHMENTS

Hanger Rod Structure Attachments

Selection Procedure
1) Determine structure type to attach hanger rod
A) Concrete
B) Wood Beam
C) Structural Steel

2) Reference rod size and hanger rod load from Appendix 1 & 2.

3) Select a hanger rod attachment detail with a load capacity that meets the hanger rod load

General Notes For Concrete Attachments


1) The “minimum embedment” values given on pages 40 - 43 provide the anchor capacity to reach the design loads
shown, but may be considered by the 1997 UBC to be “shallow” anchors (embedment less that 8 times the anchor
diameter). Using “shallow” anchors may increase the design seismic force, depending on the building code used.
As an alternative, consider using the following values to avoid “shallow anchor” issues:
Anchor Bolt Dia. “8x” Embedment
3/8” 3” (76mm)
1/2” 4” (101mm)
5/8” 5” (127mm)
3/4” 6” (152mm)

2) Size and number of expansion anchors is based on "without special inspection" values given in ICBO (International
Conference of Building Officials) Report No. 4627 dated February 1, 2001, Hilti Kwik Bolt - II Carbon Steel
Allowable Tension and Shear Values.

3) Other anchors may be used providing they are listed in an ICBO ES Evaluation Report, which was tested in
accordance with AC01, including the seismic qualification tests of AC01 Section 5.6. These values must meet or
exceed the values provided in ICBO Report No. 4627, and are approved by the structural engineer of record.
OSHPD change order is required for California hospitals.

4) For California hospitals and schools, 50% of the expansion type anchor (alternate anchors in a group) shall be
proof tested per Appendix 3. Other projects may have similar requirements, check local codes and ordinances.

5) Cast in place concrete anchors require special inspection as indicated in the building code for the local
jurisdiction.

6) When slab thickness is less than the minimum allowable, but in excess of the minimum anchor embedment, a thru
bolt approach may be used if approved by the site engineer.

7) When installing drill-in anchors in existing non-prestressed reinforced concrete, use care and caution to avoid
cutting or damaging the existing reinforcing bars. When installing them into existing prestressed concrete (pre-or
post-tensioned), locate the prestressed tendons by using a non-destructive method prior to installation. Exercise
extreme care and caution to avoid cutting or damaging the tendons during installation. Maintain a minimum
clearance of 1 inch (25mm) between the reinforcement and the drilled-in anchor.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 39 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:12 PM Page 1

HANGER ROD ATTACHMENTS


Concrete Attachments To Slab

Minimum distance from edge of concrete


to center of bolt is (12 x 'D').
Expansion anchors
of diameter 'D'.

‘T’

Minimum embedment of
anchor in concrete is 'E'.

Rod Coupler, Hex Nut


& B200 Series Square Washer
(See Page 62)

All Threaded Rod


(See Page 57)

Load

Allowable Minimum Minimum


Diameter Load ** Embedment Concrete
'D' (In Tension) 'E' Coverage ‘T’
in. (mm) lbs. (kN) in. (mm) in. (mm)

3/8" (9) 605 (2.69) 21/2" (63) 3/4" (19)


1/2" (13) 1000 (4.45) 31/2" (89) 11/16" (27)
5/8" (16) 1335 (5.94) 4" (101) 13/8" (35)
3/4" (19) 1940 (8.63) 43/4" (120) 17/16" (36)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be
used when seismic bracing is not required.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 40 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 2

HANGER ROD ATTACHMENTS


Concrete Attachments

Minimum distance from edge of To Metal Deck


concrete to center of expansion
anchor is (10 x 'D').
1" (25mm) Min.

‘T’

Expansion anchors
of diameter 'D'.
Rod Coupler, Hex Nut
& B200 Series Square Washer
All Threaded Rod (See Page 62)
(See Page 57) Load

Light Weight Concrete

Allowable Minimum Minimum


Diameter Load ** Embedment Concrete
'D' (In Tension) 'E' Coverage ‘T’
in. (mm) lbs. (kN) in. (mm) in. (mm)

3/8" (9) 395 (1.75) 21/4" (57.1) 3/4" (19)


1/2" (13) 440 (1.96) 21/4" (57.1) 11/16" (27)
5/8" (16) 835 (3.71) 41/2" (114.3) 13/8" (35)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum light weight concrete.
** See important notes on page 39.

Normal Weight Concrete

Allowable Minimum Minimum


Diameter Load ** Embedment Concrete
'D' (In Tension) 'E' Coverage ‘T’
in. (mm) lbs. (kN) in. (mm) in. (mm)

3/8" (9) 605 (2.69) 21/2" (63.5) 3/4" (19)


1/2" (13) 1000 (4.45) 31/2" (88.9) 11/16" (27)
5/8" (16) 1335 (5.94) 4" (101.6) 13/8" (35)
3/4" (19) 1940 (8.63) 43/4" (120.6) 17/16" (36)

* Hilti Kwik Bolt II in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used
when seismic bracing is not required.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 41 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 3

HANGER ROD ATTACHMENTS


Concrete Attachments

To Slab

Minimum distance from edge of concrete


to center of bolt is (10 x 'D').
B2501 cast in place anchors
of diameter 'D'.
(See Page 75)

1" (25mm) Min.

Minimum embedment
of anchor in
concrete is 'E'.

Hex Nuts
& B200 Series
Square Washer
(See Page 62)
All Threaded Rod
(See Page 57)

Load

Anchor Rod Allowable Minimum


Part Size Load ** Embedment
Number (In Tension) 'E'
in. (mm) lbs. (kN) in. (mm)

B2501-3/8 3/8" (9) 610 (2.71) 3" (76)

B2501-1/2 1/2" (13) 1130 (5.02) 4" (101)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used when
seismic bracing is not required.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 42 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 4

HANGER ROD ATTACHMENTS


Concrete Attachments
Minimum distance from To Metal Deck
edge of concrete to center
of anchor is (10 x 'D').
B2501 cast in place
anchors of diameter 'D'.
(See Page 75)

1" (25mm) Min.

Hex Nut
& B200 Series All Threaded Rod
Square Washer (See Page 57)
(See Page 62)

Load

Light Weight Concrete

Anchor Rod Allowable Minimum


Part Size Load ** Embedment
Number ‘D’ 'E'
in. (mm) lbs. (kN) in. (mm)

B2501-3/8 3/8" (9) 610 (2.71) 3" (76)

B2501-1/2 1/2" (13) 653 (2.90) 4" (101)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum light weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used when
seismic bracing is not required.

Normal Weight Concrete

Anchor Rod Allowable Minimum


Part Size Load ** Embedment
Number ‘D’ 'E'
in. (mm) lbs. (kN) in. (mm)

B2501-3/8 3/8" (9) 610 (2.71) 3" (76)

B2501-1/2 1/2" (13) 871 (3.87) 4" (101)

* B-Line Figure B2501 in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used when
seismic bracing is not required.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 43 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 5

HANGER ROD ATTACHMENTS


Concrete Attachments

To Slab

Minimum distance from edge of concrete B2500 Spot Insert with N2500
to center of bolt is (10 x 'D'). Insert Nut of thread size 'D'.
(See Page 76)

1" (25mm) Min.

Minimum embedment
B200 Series Square Washer of anchor in
& Hex Nut concrete is 'E'.
(See Page 62) All Threaded Rod
(See Page 57)

Load

Minimum
Allowable
Square Nut Thread Minimum Insert Distance
Load **
Part Size Embedment Between
(In Tension)
Number 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm)

N2500-3/8 529 (2.35) 3/8"-16 19/16" (40) 41/2" (114)

N2500-1/2 529 (2.35) 1/2"-13 19/16" (40) 6" (152)

N2500-5/8 529 (2.35) 5/8"-11 19/16" (40) 6" (152)

N2500-3/4 529 (2.35) 3/4"-10 19/16" (40) 6" (152)

N2500-7/8 529 (2.35) 7/8"-9 19/16" (40) 6" (152)

* B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used when
seismic bracing is not required.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 44 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 6

HANGER ROD ATTACHMENTS


Concrete Attachments

Minimum distance from To Metal Deck


edge of concrete to center B2500 Spot Insert with N2500
of anchor is (10 x 'D'). Insert Nut of thread size 'D'.
(See Page 76)

1" (25mm) Min.

B200 Series Square Washer


& Hex Nut All Threaded Rod
(See Page 62) (See Page 57)

Load

Minimum
Allowable
Square Nut Thread Minimum Insert Distance
Light Weight Load **
Part Size Embedment Between
(In Tension)
Concrete Number 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm)

N2500-3/8 397 (1.76) 3/8"-16 19/16" (40) 41/2" (114)

N2500-1/2 397 (1.76) 1/2"-13 19/16" (40) 41/2" (114)

N2500-5/8 397 (1.76) 5/8"-11 19/16" (40) 41/2" (114)

N2500-3/4 397 (1.76) 3/4"-10 19/16" (40) 41/2" (114)

N2500-7/8 397 (1.76) 7/8"-9 19/16" (40) 41/2" (114)

* B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum light weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used when seismic bracing is not required.

Minimum
Allowable
Square Nut Thread Minimum Insert Distance
Normal Weight Part
Load **
Size Embedment Between
Concrete (In Tension)
Number 'D' 'E' Anchors
lbs. (kN) in. (mm) in. (mm)

N2500-3/8 529 (2.35) 3/8"-16 19/16" (40) 41/2" (114)

N2500-1/2 529 (2.35) 1/2"-13 19/16" (40) 41/2" (114)

N2500-5/8 529 (2.35) 5/8"-11 19/16" (40) 41/2" (114)

N2500-3/4 529 (2.35) 3/4"-10 19/16" (40) 41/2" (114)

N2500-7/8 529 (2.35) 7/8"-9 19/16" (40) 41/2" (114)

* B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete.
** See important notes on page 39.
Note: See B446 & B446C on page 56 for a flexible connection which may be used when seismic bracing is not required.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 45 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 7

HANGER ROD ATTACHMENTS


Concrete Attachments

To Slab

B-Line Channel Nut


(See Page 61)

B200 Series Square


B32I-12 or stronger
Washer, Hex Nut
Concrete Insert attached to
(See Page 62)
concrete structure
(See Pages 77 & 78)

Note: Reduce load by 50%


when connection is
within 2” (51mm) from the
All Threaded Rod
end of the insert.
(See Page 57)

Load

Channel
Allowable
Nut
Load
ATR Part
(In Tension)
Size Number
lbs. (kN)

3/8"-16 N228 Series 610 (2.71)


1/2"-13 N225 Series 1130 (5.02)
5/8"-11 N255 Series 1810 (8.05)
3/4"-10 N275 Series 2000 (8.89)
7/8"-9 N278 Series 2000 (8.89)

Note: See B446 & B446C on page 56 for a flexible connection which may be
used when seismic bracing is not required.
Note: Pre-cast anchors must be accurately secured prior to pouring concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 46 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 8

HANGER ROD ATTACHMENTS


Wood Attachments

CL

Must be above the neutral


axis of wood beam and a
minimum of (4 x ‘D’) from Bolt Diameter
bottom of beam. ‘D’

‘TL’
‘E’ B3060
Side Beam
Angle Clip
(See Page 72)
Flat Washer
(See Page 62) B655 Flat Washer
Rod Coupler (See Page 62)
B3213
(See Page 62)
Coach Screw
Flat Washer or Hex Nuts
Rod Hex Nuts B200 Series (See Page 62)
(See Page 72) (See Page 62)
Square Washer
All Threaded Rod & Hex Nut
ATR (See Page 62)
(See Page 57)
All Threaded Rod
ATR
(See Page 57) Load
Load

Allowable Load
ATR Bolt for Beam Thickness
Rod Diameter 11/2” (38mm) 31/2” (89mm)
‘D’ Minimum Minimum
Part Rod Design Minimum Thread lbs. (kN) lbs. (kN)
Number Size Load Embedment Length
3/8"-16 3/8"-16 200 (.89) 250 (1.11)
'E' ‘TL’
lbs. (kN) in. (mm) in. (mm) 1/2"-13 1/2"-13 300 (1.33) 460 (2.04)
B3213-3/8 3/8"-16 559 (2.48) 3" (76) 2" (51) 5/8"-11 5/8"-11 360 (1.60) 700 (3.11)
B3213-1/2 1/2"-13 659 (2.93) 3" (76) 21/2" (63) 3/4"-10 3/4"-10 420 (1.87) 870 (3.87)

Note: See B446 & B446C on page 56 for a flexible connection Note: See B446 & B446C on page 56 for a flexible connection
which may be used when seismic bracing is not required. which may be used when seismic bracing is not required.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 47 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 9

HANGER ROD ATTACHMENTS


Strut Attachments

Typical All Thread Rod Attachment to Strut

12 Ga. (2.6mm)
B-Line Channel Nut B-Line Channel
(See Page 61)

B200 Series
All Threaded Rod Square Washer
ATR (See Page 62)
(See Page 57) Hex Nut
(See Page 62)

Channel nuts, square washers, and hex nuts shall be sized to fit all threaded rod.

ATR Channel Nut Square


Size Part Number Washer

3/8"-16 N228, N228WO


B201
TN228, FN228
1/2"-13 N225, N225WO
B202
TN225
5/8"-11 N255, N255WO B202-1
3/4"-10 N275, N275WO B202-2
7/8"-9 N278, N278WO B202-3

Allowable load determined by the lowest value:


1). Channel Nut Pullout (page 61)
2). Channel Concentrated Load Capacity (page 22)
3). Channel Attachment To Structure (pages 49 - 51)

Note: See B446 & B446C on page 56 for a flexible connection


which may be used when seismic bracing is not required.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 48 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 10

HANGER ROD ATTACHMENTS & APPROVED COMPONENTS


SEISMIC APPROVAL: To be used as a
vertical ATR support. Not usable as a 23/8" 31/8"
structural attachment for seismic brace. (60mm)
(79mm)

Sold in Pieces 1"


(25mm)
Design Load:
1200 Lbs. (5.34 kN)
when used in pairs
33/8"
(86mm)
Recommended Torque: B441-22
150 in.-lbs. (16.9 N•m)
BEAM CLAMP
1/4"
For use with 15/8" (41mm) high channel. (6mm)
ATR Allowable Load
Size lbs. (kN)

3/8"-16 610 (2.71)


1/2"-13 1130 (5.02)
23/8" 31/8"
(60mm) (79mm)
5/8"-11 1200 (5.34)
3/4"-10 1200 (5.34)
7/8"-9 1200 (5.34)
1"
(25mm)

B441-22A
BEAM CLAMP 5"
For use with 27/16" (62mm) to (127mm)
31/4" (82mm) high channel.
1/4"
(6mm)

SEISMIC APPROVAL: To be used as a B751 Clamp


Not Included
vertical ATR support. Not usable as a
structural attachment for seismic brace.
Includes: B701-J__-3/8" J-Hook
Overall
1 pc. B751 Beam Clamp Height
1 pc. B701 Type J-Hook only 31/4”
1 pc. SA203-158 Clip (82mm)
1 pc. 3/8"-16 Hex Nut

For Flange 3/8" (9mm) 500 Lb. (2.22kN)


Part No. Width Rod Size Design Load
in. (mm)
B751 Includes: 1 pc. B752 Swivel Body
B751-J4-3/8 3" - 6" (76 - 152) Clamp 1 pc. 5/16"-18 x 13/4" HHCS
B751-J6-3/8 5" - 9" (127 - 228)
1 pc. 5/16"-18 Hex Nut
B751-J9-3/8 8" - 12" (203 - 305)
Load 1
B751-J12-3/8 11" - 15" (279 - 381) Note: Eliminates bending moment in threaded rod
Load 2 support for a flexible connection. Can be used
when seismic bracing is not required.
ATR Allowable Load 1 Allowable Load 2 B751-J__-3/8 Series
Size lbs. (kN) lbs. (kN)
BEAM CLAMP B752
3/8"-16 500 (2.22) 300 (1.33) ASSEMBLY BEAM CLAMP SWIVEL

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 49 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 11

HANGER ROD ATTACHMENTS & APPROVED COMPONENTS


SEISMIC APPROVAL: To be used as a
vertical ATR support. Not usable as a
structural attachment for seismic brace.

For Flange ATR


Part No. Width Length
in. (mm) in. (mm)
33/8"
B761-22-4 4" - 57/8" (101-149) 4" (101) (86mm)
Square U-Bolt
B761-22-6 6" - 87/8" (152-225) 6" (152) and Hex Nuts
Included
B761-22-9 9" - 117/8" (228-301) 9" (228)
B761-22-12 12" - 147/8" (305-378) 12" (305) 1/4"
(6mm)

Includes: ATR Allowable Load


2 pcs. B760 Plate Size lbs. (kN)

2 pcs. B500-33/8" U-Bolts only 3/8"-16 610 (2.71)


1 pc. 3/8-16 ATR (Length) 1/2"-13 1130 (5.02) 3"
6 pcs. 3/8"-16 Hex Nuts 5/8"-11 (76mm)
1810 (8.05) 3/8"-16 ATR and Hex Nuts
Recommended Torque: 3/4"-10 2000 (8.89)
'U-Bolt" Nuts 150 in.-lbs. (16.9 N•m) 7/8"-9 2000 (8.89)
ATR Nuts 60 in.-lbs. (6.8 N•m)
For use with 15/8" (41mm) high channel.
B761-22 Series
BEAM CLAMP

SEISMIC APPROVAL: To be used as a


vertical ATR support. Not usable as a
structural attachment for seismic brace.

For Flange ATR


Part No. Width Length
in. (mm) in. (mm) 5"
Square U-Bolt (127mm)
B761-22A-4 4" - 57/8" (101-149) 4" (101)
and Hex Nuts
B761-22A-6 6" - 87/8" (152-225) 6" (152) Included
B761-22A-9 9" - 117/8" (228-301) 9" (228)
B761-22A-12 12" - 147/8" (305-378) 12" (305)

1/4"
Includes: (6mm)
ATR Allowable Load
2 pcs. B760 Plate
Size lbs. (kN)
2 pcs. B500-5" U-Bolts only
1 pc. 3/8-16 ATR (Length) 3/8"-16 610 (2.71)
6 pcs. 3/8"-16 Hex Nuts 1/2"-13 1130 (5.02)
5/8"-11 3"
Recommended Torque: 1810 (8.05)
(76mm) 3/8"-16 ATR and Hex Nuts
'U-Bolt" Nuts 150 in.-lbs. (16.9 N•m) 3/4"-10 2000 (8.89)
ATR Nuts 60 in.-lbs. (6.8 N•m) 7/8"-9 2000 (8.89)

For use with 27/16" (62mm) to B761-22A Series


31/4" (41mm) high channel. BEAM CLAMP

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 50 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 12

HANGER ROD ATTACHMENTS & APPROVED COMPONENTS


SEISMIC APPROVAL: To be used as a
vertical ATR support. Not usable as a
structural attachment for seismic brace.

For Flange
Square U-Bolt
Part No. Width
in. (mm)
and Hex Nuts

B760-22-4 4" - 57/8" (101-149) 33/8"


(86mm)
B760-22-6 6" - 87/8" (152-225)
B760-22-9 9" - 117/8" (228-301)

B760-22-12 12" - 147/8" (305-378)

3"
Includes: (76mm)
1 pc. B760 Plate ATR Allowable Load
1/4"
Size lbs. (kN)
1 pc. B701 Type J-Hook only (6mm)
1 pc. B500-33/8" U-Bolt only 3/8"-16 610 (2.71)
3 pcs. 3/8"-16 Hex Nuts 1/2"-13 1130 (5.02)
5/8"-11 1810 (8.05) 3/8" (9mm) Diameter
Recommended Torque:
'U-Bolt" Nuts 150 in.-lbs. (16.9 N•m) 3/4"-10 2000 (8.89)
J-Hook and Hex Nut
ATR Nuts 60 in.-lbs. (6.8 N•m) 7/8"-9 2000 (8.89)

For use with 15/8" (41mm) high channel.


B760-22 Series
BEAM CLAMP

SEISMIC APPROVAL: To be used as a Square U-Bolt


vertical ATR support. Not usable as a and Hex Nuts
structural attachment for seismic brace.

For Flange 5"


Part No. Width (127mm)
in. (mm)

B760-22A-4 4" - 57/8" (101-149)

B760-22A-6 6" - 87/8" (152-225)


B760-22A-9 9" - 117/8" (228-301)

B760-22A-12 12" - 147/8" (305-378)


3"
Includes: (76mm)
1 pc. B760 Plate ATR Allowable Load 1/4"
1 pc. B701 Type J-Hook only Size lbs. (kN) (6mm)
1 pc. B500-5" U-Bolt only 3/8"-16 610 (2.71)
3 pcs. 3/8"-16 Hex Nuts
1/2"-13 1130 (5.02)
Recommended Torque: 5/8"-11 1810 (8.05)
3/8" (9mm) Diameter
'U-Bolt" Nuts 150 in.-lbs. (16.9 N•m) 3/4"-10
J-Hook and Hex Nut
2000 (8.89)
ATR Nuts 60 in.-lbs. (6.8 N•m)
7/8"-9 2000 (8.89)
For use with 27/16" (62mm) to
B760-22A Series
31/4" (41mm) high channel.
BEAM CLAMP

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 51 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 13

HANGER ROD ATTACHMENTS & APPROVED COMPONENTS


SEISMIC APPROVAL: To be used as a 3/4"
vertical ATR support. Not usable as a (19mm)
structural attachment for seismic brace. Setscrew and
Locknut Included
Retaining
Rod Size Design Strap is 'A'
Part No. 'A' 'C' Load
in. (mm) lbs. (kN)
required,
order B3362
B3036L-3/8 3/8"-16 13/4" (44) 400 (1.78) thru B3365
B3036L-1/2 1/2"-13 13/4" (44) 400 (1.78) separately. 'C'
B3036L-5/8 5/8"-11 17/8" (47) 450 (2.00)

Setscrew Torque: 1/4” = 4 ft•lbs 3/8” = 5 ft•lbs 1/2” = 11 ft•lbs B3036L Series
MALLEABLE IRON C-CLAMP
WITH LOCKNUT

SEISMIC APPROVAL: To be used as a


vertical ATR support. Not usable as a
structural attachment for seismic brace. 'D'
Setscrew and
Rod Size Design Retaining Locknut Included
Part No. 'A' 'D' Load Strap is
in. (mm) lbs. (kN) required,
order B3362 'A'
B351L-3/8 3/8"-16 3/4" (19) 230 (1.03)
thru B3365
B351L-1/2 1/2"-13 3/4" (19) 380 (1.71) separately.
B351L-5/8 5/8"-11 3/4" (19) 550 (2.47)
B351L-3/4 3/4"-10 3/4" (19) 630 (2.83)
B351L-7/8 7/8"-9 1" (25) 1200 (5.34)

B351L Series
Setscrew Torque: 1/4” = 4 ft•lbs 3/8” = 5 ft•lbs 1/2” = 11 ft•lbs
STEEL C-CLAMP WITH LOCKNUT

SEISMIC APPROVAL: To be used as a


12 ga. 3/4"
vertical ATR support. Not usable as a (19mm) (19mm)
structural attachment for seismic brace.

Part No. For Use With ‘W’


in. (mm)

B3362-L B351L-3/8" & 1/2" 11/4" (32) 'L'

B3363-L B351L-5/8" & 3/4" - B3036L-3/8" & 1/2" 11/4" (32)

B3364-L B3036L-5/8" & 3/4" 11/4" (32) 'W'


B3365-L B351L-7/8" 11/2" (38)

When ordering specify 'L' (Length) as a suffix to the part number. B3362 thru B3365
'L' = 6" (152mm), 8" (203mm), 10" (254mm), 12" (305mm) RETAINING STRAP

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 52 of
Structural Engineer S 3913
**SRS2002-OSpg.40-53 (11/02) N 1/3/03 5:13 PM Page 14

HANGER ROD ATTACHMENTS & APPROVED COMPONENTS


SEISMIC APPROVAL: To be used as a vertical ATR support. 'B' Setscrew
Not usable as a structural attachment for seismic brace. Included

Part Rod Setscrew 'C' 'T' Design Load 11/8"


No. Size 'B' in. (mm) in. (mm) lbs. (kN) (28mm)
'T'
B303 1/4"-20 3/8"-16 25/16" (59) 11 Ga. (3) 400 (1.78)
B304 5/16"-18 3/8"-16 25/16" (59) 11 Ga. (3) 600 (2.67) Retaining
3/8"-16 3/8"-16
Strap is 7/8"
B305 25/16" (59) 11 Ga. (3) 600 (2.67)
required, (22mm)
B306 3/8"-16 1/2"-13 27/16" (62) 7 Ga. (4) 1100 (4.89) order B312 'C'
B307 1/2"-13 1/2"-13 27/16" (62) 7 Ga. (4) 1100 (4.89) separately.
B308 1/2"-13 1/2"-13 29/16" (65) 1/4" (6) 1500 (6.67) 'A'
B309 5/8"-11 1/2"-13 29/16" (65) 1/4" (6) 1500 (6.67)
21/2"
(63mm)
Recommended Setscrew Torque:
3/8"-16 150 in.-lbs. (16.9 N•m) B303 Thru B309
1/2"-13 350 in.-lbs. (39.5 N•m)
BEAM CLAMP
'B' Setscrew
SEISMIC APPROVAL: To be used as a Included
vertical ATR support. Not usable as a
structural attachment for seismic brace. 15/8"
'T' (41mm)

Part Rod Setscrew 'C' 'T' Design Load


No. Size 'B' in. (mm) in. (mm) lbs. (kN)

3/8"-16 1/2"-13 Retaining 111/16"


B321-1 39/16" (92) 1/4" (6) 1300 (5.78)
Strap is (43mm)
B321-2 1/2"-13 1/2"-13 39/16" (92) 1/4" (6) 1400 (6.23) required,
'C'
B321-3 5/8"-11 1/2"-13 39/16" (92) 1/4" (6) 1600 (7.12) order B312
5/8"-11 5/8"-11
separately.
B321-4 323/32" (94) 5/16" (8) 1800 (8.00)
B321-5 3/4"-13 5/8"-11 323/32" (94) 5/16" (8) 2000 (8.89) 'A'
31/4"
(82mm)
Recommended Setscrew Torque: Minimum Flange Thickness:
3/8"-16 150 in.-lbs. (16.9 N•m) B321 SERIES
B321-1 thru B321-3 3/8" (9mm)
1/2"-13 350 in.-lbs. (39.5 N•m)
B321-4 and B321-5 5/8" (16mm) BEAM CLAMP

SEISMIC APPROVAL: To be used as a


vertical ATR support. Not usable as a
structural attachment for seismic brace. 'A'

For Flange
'A' 11/4"
Part No. Width (32mm)
in. (mm) in. (mm) 13/4"
(44mm)
B312S-6 6" (152) 95/8" (244)
B312S-9 9" (228) 125/8" (320) 1/4" 1/2"

(6mm) (13mm)
B312S-12 12" (305) 155/8" (397)
B312S-15 15" (381) 185/8" (473)

For maximum beam thickness of 3/4" (19mm). B312S SERIES


For thicker beams step up one flange width size. ANCHOR STRAP FOR USE WITH
Material: 12 Gauge (2.7mm) B303 thru B309 and B321 SERIES

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 53 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 1

HANGER ROD ATTACHMENTS & APPROVED COMPONENTS


SEISMIC APPROVAL: To be used as a vertical ATR support.
Not usable as a structural attachment for seismic brace.

Retaining
Rod Size Throat Design
Strap is
Part No. 'A' Opening Load
in. (mm) lbs. (kN)
required,
order B3367
B3033-3/8 3/8"-16 11/4" (32) 500 (2.22) separately.
B3033-1/2 1/2"-13 11/4" (32) 700 (3.11)
B3033-5/8 5/8"-11 15/16" (33) 900 (4.00)
B3033-3/4 3/4"-10 15/16" (33) 900 (4.00)

Setscrew Torque: 1/4” = 4 ft•lbs 3/8” = 5 ft•lbs 1/2” = 11 ft•lbs


B3033
BEAM CLAMP

SEISMIC APPROVAL: To be used as a


vertical ATR support. Not usable as a
structural attachment for seismic brace.
Retaining
Strap is
Rod Size Throat Design required,
Part No. 'A' Opening Load order B3367
in. (mm) lbs. (kN)
separately.
B3034-3/8 3/8"-16 3/4" (19) 400 (1.78)
B3034-1/2 1/2"-13 3/4" (19) 700 (3.11)

Setscrew Torque: 1/4” = 4 ft•lbs 3/8” = 5 ft•lbs

B3034
BEAM CLAMP

SEISMIC APPROVAL: To be used as a


vertical ATR support. Not usable as a
structural attachment for seismic brace. ’B’

‘A’ ‘B’
Part No. Width Diameter
in. (mm) in. (mm)
’L’
B3367-3/8 11/4" (32) 7/16" (11)
B3367-1/2 11/4" (32) 9/16" (14) ’A’
B3367-5/8 11/4" (32) 11/16" (17)
Material Thickness: 11 Ga. (3.0mm)
B3367-3/4 11/4" (32) 13/16" (20)
Specify ‘L’ Length
(add 2” (51mm) to flange width)
B3367 SERIES
ANCHOR STRAP FOR USE WITH B3033 and B3034 SERIES

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 54 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 2

HANGER ROD ATTACHMENTS


Structural Steel

Hex Nut
& Washer
(See Page 62) B3248
Square Washer
B-Line B3234 1/4” Thick Sized
Bevel Washer Flat Washer or
B200 Series To Fit Joist
When Required
(See Page 74)
(See Page 74) Square Washer
(See Page 62)

Hex Nut Hex Nut


& Washer & Washer
(See Page 62) (See Page 62)
All Threaded All Threaded
Rod Rod
(See Page 57) (See Page 57) All Threaded
Rod
(See Page 57)

Load Load
Load

ATR Allowable Load*


Size lbs. (kN)

3/8"-16 610 (2.71)


1/2"-13 1130 (5.02)
5/8"-11 1810 (8.05)
3/4"-10 2710 (12.05)
7/8"-9 3770 (16.77)

* Maximum load allowed for


ATR, actual load may be
determined by structural
steel capacity.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 55 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 3

HANGER ROD SWIVEL ATTACHMENTS

23/4
(69.8) 23/4
A (69.8)
1 A
(25.4)

B
A

B446 B446C
SWIVEL HANGER Note: Eliminates bending moment in SWIVEL HANGER
(FEMALE-MALE) threaded rod support for a (FEMALE-FEMALE)
flexible connection. Can be
used when seismic bracing is
not required.

Design Load
Part No. A B lbs. (kN)

B446-3/8 B446C-3/8 3/8”-16 HN 3/8”-16 HHCS 610 (2.71)

B446-1/2 B446C-1/2 1/2”-13 HN 1/2”-13 HHCS 1130 (5.02)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 56 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 4

THREADED ROD (ATR)

TABLE 5
Rod Allowable
Size Loads
lbs. (kN)
3/8"-16 610 (2.71)
1/2"-13 1130 (5.02)
5/8"-11 1810 (8.05)
3/4"-10 2710 (12.05)
7/8"-9 3770 (16.77)

* Anchor capacity may be lower


than all threaded rod.

ALL THREADED ROD - ATR

THREADED ROD - MAXIMUM LENGTH WITHOUT STIFFENER

ATR
All Threaded Rod TABLE 6
Table 5 B22 Channel
Longitudinal or Transverse Brace Max. Rod Length
(9’-4” (2.8 m) Maximum Length) ATR Without Rod
Size Stiffener
in. (mm)

3/8"-16 19" (482.6)


1/2"-13 25" (635.0)
5/8"-11 31" (787.4)
B-Line Channel
3/4"-10 37" (939.8)
Size as Required
(See Page 22) 7/8"-9 43" (1092.2)

Note: If rod stiffener is required


see Table 7 - page 58

B335-2-1/2 Adjustable Hinges


Longitudinal & Transverse Braces
(See Page 59)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 57 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 5

APPROVED COMPONENTS
SC228 HANGER ROD SC-UB HANGER ROD
STIFFENER ASSEMBLY STIFFENER ASSEMBLY
For 3/8" thru 5/8" ATR For 3/4" & 7/8" ATR
(Order B22 Channel Separately) (Order B22 Channel Separately)

B3188-11/4” WO ATR
U-Bolt All Threaded Rod
(See Page 57)
SC228 Hanger
Rod Stiffener
Assembly
2-Hole Plate B22 Channel
1/4” x 15/8” x 31/2”
(6mm x 41mm x 89mm)
B22 Channel ATR
Rod Stiffener All Threaded Rod
(See Page 57)
3/8” Hex Nuts

Note: SC-UB assembly includes U-Bolt, 2-Hole Plate


& 3/8"-16 Hex Nuts.

APPROVED COMPONENTS

ATR
All Threaded Rod TABLE 7
Maximum distance (See Page 57)
from top of hanger ROD STIFFENER CHART
rod to first bolt of the B22 Channel
channel rod stiffener Longitudinal or Transverse Brace ATR X
is 6” (152.4mm). (9’-4” (2.8 m) Maximum Length) Size Max. Spacing
Between SC-228
or SC-UB
‘X’ in. (mm)

3/8"-16 13" (330.2)


1/2"-13 18" (457.2)
Maximum distance from
5/8"-11 23" (584.2)
top of channel where
the hanger rod is 3/4"-10 28" (711.2)
attached to the first B22 Channel 7/8"-9 33" (838.2)
bolt of the channel rod Rod Stiffener with SC228
stiffener is 6” (152.4mm). or SC-UB Assemblies Note: Minimum of (2) - SC228 or
SC-UB are required per rod.
B-Line channel B335-2-1/2 Adjustable Hinges
size as required. Longitudinal & Transverse Braces
(See Page 22) (See Page 59)

Rod Stiffeners required only on hanger rods that have seismic bracing attached to the hanger or trapeze.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 58 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 6

APPROVED COMPONENTS
SEISMIC APPROVAL:
Longitudinal and Transverse
Brace Attachments
9/16" Dia. (14mm) 2 Holes 15/8"
(41mm)
17/8" (47mm) center to center Hole Dia.
Part
No. 'H'
in. (mm)
13/16"
(20mm) B335V-1/2 9/16" (14)
B335V-5/8 11/16" (17)

43/4" B335V-3/4 13/16" (20)


'H' (120mm)
Material Thickness: 1/4" (6 mm)

B335V SERIES THREE HOLE ADJUSTABLE HALF HINGE


9/16" Dia. (14mm) 2 Holes 15/8"
(41mm)
17/8" (47mm) center to center
Part Hole Dia.
No. 'H'
13/16" in. (mm)
'H' (20mm)
B335-2-3/8 7/16" (11)
43/4" B335-2-1/2 9/16" (14)
(120mm)
B335-2-5/8 11/16" (17)
B335-2-3/4 13/16" (20)
13/16" 71/2"
(20mm) (190mm)
Material Thickness: 1/4" (6 mm)

B335-2 SERIES THREE HOLE ADJUSTABLE HINGE


13/16"
(20mm)

15/8"
(41mm)

30° Min.
17/8"
(47mm)

33/4"
(95mm)

53/8"
(136mm)

B634 SINGLE CHANNEL ADJUSTABLE HINGE


1/2" Channel Nuts & Bolts not included - order seperately (see pages 61 & 62)

Note: See Page 66 for alternate hinge types.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 59 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 7

APPROVED COMPONENTS

SEISMIC APPROVAL:
NOTE: B633 can be substituted for Longitudinal and Transverse
B335-2, in any detail, provided the Brace Attachments
hole diameter 'H' remains the same.

9/16" Dia. (14mm)


31/4"
(82mm) 2 Holes
Part Hole Dia.
No. 'H'
in. (mm)

B633-1/2 9/16" (14)


15/8"
(41mm) B633-5/8 11/16" (17)
B633-3/4 13/16" (20)
'H' B633-7/8 15/16" (24)
41/2"
(114mm) Material Thickness: 1/4" (6 mm)

B633 SERIES ADJUSTABLE SEISMIC HINGE FITTING

NOTE: B650 can be substituted for B335-2, in any


detail, provided the slot width 'W' remains
Hole Dia.
the same as the ‘H’ of the B335-2. Part
No. 'W'
in. (mm)

Bracket Thickness: B650-3/8 25/64" (10)


12 Ga. (2.6mm) B650-1/2 33/64" (13)
9/16"Dia. (14mm)
2" B650-5/8 41/64" (16)
2 Holes (51mm)
B650-3/4 49/64" (19)
17/8" (47mm)
Plate Center to Center
9/16"Dia. (14mm)
Existing
ATR 31/2" 2 Holes
(89mm) 17/8" (47mm)
11/2"
(38mm) Center to
'W' Center
49/32"
Bracket (109mm) 'W'
15/8"
(41mm)
2"
(51mm) 121/32" B129 Plate Thickness:
Key 23/32" (42mm)
1/4" (6.3mm)
(53mm)
Key Thickness:
10 Ga. (3.4mm)

B650 SERIES RETROFIT 45° SEISMIC BRACE FITTING

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 60 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 8

APPROVED COMPONENTS
Channel Nuts

SEISMIC APPROVAL:
Longitudinal and Transverse
Brace Attachments

Nut Without Spring


Twirl Nut
(NxxxWO)
Spring Nut (TNxxx)
(Nxxx)

Resistance to Slip
Resistance To Slip * In Channel Nut
Thread Nut Part 12 Ga. (2.6mm) 14 Ga. (1.9mm) Thickness
Size Numbers lbs. (kN) lbs. (kN) in. (mm)

3/8"-16 N228, N228WO, TN228 800 (3.56) 600 (2.67) 3/8" (9)

1/2"-13 N225, N225WO, TN225 1500 (6.67) 1000 (4.45) 1/2" (13)

5/8"-11 N255, N255WO 1500 (6.67) 1000 (4.45) 1/2" (13)

3/4"-10 N275, N275WO 1500 (6.67) 1000 (4.45) 1/2" (13)

7/8"-9 N278, N278WO 1500 (6.67) 1000 (4.45) 1/2" (13)

Pull-Out Strength
Pull-Out Strength * In Channel Nut
Thread Nut Part 12 Ga. (2.6mm) 14 Ga. (1.9mm) Thickness
Size Numbers lbs. (kN) lbs. (kN) in. (mm)

3/8"-16 N228, N228WO, TN228 1100 (4.89) 1000 (4.45) 3/8" (9)

1/2"-13 N225, N225WO, TN225 2000 (8.90) 1400 (6.23) 1/2" (13)

5/8"-11 N255, N255WO 2000 (8.90) 1400 (6.23) 1/2" (13)

3/4"-10 N275, N275WO 2000 (8.90) 1400 (6.23) 1/2" (13)

7/8"-9 N278, N278WO 2000 (8.90) 1400 (6.23) 1/2" (13)

* With a Safety Factor of 3.


Note: Required bolt torque shown in note D) page 9.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 61 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 9

APPROVED COMPONENTS

Hardware

SEISMIC APPROVAL:
Longitudinal and Transverse
Brace Attachments

HHCS - HEX HEAD CAP SCREWS LW - LOCK WASHERS FW - FLAT WASHERS


(Example - HHCS 1/2 x 1 1/4) (Example - LW 1/2)
(Example - FW 1/2)

B655 - ROD COUPLINGS HN - HEX NUTS


(Example - B655-1/2) (Example - HN 1/2)

15/8"
(41mm)
Hole Bolt
Part No. Size Size
in. (mm) in. (mm)

B200 3/8" (9) 5/16" (8)


B201 7/16" (11) 3/8" (9)
B202 9/16" (14) 1/2" (13)
B202-1 11/16" (17) 5/8" (16)
Hole Size
B202-2 13/16" (20) 3/4" (19)
B202-3 15/16" (24) 7/8" (22)

B200 Series Square Washers

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 62 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 10

APPROVED COMPONENTS
Pipe
'A' Pipe Size Clevis Hanger Sleeve
(Rod Size) in. (mm) Part No. Part No.*
Hanger Rod 1/2" (15) B3100-1/2 N/A
Not Included
3/4" (20) B3100-3/4 N/A
1" (25) B3100-1 B3100PS-1
11/4" (32) B3100-11/4 B3100PS-11/4
11/2" (40) B3100-11/2 B3100PS-11/2
2" (50) B3100-2 B3100PS-2
21/2" (65) B3100-21/2 B3100PS-21/2
3" (80) B3100-3 B3100PS-3
31/2" (90) B3100-31/2 B3100PS-31/2
4" (100) B3100-4 B3100PS-4
5" (125) B3100-5 B3100PS-5
6" (150) B3100-6 B3100PS-6
8" (200) B3100-8 B3100PS-8
10" (250) B3100-10 B3100PS-10
12" (300) B3100-12 B3100PS-12

*Not included when ordering standard


B3100 B3100 Series Clevis Hanger.
Standard Clevis Hanger
SEISMIC APPROVAL:
Nominal Rod Size Design Load
Part No. Pipe Size 'A'
Transverse Brace Attachment
in. (mm) lbs. (kN)

B3100-1/2 1/2" (15) 3/8"-16 610 (2.71)

B3100-3/4 3/4" (20) 3/8"-16 610 (2.71)


Underwriter's Laboratories Listed for 3/4" (20) thru
B3100-1 1" (25) 3/8"-16 610 (2.71) 12" (300). Complies with Federal Specification
WW-H-171E Type 1 and Manufacturers'
B3100-11/4 11/4" (32) 3/8"-16 610 (2.71)
Standardization Society SP-69 Type 1.
B3100-11/2 11/2" (40) 3/8"-16 610 (2.71)

B3100-2 2" (50) 3/8"-16 610 (2.71) Note: When attaching seismic bracing to clevis
hanger, install a B3100 Pipe Sleeve over the cross
B3100-21/2 21/2" (65) 1/2"-13 1130 (5.02) bolt (see Seismic Restraints Brochure).
B3100-3 3" (80) 1/2"-13 1130 (5.02) Order B3100PS (Pipe Sleeve) separately.

B3100-31/2 31/2" (90) 1/2"-13 1130 (5.02)

B3100-4 4" 5/8"-11 1430


(100) (6.36) B3100PS
B3100-5 5" (125) 5/8"-11 1430 (6.36) Pipe Sleeve
B3100-6 6" (150) 3/4"-10 1940 (8.63)

B3100-8 8" (200) 7/8"-9 2000 (8.89)

B3100-10 10" (250) 7/8"-9 3600 (16.01)

B3100-12 12" (300) 7/8"-9 3770 (16.77)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 63 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 11

APPROVED COMPONENTS
SEISMIC APPROVAL:
Transverse bracing of pipe (insulated
or non-insulated) and conduit.
'A'
(Rod Size)

'D'
Approvals: Underwriter's Laboratories Listed
for 3/4" (20) thru 12" (300). Complies with
Manufacturers' Standardization Society SP-69 Type 5.

Bolt Size

B3690 Series
Adjustable 'J' Hanger

Nominal Bolt Rod Size Hole Dia. Design Load


Part No. Pipe Size Size 'A' 'D'
in. (mm) in. (mm) lbs. kN

B3690-1/2 1/2" (15) 1/4"-20 x 21/4” 3/8"-16 13/32" (10) 400 (1.78)

B3690-3/4 3/4" (20) 1/4"-20 x 21/2” 3/8"-16 13/32" (10) 400 (1.78)

B3690-1 1" (25) 1/4"-20 x 23/4” 3/8"-16 13/32" (10) 400 (1.78)

B3690-11/4 11/4" (32) 1/4"-20 x 3” 3/8"-16 13/32" (10) 400 (1.78)

B3690-11/2 11/2" (40) 1/4"-20 x 31/4” 3/8"-16 13/32" (10) 400 (1.78)

B3690-2 2" (50) 1/4"-20 x 31/4” 3/8"-16 13/32" (10) 400 (1.78)

B3690-21/2 21/2" (65) 3/8"-16 x 41/2” 1/2"-13 9/16" (14) 800 (3.56)

B3690-3 3" (80) 3/8"-16 x 5” 1/2"-13 9/16" (14) 800 (3.56)

B3690-31/2 31/2" (90) 3/8"-16 x 51/2” 1/2"-13 9/16" (14) 800 (3.56)

B3690-4 4" (100) 3/8"-16 x 61/2” 5/8"-11 9/16" (14) 800 (3.56)

B3690-5 5" (125) 3/8"-16 x 71/2” 5/8"-11 9/16" (14) 800 (3.56)

B3690-6 6" (150) 3/8"-16 x 81/2” 3/4"-10 9/16" (14) 1000 (4.45)

B3690-8 8" (200) 3/8"-16 x 101/2” 7/8"-9 9/16" (14) 1200 (5.34)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 64 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 12

APPROVED COMPONENTS

SEISMIC APPROVAL:
Transverse and Longitudinal
Load Bracing of Pipe or Conduit.
Bolt Size

Brace Attachment
Bolt Size

Complies with Federal Specification WW-H-171E


Type 3 and Manufacturers' Standardization Society
SP-69 Type3.

B3144 Series
Double Bolt Pipe Clamp

Nominal Load Bolt Brace Attachment Maximum Design Load For Service Temp.
Part No. Pipe Size Size Bolt Size 650°F (343°C) 750°F (399°C)
in. (mm) lbs. (kN) lbs. (kN)

B3144-11/2 11/2" (40) 5/8"-11 x 21/2" 1/2"-13 x 21/2" 1545 (6.87) 1380 (6.14)
B3144-2 2" (50) 5/8"-11 x 21/2" 1/2"-13 x 21/2" 1545 (6.87) 1380 (6.14)

B3144-21/2 21/2" (65) 5/8"-11 x 21/2" 1/2"-13 x 21/2" 1545 (6.87) 1380 (6.14)
B3144-3 3" (80) 5/8"-11 x 21/2" 1/2"-13 x 21/2" 1545 (6.87) 1380 (6.14)
B3144-4 4" (100) 3/4"-10 x 3" 5/8"-11 x 23/4" 2500 (11.12) 2230 (9.92)
B3144-5 5" (125) 3/4"-10 x 3" 5/8"-11 x 23/4" 2500 (11.12) 2230 (9.92)
B3144-6 6" (150) 1"-8 x 31/2" 3/4"-10 x 31/4" 2865 (12.74) 2555 (9.92)
B3144-8 8" (200) 1"-8 x 31/2" 3/4"-10 x 31/4" 2865 (12.74) 2555 (9.92)
B3144-10 10" (250) 1"-8 x 31/2" 3/4"-10 x 31/4" 3240 (14.41) 2890 (12.85)
B3144-12 12" (300) 1"-8 x 31/2" 3/4"-10 x 31/4" 3240 (14.41) 2890 (12.85)

See note D) on page 9 for required tightening torques.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 65 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 13

APPROVED COMPONENTS

Seismic Approval:
Transverse Bracing of
'A' Pipe or Conduit.
(Rod Size)

Complies with Federal Specification WW-H-171E


Type 44 and Manufacturers' Standardization Society
SP-69 Type 43.

Axle Size

B3110 Series
Adjustable Steel Yoke Pipe Roll

Nominal Rod Size Axle Maximum Design


Part No. Pipe Size 'A' Size O.D. Covering Load
in. (mm) in. (mm) in. (mm) lbs. kN

B3110-2 2" (50) 3/8"-16 3/8" (9.5) 25/8" (67) 150 (.67)
B3110-21/2 21/2" (65) 1/2"-13 1/2" (12.7) 3" (76) 225 (1.00)
B3110-3 3" (80) 1/2"-13 1/2" (12.7) 35/8" (92) 310 (1.38)
B3110-31/2 31/2" (90) 1/2"-13 1/2" (12.7) 41/8" (105) 390 (1.73)
B3110-4 4" (100) 5/8"-11 1/2" (12.7) 411/16" (119) 475 (2.11)
B3110-5 5" (125) 5/8"-11 5/8" (15.9) 53/4" (146) 685 (3.04)
B3110-6 6" (150) 3/4"-10 3/4" (19.0) 63/4" (171) 780 (3.47)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 66 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 14

APPROVED COMPONENTS

Seismic Approval:
Transverse and Longitudinal
Bracing of Pipe or Conduit.
Bolt Size

Underwriter's Laboratories Listed for 3/4" (20mm) thru


12" (300mm). Complies with Federal Specification
WW-H-171E Type 4 and Manufacturers'
Standardization Society SP-69 Type 4.

B3140 Series
STANDARD PIPE CLAMP

Nominal Bolt Maximum Design Load For Service Temp.


Part No. Pipe Size Size 650°F (343°C) 750°F (399°C)
in. (mm) lbs. kN lbs. kN

B3140-1/2 1/2" (15) 5/16"-18 x 11/4" 500 (2.22) 445 (1.98)


B3140-3/4 3/4" (20) 5/16"-18 x 11/4" 500 (2.22) 445 (1.98)
B3140-1 1" (25) 5/16"-18 x 11/4" 500 (2.22) 445 (1.98)
B3140-11/4 11/4" (32) 5/16"-18 x 11/4" 500 (2.22) 445 (1.98)
B3140-11/2 11/2" (40) 5/16"-18 x 11/4" 800 (3.56) 715 (3.18)
B3140-2 2" (50) 1/2"-13 x 2" 1040 (4.62) 930 (4.13)
B3140-21/2 21/2" (65) 1/2"-13 x 2" 1040 (4.62) 930 (4.13)
B3140-3 3" (80) 1/2"-13 x 2" 1040 (4.62) 930 (4.13)
B3140-31/2 31/2" (90) 1/2"-13 x 2" 1040 (4.62) 930 (4.13)
B3140-4 4" (100) 5/8"-11 x 21/4" 1040 (4.62) 930 (4.13)
B3140-5 5" (125) 5/8"-11 x 21/2" 1040 (4.62) 930 (4.13)
B3140-6 6" (150) 3/4"-10 x 23/4" 1615 (7.18) 1440 (6.40)
B3140-8 8" (200) 3/4"-10 x 3" 1615 (7.18) 1440 (6.40)

See note D) on page 9 for required tightening torques.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 67 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 15

APPROVED COMPONENTS

Copper Adjustable
Tubing Size Clevis Hanger Sleeve
in. (mm) Part No. Part No.*
1/2" (15) B3104CT-1/2 N/A
'A'
(Rod Size) 3/4" (20) B3104CT-3/4 N/A
Hanger Rod 1" (25) B3104CT-1 B3104CTPS-1
Not Included 11/4" (32) B3104CT-11/4 B3104CTPS-11/4
11/2" (40) B3104CT-11/2 B3104CTPS-11/2
2" (50) B3104CT-2 B3104CTPS-2
21/2" (65) B3104CT-21/2 B3104CTPS-21/2
3" (80) B3104CT-3 B3104CTPS-3
31/2" (90) B3104CT-31/2 B3104CTPS-31/2
4" (100) B3104CT-4 B3104CTPS-4

*Not included when ordering standard B3104CT Series


Clevis Hanger.

Seismic Approval:
Transverse bracing of copper tubing
Finish: Dura-Copper Epoxy Paint. (insulated or non-insulated).
This non-metallic coating eliminates dissimilar
metal contact between the hanger and the
copper tubing.

B3104CT
Copper Tubing Clevis Hanger

Nominal Rod Size Design Load


Note: When attaching seismic bracing to clevis
Part No. Tubing Size 'A'
hanger, install a B3104CTPS Pipe Sleeve over the
in. (mm) lbs. (kN)
cross bolt (see Seismic Restraints Brochure). Order
B3104CT-1/2 1/2" (15) 3/8"-16 150 (0.67) B3104CTPS (Pipe Sleeve) separately.
B3104CT-3/4 3/4" (20) 3/8"-16 250 (1.11)
B3104CT-1 1" (25) 3/8"-16 250 (1.11)
B3104CT-11/4 11/4" (32) 3/8"-16 250 (1.11)
B3104CT-11/2 11/2" (40) 3/8"-16 250 (1.11)
B3104CT-2 2" (50) 3/8"-16 250 (1.11)
B3104CT-21/2 21/2" (65) 1/2"-13 350 (1.55)
B3104CT-3 3" (80) 1/2"-13 350 (1.55)
B3104CT-31/2 31/2" (90) 1/2"-13 350 (1.55)
B3104CT-4 4" (100) 5/8"-11 400 (1.78)

B3104CTPS
Pipe Sleeve

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 68 of
Structural Engineer S 3913
**SRS2002-OSpg.54-69 (11/02) N 1/3/03 5:29 PM Page 16

APPROVED COMPONENTS

Seismic Approval:
Transverse and Longitudinal
Bracing of Steel Pipe &
Bolts and Nuts Copper Tubing.
Included

Approvals: Complies with Federal Specification


WW-H-171E Type 4 and Manufacturers'
Standardization Society SP-69 Type 8.
'L' Underwriter's Laboratories Listed for 3/4" (20mm)
Bolt Size thru 8" (200mm) on Standard Riser Clamp only.

B3373 - Standard Riser Clamp


Nominal Design Load
Part No. Pipe Size 'L' Bolt Size lbs. kN

B3373-1 1" (25) 99/16" (242.9) 3/8"-16 x 11/4" 255 (1.13)


B3373-11/4 11/4" (32) 10" (254.0) 3/8"-16 x 11/2" 255 (1.13)
B3373-11/2 11/2" (40) 105/16" (261.9) 3/8"-16 x 11/2" 255 (1.13)
B3373-2 2" (50) 103/4" (273.0) 3/8"-16 x 11/2" 255 (1.13)
B3373-21/2 21/2" (65) 111/4" (285.7) 3/8"-16 x 11/2" 390 (1.73)
B3373-3 3" (80) 1115/16" (303.2) 3/8"-16 x 11/2" 530 (2.35)
B3373-31/2 31/2" (90) 123/8" (314.3) 1/2"-13 x 13/4" 670 (2.98)
B3373-4 4" (100) 127/8" (327.0) 1/2"-13 x 13/4" 810 (3.60)
B3373-5 5" (125) 14" (355.6) 1/2"-13 x 2" 1160 (5.16)
B3373-6 6" (150) 151/16" (382.6) 1/2"-13 x 2" 1570 (6.98)
B3373-8 8" (200) 171/4" (438.2) 5/8"-11 x 21/2" 2500 (11.12)
B3373-10 10" (250) 197/16" (493.7) 5/8"-11 x 21/2" 2500 (11.12)
B3373-12 12" (300) 2011/16" (550.9) 5/8"-11 x 3" 2700 (12.01)

See note D) on page 9 for required tightening torques.

B3373CT - Riser Clamp for Copper Tubing


Nominal Design Load
Part No. Tubing Size 'L' Bolt Size lbs. kN

B3373CT-1/2 1/2" (15) 815/16" (227.0) 5/16"-18 x 1" 75 (.33)


B3373CT-3/4 3/4" (20) 91/16" (234.9) 5/16"-18 x 1" 75 (.33)
B3373CT-1 1" (25) 95/16" (236.5) 3/8"-16 x 1" 120 (.53)
B3373CT-11/4 11/4" (32) 99/16" (242.9) 3/8"-16 x 1" 150 (.67)
Finish: For B3373CT is
B3373CT-11/2 11/2" (40) 97/8" (250.8) 3/8"-16 x 11/4" 150 (.67) Dura-Copper Epoxy Paint.
B3373CT-2 2" (50) 107/16" (265.1) 3/8"-16 x 11/4" 150 (.67)
B3373CT-21/2 21/2" (65) 1015/16" (277.8) 3/8"-16 x 11/4" 300 (1.33) This non-metallic coating
B3373CT-3 3" (80) 117/16" (290.5) 3/8"-16 x 11/4" 300 (1.33)
eliminates dissimilar metal
contact between the hanger
B3373CT-31/2 31/2" (90) 1115/16" (303.2) 3/8"-16 x 11/4" 300 (1.33)
and the copper tubing.
B3373CT-4 4" (100) 121/2" (317.5) 1/2"-13 x 13/4" 300 (1.33)

See note D) on page 9 for required tightening torques.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 69 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:17 PM Page 1

APPROVED COMPONENTS
Vertical Load Seismic Approval:
Attachment of Pipe, Tubing or Conduit
to Transverse and Longitudinal Bracing
of Pipe or Conduit.

Includes Slotted Hex Head


Machine Screw and Square Nut

FT
B2000 Series
FL Pipe & Conduit Clamps

Bolt Bolt Design Loads *


Part No. Size Size Torque Vertical FT FL
in. (mm) ft.•lbs. (Nm) lbs. (kN) lbs. (kN) lbs. (kN)

B2001 1/2" (15) 1/4"-20 6 (8.1) 400 (1.78) 75 (0.33) 50 (0.22)


B2002 3/4" (20) 1/4"-20 6 (8.1) 400 (1.78) 100 (0.44) 75 (0.33)
EMT 1/4"-20
B2003 1" (25) 6 (8.1) 600 (2.67) 100 (0.44) 75 (0.33)
Conduit
Sizes B2004 11/4" (32) 1/4"-20 6 (8.1) 600 (2.67) 150 (0.67) 150 (0.67)
B2005 11/2" (40) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 150 (0.67)
B2006 2" (50) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 200 (0.89)

B2008 1/2" (15) 1/44"-20 6 (8.1) 400 (1.78) 75 (0.33) 50 (0.22)


B2009 3/4" (20) 1/4"-20 6 (8.1) 600 (2.67) 100 (0.44) 75 (0.33)
B2010 1" (25) 1/4"-20 6 (8.1) 600 (2.67) 100 (0.44) 75 (0.33)
B2011 11/4" (32) 1/4"-20 6 (8.1) 600 (2.67) 150 (0.67) 150 (0.67)
Rigid B2012 11/2" (40) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 150 (0.67)
Conduit 5/16"-18
B2013 2" (50) 9 (12.2) 800 (3.56) 250 (1.11) 200 (0.89)
or
Pipe B2014 21/2" (65) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 200 (0.89)
Sizes B2015 3" (80) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 200 (0.89)
B2016 31/2" (90) 5/16"-18 10 (13.5) 1000 (4.45) 350 (1.55) 200 (0.89)
B2017 4" (100) 5/16"-18 10 (13.5) 1000 (4.45) 350 (1.55) 250 (1.11)
B2019 5" (125) 5/16"-18 10 (13.5) 1000 (4.45) 450 (2.00) 250 (1.11)
B2020 6" (150) 3/8"-16 13 (17.6) 1000 (4.45) 450 (2.00) 250 (1.11)

B2026 1/2" (15) 1/4"-20 6 (8.1) 400 (1.78) 75 (0.33) 50 (0.22)


B2028 3/4" (20) 1/4"-20 6 (8.1) 400 (1.78) 100 (0.44) 75 (0.33)
B2030 1" (25) 1/4"-20 6 (8.1) 600 (2.67) 100 (0.44) 75 (0.33)
B2032 11/4" (32) 1/4"-20 6 (8.1) 600 (2.67) 150 (0.67) 150 (0.67)
Copper
B2034 11/2" (40) 1/4"-20 6 (8.1) 600 (2.67) 250 (1.11) 150 (0.67)
Tubing
B2038 2" (50) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 150 (0.67)
Sizes
B2042 21/2" (65) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 200 (0.89)
B2046 3" (80) 5/16"-18 9 (12.2) 800 (3.56) 250 (1.11) 200 (0.89)
B2050 31/2" (90) 5/16"-18 10 (13.5) 1000 (4.45) 350 (1.55) 200 (0.89)
B2054 4" (100) 5/16"-18 10 (13.5) 1000 (4.45) 350 (1.55) 250 (1.11)

FT = Transverse Design Load FL = Longitudinal Design Load * Minimum Safety Factor of 3.0
Design Loads are to be used in orientation as shown for seismic design purposes only.
Contact the factory for gravity application design loads.
See note D) on page 9 for required tightening torques.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 70 of
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:17 PM Page 2

APPROVED COMPONENTS
Vertical Load
Seismic Approval:
Transverse or Longitudinal Brace for
Pipe or Conduit. Attachment of Pipe or
Conduit to 12 Ga. (2.6mm) 15/8” (41mm)
Wide Strut.

Bolts and Channel Nuts


FL Not Included

FT

B2400 Series
Standard Pipe Straps

Bolt Bolt Design Loads *


Part No. Size Size Torque Vertical FT FL
in. (mm) ft.•lbs. (Nm) lbs. (kN) lbs. (kN) lbs. (kN)

B2400-1/2 1/2" (15) 1/4"-20 6 (8.1) 600 (2.67) 600 (2.67) 105 (0.47)
B2400-3/4 3/4" (20) 1/4"-20 6 (8.1) 600 (2.67) 600 (2.67) 105 (0.47)
B2400-1 1" (25) 1/4"-20 6 (8.1) 600 (2.67) 600 (2.67) 120 (0.53)
B2400-11/4 11/4" (32) 1/4"-20 6 (8.1) 600 (2.67) 600 (2.67) 120 (0.53)
B2400-11/2 11/2" (40) 1/4"-20 6 (8.1) 600 (2.67) 600 (2.67) 120 (0.53)
B2400-2 2" (50) 3/8"-16 19 (25.4) 1200 (5.34) 1200 (5.34) 200 (0.89)
B2400-21/2 21/2" (65) 3/8"-16 19 (25.4) 1200 (5.34) 1200 (5.34) 200 (0.89)
B2400-3 3" (80) 3/8"-16 19 (25.4) 1200 (5.34) 1200 (5.34) 400 (1.78)
B2400-31/2 31/2" (90) 3/8"-16 19 (25.4) 1200 (5.34) 1200 (5.34) 400 (1.78)
B2400-4 4" (100) 1/2"-13 50 (66.9) 1500 (6.67) 1500 (6.67) 750 (3.33)
B2400-5 5" (125) 1/2"-13 50 (66.9) 1500 (6.67) 1500 (6.67) 750 (3.33)
B2400-6 6" (150) 1/2"-13 50 (66.9) 1500 (6.67) 1500 (6.67) 750 (3.33)
B2400-8 8" (200) 1/2"-13 50 (66.9) 1500 (6.67) 1500 (6.67) 750 (3.33)
B2400-10 10" (250) 1/2"-13 50 (66.9) 1500 (6.67) 1500 (6.67) 750 (3.33)
B2400-12 12" (300) 1/2"-13 50 (66.9) 1500 (6.67) 1500 (6.67) 750 (3.33)

FT = Transverse Design Load FL = Longitudinal Design Load * Minimum Safety Factor of 3.0

Design Loads are to be used in orientation as shown for seismic design purposes only.
Contact the factory for gravity application design loads.
See note D) on page 9 for required tightening torques.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 71 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:17 PM Page 3

APPROVED COMPONENTS
Seismic Approval:
Hanger Rod Attachment
'C'
Material: Steel
Specify 'L'
Standard Finish: Plain or Electro-Plated Zinc
Service: Designed for suspending hanger rods from
wood structures.
'A' 'B'
Thread Size Ordering: Specify part number, rod size, length and
finish.

B3213 Series
Coach Screw Rod

Coach Screw Rod Thread


Thread Standard Rod Lengths Thread Length Length Design Load
Part No. Size 'A' 'L' 'B' 'C'
in. (mm) in. (mm) in. (mm) lbs. (kN)

3 3 1
B3213- /8 x 'L' /8"-16 *3 /2", 6", 8", 10", 12" (88.9, 152.4, 203.2, 254.0, 304.8) 2" (50.8) 2" (50.8) 390 (1.73)

1 1 1 1 1
B3213- /2 x 'L' /2"-13 *3 /2", 6", 8", 10", 12" (88.9, 152.4, 203.2, 254.0, 304.8) 2 /2" (63.5) 2 /2" (63.5) 640 (2.84)

*3/8 x 31/2” (89mm) and 1/2 x 31/2” (89mm) will have a coach screw thread length of 2" (50.8) and a rod thread length of 1" (25.4).
Design Load is based on proper installation and solid wood.

Seismic Approval:
'T'
Hanger Rod Attachment
'B'
'A'
Hole Size Material: Steel (Stainless steel available)
'D'
Standard Finish: Plain or Electro-Plated
Service: Designed for attaching a hanger rod to
'C' 'D' the side of beams or walls.
Ordering: Specify part number and finish.
'B'

B3060
Side Beam Angle Clip

Hole Size Design Load


Part No. 'A' 'B' 'C' 'D' 'T'
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN)

3 7 3 1 1
B3060- /8 /16" (11.1) 2 /16" (55.6) 2" (50.8) 1 /4" (31.7) /4" (6.3) 305 (1.35)

B3060-1/2 9
/16" (14.3) 23/16" (55.6) 2" (50.8) 11/4" (31.7) 1
/4" (6.3) 565 (2.51)
5 11 1 1
B3060- /8 /16" (17.5) 2" (50.8) 2" (50.8) 1 /4" (31.7) /4" (6.3) 909 (4.02)

B3060-3/4 13
/16" (20.6) 3" (76.2) 3" (76.2) 13/4" (44.4) 3
/8" (9.5) 1355 (6.03)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 72 of
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:17 PM Page 4

APPROVED COMPONENTS

Seismic Approval:
Structure Attachment

'A'
Hole Size
'C'
Material: Steel
Standard Finish: Plain or Electro-Plated Zinc
'B'
Hole Spacing Service: Designed for brace attachment to the side of
wood beams.

6” Ordering: Specify part number and finish.


(152mm)
9/16” (14mm)
Hole

4”
(101mm)
3/8”
(9mm)

B3060SW
Side Beam Angle Clip for Wood Beams

Hole Size
Part No. 'A' 'B' 'C'
in. (mm) in. (mm) in. (mm)

B3060SW-1/2 9
/16" (14.3) 2" (50.8) 4" (101.6)
5 11
B3060SW- /8 /16" (17.5) 21/2" (63.5) 5" (127.0)
3 13
B3060SW- /4 /16" (20.6) 3" (76.2) 6" (152.4)
1
B3060SW-1 1 /8" (28.6) 4" (101.6) 8" (203.2)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 73 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:17 PM Page 5

APPROVED COMPONENTS

Seismic Approval:
Structure Attachment
'T'2

Material: Malleable Iron


Standard Finish: Plain

'A 'A Service: Designed for attaching bolts to the taper


of an I-beam or channel flange.
'T'1 Ordering: Specify part number and finish.
B3234
Bevel Washer

For Bolt Hole


Part No. Size Diameter 'A' T1 T2
in. (mm) in. (mm) in. (mm) in. (mm)
3 3 7 1 5 11
B3234- /8 /8"-16 /16" (11.1) 1 /4" (31.7) /32" (3.9) /32" (8.7)
B3234-1/2 1
/2"-13 9
/16" (14.2) 11/4" (31.7) 5
/32" (3.9) 11
/32" (8.7)
B3234-5/8 5
/8"-11 11
/16" (17.4) 11/2" (38.1) 5
/32" (3.9) 13
/32" (10.3)
B3234-3/4 3
/4"-10 13
/16" (20.6) 11/2" (38.1) 7
/32" (5.5) 15
/32" (11.9)
B3234-7/8 7
/8"-9 15
/16" (23.8) 2" (50.8) 7
/32" (5.5) 9
/16" (14.3)

Specify 'C'
'T'

B3248
Steel Washer Plate

Part No. 'A' 'T' “C” 'A 'A


in. (mm) in. (mm)

B3248-2 x 2 x 1/4 2" (50.8) 1


/4" (6.3)
1 1
B3248-3 x 3 x /4 3" (76.2) /4" (6.3) Seismic Approval:
B3248-4 x 4 x 1/4 4" (101.6) 1
/4" (6.3) Structure Attachment
B3248-5 x 5 x 1/4 5" (127.0) 1
/4" (6.3)
1 1
B3248-6 x 6 x /4 6" (152.4) /4" (6.3)

B3248-3 x 3 x 3/8 3" (76.2) 3


/8" (9.5) Specify Material: Steel
3 3
B3248-4 x 4 x /8 4" (101.6) /8" (9.5) Rod Standard Finish: Plain
B3248-5 x 5 x 3/8 5" (127.0) 3
/8" (9.5) Size Service: Designed as a heavy-duty washer to
B3248-6 x 6 x 3/8 6" (152.4) 3
/8" (9.5) suspend hanger rods.
B3248-4 x 4 x 1/2 4" (101.6) 1
/2" (12.7) Ordering: Specify part number, rod size and finish.
1 1
B3248-5 x 5 x /2 5" (127.0) /2" (12.7)

B3248-6 x 6 x 1/2 6" (152.4) 1


/2" (12.7)
1 1
B3248-8 x 8 x /2 8" (203.2) /2" (12.7)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 74 of
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:17 PM Page 6

APPROVED COMPONENTS

Seismic Approval:
Structure Attachment

Material: Steel
Standard Finish: Plain or Electro-Plated
Service: Designed to be embedded in concrete for
attachment of 3/8"-16 to 1/2"-13 hanger rods.
Ordering: Specify part number, size and finish.
How to Install: Locate and nail to form. Pour
concrete and strip forms when set. Remove color
coded plug, install rod and lock with jam nut.

'A'

'H'

11/4”
(31.7mm)

B2501
Spot Insert

Part No. Rod Size 'A' 'H'


in. (mm) in. (mm)
3 3 15 7
B2501- /8 /8"-16 3 /64" (82.1) 1 /8" (47.6)
1 1 5 7
B2501- /2 /2"-13 4 /16" (109.5) 1 /8" (47.6)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 75 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:18 PM Page 7

APPROVED COMPONENTS
2” Seismic Approval:
(50.8mm)
Structure Attachment
31/4”
(82.5mm)
Material: Steel
Standard Finish: Electro-Plated
Service: Designed to be embedded in concrete for
Material attachment of 3/8”-16 through 7/8”-9 hanger rods.
12 Ga.
(2.6mm) Ordering: Specify part number and finish for both
spot insert and square nut.

11/2” 19/16”
(38.1mm) (39.7mm)
Knockout
for Square Nut
Insertion

B2500
Spot Insert Thread
* Order N2500 Nuts Separately Size
11/4” Part No. 'A'
(31.7mm) 5/16”
(7.9mm) N2500-1/2 1
/2"-13
N2500-5/8 5
/8"-11
3 3
11/4” N2500- /4 /4"-10
(31.7mm)
N2500-7/8 7
/8"-9

Thread Size ‘A’

N2500
Square Nut

Seismic Approval:
Structure Attachment

Wedge Anchors
Approved for sizes 3/8, 1/2, 5/8 and 3/4 with minimum
embedment depth noted on approved details.
Hilti KB-II or approved equal

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 76 of
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:18 PM Page 8

APPROVED COMPONENTS
CONCRETE INSERT
15/8"
4" (41mm)
(101mm)
29/16"
(65mm)
11/2"
(38mm)

3/4"
(19mm)
15/8"
(41mm) 27/8"
13/8" (73mm)
(35mm) .188 (4.8mm) Knockouts
for Nailing Inserts to
B3332 11/16"
Forms
End Cap Styrofoam (17mm)
Filler
Styrofoam Filler
13/8"
B32I-8 (35mm)

Part No. Length Design Load*


B32I-12 thru B32I-240
in. (mm) lbs. (kN)

B32I-8 8" (203) 1200 (5.34)


B206 End Caps
B32I-12 12" (305) 2000 (8.89)
B32I-16 16" (406) 2000 (8.89)
Seismic Approval:
B32I-20 20" (508) 2000 (8.89)
Structure Attachment
B32I-24 24" (609) 2000 (8.89)
B32I-32 32" (813) 2000 (8.89)
Material: 12 Ga. (2.6mm)

B32I-40 40" (914) 2000 (8.89)


B32I-48 48" (1219) 2000 (8.89) Loads concentrated within the last 2" (51mm) of
B32I-60 60" (1524) 2000 (8.89) concrete inserts 8" (203mm) and longer should not
B32I-72 72" (1829) 2000 (8.89)
exceed 1000 Lbs. (4.45kN).
B32I-84 84" (2133) 2000 (8.89) Concrete inserts should be secured to forms on
B32I-96 96" (2438) 2000 (8.89)
16" (406mm) to 24" (609mm) intervals.
B32I-108 108" (2743) 2000 (8.89) B32I continuous concrete inserts are made from
B32I-120 120" (3048) 2000 (8.89) B32 channel. Use channel nuts designed for use in
B32 channel.
B32I-144 144" (3657) 2000 (8.89)
B32I-168 168" (4267) 2000 (8.89) Styrofoam fillers are supplied with all B32I concrete
inserts. B3332 end caps are furnished with inserts
B32I-192 192" (4877) 2000 (8.89)
through 16" (406mm) long, and B206 end caps are
B32I-216 216" (5486) 2000 (8.89) furnished with inserts over 16" (406mm) long.
B32I-240 240" (6096) 2000 (8.89)

* Continuous insert allowable load per foot of


insert - 2000 lbs. (8.89kN) in 3000 psi (20.7MPa)
normal weight concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 77 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:18 PM Page 9

APPROVED COMPONENTS
CONCRETE INSERT
15/8"
4" (41mm)
(101mm)
29/16"
(65mm)
11/2"
(38mm)

3/4"
(19mm)
15/8" 31/8"
(41mm) (79mm)
15/8"
(41mm) .188 (4.8mm) Knockouts
Styrofoam for Nailing Inserts to
11/16"
B3322 Filler Forms
(17mm)
End Cap
Styrofoam Filler
15/8"
B22I-8 (41mm)

Part No. Length Design Load*


B22I-12 thru B22I-240
in. (mm) lbs. (kN)
B205 End Caps
B22I-8 8" (203) 1200 (5.34)
B22I-12 12" (305) 2000 (8.89)
B22I-16 16" (406) 2000 (8.89)
Seismic Approval:
B22I-20 20" (508) 2000 (8.89)
Structure Attachment
B22I-24 24" (609) 2000 (8.89)
B22I-32 32" (813) 2000 (8.89)
Material: 12 Ga. (2.6mm)

B22I-40 40" (914) 2000 (8.89)


B22I-48 48" (1219) 2000 (8.89) Loads concentrated within the last 2" (51mm) of
B22I-60 60" (1524) 2000 (8.89) concrete inserts 8" (203mm) and longer should not
B22I-72 72" (1829) 2000 (8.89)
exceed 1000 Lbs. (4.45kN).
B22I-84 84" (2133) 2000 (8.89) Concrete inserts should be secured to forms on
B22I-96 96" (2438) 2000 (8.89)
16" (406mm) to 24" (609mm) intervals.
B22I-108 108" (2743) 2000 (8.89) B22I continuous concrete inserts are made from
B22I-120 120" (3048) 2000 (8.89) B22 channel. Use channel nuts designed for use in
B22 channel.
B22I-144 144" (3657) 2000 (8.89)
B22I-168 168" (4267) 2000 (8.89) Styrofoam fillers are supplied with all B22I concrete
inserts. B3322 end caps are furnished with inserts
B22I-192 192" (4877) 2000 (8.89)
through 16" (406mm) long, and B205 end caps are
B22I-216 216" (5486) 2000 (8.89) furnished with inserts over 16" (406mm) long.
B22I-240 240" (6096) 2000 (8.89)

* Continuous insert allowable load per foot of


insert - 2000 lbs. (8.89kN) in 3000 psi (20.7MPa)
normal weight concrete.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 78 of
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:18 PM Page 10

METRIC CONVERSION CHARTS


To Convert From To Multiply By To Convert From To Multiply By

Angle Length
degree radian (rad) 1.745329 x 10-2 foot (ft) meter (m) 3.048000 x 10-1
radian (rad) degree 5.729578 x 10+1 inch (in) meter (m) 2.540000 x 10-2
mil meter (m) 2.540000 x 10-5
Area
inch (in) micrometer (µm) 2.540000 x 10+4
foot2 square meter (m2) 9.290304 x 10-2
inch2 square meter (m2) 6.451600 x 10-4 meter (m) foot (ft) 3.280840
circular mil square meter (m2) 5.067075 x 10-10 meter (m) inch (in) 3.937008 x 10+1
sq. centimeter (cm2) square inch (in2) 1.550003 x 10-1 meter (m) mil 3.937008 x 10+4
square meter (m2) foot2 1.076391 x 10+1 micrometer (µm) inch (in) 3.937008 x 10-5
square meter (m2) inch2 1.550003 x 10+3 Volume
square meter (m2) circular mil 1.973525 x 10+9 foot3 cubic meter (m3) 2.831685 x 10-2
inch3 cubic meter (m3) 1.638706 x 10-5
Temperature
cubic centimeter (cm3) cubic inch (in3) 6.102374 x 10-2
degree Fahrenheit degree Celsius t°C = (t°F - 32) / 1.8
cubic meter (m3) foot3 3.531466 x 10+1
degree Celsius degree Fahrenheit t°F = 1.8 t°C + 32
cubic meter (m3) inch3 6.102376 x 10+4
Force gallon (U.S. liquid) cubic meter (m3) 3.785412 x 10-3
pounds-force (lbf) newtons (N) 4.448222

To Convert From To Multiply By


Bending Moment or Torque
lbf•ft newton meter (N•m) 1.355818
lbf•in newton meter (N•m) 1.129848 x 10-1
N•m lbf•ft 7.375621 x 10-1
N•m lbf•in 8.850748
Mass
pound (avoirdupois) kilogram (kg) 4.535924 x 10-1
kilogram (kg) pound (avoirdupois) 2.204622
Mass Per Unit Length
lb/ft kilogram per meter (kg/m) 1.488164
lb/in kilogram per meter (kg/m) 1.785797 x 10+1
kg/m lb/ft 6.719689 x 10-1
kg/m lb/in 5.599741 x 10-2
Mass Per Unit Volume
lb/ft3 kilogram per cubic meter (kg/m3) 1.601846 x 10+1
lb/in 3 kilogram per cubic meter (kg/m3) 2.767990 x 10+4
kg/m3 lb/ft3 6.242797 x 10-2
kg/m3 lb/in3 3.612730 x 10-5
lbs/ft 3 lbs/in3 1.728000 x 10+3
Mass Per Area Unit
lb/ft2 kilogram per square meter (kg/m2) 4.882428
kg/m 2 pound per square foot (lb/ft2) 2.048161 x 10-1
Pressure or Stress
lbf/in2 (psi) pascal (Pa) 6.894757 x 10+3
kip/in2 (ksi) pascal (Pa) 6.894757 x 10+6
lbf/in2 (psi) megapascals (MPa) 6.894757 x 10-3
pascal (Pa) pound force per sq. inch (psi) 1.450377 x 10-4
pascal (Pa) kip per sq. inch (ksi) 1.450377 x 10-7

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 79 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:18 PM Page 11

APPENDIX - SEISMIC MAP

SEISMIC MAP *

2B 2A
3
0 1
1
2B
3 4 2A
2B
0 2A
1
3
2B
3 2A
3
4 1
1
0

1 1
4 3 2A
2A

2B 1
1
3
4 3
2A
3 2A
1 2B 1
0 1
Alaska 1
1
0
2B
2B 1
3
Hawaii 0
1 4 2B
0
4

3 4

4
3 Refer to Figure 16A-2
Aleutian Islands Puerto Rico
for California.

* Uniform Building Code

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 80 of
Structural Engineer S 3913
**SRS2002-OSpg.70-81 (11/02) N 1/3/03 5:18 PM Page 12

This Page Has Been


Intentionally Left Blank

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 81 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 1

Appendix 1
Support Spacing for Single Rod Hanger Piping

Pages 83 - 86 Tables 1 & 2 for Seismic Force Level 0.15g (ASD)

Pages 87 - 90 Tables 1 & 2 for Seismic Force Level 0.30g (ASD)

Pages 91 - 94 Tables 1 & 2 for Seismic Force Level 0.45g (ASD)

Pages 95 - 98 Tables 1 & 2 for Seismic Force Level 0.50g (ASD)

Pages 99 - 102 Tables 1 & 2 for Seismic Force Level 0.75g (ASD)

Pages 103 - 106 Tables 1 & 2 for Seismic Force Level 1.00g (ASD)

Table 1 - Maximum Hanger Spacing for Steel Pipe


Table 2 - Maximum Hanger Spacing for Copper Tubing

This Appendix contains bracing tables developed using allowable stress design
(ASD) for the following seismic force values (i.e. “g-values”): .15g (ASD),
.30g (ASD), .45g (ASD), .50g (ASD), .75g (ASD), and 1.0g (ASD). The
building code uses strength design which can be increased by a factor of 1.4.
(See page 1 for further information.) These charts cover the vast majority of
seismic requirements from coast to coast, from Zone 1 to Zone 4 applications,
and take into account the many codes which may be referenced for a specific
project.

The seismic zone, building type, and other factors determine the level of
seismic force for a particular project. The project design professional should
determine the correct seismic force value using the appropriate building code and
local requirements. Use of the correct table is very important to ensure that the
correct brace spacing and anchorage is provided. See pages 1 - 8 for more
information.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 82 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 2

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 1 - Maximum Hanger Spacing for Steel Pipe
Seismic Force Level (g’s) 0.15g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 40 (12.19) I 80 (24.38) I 17 (0.07) 3/8"-16 0.98 (1.46)
1/2" (15) 6 (1.83) 36 (10.98) I 72 (21.94) I 17 (0.07) 3/8"-16 0.98 (1.46)
1/2" (15) 7 (2.13) 35 (10.67) I 70 (21.35) I 17 (0.07) 3/8"-16 0.98 (1.46)
1/2" (15) 8 (2.44) 40 (12.19) I 80 (24.38) I 20 (0.09) 3/8"-16 0.98 (1.46)
1/2" (15) 10 (3.05) 40 (12.19) I 80 (24.38) I 22 (0.10) 3/8"-16 0.98 (1.46)

3/4" (20) 5 (1.52) 40 (12.19) I 80 (24.38) I 23 (0.10) 3/8"-16 1.36 (2.02)


3/4" (20) 6 (1.83) 36 (10.98) I 72 (21.94) I 23 (0.10) 3/8"-16 1.36 (2.02)
3/4" (20) 7 (2.13) 35 (10.67) I 70 (21.35) I 24 (0.10) 3/8"-16 1.36 (2.02)
3/4" (20) 8 (2.44) 40 (12.19) I 80 (24.38) I 28 (0.12) 3/8"-16 1.36 (2.02)
3/4" (20) 10 (3.05) 40 (12.19) I 80 (24.38) I 31 (0.14) 3/8"-16 1.36 (2.02)

1" (25) 5 (1.52) 40 (12.19) I 80 (24.38) I 36 (0.16) 3/8"-16 2.06 (3.06)


1" (25) 6 (1.83) 36 (10.98) I 72 (21.94) I 35 (0.15) 3/8"-16 2.06 (3.06)
1" (25) 7 (2.13) 35 (10.67) I 70 (21.35) I 37 (0.16) 3/8"-16 2.06 (3.06)
1" (25) 8 (2.44) 40 (12.19) I 80 (24.38) I 42 (0.18) 3/8"-16 2.06 (3.06)
1" (25) 10 (3.05) 40 (12.19) I 80 (24.38) I 46 (0.20) 3/8"-16 2.06 (3.06)

11/4" (32) 5 (1.52) 40 (12.19) I 80 (24.38) I 50 (0.22) 3/8"-16 2.92 (4.34)


11/4" (32) 6 (1.83) 36 (10.98) I 72 (21.94) I 50 (0.22) 3/8"-16 2.92 (4.34)
11/4" (32) 7 (2.13) 35 (10.67) I 70 (21.35) I 52 (0.23) 3/8"-16 2.92 (4.34)
11/4" (32) 8 (2.44) 40 (12.19) I 80 (24.38) I 60 (0.26) 3/8"-16 2.92 (4.34)
11/4" (32) 10 (3.05) 40 (12.19) I 80 (24.38) I 66 (0.29) 3/8"-16 2.92 (4.34)

11/2" (40) 5 (1.52) 40 (12.19) I 80 (24.38) I 62 (0.27) 3/8"-16 3.60 (5.36)


11/2" (40) 6 (1.83) 36 (10.98) I 72 (21.94) I 62 (0.27) 3/8"-16 3.60 (5.36)
11/2" (40) 9 (2.74) 36 (10.98) I 72 (21.94) I 73 (0.32) 3/8"-16 3.60 (5.36)
11/2" (40) 10 (3.05) 40 (12.19) I 80 (24.38) I 81 (0.36) 3/8"-16 3.60 (5.36)
11/2" (40) 12 (3.66) 36 (10.98) I 72 (21.94) I 84 (0.37) 3/8"-16 3.60 (5.36)

2" (50) 5 (1.52) 40 (12.19) I 80 (24.38) I 88 (0.39) 3/8"-16 5.10 (7.59)


2" (50) 6 (1.83) 36 (10.98) I 72 (21.94) I 87 (0.38) 3/8"-16 5.10 (7.59)
2" (50) 8 (2.44) 40 (12.19) I 80 (24.38) I 104 (0.46) 3/8"-16 5.10 (7.59)
2" (50) 10 (3.05) 40 (12.19) I 80 (24.38) I 115 (0.51) 3/8"-16 5.10 (7.59)
2" (50) 12 (3.66) 36 (10.98) I 72 (21.94) I 119 (0.53) 3/8"-16 5.10 (7.59)

21/2" (65) 5 (1.52) 40 (12.19) I 80 (24.38) I 136 (0.60) 1/2"-13 7.87 (11.71)
21/2" (65) 6 (1.83) 36 (10.98) I 72 (21.94) I 135 (0.60) 1/2"-13 7.87 (11.71)
21/2" (65) 8 (2.44) 40 (12.19) I 80 (24.38) I 161 (0.71) 1/2"-13 7.87 (11.71)
21/2" (65) 10 (3.05) 40 (12.19) I 80 (24.38) I 177 (0.79) 1/2"-13 7.87 (11.71)
21/2" (65) 12 (3.66) 36 (10.98) I 72 (21.94) I 184 (0.82) 1/2"-13 7.87 (11.71)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 83 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 3

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Field Maximum Transverse Maximum Longitudinal Hanger &
Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 6 (1.83) 36 (10.98) I 72 (21.94) I 184 (0.82) 1/2"-13 10.75 (16.00)
3" (80) 8 (2.44) 40 (12.19) I 80 (24.38) II 219 (0.97) 1/2"-13 10.75 (16.00)
3" (80) 10 (3.05) 40 (12.19) I 80 (24.38) II 242 (1.07) 1/2"-13 10.75 (16.00)
3" (80) 12 (3.66) 36 (10.98) I 72 (21.94) I 252 (1.12) 1/2"-13 10.75 (16.00)
3" (80) 15 (4.57) 30 (9.15) I 60 (18.30) I 266 (1.18) 1/2"-13 10.75 (16.00)

31/2" (90) 6 (1.83) 36 (10.98) I 72 (21.94) II 229 (1.02) 1/2"-13 13.39 (19.92)
31/2" (90) 8 (2.44) 40 (12.19) I 80 (24.38) II 273 (1.21) 1/2"-13 13.39 (19.92)
31/2" (90) 10 (3.05) 40 (12.19) I 80 (24.38) II 301 (1.34) 1/2"-13 13.39 (19.92)
31/2" (90) 12 (3.66) 36 (10.98) I 72 (21.94) II 313 (1.39) 1/2"-13 13.39 (19.92)
31/2" (90) 15 (4.57) 30 (9.15) I 60 (18.30) I 331 (1.47) 1/2"-13 13.39 (19.92)

4" (100) 6 (1.83) 36 (10.98) I 72 (21.94) II 279 (1.24) 5/8"-11 16.31 (24.27)
4" (100) 8 (2.44) 40 (12.19) I 80 (24.38) II 333 (1.48) 5/8"-11 16.31 (24.27)
4" (100) 10 (3.05) 40 (12.19) I 80 (24.38) II 367 (1.63) 5/8"-11 16.31 (24.27)
4" (100) 12 (3.66) 36 (10.98) I 72 (21.94) II 382 (1.70) 5/8"-11 16.31 (24.27)
4" (100) 15 (4.57) 30 (9.15) I 60 (18.30) II 404 (1.79) 5/8"-11 16.31 (24.27)

5" (125) 8 (2.44) 40 (12.19) II 80 (24.38) III 477 (2.12) 5/8"-11 23.39 (34.81)
5" (125) 10 (3.05) 40 (12.19) II 80 (24.38) III 526 (2.34) 5/8"-11 23.39 (34.81)
5" (125) 12 (3.66) 36 (10.98) II 72 (21.94) III 547 (2.43) 5/8"-11 23.39 (34.81)
5" (125) 15 (4.57) 30 (9.15) I 60 (18.30) II 579 (2.57) 5/8"-11 23.39 (34.81)
5" (125) 18 (5.49) 36 (10.98) II 54 (16.47) II 632 (2.81) 5/8"-11 23.39 (34.81)

6" (150) 8 (2.44) 40 (12.19) II 80 (24.38) IV 642 (2.85) 3/4"-10 31.49 (46.86)
6" (150) 10 (3.05) 40 (12.19) II 80 (24.38) IV 709 (3.15) 3/4"-10 31.49 (46.86)
6" (150) 12 (3.66) 36 (10.98) II 72 (21.94) IV 737 (3.28) 3/4"-10 31.49 (46.86)
6" (150) 15 (4.57) 30 (9.15) II 60 (18.30) III 779 (3.46) 3/4"-10 31.49 (46.86)
6" (150) 18 (5.49) 36 (10.98) II 72 (21.94) IV 935 (4.16) 3/4"-10 31.49 (46.86)

8" (200) 8 (2.44) 40 (12.19) III 80 (24.38) V 1025 (4.56) 3/4"-10 50.23 (74.75)
8" (200) 10 (3.05) 40 (12.19) III 80 (24.38) V 1130 (5.02) 3/4"-10 50.23 (74.75)
8" (200) 12 (3.66) 36 (10.98) III 72 (21.94) V 1175 (5.22) 3/4"-10 50.23 (74.75)
8" (200) 15 (4.57) 30 (9.15) III 60 (18.30) IV 1243 (5.53) 3/4"-10 50.23 (74.75)
8" (200) 20 (6.10) 40 (12.19) III 80 (24.38) V 1658 (7.37) 3/4"-10 50.23 (74.75)

10" (250) 8 (2.44) 40 (12.19) IV 56 (17.08) V 1253 (5.57) 7/8"-9 74.60 (111.01)
10" (250) 10 (3.05) 40 (12.19) IV 60 (18.29) V 1455 (6.47) 7/8"-9 74.60 (111.01)
10" (250) 12 (3.66) 36 (10.98) IV 60 (18.29) V 1611 (7.16) 7/8"-9 74.60 (111.01)
10" (250) 15 (4.57) 30 (9.15) IV 60 (18.29) V 1846 (8.21) 7/8"-9 74.60 (111.01)
10" (250) 20 (6.10) 40 (12.19) IV 60 (18.29) V 2238 (9.95) 7/8"-9 74.60 (111.01)

12" (300) 8 (2.44) 40 (12.19) V 40 (12.19) V 1470 (6.54) 7/8"-9 102.10 (151.94)
12" (300) 10 (3.05) 40 (12.19) V 40 (12.19) V 1685 (7.49) 7/8"-9 102.10 (151.94)
12" (300) 12 (3.66) 36 (10.98) V 36 (10.98) V 1838 (8.17) 7/8"-9 102.10 (151.94)
12" (300) 15 (4.57) 30 (9.15) V 45 (13.72) V 2297 (10.22) 7/8"-9 102.10 (151.94)
12" (300) 18 (5.49) 36 (10.98) V 36 (10.98) V 2481 (11.03) 7/8"-9 102.10 (151.94)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 84 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 4

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING

Table 2 - Maximum Hanger Spacing for Copper Tubing


Seismic Force Level (g’s) 0.15g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 25 (7.62) I 50 (15.25) I 5.5 (0.024) 3/8"-16 0.43 (0.64)
1/2" (15) 6 (1.83) 24 (7.32) I 48 (14.64) I 5.8 (0.025) 3/8"-16 0.43 (0.64)
1/2" (15) 7 (2.13) 21 (6.40) I 42 (12.81) I 5.9 (0.026) 3/8"-16 0.43 (0.64)
1/2" (15) 8 (2.44) 24 (7.32) I 48 (14.64) I 6.7 (0.030) 3/8"-16 0.43 (0.64)
1/2" (15) 10 (3.05) 10 (3.05) I 20 (6.10) I 5.8 (0.026) 3/8"-16 0.43 (0.64)

3/4" (20) 5 (1.52) 30 (9.15) I 60 (18.30) I 11.8 (0.052) 3/8"-16 0.83 (1.23)
3/4" (20) 6 (1.83) 30 (9.15) I 60 (18.30) I 12.7 (0.056) 3/8"-16 0.83 (1.23)
3/4" (20) 7 (2.13) 28 (8.54) I 56 (17.08) I 13.1 (0.058) 3/8"-16 0.83 (1.23)
3/4" (20) 8 (2.44) 24 (7.32) I 48 (14.64) I 12.9 (0.057) 3/8"-16 0.83 (1.23)
3/4" (20) 10 (3.05) 20 (6.10) I 40 (12.19) I 13.7 (0.061) 3/8"-16 0.83 (1.23)

1" (25) 5 (1.52) 35 (10.67) I 70 (21.35) I 18.6 (0.083) 3/8"-16 1.18 (1.75)
1" (25) 6 (1.83) 36 (10.98) I 72 (21.94) I 20.2 (0.090) 3/8"-16 1.18 (1.75)
1" (25) 7 (2.13) 35 (10.67) I 70 (21.35) I 21.1 (0.094) 3/8"-16 1.18 (1.75)
1" (25) 8 (2.44) 32 (9.76) I 64 (19.52) I 21.2 (0.094) 3/8"-16 1.18 (1.75)
1" (25) 10 (3.05) 30 (9.15) I 60 (18.30) I 23.0 (0.102) 3/8"-16 1.18 (1.75)

11/4" (32) 5 (1.52) 40 (12.19) I 80 (24.38) I 27.1 (0.120) 3/8"-16 1.57 (2.33)
11/4" (32) 6 (1.83) 36 (10.98) I 72 (21.94) I 26.8 (0.119) 3/8"-16 1.57 (2.33)
11/4" (32) 7 (2.13) 35 (10.67) I 70 (21.35) I 28.0 (0.124) 3/8"-16 1.57 (2.33)
11/4" (32) 8 (2.44) 40 (12.19) I 80 (24.38) I 32.0 (0.142) 3/8"-16 1.57 (2.33)
11/4" (32) 10 (3.05) 30 (9.15) I 60 (18.30) I 30.6 (0.136) 3/8"-16 1.57 (2.33)

11/2" (40) 5 (1.52) 40 (12.19) I 80 (24.38) I 36.2 (0.161) 3/8"-16 2.10 (3.17)
11/2" (40) 6 (1.83) 36 (10.98) I 72 (21.94) I 35.9 (0.159) 3/8"-16 2.10 (3.17)
11/2" (40) 8 (2.44) 40 (12.19) I 80 (24.38) I 42.8 (0.190) 3/8"-16 2.10 (3.17)
11/2" (40) 10 (3.05) 40 (12.19) I 80 (24.38) I 47.2 (0.210) 3/8"-16 2.10 (3.17)
11/2" (40) 12 (3.66) 36 (10.98) I 72 (21.94) I 49.1 (0.218) 3/8"-16 2.10 (3.17)

2" (50) 5 (1.52) 40 (12.19) I 80 (24.38) I 58.1 (0.258) 3/8"-16 3.37 (5.01)
2" (50) 6 (1.83) 36 (10.98) I 72 (21.94) I 57.6 (0.256) 3/8"-16 3.37 (5.01)
2" (50) 8 (2.44) 40 (12.19) I 80 (24.38) I 68.7 (0.305) 3/8"-16 3.37 (5.01)
2" (50) 10 (3.05) 40 (12.19) I 80 (24.38) I 75.8 (0.337) 3/8"-16 3.37 (5.01)
2" (50) 12 (3.66) 36 (10.98) I 72 (21.94) I 78.9 (0.351) 3/8"-16 3.37 (5.01)

21/2" (65) 5 (1.52) 40 (12.19) I 80 (24.38) I 84.9 (0.377) 1/2"-13 4.92 (7.32)
21/2" (65) 6 (1.83) 36 (10.98) I 72 (21.94) I 84.1 (0.374) 1/2"-13 4.92 (7.32)
21/2" (65) 9 (2.74) 36 (10.98) I 72 (21.94) I 99.6 (0.443) 1/2"-13 4.92 (7.32)
21/2" (65) 10 (3.05) 40 (12.19) I 80 (24.38) I 110.7 (0.492) 1/2"-13 4.92 (7.32)
21/2" (65) 12 (3.66) 36 (10.98) I 72 (21.94) I 115.1 (0.512) 1/2"-13 4.92 (7.32)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 85 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 5

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.15g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 5 (1.52) 40 (12.19) I 80 (24.38) I 120.1 (0.534) 1/2"-13 6.96 (10.35)
3" (80) 6 (1.83) 36 (10.98) I 72 (21.94) I 119.0 (0.529) 1/2"-13 6.96 (10.35)
3" (80) 8 (2.44) 40 (12.19) I 80 (24.38) I 142.0 (0.631) 1/2"-13 6.96 (10.35)
3" (80) 10 (3.05) 40 (12.19) I 80 (24.38) I 156.6 (0.696) 1/2"-13 6.96 (10.35)
3" (80) 12 (3.66) 36 (10.98) I 72 (21.94) I 162.9 (0.724) 1/2"-13 6.96 (10.35)

31/2" (90) 5 (1.52) 40 (12.19) I 80 (24.38) I 155.6 (0.692) 1/2"-13 9.02 (13.42)
31/2" (90) 6 (1.83) 36 (10.98) I 72 (21.94) I 154.2 (0.686) 1/2"-13 9.02 (13.42)
31/2" (90) 8 (2.44) 40 (12.19) I 80 (24.38) I 184.0 (0.818) 1/2"-13 9.02 (13.42)
31/2" (90) 10 (3.05) 40 (12.19) I 80 (24.38) I 202.9 (0.902) 1/2"-13 9.02 (13.42)
31/2" (90) 12 (3.66) 36 (10.98) I 72 (21.94) I 211.1 (0.939) 1/2"-13 9.02 (13.42)

4" (100) 6 (1.83) 36 (10.98) I 72 (21.94) II 197.8 (0.880) 1/2"-13 11.57 (17.21)
4" ( 100) 8 (2.44) 40 (12.19) I 80 (24.38) II 236.0 (1.050) 1/2"-13 11.57 (17.21)
4" ( 100) 10 (3.05) 40 (12.19) I 80 (24.38) II 260.3 (1.158) 1/2"-13 11.57 (17.21)
4" ( 100) 12 (3.66) 36 (10.98) I 72 (21.94) II 270.7 (1.204) 1/2"-13 11.57 (17.21)
4" ( 100) 15 (4.57) 30 (9.15) I 60 (18.30) I 286.3 1.273) 1/2"-13 11.57 (17.21)

Notes:
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer
hanger spacing may be required when additional valves and fittings increase the load. For
electrical conduit support spacing and weight of conduit filled with conductors information,
see B-Line Strut Systems Catalog.
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for
brace attachment details
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity
and the additional seismic forces. Select a rod attachment detail from pages 39 thru 56 that meets
the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod
stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at
braced locations. Unbraced hangers never require rod stiffeners. Select a pipe hanger from pages
63 thru 71 that meets the hanger load requirements.
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.
5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See
Note E) on page 9.
6). Seismic forces include 1/3 of horizontal seismic force applied in vertical direction.
7). Charts on pages 83 - 86 are for 0.15g (ASD) applications.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 86 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 6

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 1 - Maximum Hanger Spacing for Steel Pipe
Seismic Force Level (g’s) 0.30g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 35 (10.67) I 70 (21.35) I 26 (0.115) 3/8"-16 0.98 (1.46)
1/2" (15) 6 (1.83) 30 (9.15) I 60 (18.30) I 24 (0.107) 3/8"-16 0.98 (1.46)
1/2" (15) 7 (2.13) 28 (8.54) I 56 (17.08) I 24 (0.107) 3/8"-16 0.98 (1.46)
1/2" (15) 8 (2.44) 32 (9.76) I 64 (19.52) I 27 (0.120) 3/8"-16 0.98 (1.46)
1/2" (15) 10 (3.05) 30 (9.15) I 60 (18.30) I 28 (0.124) 3/8"-16 0.98 (1.46)

3/4" (20) 5 (1.52) 40 (12.19) I 80 (24.38) I 40 (0.178) 3/8"-16 1.36 (2.02)


3/4" (20) 6 (1.83) 36 (10.98) I 72 (21.94) I 38 (0.169) 3/8"-16 1.36 (2.02)
3/4" (20) 7 (2.13) 35 (10.67) I 70 (21.35) I 39 (0.173) 3/8"-16 1.36 (2.02)
3/4" (20) 8 (2.44) 32 (9.76) I 64 (19.52) I 38 (0.169) 3/8"-16 1.36 (2.02)
3/4" (20) 10 (3.05) 30 (9.15) I 60 (18.30) I 39 (0.173) 3/8"-16 1.36 (2.02)

1" (25) 5 (1.52) 40 (12.19) I 80 (24.38) I 61 (0.271) 3/8"-16 2.06 (3.06)


1" (25) 6 (1.83) 36 (10.98) I 72 (21.94) I 58 (0.258) 3/8"-16 2.06 (3.06)
1" (25) 7 (2.13) 35 (10.67) I 70 (21.35) I 59 (0.262) 3/8"-16 2.06 (3.06)
1" (25) 8 (2.44) 40 (12.19) I 80 (24.38) I 68 (0.302) 3/8"-16 2.06 (3.06)
1" (25) 10 (3.05) 40 (12.19) I 80 (24.38) I 72 (0.320) 3/8"-16 2.06 (3.06)

11/4" (32) 5 (1.52) 40 (12.19) I 80 (24.38) I 86 (0.382) 3/8"-16 2.92 (4.34)


11/4" (32) 6 (1.83) 36 (10.98) I 72 (21.94) I 82 (0.365) 3/8"-16 2.92 (4.34)
11/4" (32) 7 (2.13) 35 (10.67) I 70 (21.35) I 84 (0.373) 3/8"-16 2.92 (4.34)
11/4" (32) 8 (2.44) 40 (12.19) I 80 (24.38) I 96 (0.427) 3/8"-16 2.92 (4.34)
11/4" (32) 10 (3.05) 40 (12.19) I 80 (24.38) I 102 (0.453) 3/8"-16 2.92 (4.34)

11/2" (40) 5 (1.52) 40 (12.19) I 80 (24.38) I 106 (0.471) 3/8"-16 3.60 (5.36)
11/2" (40) 6 (1.83) 36 (10.98) I 72 (21.94) I 102 (0.453) 3/8"-16 3.60 (5.36)
11/2" (40) 9 (2.74) 36 (10.98) I 72 (21.94) I 113 (0.502) 3/8"-16 3.60 (5.36)
11/2" (40) 10 (3.05) 40 (12.19) I 80 (24.38) I 126 (0.560) 3/8"-16 3.60 (5.36)
11/2" (40) 12 (3.66) 36 (10.98) I 72 (21.94) I 125 (0.556) 3/8"-16 3.60 (5.36)

2" (50) 5 (1.52) 40 (12.19) I 80 (24.38) I 150 (0.667) 3/8"-16 5.10 (7.59)
2" (50) 6 (1.83) 36 (10.98) I 72 (21.94) I 144 (0.640) 3/8"-16 5.10 (7.59)
2" (50) 8 (2.44) 40 (12.19) I 80 (24.38) I 167 (0.743) 3/8"-16 5.10 (7.59)
2" (50) 10 (3.05) 40 (12.19) I 80 (24.38) I 178 (0.792) 3/8"-16 5.10 (7.59)
2" (50) 12 (3.66) 36 (10.98) I 72 (21.94) I 177 (0.787) 3/8"-16 5.10 (7.59)

21/2" (65) 5 (1.52) 40 (12.19) I 80 (24.38) II 232 (1.032) 1/2"-13 7.87 (11.71)
21/2" (65) 6 (1.83) 36 (10.98) I 72 (21.94) II 222 (0.987) 1/2"-13 7.87 (11.71)
21/2" (65) 8 (2.44) 40 (12.19) I 80 (24.38) II 258 (1.147) 1/2"-13 7.87 (11.71)
21/2" (65) 10 (3.05) 40 (12.19) I 80 (24.38) II 275 (1.223) 1/2"-13 7.87 (11.71)
21/2" (65) 12 (3.66) 36 (10.98) I 72 (21.94) II 274 (1.219) 1/2"-13 7.87 (11.71)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 87 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 7

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Field Maximum Transverse Maximum Longitudinal Hanger &
Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 6 (1.83) 36 (10.98) I 72 (21.94) III 303 (1.348) 1/2"-13 10.75 (16.00)
3" (80) 8 (2.44) 40 (12.19) II 80 (24.38) III 353 (1.570) 1/2"-13 10.75 (16.00)
3" (80) 10 (3.05) 40 (12.19) II 80 (24.38) III 376 (1.672) 1/2"-13 10.75 (16.00)
3" (80) 12 (3.66) 36 (10.98) I 72 (21.94) III 374 (1.663) 1/2"-13 10.75 (16.00)
3" (80) 15 (4.57) 30 (9.15) I 60 (18.30) II 371 (1.650) 1/2"-13 10.75 (16.00)

31/2" (90) 6 (1.83) 36 (10.98) II 72 (21.94) III 378 (1.681) 1/2"-13 13.39 (19.92)
31/2" (90) 8 (2.44) 40 (12.19) II 80 (24.38) IV 439 (1.952) 1/2"-13 13.39 (19.92)
31/2" (90) 10 (3.05) 40 (12.19) II 80 (24.38) IV 469 (2.086) 1/2"-13 13.39 (19.92)
31/2" (90) 12 (3.66) 36 (10.98) II 72 (21.94) III 466 (2.073) 1/2"-13 13.39 (19.92)
31/2" (90) 15 (4.57) 30 (9.15) II 60 (18.30) III 462 (2.055) 1/2"-13 13.39 (19.92)

4" (100) 6 (1.83) 36 (10.98) II 72 (21.94) III 401 (1.783) 5/8"-11 16.31 (24.27)
4" (100) 8 (2.44) 40 (12.19) II 80 (24.38) III 457 (2.033) 5/8"-11 16.31 (24.27)
4" (100) 10 (3.05) 40 (12.19) II 80 (24.38) III 473 (2.104) 5/8"-11 16.31 (24.27)
4" (100) 12 (3.66) 36 (10.98) II 72 (21.94) III 509 (2.264) 5/8"-11 16.31 (24.27)
4" (100) 15 (4.57) 30 (9.15) II 60 (18.30) III 563 (2.504) 5/8"-11 16.31 (24.27)

5" (125) 8 (2.44) 40 (12.19) III 80 (24.38) IV 635 (2.824) 5/8"-11 23.39 (34.81)
5" (125) 10 (3.05) 40 (12.19) III 80 (24.38) IV 595 (2.646) 5/8"-11 23.39 (34.81)
5" (125) 12 (3.66) 36 (10.98) III 72 (21.94) IV 595 (2.646) 5/8"-11 23.39 (34.81)
5" (125) 15 (4.57) 30 (9.15) III 60 (18.30) IV 595 (2.646) 5/8"-11 23.39 (34.81)
5" (125) 18 (5.49) 36 (10.98) III 72 (21.94) IV 536 (2.384) 5/8"-11 23.39 (34.81)

6" (150) 8 (2.44) 40 (12.19) IV 48 (14.64) IV 731 (3.251) 3/4"-10 31.49 (46.86)
6" (150) 10 (3.05) 40 (12.19) IV 50 (15.25) IV 819 (3.643) 3/4"-10 31.49 (46.86)
6" (150) 12 (3.66) 36 (10.98) IV 48 (14.64) IV 869 (3.865) 3/4"-10 31.49 (46.86)
6" (150) 15 (4.57) 30 (9.15) IV 45 (13.72) IV 945 (4.203) 3/4"-10 31.49 (46.86)
6" (150) 18 (5.49) 36 (10.98) IV 36 (10.98) IV 964 (4.288) 3/4"-10 31.49 (46.86)

8" (200) 8 (2.44) 40 (12.19) V 40 (12.19) V 1045 (4.648) 3/4"-10 50.23 (74.75)
8" (200) 10 (3.05) 40 (12.19) V 40 (12.19) V 1155 (5.137) 3/4"-10 50.23 (74.75)
8" (200) 12 (3.66) 36 (10.98) V 36 (10.98) V 1205 (5.360) 3/4"-10 50.23 (74.75)
8" (200) 15 (4.57) 30 (9.15) IV 45 (13.72) V 1507 (6.703) 3/4"-10 50.23 (74.75)
8" (200) 20 (6.10) 40 (12.19) V 40 (12.19) V 1708 (7.588) 3/4"-10 50.23 (74.75)

10" (250) 8 (2.44) 24 (7.32) V 24 (7.32) V 1194 (5.311) 7/8"-9 74.60 (111.01)
10" (250) 10 (3.05) 30 (9.15) V 30 (9.15) V 1492 (6.636) 7/8"-9 74.60 (111.01)
10" (250) 12 (3.66) 24 (7.32) V 24 (7.32) V 1522 (6.770) 7/8"-9 74.60 (111.01)
10" (250) 15 (4.57) 30 (9.15) V 30 (9.15) V 1902 (8.460) 7/8"-9 74.60 (111.01)
10" (250) 20 (6.10) 20 (6.10) V 20 (6.10) V 2089 (9.292) 7/8"-9 74.60 (111.01)

12" (300) 8 (2.44) 16 (4.88) V 16 (4.88) V 1388 (6.174) 7/8"-9 102.10 (151.94)
12" (300) 10 (3.05) 20 (6.10) V 20 (6.10) V 1736 (7.722) 7/8"-9 102.10 (151.94)
12" (300) 12 (3.66) 12 (3.66) V 12 (3.66) V 1715 (7.628) 7/8"-9 102.10 (151.94)
12" (300) 15 (4.57) 15 (4.57) V 15 (4.57) V 2144 (9.536) 7/8"-9 102.10 (151.94)
12" (300) 16 (4.88) 16 (4.88) V 16 (4.88) V 2287 (10.172) 7/8"-9 102.10 (151.94)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 88 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 8

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.30g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 20 (6.10) I 40 (12.19) I 7.5 (0.033) 3/8"-16 0.43 (0.64)
1/2" (15) 6 (1.83) 18 (5.49) I 36 (10.98) I 7.8 (0.033) 3/8"-16 0.43 (0.64)
1/2" (15) 7 (2.13) 14 (4.27) I 28 (8.54) I 6.9 (0.030) 3/8"-16 0.43 (0.64)
1/2" (15) 8 (2.44) 16 (4.88) I 32 (9.76) I 7.9 (0.035) 3/8"-16 0.43 (0.64)
1/2" (15) 10 (3.05) 10 (3.05) I 20 (6.10) I 7.3 (0.032) 3/8"-16 0.43 (0.64)

3/4" (20) 5 (1.52) 20 (6.10) I 40 (12.19) I 14.5 (0.064) 3/8"-16 0.83 (1.23)
3/4" (20) 6 (1.83) 18 (5.49) I 36 (10.98) I 14.4 (0.064) 3/8"-16 0.83 (1.23)
3/4" (20) 7 (2.13) 14 (4.27) I 28 (8.54) I 13.4 (0.059) 3/8"-16 0.83 (1.23)
3/4" (20) 8 (2.44) 16 (4.88) I 32 (9.76) I 15.3 (0.068) 3/8"-16 0.83 (1.23)
3/4" (20) 10 (3.05) 10 (3.05) I 20 (6.10) I 14.1 (0.063) 3/8"-16 0.83 (1.23)

1" (25) 5 (1.52) 25 (7.62) I 50 (15.25) I 24.2 (0.107) 3/8"-16 1.18 (1.75)
1" (25) 6 (1.83) 24 (7.32) I 48 (14.64) I 24.8 (0.110) 3/8"-16 1.18 (1.75)
1" (25) 7 (2.13) 21 (6.40) I 42 (12.81) I 24.0 (0.107) 3/8"-16 1.18 (1.75)
1" (25) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 27.4 (0.122) 3/8"-16 1.18 (1.75)
1" (25) 10 (3.05) 20 (6.10) I 40 (12.19) I 27.1 (0.120) 3/8"-16 1.18 (1.75)

11/4" (32) 5 (1.52) 30 (9.15) I 60 (18.30) I 36.9 (0.164) 3/8"-16 1.57 (2.33)
11/4" (32) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 33.0 (0.147) 3/8"-16 1.57 (2.33)
11/4" (32) 7 (2.13) 28 (8.54) I 56 (17.08) I 38.5 (0.171) 3/8"-16 1.57 (2.33)
11/4" (32) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 36.4 (0.162) 3/8"-16 1.57 (2.33)
11/4" (32) 10 (3.05) 20 (6.10) I 40 (12.19) I 36.1 (0.160) 3/8"-16 1.57 (2.33)

11/2" (40) 5 (1.52) 30 (9.15) I 60 (18.30) I 49.3 (0.219) 3/8"-16 2.10 (3.17)
11/2" (40) 6 (1.83) 30 (9.15) I 60 (18.30) I 51.7 (0.230) 3/8"-16 2.10 (3.17)
11/2" (40) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 48.7 (0.216) 3/8"-16 2.10 (3.17)
11/2" (40) 10 (3.05) 20 (6.10) I 40 (12.19) I 48.3 (0.215) 3/8"-16 2.10 (3.17)
11/2" (40) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 58.0 (0.258) 3/8"-16 2.10 (3.17)

2" (50) 5 (1.52) 35 (10.67) I 70 (22.35) I 89.3 (0.397) 3/8"-16 3.37 (5.01)
2" (50) 6 (1.83) 36 (10.98) I 72 (21.94) I 95.0 (0.422) 3/8"-16 3.37 (5.01)
2" (50) 8 (2.44) 32 (9.76) I 64 (19.52) I 94.4 (0.420) 3/8"-16 3.37 (5.01)
2" (50) 10 (3.05) 30 (9.15) I 60 (18.30) I 97.7 (0.434) 3/8"-16 3.37 (5.01)
2" (50) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 93.0 (0.413) 3/8"-16 3.37 (5.01)

21/2" (65) 5 (1.52) 40 (12.19) I 80 (24.38) I 145.1 (0.645) 1/2"-13 4.92 (7.32)
21/2" (65) 6 (1.83) 36 (10.98) I 72 (21.94) I 138.7 (0.617) 1/2"-13 4.92 (7.32)
21/2" (65) 9 (2.74) 36 (10.98) I 72 (21.94) I 155.0 (0.689) 1/2"-13 4.92 (7.32)
21/2" (65) 10 (3.05) 30 (9.15) I 60 (18.30) I 142.7 (0.635) 1/2"-13 4.92 (7.32)
21/2" (65) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 135.8 (0.604) 1/2"-13 4.92 (7.32)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 89 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 9

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.30g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 5 (1.52) 40 (12.19) I 80 (24.38) II 205.3 (0.913) 1/2"-13 6.96 (10.35)
3" (80) 6 (1.83) 36 (10.98) I 72 (21.94) II 196.3 (0.873) 1/2"-13 6.96 (10.35)
3" (80) 8 (2.44) 40 (12.19) I 80 (24.38) II 228.3 (1.015) 1/2"-13 6.96 (10.35)
3" (80) 10 (3.05) 40 (12.19) I 80 (24.38) II 243.6 (1.083) 1/2"-13 6.96 (10.35)
3" (80) 12 (3.66) 36 (10.98) I 72 (21.94) II 242.2 (1.077) 1/2"-13 6.96 (10.35)

31/2" (90) 5 (1.52) 40 (12.19) I 80 (24.38) III 266.1 (1.183) 1/2"-13 9.02 (13.42)
31/2" (90) 6 (1.83) 36 (10.98) I 72 (21.94) II 254.4 (1.131) 1/2"-13 9.02 (13.42)
31/2" (90) 8 (2.44) 40 (12.19) I 80 (24.38) III 295.8 (1.316) 1/2"-13 9.02 (13.42)
31/2" (90) 10 (3.05) 40 (12.19) I 80 (24.38) III 315.7 (1.404) 1/2"-13 9.02 (13.42)
31/2" (90) 12 (3.66) 36 (10.98) I 72 (21.94) II 313.9 (1.396) 1/2"-13 9.02 (13.42)

4" (100) 5 (1.52) 40 (12.19) II 80 (24.38) III 341.3 (1.518) 1/2"-13 11.57 (17.21)
4" ( 100) 6 (1.83) 36 (10.98) II 72 (21.94) III 326.3 (1.451) 1/2"-13 11.57 (17.21)
4" ( 100) 8 (2.44) 40 (12.19) II 80 (24.38) III 379.5 (1.688) 1/2"-13 11.57 (17.21)
4" ( 100) 9 (2.74) 36 (10.98) II 72 (21.94) III 364.4 (1.621) 1/2"-13 11.57 (17.21)
4" ( 100) 11 (3.35) 33 (10.06) I 66 (20.13) III 369.1 (1.642) 1/2"-13 11.57 (17.21)

Notes:
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer
hanger spacing may be required when additional valves and fittings increase the load. For
electrical conduit support spacing and weight of conduit filled with conductors information,
see B-Line Strut Systems Catalog.
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for
brace attachment details
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity
and the additional seismic forces. Select a rod attachment detail from pages 39 thru 56 that meets
the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod
stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at
braced locations. Unbraced hangers never require rod stiffeners. Select a pipe hanger from pages
63 thru 71 that meets the hanger load requirements.
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.
5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See
Note E) on page 9.
6). Seismic forces include 1/3 of horizontal seismic force applied in vertical direction.
7). Charts on pages 87 - 90 are for 0.30g (ASD) applications.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 90 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 10

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 1 - Maximum Hanger Spacing for Steel Pipe
Seismic Force Level (g’s) 0.45g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 25 (7.62) I 50 (15.24) I 28 (0.124) 3/8"-16 0.98 (1.41)
1/2" (15) 6 (1.83) 24 (7.31) I 48 (14.63) I 28 (0.124) 3/8"-16 0.98 (1.46)
1/2" (15) 7 (2.13) 28 (8.54) I 56 (17.07) I 33 (0.147) 3/8"-16 0.98 (1.46)
1/2" (15) 8 (2.44) 24 (7.31) I 48 (14.63) I 30 (0.133) 3/8"-16 0.98 (1.46)
1/2" (15) 10 (3.05) 20 (6.09) I 40 (12.19) I 29 (0.129) 3/8"-16 0.98 (1.46)

3/4" (20) 5 (1.52) 30 (9.15) I 60 (18.30) I 45 (0.200) 3/8"-16 1.36 (2.02)


3/4" (20) 6 (1.83) 30 (9.15) I 60 (18.30) I 46 (0.204) 3/8"-16 1.36 (2.02)
3/4" (20) 7 (2.13) 28 (8.54) I 56 (17.07) I 45 (0.200) 3/8"-16 1.36 (2.02)
3/4" (20) 8 (2.44) 24 (7.31) I 48 (14.63) I 42 (0.187) 3/8"-16 1.36 (2.02)
3/4" (20) 10 (3.05) 20 (6.09) I 40 (12.19) I 40 (0.178) 3/8"-16 1.36 (2.02)

1" (25) 5 (1.52) 35 (10.67) I 70 (21.35) I 77 (0.342) 3/8"-16 2.06 (3.06)


1" (25) 6 (1.83) 36 (10.98) I 72 (21.94) I 81 (0.360) 3/8"-16 2.06 (3.06)
1" (25) 7 (2.13) 35 (10.67) I 70 (21.35) I 81 (0.360) 3/8"-16 2.06 (3.06)
1" (25) 8 (2.44) 32 (9.75) I 64 (19.51) I 78 (0.347) 3/8"-16 2.06 (3.06)
1" (25) 10 (3.05) 30 (9.15) I 60 (18.30) I 79 (0.351) 3/8"-16 2.06 (3.06)

11/4" (32) 5 (1.52) 40 (12.19) I 80 (24.38) I 122 (0.542) 3/8"-16 2.92 (4.34)
11/4" (32) 6 (1.83) 36 (10.98) I 72 (21.94) I 115 (0.511) 3/8"-16 2.92 (4.34)
11/4" (32) 7 (2.13) 35 (10.67) I 70 (21.35) I 115 (0.511) 3/8"-16 2.92 (4.34)
11/4" (32) 8 (2.44) 40 (12.19) I 80 (24.38) I 132 (0.587) 3/8"-16 2.92 (4.34)
11/4" (32) 10 (3.05) 30 (9.15) I 80 (24.38) I 112 (0.498) 3/8"-16 2.92 (4.34)

11/2" (40) 5 (1.52) 40 (12.19) I 80 (24.38) II 150 (0.667) 3/8"-16 3.60 (5.36)
11/2" (40) 6 (1.83) 36 (10.98) I 72 (21.94) I 141 (0.627) 3/8"-16 3.60 (5.36)
11/2" (40) 9 (2.74) 36 (10.98) I 72 (21.94) I 154 (0.685) 3/8"-16 3.60 (5.36)
11/2" (40) 10 (3.05) 40 (12.19) I 80 (24.38) II 171 (0.760) 3/8"-16 3.60 (5.36)
11/2" (40) 12 (3.66) 36 (10.98) I 72 (21.94) I 166 (0.738) 3/8"-16 3.60 (5.36)

2" (50) 5 (1.52) 40 (12.19) I 80 (24.38) II 213 (0.947) 3/8"-16 5.10 (7.59)
2" (50) 6 (1.83) 36 (10.98) I 72 (21.94) II 200 (0.889) 3/8"-16 5.10 (7.59)
2" (50) 8 (2.44) 40 (12.19) I 80 (24.38) II 231 (1.027) 3/8"-16 5.10 (7.59)
2" (50) 10 (3.05) 40 (12.19) I 80 (24.38) II 242 (1.076) 3/8"-16 5.10 (7.59)
2" (50) 12 (3.66) 36 (10.98) I 72 (21.94) II 236 (1.050) 3/8"-16 5.10 (7.59)

21/2" (65) 5 (1.52) 40 (12.19) II 80 (24.38) II 329 (1.463) 1/2"-13 7.87 (11.71)
21/2" (65) 6 (1.83) 36 (10.98) II 72 (21.94) II 309 (1.374) 1/2"-13 7.87 (11.71)
21/2" (65) 8 (2.44) 40 (12.19) II 80 (24.38) II 356 (1.583) 1/2"-13 7.87 (11.71)
21/2" (65) 10 (3.05) 40 (12.19) II 80 (24.38) II 374 (1.663) 1/2"-13 7.87 (11.71)
21/2" (65) 12 (3.66) 36 (10.98) II 72 (21.94) II 364 (1.619) 1/2"-13 7.87 (11.71)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 91 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 11

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Field Maximum Transverse Maximum Longitudinal Hanger &
Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 6 (1.83) 36 (10.98) II 72 (21.94) IV 422 (1.877) 1/2"-13 10.75 (16.00)
3" (80) 8 (2.44) 40 (12.19) II 80 (24.38) IV 486 (2.162) 1/2"-13 10.75 (16.00)
3" (80) 10 (3.05) 40 (12.19) II 80 (24.38) IV 511 (2.273) 1/2"-13 10.75 (16.00)
3" (80) 12 (3.66) 36 (10.98) II 72 (21.94) IV 497 (2.211) 1/2"-13 10.75 (16.00)
3" (80) 15 (4.57) 30 (9.15) II 60 (18.30) III 476 (2.117) 1/2"-13 10.75 (16.00)

31/2" (90) 6 (1.83) 36 (10.98) III 72 (21.94) IV 526 (2.340) 1/2"-13 13.39 (19.92)
31/2" (90) 8 (2.44) 40 (12.19) III 80 (24.38) V 605 (2.691) 1/2"-13 13.39 (19.92)
31/2" (90) 10 (3.05) 40 (12.19) III 80 (24.38) V 636 (2.829) 1/2"-13 13.39 (19.92)
31/2" (90) 12 (3.66) 36 (10.98) III 72 (21.94) IV 619 (2.753) 1/2"-13 13.39 (19.92)
31/2" (90) 15 (4.57) 30 (9.15) II 60 (18.30) IV 592 (2.633) 1/2"-13 13.39 (19.92)

4" (100) 6 (1.83) 36 (10.98) III 72 (21.94) V 641 (2.851) 5/8"-11 16.31 (24.27)
4" (100) 8 (2.44) 40 (12.19) III 80 (24.38) V 737 (3.278) 5/8"-11 16.31 (24.27)
4" (100) 10 (3.05) 40 (12.19) III 80 (24.38) V 775 (3.447) 5/8"-11 16.31 (24.27)
4" (100) 12 (3.66) 36 (10.98) III 72 (21.94) V 753 (3.349) 5/8"-11 16.31 (24.27)
4" (100) 15 (4.57) 30 (9.15) III 60 (18.30) IV 722 (3.211) 5/8"-11 16.31 (24.27)

5" (125) 8 (2.44) 40 (12.19) IV 40 (12.19) IV 636 (2.829) 5/8"-11 23.39 (34.81)
5" (125) 10 (3.05) 40 (12.19) IV 40 (12.19) IV 690 (3.069) 5/8"-11 23.39 (34.81)
5" (125) 12 (3.66) 36 (10.98) IV 36 (10.98) IV 702 (3.122) 5/8"-11 23.39 (34.81)
5" (125) 15 (4.57) 30 (9.15) III 45 (13.71) IV 877 (3.901) 5/8"-11 23.39 (34.81)
5" (125) 18 (5.49) 36 (10.98) IV 36 (10.98) IV 863 (3.838) 5/8"-11 23.39 (34.81)

6" (150) 8 (2.44) 32 (9.76) IV 32 (9.76) IV 743 (3.305) 3/4"-10 31.49 (46.86)
6" (150) 10 (3.05) 30 (9.15) IV 30 (9.15) IV 787 (3.500) 3/4"-10 31.49 (46.86)
6" (150) 12 (3.66) 24 (7.32) IV 24 (7.32) IV 775 (3.447) 3/4"-10 31.49 (46.86)
6" (150) 15 (4.57) 30 (9.15) IV 30 (9.15) IV 948 (4.217) 3/4"-10 31.49 (46.86)
6" (150) 18 (5.49) 18 (5.49) IV 18 (5.49) IV 907 (4.034) 3/4"-10 31.49 (46.86)

8" (200) 8 (2.44) 24 (7.32) V 24 (7.32) V 1005 (4.470) 3/4"-10 50.23 (74.75)
8" (200) 10 (3.05) 30 (9.15) V 30 (9.15) V 1256 (5.587) 3/4"-10 50.23 (74.75)
8" (200) 12 (3.66) 24 (7.32) V 24 (7.32) V 1236 (5.498) 3/4"-10 50.23 (74.75)
8" (200) 15 (4.57) 30 (9.15) V 30 (9.15) V 1544 (6.868) 3/4"-10 50.23 (74.75)
8" (200) 20 (6.10) 20 (6.10) V 20 (6.10) V 1607 (7.148) 3/4"-10 50.23 (74.75)

10" (250) 8 (2.44) 16 (4.88) V 16 (4.88) V 1223 (5.440) 7/8"-9 74.60 (111.01)
10" (250) 10 (3.05) 20 (6.10) V 20 (6.10) V 1529 (6.801) 7/8"-9 74.60 (111.01)
10" (250) 12 (3.66) 12 (3.66) V 12 (3.66) V 1432 (6.370) 7/8"-9 74.60 (111.01)
10" (250) 15 (4.57) 15 (4.57) V 15 (4.57) V 1790 (7.962) 7/8"-9 74.60 (111.01)
10" (250) 20 (6.10) 20 (6.10) V 20 (6.10) V 2387 (10.618) 7/8"-9 74.60 (111.01)

12" (300) 8 (2.44) 8 (2.44) V 8 (2.44) V 1307 (5.814) 7/8"-9 102.10 (151.94)
12" (300) 10 (3.05) 10 (3.05) V 10 (3.05) V 1633 (7.264) 7/8"-9 102.10 (151.94)
12" (300) 12 (3.66) 12 (3.66) V 12 (3.66) V 1960 (8.718) 7/8"-9 102.10 (151.94)
12" (300) 15 (4.57) 15 (4.57) V 15 (4.57) V 2450 (10.898) 7/8"-9 102.10 (151.94)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 92 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:19 PM Page 12

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.45g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 15 (4.57) I 30 (9.14) I 8.3 (0.037) 3/8"-16 0.43 (0.64)
1/2" (15) 6 (1.83) 12 (3.66) I 24 (7.32) I 7.6 (0.034) 3/8"-16 0.43 (0.64)
1/2" (15) 7 (2.13) 14 (4.27) I 28 (8.54) I 8.9 (0.039) 3/8"-16 0.43 (0.64)
1/2" (15) 8 (2.44) 8 (2.44) I 16 (4.88) I 7.1 (0.031) 3/8"-16 0.43 (0.64)
1/2" (15) 10 (3.05) 0 (0.00) I 0 (0.00) I 4.9 (0.022) 3/8"-16 0.43 (0.64)

3/4" (20) 5 (1.52) 15 (4.57) I 30 (9.14) I 16.0 (0.071) 3/8"-16 0.83 (1.23)
3/4" (20) 6 (1.83) 12 (3.66) I 24 (7.32) I 14.7 (0.065) 3/8"-16 0.83 (1.23)
3/4" (20) 7 (2.13) 14 (4.27) I 28 (8.54) I 17.1 (0.076) 3/8"-16 0.83 (1.23)
3/4" (20) 8 (2.44) 8 (2.44) I 16 (4.88) I 13.6 (0.060) 3/8"-16 0.83 (1.23)
3/4" (20) 10 (3.05) 10 (3.05) I 20 (6.10) I 17.0 (0.075) 3/8"-16 0.83 (1.23)

1" (25) 5 (1.52) 20 (6.10) I 40 (12.19) I 28.0 (0.124) 3/8"-16 1.18 (1.75)
1" (25) 6 (1.83) 18 (5.48) I 36 (10.97) I 27.3 (0.121) 3/8"-16 1.18 (1.75)
1" (25) 7 (2.13) 14 (4.27) I 28 (8.54) I 24.4 (0.108) 3/8"-16 1.18 (1.75)
1" (25) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 27.8 (0.123) 3/8"-16 1.18 (1.75)
1" (25) 10 (3.05) 10 (3.05) I 20 (6.10) I 24.2 (0.107) 3/8"-16 1.18 (1.75)

11/4" (32) 5 (1.52) 20 (6.10) I 40 (12.19) I 37.3 (0.166) 3/8"-16 1.57 (2.33)
11/4" (32) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 44.7 (0.199) 3/8"-16 1.57 (2.33)
11/4" (32) 7 (2.13) 21 (6.40) I 42 (12.80) I 42.3 (0.188) 3/8"-16 1.57 (2.33)
11/4" (32) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 37.1 (0.165) 3/8"-16 1.57 (2.33)
11/4" (32) 10 (3.05) 20 (6.10) I 40 (12.19) I 46.3 (0.206) 3/8"-16 1.57 (2.33)

11/2" (40) 5 (1.52) 25 (7.62) I 50 (15.24) I 59.3 (0.264) 3/8"-16 2.10 (3.17)
11/2" (40) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 59.8 (0.266) 3/8"-16 2.10 (3.17)
11/2" (40) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 64.7 (0.288) 3/8"-16 2.10 (3.17)
11/2" (40) 10 (3.05) 20 (6.10) I 40 (12.19) I 61.9 (0.275) 3/8"-16 2.10 (3.17)
11/2" (40) 12 (3.66) 12 (3.66) I 24 (7.32) I 51.7 (0.230) 3/8"-16 2.10 (3.17)

2" (50) 5 (1.52) 30 (9.15) I 60 (18.30) I 110.4 (0.491) 3/8"-16 3.37 (5.01)
2" (50) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 96.0 (0.427) 3/8"-16 3.37 (5.01)
2" (50) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 103.8 (0.462) 3/8"-16 3.37 (5.01)
2" (50) 10 (3.05) 20 (6.10) I 40 (12.19) I 99.4 (0.442) 3/8"-16 3.37 (5.01)
2" (50) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 119.3 (0.530) 3/8"-16 3.37 (5.01)

21/2" (65) 5 (1.52) 30 (9.15) I 55 (16.76) I 150.1 (0.667) 1/2"-13 4.92 (7.32)
21/2" (65) 6 (1.83) 30 (9.15) I 54 (16.46) I 153.5 (0.683) 1/2"-13 4.92 (7.32)
21/2" (65) 9 (2.74) 27 (8.23) I 54 (16.46) I 170.5 (0.758) 1/2"-13 4.92 (7.32)
21/2" (65) 10 (3.05) 30 (9.15) I 50 (15.24) I 167.3 (0.744) 1/2"-13 4.92 (7.32)
21/2" (65) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 174.2 (0.775) 1/2"-13 4.92 (7.32)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 93 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 13

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.45g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 5 (1.52) 35 (10.67) II 70 (21.33) III 259.3 (1.153) 1/2"-13 6.96 (10.35)
3" (80) 6 (1.83) 30 (9.15) I 60 (18.29) II 235.9 (1.049) 1/2"-13 6.96 (10.35)
3" (80) 8 (2.44) 32 (9.75) II 64 (19.61) II 264.5 (1.176) 1/2"-13 6.96 (10.35)
3" (80) 10 (3.05) 30 (9.15) II 60 (18.29) II 267.9 (1.191) 1/2"-13 6.96 (10.35)
3" (80) 12 (3.66) 24 (7.32) I 48 ( 14.64) II 246.4 (1.096) 1/2"-13 6.96 (10.35)

31/2" (90) 5 (1.52) 35 (10.67) II 70 (21.33) III 336.0 (1.494) 1/2"-13 9.02 (13.42)
31/2" (90) 8 (2.44) 32 (9.75) II 64 (19.61) III 342.7 (1.524) 1/2"-13 9.02 (13.42)
31/2" (90) 10 (3.05) 30 (9.15) II 60 (18.29) III 347.3 (1.545) 1/2"-13 9.02 (13.42)
31/2" (90) 12 (3.66) 24 (7.32) II 48 ( 14.64) II 319.3 (1.420) 1/2"-13 9.02 (13.42)

4" (100) 5 (1.52) 36 (10.98) II 72 (21.94) IV 454.7 (2.022) 1/2"-13 11.57 (17.21)
4" ( 100) 6 (1.83) 32 (9.75) II 64 (19.61) IV 439.6 (1.955) 1/2"-13 11.57 (17.21)
4" ( 100) 8 (2.44) 30 (9.15) II 60 (18.29) III 445.4 (1.981) 1/2"-13 11.57 (17.21)
4" ( 100) 9 (2.74) 36 (10.98) II 72 (21.94) IV 534.5 (2.377) 1/2"-13 11.57 (17.21)
4" ( 100) 11 (3.35) 30 (9.15) II 60 (18.29) III 511.9 (2.277) 1/2"-13 11.57 (17.21)

Notes:
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer
hanger spacing may be required when additional valves and fittings increase the load. For
electrical conduit support spacing and weight of conduit filled with conductors information,
see B-Line Strut Systems Catalog.
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for
brace attachment details
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity
and the additional seismic forces. Select a rod attachment detail from pages 39 thru 56 that meets
the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod
stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at
braced locations. Unbraced hangers never require rod stiffeners. Select a pipe hanger from pages
63 thru 71 that meets the hanger load requirements.
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.
5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See
Note E) on page 9.
6). Seismic forces include 1/3 of horizontal seismic force applied in vertical direction.
7). Charts on pages 91 - 94 are for 0.45g (ASD) applications.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 94 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 14

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 1 - Maximum Hanger Spacing for Steel Pipe
Seismic Force Level (g’s) 0.50g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 25 (7.62) I 50 (15.24) I 30 (0.233) 3/8"-16 0.98 (1.46)
1/2" (15) 6 (1.83) 24 (7.32) I 48 (14.63) I 30 (0.233) 3/8"-16 0.98 (1.46)
1/2" (15) 7 (2.13) 21 (6.40) I 42 (12.80) I 29 (0.129) 3/8"-16 0.98 (1.46)
1/2" (15) 8 (2.44) 24 (7.32) I 48 (14.63) I 33 (0.147) 3/8"-16 0.98 (1.46)
1/2" (15) 10 (3.05) 20 (6.10) I 40 (12.19) I 31 (0.138) 3/8"-16 0.98 (1.46)

3/4" (20) 5 (1.52) 30 (9.14) I 60 (18.30) I 49 (0.218) 3/8"-16 1.36 (2.02)


3/4" (20) 6 (1.83) 30 (9.14) I 60 (18.30) I 50 (0.222) 3/8"-16 1.36 (2.02)
3/4" (20) 7 (2.13) 28 (8.53) I 56 (17.07) I 49 (0.218) 3/8"-16 1.36 (2.02)
3/4" (20) 8 (2.44) 24 (7.32) I 48 (14.63) I 45 (0.200) 3/8"-16 1.36 (2.02)
3/4" (20) 10 (3.05) 20 (6.10) I 40 (12.19) I 43 (0.191) 3/8"-16 1.36 (2.02)

1" (25) 5 (1.52) 35 (10.67) I 70 (21.35) I 84 (0.373) 3/8"-16 2.06 (3.06)


1" (25) 6 (1.83) 30 (9.14) I 60 (18.30) I 76 (0.338) 3/8"-16 2.06 (3.06)
1" (25) 7 (2.13) 28 (8.53) I 56 (17.07) I 75 (0.333) 3/8"-16 2.06 (3.06)
1" (25) 8 (2.44) 32 (9.75) I 64 (19.51) I 85 (0.378) 3/8"-16 2.06 (3.06)
1" (25) 10 (3.05) 30 (9.14) I 60 (18.30) I 86 (0.382) 3/8"-16 2.06 (3.06)

11/4" (32) 5 (1.52) 35 (10.67) I 70 (21.35) I 119 (0.529) 3/8"-16 2.92 (4.34)
11/4" (32) 6 (1.83) 36 (10.98) I 72 (21.94) I 126 (0.560) 3/8"-16 2.92 (4.34)
11/4" (32) 7 (2.13) 35 (10.67) I 70 (21.35) I 126 (0.560) 3/8"-16 2.92 (4.34)
11/4" (32) 8 (2.44) 32 (9.75) I 64 (19.51) I 121 (0.538) 3/8"-16 2.92 (4.34)
11/4" (32) 10 (3.05) 30 (9.14) I 60 (18.30) I 122 (0.542) 3/8"-16 2.92 (4.34)

11/2" (40) 5 (1.52) 40 (12.19) I 80 (24.38) II 165 (0.734) 3/8"-16 3.60 (5.36)
11/2" (40) 6 (1.83) 36 (10.98) I 72 (21.94) II 155 (0.689) 3/8"-16 3.60 (5.36)
11/2" (40) 9 (2.74) 36 (10.98) I 72 (21.94) II 167 (0.743) 3/8"-16 3.60 (5.36)
11/2" (40) 10 (3.05) 30 (9.14) I 60 (18.30) I 150 (0.667) 3/8"-16 3.60 (5.36)
11/2" (40) 12 (3.66) 36 (10.98) I 72 (21.94) II 180 (0.800) 3/8"-16 3.60 (5.36)

2" (50) 5 (1.52) 40 (12.19) I 80 (24.38) II 234 (1.041) 3/8"-16 5.10 (7.59)
2" (50) 6 (1.83) 36 (10.98) I 72 (21.94) II 219 (0.974) 3/8"-16 5.10 (7.59)
2" (50) 8 (2.44) 40 (12.19) I 80 (24.38) II 252 (1.121) 3/8"-16 5.10 (7.59)
2" (50) 10 (3.05) 40 (12.19) I 80 (24.38) II 263 (1.170) 3/8"-16 5.10 (7.59)
2" (50) 12 (3.66) 36 (10.98) I 72 (21.94) II 255 (1.134) 3/8"-16 5.10 (7.59)

21/2" (65) 5 (1.52) 40 (12.19) II 80 (24.38) III 361 (1.606) 1/2"-13 7.87 (11.71)
21/2" (65) 6 (1.83) 36 (10.98) II 72 (21.94) III 338 (1.503) 1/2"-13 7.87 (11.71)
21/2" (65) 8 (2.44) 40 (12.19) II 80 (24.38) III 388 (1.726) 1/2"-13 7.87 (11.71)
21/2" (65) 10 (3.05) 40 (12.19) II 80 (24.38) III 407 (1.810) 1/2"-13 7.87 (11.71)
21/2" (65) 12 (3.66) 36 (10.98) II 72 (21.94) III 393 (1.748) 1/2"-13 7.87 (11.71)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 95 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 15

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Field Maximum Transverse Maximum Longitudinal Hanger &
Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 6 (1.83) 36 (10.98) II 72 (21.94) IV 462 (2.055) 1/2"-13 10.75 (16.00)
3" (80) 8 (2.44) 40 (12.19) III 80 (24.38) IV 530 (2.357) 1/2"-13 10.75 (16.00)
3" (80) 10 (3.05) 40 (12.19) III 80 (24.38) IV 555 (2.469) 1/2"-13 10.75 (16.00)
3" (80) 12 (3.66) 36 (10.98) II 72 (21.94) IV 537 (2.389) 1/2"-13 10.75 (16.00)
3" (80) 15 (4.57) 30 (9.15) II 60 (18.30) IV 511 (2.273) 1/2"-13 10.75 (16.00)

31/2" (90) 6 (1.83) 36 (10.98) III 72 (21.94) V 576 (2.562) 1/2"-13 13.39 (19.92)
31/2" (90) 8 (2.44) 40 (12.19) III 80 (24.38) V 661 (2.940) 1/2"-13 13.39 (19.92)
31/2" (90) 10 (3.05) 40 (12.19) III 80 (24.38) V 692 (3.078) 1/2"-13 13.39 (19.92)
31/2" (90) 12 (3.66) 36 (10.98) III 72 (21.94) V 669 (2.976) 1/2"-13 13.39 (19.92)
31/2" (90) 15 (4.57) 30 (9.15) II 60 (18.30) IV 636 (2.829) 1/2"-13 13.39 (19.92)

4" (100) 6 (1.83) 36 (10.98) III 72 (21.94) V 701 (3.118) 5/8"-11 16.31 (24.27)
4" (100) 8 (2.44) 40 (12.19) IV 80 (24.38) V 805 (3.581) 5/8"-11 16.31 (24.27)
4" (100) 10 (3.05) 40 (12.19) IV 80 (24.38) V 843 (3.750) 5/8"-11 16.31 (24.27)
4" (100) 12 (3.66) 36 (10.98) III 72 (21.94) V 815 (3.625) 5/8"-11 16.31 (24.27)
4" (100) 15 (4.57) 30 (9.15) III 60 (18.30) V 775 (3.447) 5/8"-11 16.31 (24.27)

5" (125) 8 (2.44) 40 (12.19) IV 40 (12.19) V 686 (3.051) 5/8"-11 23.39 (34.81)
5" (125) 10 (3.05) 40 (12.19) IV 40 (12.19) V 741 (3.296) 5/8"-11 23.39 (34.81)
5" (125) 12 (3.66) 36 (10.98) IV 36 (10.98) V 748 (3.327) 5/8"-11 23.39 (34.81)
5" (125) 15 (4.57) 30 (9.15) IV 30 (9.15) V 760 (3.380) 5/8"-11 23.39 (34.81)
5" (125) 18 (5.49) 36 (10.98) IV 36 (10.98) V 912 (4.056) 5/8"-11 23.39 (34.81)

6" (150) 8 (2.44) 24 (7.31) IV 24 (7.31) IV 672 (2.989) 3/4"-10 31.49 (46.86)
6" (150) 10 (3.05) 30 (9.15) IV 30 (9.15) IV 840 (3.736) 3/4"-10 31.49 (46.86)
6" (150) 12 (3.66) 24 (7.31) IV 24 (7.31) IV 819 (3.643) 3/4"-10 31.49 (46.86)
6" (150) 15 (4.57) 30 (9.15) IV 30 (9.15) IV 1023 (4.550) 3/4"-10 31.49 (46.86)
6" (150) 18 (5.49) 18 (5.49) IV 18 (5.49) IV 945 (4.203) 3/4"-10 31.49 (46.86)

8" (200) 8 (2.44) 24 (7.31) V 24 (7.31) V 1072 (4.768) 3/4"-10 50.23 (74.75)
8" (200) 10 (3.05) 20 (6.09) V 20 (6.09) V 1088 (4.839) 3/4"-10 50.23 (74.75)
8" (200) 12 (3.66) 24 (7.31) V 24 (7.31) V 1306 (5.809) 3/4"-10 50.23 (74.75)
8" (200) 15 (4.57) 15 (4.57) V 15 (4.57) V 1256 (6.587) 3/4"-10 50.23 (74.75)
8" (200) 20 (6.10) 20 (6.10) V 20 (6.10) V 1674 (7.446) 3/4"-10 50.23 (74.75)

10" (250) 8 (2.44) 16 (4.88) V 16 (4.88) V 1293 (5.751) 7/8"-9 74.60 (111.01)
10" (250) 10 (3.05) 10 (3.05) V 10 (3.05) V 1243 (5.529) 7/8"-9 74.60 (111.01)
10" (250) 12 (3.66) 12 (3.66) V 12 (3.66) V 1492 (6.637) 7/8"-9 74.60 (111.01)
10" (250) 15 (4.57) 15 (4.57) V 15 (4.57) V 1866 (8.296) 7/8"-9 74.60 (111.01)
10" (250) 18 (5.49) 18 (5.49) V 18 (5.49) V 2238 (9.955) 7/8"-9 74.60 (111.01)

12" (300) 8 (2.44) 8 (2.44) V 8 (2.44) V 1361 (6.054) 7/8"-9 102.10 (151.94)
12" (300) 10 (3.05) 10 (3.05) V 10 (3.05) V 1701 (7.566) 7/8"-9 102.10 (151.94)
12" (300) 12 (3.66) 12 (3.66) V 12 (3.66) V 2042 (9.083) 7/8"-9 102.10 (151.94)
12" (300) 13 (3.96) 13 (3.96) V 13 (3.96) V 2212 (9.839) 7/8"-9 102.10 (151.94)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 96 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 16

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.50g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 15 (4.57) I 30 (9.15) I 9.0 (0.040) 3/8"-16 0.43 (0.64)
1/2" (15) 6 (1.83) 12 (3.66) I 24 (7.32) I 8.2 (0.036) 3/8"-16 0.43 (0.64)
1/2" (15) 7 (2.13) 14 (4.27) I 28 (8.54) I 9.5 (0.042) 3/8"-16 0.43 (0.64)
1/2" (15) 8 (2.44) 8 (2.44) I 16 (4.88) I 7.5 (0.033) 3/8"-16 0.43 (0.64)
1/2" (15) 9 (2.74) 9 (2.74) I 18 (5.49) I 8.4 (0.037) 3/8"-16 0.43 (0.64)

3/4" (20) 5 (1.52) 15 (4.57) I 30 (9.15) I 17.3 (0.077) 3/8"-16 0.83 (1.23)
3/4" (20) 6 (1.83) 12 (3.66) I 24 (7.32) I 15.8 (0.070) 3/8"-16 0.83 (1.23)
3/4" (20) 7 (2.13) 14 (4.27) I 28 (8.54) I 18.4 (0.082) 3/8"-16 0.83 (1.23)
3/4" (20) 8 (2.44) 8 (2.44) I 16 (4.88) I 14.4 (0.064) 3/8"-16 0.83 (1.23)
3/4" (20) 10 (3.05) 10 (3.05) I 20 (6.10) I 18.0 (0.080) 3/8"-16 0.83 (1.23)

1" (25) 5 (1.52) 20 (6.10) I 40 (12.19) I 30.5 (0.135) 3/8"-16 1.18 (1.75)
1" (25) 6 (1.83) 18 (5.49) I 36 (10.97) I 29.5 (0.131) 3/8"-16 1.18 (1.75)
1" (25) 7 (2.13) 14 (4.27) I 28 (8.54) I 26.2 (0.116) 3/8"-16 1.18 (1.75)
1" (25) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 29.9 (0.133) 3/8"-16 1.18 (1.75)
1" (25) 10 (3.05) 10 (3.05) I 20 (6.10) I 25.6 (0.114) 3/8"-16 1.18 (1.75)

11/4" (32) 5 (1.52) 20 (6.10) I 40 (12.19) I 40.6 (0.180) 3/8"-16 1.57 (2.33)
11/4" (32) 6 (1.83) 18 (5.49) I 36 (10.97) I 39.2 (0.174) 3/8"-16 1.57 (2.33)
11/4" (32) 7 (2.13) 21 (6.40) I 42 (12.80) I 45.8 (0.204) 3/8"-16 1.57 (2.33)
11/4" (32) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 39.8 (0.177) 3/8"-16 1.57 (2.33)
11/4" (32) 10 (3.05) 10 (3.05) I 20 (6.10) I 34.0 (0.151) 3/8"-16 1.57 (2.33)

11/2" (40) 5 (1.52) 25 (7.62) I 50 (15.24) I 64.7 (0.288) 3/8"-16 2.10 (3.17)
11/2" (40) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 65.1 (0.289) 3/8"-16 2.10 (3.17)
11/2" (40) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 53.2 (0.236) 3/8"-16 2.10 (3.17)
11/2" (40) 10 (3.05) 20 (6.10) I 40 (12.19) I 66.5 (0.296) 3/8"-16 2.10 (3.17)
11/2" (40) 12 (3.66) 12 (3.66) I 24 (7.32) I 54.6 (0.243) 3/8"-16 2.10 (3.17)

2" (50) 5 (1.52) 25 (7.62) I 50 (15.24) I 103.9 (0.462) 3/8"-16 3.37 (5.01)
2" (50) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 104.5 (0.465) 3/8"-16 3.37 (5.01)
2" (50) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 112.3 (0.499) 3/8"-16 3.37 (5.01)
2" (50) 10 (3.05) 20 (6.10) I 40 (12.19) I 106.7 (0.474) 3/8"-16 3.37 (5.01)
2" (50) 12 (3.66) 12 (3.66) I 24 (7.32) I 87.6 (0.389) 3/8"-16 3.37 (5.01)

21/2" (65) 5 (1.52) 30 (9.15) I 60 (18.29) II 176.3 (0.784) 1/2"-13 4.92 (7.32)
21/2" (65) 6 (1.83) 30 (9.15) I 60 (18.29) II 182.0 (0.809) 1/2"-13 4.92 (7.32)
21/2" (65) 9 (2.74) 27 (8.23) I 54 (16.46) II 184.5 (0.820) 1/2"-13 4.92 (7.32)
21/2" (65) 10 (3.05) 20 (6.10) I 40 (12.19) I 155.8 (0.693) 1/2"-13 4.92 (7.32)
21/2" (65) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 187.0 (0.832) 1/2"-13 4.92 (7.32)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 97 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 17

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.50g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 5 (1.52) 30 (9.15) I 60 (18.29) II 249.4 (1.109) 1/2"-13 6.96 (10.35)
3" (80) 6 (1.83) 30 (9.15) II 60 (18.29) II 257.5 (1.145) 1/2"-13 6.96 (10.35)
3" (80) 8 (2.44) 32 (9.75) II 64 (19.51) III 287.7 (1.279) 1/2"-13 6.96 (10.35)
3" (80) 10 (3.05) 30 (9.15) II 60 (18.29) II 290.0 (1.290) 1/2"-13 6.96 (10.35)
3" (80) 12 (3.66) 24 (7.32) II 48 ( 14.64) II 264.5 (1.176) 1/2"-13 6.96 (10.35)

31/2" (90) 5 (1.52) 35 (10.67) II 70 (21.33) III 368.3 (1.638) 1/2"-13 9.02 (13.42)
31/2" (90) 6 (1.83) 36 (10.98) II 72 (21.94) IV 387.9 (1.725) 1/2"-13 9.02 (13.42)
31/2" (90) 8 (2.44) 32 (9.75) II 64 (19.51) III 372.8 (1.658) 1/2"-13 9.02 (13.42)
31/2" (90) 10 (3.05) 30 (9.15) II 60 (18.29) III 375.8 (1.671) 1/2"-13 9.02 (13.42)
31/2" (90) 12 (3.66) 24 (7.32) II 48 ( 14.64) III 342.7 (1.524) 1/2"-13 9.02 (13.42)

4" (100) 5 (1.52) 40 (12.19) III 70 (21.33) IV 472.4 (2.101) 1/2"-13 11.57 (17.21)
4" ( 100) 6 (1.83) 36 (10.98) II 72 (21.94) IV 497.5 (2.213) 1/2"-13 11.57 (17.21)
4" ( 100) 8 (2.44) 40 (12.19) III 64 (19.51) IV 478.2 (2.127) 1/2"-13 11.57 (17.21)
4" ( 100) 10 (3.05) 36 (10.98) III 60 (18.29) IV 482.1 (2.144) 1/2"-13 11.57 (17.21)
4" ( 100) 12 (3.66) 33 (10.06) II 48 ( 14.64) III 439.6 (1.955) 1/2"-13 11.57 (17.21)

Notes:
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer
hanger spacing may be required when additional valves and fittings increase the load. For
electrical conduit support spacing and weight of conduit filled with conductors information,
see B-Line Strut Systems Catalog.
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for
brace attachment details
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity
and the additional seismic forces. Select a rod attachment detail from pages 39 thru 56 that meets
the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod
stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at
braced locations. Unbraced hangers never require rod stiffeners. Select a pipe hanger from pages
63 thru 71 that meets the hanger load requirements.
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.
5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See
Note E) on page 9.
6). Seismic forces include 1/3 of horizontal seismic force applied in vertical direction.
7). Charts on pages 95 - 98 are for 0.50g (ASD) applications.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 98 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 18

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 1 - Maximum Hanger Spacing for Steel Pipe
Seismic Force Level (g’s) 0.75g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 20 (6.10) I 40 (12.19) I 36 (0.161) 3/8"-16 0.98 (1.46)
1/2" (15) 6 (1.83) 18 (5.48) I 36 (10.98) I 34 (0.151) 3/8"-16 0.98 (1.46)
1/2" (15) 7 (2.13) 21 (6.40) I 42 (12.80) I 39 (0.173) 3/8"-16 0.98 (1.46)
1/2" (15) 8 (2.44) 16 (4.88) I 32 (9.75) I 33 (0.147) 3/8"-16 0.98 (1.46)
1/2" (15) 10 (3.05) 10 (3.05) I 20 (6.10) I 27 (0.120) 3/8"-16 0.98 (1.46)

3/4" (20) 5 (1.52) 25 (7.62) I 50 (15.24) I 59 (0.262) 3/8"-16 1.36 (2.02)


3/4" (20) 6 (1.83) 24 (7.32) I 48 (14.63) I 59 (0.262) 3/8"-16 1.36 (2.02)
3/4" (20) 7 (2.13) 21 (6.40) I 42 (12.80) I 55 (0.244) 3/8"-16 1.36 (2.02)
3/4" (20) 8 (2.44) 24 (7.32) I 48 (14.63) I 63 (0.280) 3/8"-16 1.36 (2.02)
3/4" (20) 10 (3.05) 20 (6.10) I 40 (12.19) I 58 (0.258) 3/8"-16 1.36 (2.02)

1" (25) 5 (1.52) 25 (7.62) I 50 (15.24) I 90 (0.400) 3/8"-16 2.06 (3.06)


1" (25) 6 (1.83) 24 (7.32) I 48 (14.63) I 90 (0.400) 3/8"-16 2.06 (3.06)
1" (25) 7 (2.13) 21 (6.40) I 42 (12.80) I 83 (0.369) 3/8"-16 2.06 (3.06)
1" (25) 8 (2.44) 24 (7.32) I 48 (14.63) I 95 (0.422) 3/8"-16 2.06 (3.06)
1" (25) 10 (3.05) 20 (6.10) I 40 (12.19) I 88 (0.391) 3/8"-16 2.06 (3.06)

11/4" (32) 5 (1.52) 30 (9.14) I 60 (18.30) II 150 (0.667) 3/8"-16 2.92 (4.34)
11/4" (32) 6 (1.83) 30 (9.14) I 60 (18.30) II 153 (0.680) 3/8"-16 2.92 (4.34)
11/4" (32) 7 (2.13) 28 (8.53) I 56 (17.07) I 148 (0.658) 3/8"-16 2.92 (4.34)
11/4" (32) 8 (2.44) 24 (7.32) I 48 (14.63) I 134 (0.596) 3/8"-16 2.92 (4.34)
11/4" (32) 10 (3.05) 30 (9.14) I 60 (18.30) II 168 (0.747) 3/8"-16 2.92 (4.34)

11/2" (40) 5 (1.52) 30 (9.14) I 60 (18.30) II 184 (0.818) 3/8"-16 3.60 (5.36)
11/2" (40) 6 (1.83) 30 (9.14) I 60 (18.30) II 189 (0.841) 3/8"-16 3.60 (5.36)
11/2" (40) 9 (2.74) 27 (8.23) I 54 (16.46) II 186 (0.827) 3/8"-16 3.60 (5.36)
11/2" (40) 10 (3.05) 30 (9.14) I 48 (14.63) II 207 (0.921) 3/8"-16 3.60 (5.36)
11/2" (40) 12 (3.66) 24 (7.32) I 60 (18.30) II 184 (0.818) 3/8"-16 3.60 (5.36)

2" (50) 5 (1.52) 35 (10.67) II 70 (21.33) III 300 (1.334) 3/8"-16 5.10 (7.59)
2" (50) 6 (1.83) 36 (10.98) II 72 (21.94) III 314 (1.397) 3/8"-16 5.10 (7.59)
2" (50) 8 (2.44) 32 (9.75) II 64 (19.51) III 296 (1.316) 3/8"-16 5.10 (7.59)
2" (50) 10 (3.05) 30 (9.14) II 60 (18.30) III 293 (1.303) 3/8"-16 5.10 (7.59)
2" (50) 12 (3.66) 24 (7.32) II 48 (14.63) II 260 (1.156) 3/8"-16 5.10 (7.59)

21/2" (65) 5 (1.52) 40 (12.19) III 80 (24.38) IV 521 (2.317) 1/2"-13 7.87 (11.71)
21/2" (65) 6 (1.83) 36 (10.98) III 72 (21.94) IV 484 (2.153) 1/2"-13 7.87 (11.71)
21/2" (65) 8 (2.44) 40 (12.19) III 80 (24.38) IV 551 (2.451) 1/2"-13 7.87 (11.71)
21/2" (65) 10 (3.05) 40 (12.19) III 80 (24.38) IV 571 (2.540) 1/2"-13 7.87 (11.71)
21/2" (65) 12 (3.66) 36 (10.98) III 72 (21.94) IV 543 (2.415) 1/2"-13 7.87 (11.71)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 99 of Raafat S. Aboulhosn
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 19

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Field Maximum Transverse Maximum Longitudinal Hanger &
Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 6 (1.83) 36 (10.98) IV 54 (16.46) IV 516 (2.295) 1/2"-13 10.75 (16.00)
3" (80) 8 (2.44) 40 (12.19) IV 56 (17.07) IV 559 (2.486) 1/2"-13 10.75 (16.00)
3" (80) 10 (3.05) 40 (12.19) IV 50 (15.24) IV 537 (2.388) 1/2"-13 10.75 (16.00)
3" (80) 12 (3.66) 36 (10.98) IV 48 (14.63) IV 547 (2.433) 1/2"-13 10.75 (16.00)
3" (80) 15 (4.57) 30 (9.15) IV 45 (13.71) IV 564 (2.508) 1/2"-13 10.75 (16.00)

31/2" (90) 6 (1.83) 36 (10.98) IV 42 (12.81) IV 522 (2.322) 1/2"-13 13.39 (19.92)
31/2" (90) 8 (2.44) 40 (12.19) IV 40 (12.19) IV 536 (2.384) 1/2"-13 13.39 (19.92)
31/2" (90) 10 (3.05) 40 (12.19) IV 40 (12.19) IV 569 (2.531) 1/2"-13 13.39 (19.92)
31/2" (90) 12 (3.66) 36 (10.98) IV 36 (10.98) IV 562 (2.500) 1/2"-13 13.39 (19.92)
31/2" (90) 15 (4.57) 30 (9.15) IV 45 (13.71) IV 703 (3.127) 1/2"-13 13.39 (19.92)

4" (100) 6 (1.83) 36 (10.98) IV 36 (10.98) IV 563 (2.504) 5/8"-11 16.31 (24.27)
4" (100) 8 (2.44) 32 (9.75) IV 32 (9.75) IV 555 (2.468) 5/8"-11 16.31 (24.27)
4" (100) 10 (3.05) 30 (9.15) IV 30 (9.15) IV 571 (2.540) 5/8"-11 16.31 (24.27)
4" (100) 12 (3.66) 36 (10.98) IV 36 (10.98) IV 685 (3.047) 5/8"-11 16.31 (24.27)
4" (100) 15 (4.57) 30 (9.15) IV 30 (9.15) IV 673 (2.993) 5/8"-11 16.31 (24.27)

5" (125) 8 (2.44) 24 (7.31) IV 24 (7.31) IV 655 (2.913) 5/8"-11 23.39 (34.81)
5" (125) 10 (3.05) 20 (6.09) IV 20 (6.09) IV 643 (2.860) 5/8"-11 23.39 (34.81)
5" (125) 12 (3.66) 24 (7.31) IV 24 (7.31) IV 772 (3.434) 5/8"-11 23.39 (34.81)
5" (125) 15 (4.57) 15 (4.57) IV 15 (4.57) IV 702 (3.122) 5/8"-11 23.39 (34.81)
5" (125) 18 (5.49) 18 (5.49) IV 18 (5.49) IV 842 (3.745) 5/8"-11 23.39 (34.81)

6" (150) 8 (2.44) 16 (4.88) IV 16 (4.88) IV 693 (3.082) 3/4"-10 31.49 (46.86)
6" (150) 10 (3.05) 20 (6.09) IV 20 (6.09) IV 866 (3.852) 3/4"-10 31.49 (46.86)
6" (150) 12 (3.66) 12 (3.66) IV 12 (3.66) IV 756 (3.362) 3/4"-10 31.49 (46.86)
6" (150) 15 (4.57) 15 (4.57) IV 15 (4.57) IV 945 (4.203) 3/4"-10 31.49 (46.86)
6" (150) 18 (5.49) 18 (5.49) IV 18 (5.49) IV 1133 (5.040) 3/4"-10 31.49 (46.86)

8" (200) 8 (2.44) 16 (4.88) V 16 (4.88) V 1105 (4.915) 3/4"-10 50.23 (74.75)
8" (200) 10 (3.05) 10 (3.05) V 10 (3.05) V 1004 (4.466) 3/4"-10 50.23 (74.75)
8" (200) 12 (3.66) 12 (3.66) V 12 (3.66) V 1205 (5.360) 3/4"-10 50.23 (74.75)
8" (200) 15 (4.57) 15 (4.57) V 15 (4.57) V 1507 (6.703) 3/4"-10 50.23 (74.75)
8" (200) 18 (5.49) 18 (5.49) V 18 (5.49) V 1808 (8.042) 3/4"-10 50.23 (74.75)

10" (250) 5 (1.52) 10 (3.05) V 10 (3.05) V 1026 (4.564) 7/8"-9 74.60 (111.01)
10" (250) 6 (1.83) 12 (3.66) V 12 (3.66) V 1231 (5.476) 7/8"-9 74.60 (111.01)
10" (250) 8 (2.44) 8 (2.44) V 8 (2.44) V 1193 (5.307) 7/8"-9 74.60 (111.01)
10" (250) 10 (3.05) 10 (3.05) V 10 (3.05) V 1492 (6.637) 7/8"-9 74.60 (111.01)
10" (250) 12 (3.66) 12 (3.66) V 12 (3.66) V 1790 (7.962) 7/8"-9 74.60 (111.01)

12" (300) 5 (1.52) 5 (1.52) V 5 (1.52) V 1021 (4.541) 7/8"-9 102.10 (151.94)
12" (300) 6 (1.83) 6 (1.83) V 6 (1.83) V 1225 (5.449) 7/8"-9 102.10 (151.94)
12" (300) 8 (2.44) 8 (2.44) V 8 (2.44) V 1633 (7.264) 7/8"-9 102.10 (151.94)
12" (300) 9 (2.74) 9 (2.74) V 9 (2.74) V 1838 (8.176) 7/8"-9 102.10 (151.94)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 100 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 20

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.75g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 10 (3.05) I 20 (6.10) I 9.1 (0.040) 3/8"-16 0.43 (0.64)
1/2" (15) 6 (1.83) 12 (3.66) I 24 (7.32) I 11.0 (0.049) 3/8"-16 0.43 (0.64)
1/2" (15) 7 (2.13) 7 (2.13) I 14 (4.27) I 8.3 (0.037) 3/8"-16 0.43 (0.64)
1/2" (15) 8 (2.44) 8 (2.44) I 16 (4.88) I 9.5 (0.042) 3/8"-16 0.43 (0.64)

3/4" (20) 5 (1.52) 10 (3.05) I 20 (6.10) I 17.6 (0.078) 3/8"-16 0.83 (1.23)
3/4" (20) 6 (1.83) 12 (3.66) I 24 (7.32) I 21.2 (0.094) 3/8"-16 0.83 (1.23)
3/4" (20) 7 (2.13) 7 (2.13) I 14 (4.27) I 16.0 (0.071) 3/8"-16 0.83 (1.23)
3/4" (20) 8 (2.44) 8 (2.44) I 16 (4.88) I 18.3 (0.081) 3/8"-16 0.83 (1.23)
3/4" (20) 10 (3.05) 10 (3.05) I 20 (6.10) I 22.8 (0.101) 3/8"-16 0.83 (1.23)

1" (25) 5 (1.52) 15 (4.57) I 30 (9.15) I 33.9 (0.151) 3/8"-16 1.18 (1.75)
1" (25) 6 (1.83) 12 (3.66) I 24 (7.32) I 30.1 (0.134) 3/8"-16 1.18 (1.75)
1" (25) 7 (2.13) 14 (4.27) I 28 (8.54) I 35.1 (0.156) 3/8"-16 1.18 (1.75)
1" (25) 8 (2.44) 8 (2.44) I 16 (4.88) I 26.0 (0.115) 3/8"-16 1.18 (1.75)
1" (25) 10 (3.05) 10 (3.05) I 20 (6.10) I 32.4 (0.144) 3/8"-16 1.18 (1.75)

11/4" (32) 5 (1.52) 15 (4.57) I 30 (9.15) I 45.1 (0.200) 3/8"-16 1.57 (2.33)
11/4" (32) 6 (1.83) 18 (5.49) I 36 (10.97) I 54.2 (0.241) 3/8"-16 1.57 (2.33)
11/4" (32) 7 (2.13) 14 (4.27) I 28 (8.54) I 46.7 (0.208) 3/8"-16 1.57 (2.33)
11/4" (32) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 53.4 (0.237) 3/8"-16 1.57 (2.33)
11/4" (32) 10 (3.05) 10 (3.05) I 20 (6.10) I 43.2 (0.192) 3/8"-16 1.57 (2.33)

11/2" (40) 5 (1.52) 20 (6.10) I 40 (12.19) I 76.1 (0.338) 3/8"-16 2.10 (3.17)
11/2" (40) 6 (1.83) 18 (5.49) I 36 (10.97) I 72.4 (0.322) 3/8"-16 2.10 (3.17)
11/2" (40) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 71.4 (0.317) 3/8"-16 2.10 (3.17)
11/2" (40) 10 (3.05) 10 (3.05) I 20 (6.10) I 57.7 (0.256) 3/8"-16 2.10 (3.17)
11/2" (40) 12 (3.66) 12 (3.66) I 24 (7.32) I 69.3 (0.308) 3/8"-16 2.10 (3.17)

2" (50) 5 (1.52) 20 (6.10) I 40 (12.19) I 122.2 (0.543) 3/8"-16 3.37 (5.01)
2" (50) 6 (1.83) 18 (5.49) I 36 (10.97) I 116.3 (0.517) 3/8"-16 3.37 (5.01)
2" (50) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 114.6 (0.510) 3/8"-16 3.37 (5.01)
2" (50) 10 (3.05) 20 (6.10) I 40 (12.19) I 143.2 (0.637) 3/8"-16 3.37 (5.01)
2" (50) 12 (3.66) 12 (3.66) I 24 (7.32) I 111.2 (0.494) 3/8"-16 3.37 (5.01)

21/2" (65) 5 (1.52) 25 (7.62) I 50 (15.24) II 215.2 (0.957) 1/2"-13 4.92 (7.32)
21/2" (65) 6 (1.83) 24 (7.32) I 48 ( 14.64) II 214.0 (0.952) 1/2"-13 4.92 (7.32)
21/2" (65) 9 (2.74) 18 (5.49) I 36 (10.97) II 188.2 (0.837) 1/2"-13 4.92 (7.32)
21/2" (65) 10 (3.05) 20 (6.10) I 40 (12.19) II 209.1 (0.930) 1/2"-13 4.92 (7.32)
21/2" (65) 12 (3.66) 12 (3.66) I 24 (7.32) I 162.3 (0.722) 1/2"-13 4.92 (7.32)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 101 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 21

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 0.75g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 5 (1.52) 25 (7.62) II 50 (15.24) III 304.5 (1.354) 1/2"-13 6.96 (10.35)
3" (80) 6 (1.83) 24 (7.32) II 48 ( 14.64) III 302.7 (1.346) 1/2"-13 6.96 (10.35)
3" (80) 8 (2.44) 24 (7.32) II 48 ( 14.64) III 320.1 (1.424) 1/2"-13 6.96 (10.35)
3" (80) 10 (3.05) 20 (6.09) II 40 (12.19) II 295.8 (1.316) 1/2"-13 6.96 (10.35)
3" (80) 12 (3.66) 12 (3.66) II 24 (7.32) II 229.7 (1.022) 1/2"-13 6.96 (10.35)

31/2" (90) 5 (1.52) 25 (7.62) II 50 (15.24) IV 394.6 (1.755) 1/2"-13 9.02 (13.42)
31/2" (90) 6 (1.83) 24 (7.32) II 48 ( 14.64) IV 392.4 (1.745) 1/2"-13 9.02 (13.42)
31/2" (90) 8 (2.44) 24 (7.32) III 48 ( 14.64) IV 414.9 (1.845) 1/2"-13 9.02 (13.42)
31/2" (90) 10 (3.05) 20 (6.09) II 40 (12.19) III 383.3 (1.705) 1/2"-13 9.02 (13.42)
31/2" (90) 12 (3.66) 24 (7.32) III 48 ( 14.64) IV 460.0 (2.046) 1/2"-13 9.02 (13.42)

4" (100) 5 (1.52) 30 (9.14) III 60 (18.29) V 592.9 (2.637) 1/2"-13 11.57 (17.21)
4" ( 100) 6 (1.83) 30 (9.14) III 60 (18.29) V 607.4 (2.702) 1/2"-13 11.57 (17.21)
4" ( 100) 8 (2.44) 24 (7.32) III 48 ( 14.64) IV 532.2 (2.367) 1/2"-13 11.57 (17.21)
4" ( 100) 10 (3.05) 20 (6.09) III 40 (12.19) IV 491.7 (2.187) 1/2"-13 11.57 (17.21)
4" ( 100) 12 (3.66) 24 (7.32) III 48 ( 14.64) IV 590.0 (2.624) 1/2"-13 11.57 (17.21)

Notes:
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer
hanger spacing may be required when additional valves and fittings increase the load. For
electrical conduit support spacing and weight of conduit filled with conductors information,
see B-Line Strut Systems Catalog.
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for
brace attachment details
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity
and the additional seismic forces. Select a rod attachment detail from pages 39 thru 56 that meets
the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod
stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at
braced locations. Unbraced hangers never require rod stiffeners. Select a pipe hanger from pages
63 thru 71 that meets the hanger load requirements.
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.
5). Table 1 is are for steel pipe. Spacing limitations may exist for other types of pipe. See
Note E) on page 9.
6). Seismic forces include 1/3 of horizontal seismic force applied in vertical direction.
7). Charts on pages 99 - 102 are for 0.75g (ASD) applications.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 102 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 22

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 1 - Maximum Hanger Spacing for Steel Pipe
Seismic Force Level (g’s) 1.0g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 15 (4.57) I 30 (9.14) I 36 (0.160) 3/8"-16 0.98 (1.46)
1/2" (15) 6 (1.83) 18 (5.48) I 36 (10.98) I 43 (0.191) 3/8"-16 0.98 (1.46)
1/2" (15) 7 (2.13) 14 (4.27) I 28 (8.53) I 37 (0.164) 3/8"-16 0.98 (1.46)
1/2" (15) 8 (2.44) 16 (4.88) I 32 (9.75) I 42 (0.187) 3/8"-16 0.98 (1.46)
1/2" (15) 10 (3.05) 10 (3.05) I 20 (6.10) I 33 (0.147) 3/8"-16 0.98 (1.46)

3/4" (20) 5 (1.52) 20 (6.10) I 40 (12.19) I 63 (0.280) 3/8"-16 1.36 (2.02)


3/4" (20) 6 (1.83) 18 (5.48) I 36 (10.98) I 60 (0.267) 3/8"-16 1.36 (2.02)
3/4" (20) 7 (2.13) 21 (6.40) I 42 (12.80) I 70 (0.311) 3/8"-16 1.36 (2.02)
3/4" (20) 8 (2.44) 16 (4.88) I 32 (9.75) I 58 (0.258) 3/8"-16 1.36 (2.02)
3/4" (20) 10 (3.05) 10 (3.05) I 20 (6.10) I 45 (0.200) 3/8"-16 1.36 (2.02)

1" (25) 5 (1.52) 20 (6.10) I 40 (12.19) I 96 (0.427) 3/8"-16 2.06 (3.06)


1" (25) 6 (1.83) 24 (7.32) I 48 (14.63) I 118 (0.511) 3/8"-16 2.06 (3.06)
1" (25) 7 (2.13) 21 (6.40) I 42 (12.80) I 106 (0.471) 3/8"-16 2.06 (3.06)
1" (25) 8 (2.44) 16 (4.88) I 32 (9.75) I 88 (0.391) 3/8"-16 2.06 (3.06)
1" (25) 10 (3.05) 20 (6.10) I 40 (12.19) I 110 (0.489) 3/8"-16 2.06 (3.06)

11/4" (32) 5 (1.52) 25 (7.62) I 50 (15.24) II 165 (0.734) 3/8"-16 2.92 (4.34)
11/4" (32) 6 (1.83) 24 (7.32) I 48 (14.63) II 164 (0.729) 3/8"-16 2.92 (4.34)
11/4" (32) 7 (2.13) 21 (6.40) I 42 (12.80) I 150 (0.667) 3/8"-16 2.92 (4.34)
11/4" (32) 8 (2.44) 24 (7.32) I 48 (14.63) II 171 (0.760) 3/8"-16 2.92 (4.34)
11/4" (32) 10 (3.05) 20 (6.10) I 40 (12.19) I 156 (0.694) 3/8"-16 2.92 (4.34)

11/2" (40) 5 (1.52) 25 (7.62) I 50 (15.24) II 204 (0.907) 3/8"-16 3.60 (5.36)
11/2" (40) 6 (1.83) 24 (7.32) I 48 (14.63) II 202 (0.898) 3/8"-16 3.60 (5.36)
11/2" (40) 9 (2.74) 27 (8.23) I 54 (16.46) II 238 (1.058) 3/8"-16 3.60 (5.36)
11/2" (40) 10 (3.05) 20 (6.10) I 40 (12.19) II 192 (0.854) 3/8"-16 3.60 (5.36)
11/2" (40) 12 (3.66) 24 (7.32) I 48 (14.63) II 230 (1.023) 3/8"-16 3.60 (5.36)

2" (50) 5 (1.52) 30 (9.14) II 60 (18.30) III 340 (1.512) 3/8"-16 5.10 (7.59)
2" (50) 6 (1.83) 30 (9.14) II 60 (18.30) III 347 (1.543) 3/8"-16 5.10 (7.59)
2" (50) 8 (2.44) 24 (7.32) II 48 (14.63) III 299 (1.330) 3/8"-16 5.10 (7.59)
2" (50) 10 (3.05) 30 (9.14) II 60 (18.30) III 374 (1.663) 3/8"-16 5.10 (7.59)
2" (50) 12 (3.66) 24 (7.32) II 48 (14.63) III 326 (1.450) 3/8"-16 5.10 (7.59)

21/2" (65) 5 (1.52) 35 (10.67) III 70 (21.33) V 603 (2.682) 1/2"-13 7.87 (11.71)
21/2" (65) 6 (1.83) 36 (10.98) III 72 (21.94) V 630 (2.802) 1/2"-13 7.87 (11.71)
21/2" (65) 8 (2.44) 32 (9.75) III 64 (19.51) V 588 (2.615) 1/2"-13 7.87 (11.71)
21/2" (65) 10 (3.05) 30 (9.14) III 60 (18.30) IV 577 (2.566) 1/2"-13 7.87 (11.71)
21/2" (65) 12 (3.66) 24 (7.32) III 48 (14.63) IV 504 (2.242) 1/2"-13 7.87 (11.71)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 103 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 23

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Field Maximum Transverse Maximum Longitudinal Hanger &
Hanger Transverse Structure Longitudinal Structure Rod Water
Nominal Spacing Support Connection Support Connection Loads Rod Filled
Pipe Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 6 (1.83) 36 (10.98) IV 60 (18.30) V 731 (3.251) 1/2"-13 10.75 (16.00)
3" (80) 8 (2.44) 32 (9.75) IV 64 (19.51) V 803 (3.572) 1/2"-13 10.75 (16.00)
3" (80) 10 (3.05) 30 (9.15) IV 60 (18.30) V 788 (3.505) 1/2"-13 10.75 (16.00)
3" (80) 12 (3.66) 36 (10.98) IV 60 (18.30) V 817 (3.634) 1/2"-13 10.75 (16.00)
3" (80) 15 (4.57) 30 (9.15) IV 60 (18.30) V 860 (3.825) 1/2"-13 10.75 (16.00)

31/2" (90) 6 (1.83) 36 (10.98) V 48 (14.63) V 750 (3.336) 1/2"-13 13.39 (19.92)
31/2" (90) 8 (2.44) 40 (12.19) V 48 (14.63) V 786 (3.496) 1/2"-13 13.39 (19.92)
31/2" (90) 10 (3.05) 40 (12.19) V 50 (15.24) V 848 (3.772) 1/2"-13 13.39 (19.92)
31/2" (90) 12 (3.66) 36 (10.98) V 48 (14.63) V 857 (3.812) 1/2"-13 13.39 (19.92)
31/2" (90) 15 (4.57) 30 (9.15) IV 45 (13.71) V 870 (3.870) 1/2"-13 13.39 (19.92)

4" (100) 6 (1.83) 36 (10.98) V 42 (12.80) V 815 (3.625) 5/8"-11 16.31 (24.27)
4" (100) 8 (2.44) 40 (12.19) V 40 (12.19) V 826 (3.674) 5/8"-11 16.31 (24.27)
4" (100) 10 (3.05) 40 (12.19) V 40 (12.19) V 870 (3.870) 5/8"-11 16.31 (24.27)
4" (100) 12 (3.66) 36 (10.98) V 36 (10.98) V 848 (3.772) 5/8"-11 16.31 (24.27)
4" (100) 15 (4.57) 30 (9.15) V 30 (9.15) V 815 (3.625) 5/8"-11 16.31 (24.27)

5" (125) 8 (2.44) 24 (7.31) V 24 (7.31) V 811 (3.607) 5/8"-11 23.39 (34.81)
5" (125) 10 (3.05) 20 (6.09) V 20 (6.09) V 780 (3.469) 5/8"-11 23.39 (34.81)
5" (125) 12 (3.66) 24 (7.31) V 24 (7.31) V 936 (4.163) 5/8"-11 23.39 (34.81)
5" (125) 15 (4.57) 15 (4.57) V 15 (4.57) V 819 (3.643) 5/8"-11 23.39 (34.81)
5" (125) 18 (5.49) 18 (5.49) V 18 (5.49) V 982 (4.368) 5/8"-11 23.39 (34.81)

6" (150) 8 (2.44) 16 (4.88) V 16 (4.88) V 840 (3.736) 3/4"-10 31.49 (46.86)
6" (150) 10 (3.05) 20 (6.09) V 20 (6.09) V 1050 (4.670) 3/4"-10 31.49 (46.86)
6" (150) 12 (3.66) 12 (3.66) V 12 (3.66) V 1882 (3.923) 3/4"-10 31.49 (46.86)
6" (150) 15 (4.57) 15 (4.57) V 15 (4.57) V 1102 (4.902) 3/4"-10 31.49 (46.86)
6" (150) 18 (5.49) 18 (5.49) V 18 (5.49) V 1322 (5.880) 3/4"-10 31.49 (46.86)

8" (200) 5 (2.44) 10 (3.05) V 10 (3.05) V 837 (3.723) 3/4"-10 50.23 (74.75)
8" (200) 6 (3.05) 12 (3.66) V 12 (3.66) V 1004 (4.466) 3/4"-10 50.23 (74.75)
8" (200) 8 (3.66) 8 (2.44) V 8 (2.44) V 937 (4.168) 3/4"-10 50.23 (74.75)
8" (200) 10 (4.57) 10 (3.05) V 10 (3.05) V 1172 (5.213) 3/4"-10 50.23 (74.75)
8" (200) 12 (5.49) 12 (3.66) V 12 (3.66) V 1406 (6.254) 3/4"-10 50.23 (74.75)

10" (250) 5 (1.52) 5 (1.52) V 5 (1.52) V 870 (3.870) 7/8"-9 74.60 (111.01)
10" (250) 6 (1.83) 6 (1.83) V 6 (1.83) V 1044 (4.644) 7/8"-9 74.60 (111.01)
10" (250) 8 (2.44) 8 (2.44) V 8 (2.44) V 1392 (6.192) 7/8"-9 74.60 (111.01)
10" (250) 9 (2.74) 9 (2.74) V 9 (2.74) V 1566 (6.966) 7/8"-9 74.60 (111.01)

12" (300) 4 (1.22) 4 (1.22) V 4 (1.22) V 953 (4.239) 7/8"-9 102.10 (151.94)
12" (300) 5 (1.52) 5 (1.52) V 5 (1.52) V 1191 (5.298) 7/8"-9 102.10 (151.94)
12" (300) 6 (1.83) 6 (1.83) V 6 (1.83) V 1429 (6.356) 7/8"-9 102.10 (151.94)

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 104 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 24

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 1.0g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)
1/2" (15) 5 (1.52) 10 (3.05) I 20 (6.10) I 11.5 (0.051) 3/8"-16 0.43 (0.64)
1/2" (15) 6 (1.83) 6 (1.83) I 12 (3.66) I 8.6 (0.038) 3/8"-16 0.43 (0.64)
1/2" (15) 7 (2.13) 7 (2.13) I 14 (4.27) I 10.0 (0.044) 3/8"-16 0.43 (0.64)
1/2" (15) 8 (2.44) 8 (2.44) I 16 (4.88) I 11.5 (0.051) 3/8"-16 0.43 (0.64)

3/4" (20) 5 (1.52) 10 (3.05) I 20 (6.10) I 22.1 (0.098) 3/8"-16 0.83 (1.23)
3/4" (20) 6 (1.83) 6 (1.83) I 12 (3.66) I 16.6 (0.074) 3/8"-16 0.83 (1.23)
3/4" (20) 7 (2.13) 7 (2.13) I 14 (4.27) I 19.4 (0.086) 3/8"-16 0.83 (1.23)
3/4" (20) 8 (2.44) 8 (2.44) I 16 (4.88) I 22.1 (0.098) 3/8"-16 0.83 (1.23)

1" (25) 5 (1.52) 10 (3.05) I 20 (6.10) I 31.5 (0.140) 3/8"-16 1.18 (1.75)
1" (25) 6 (1.83) 12 (3.66) I 24 (7.32) I 37.8 (0.168) 3/8"-16 1.18 (1.75)
1" (25) 7 (2.13) 7 (2.13) I 14 (4.27) I 27.5 (0.122) 3/8"-16 1.18 (1.75)
1" (25) 8 (2.44) 8 (2.44) I 16 (4.88) I 31.5 (0.140) 3/8"-16 1.18 (1.75)
1" (25) 10 (3.05) 10 (3.05) I 20 (6.10) I 39.3 (0.175) 3/8"-16 1.18 (1.75)

11/4" (32) 5 (1.52) 15 (4.57) I 30 (9.15) I 57.6 (0.256) 3/8"-16 1.57 (2.33)
11/4" (32) 6 (1.83) 12 (3.66) I 24 (7.32) I 50.2 (0.223) 3/8"-16 1.57 (2.33)
11/4" (32) 7 (2.13) 14 (4.27) I 28 (8.54) I 58.6 (0.260) 3/8"-16 1.57 (2.33)
11/4" (32) 8 (2.44) 8 (2.44) I 16 (4.88) I 41.9 (0.186) 3/8"-16 1.57 (2.33)
11/4" (32) 10 (3.05) 10 (3.05) I 20 (6.10) I 52.3 (0.232) 3/8"-16 1.57 (2.33)

11/2" (40) 5 (1.52) 15 (4.57) I 30 (9.15) I 77.0 (0.342) 3/8"-16 2.10 (3.17)
11/2" (40) 6 (1.83) 12 (3.66) I 24 (7.32) I 67.2 (0.299) 3/8"-16 2.10 (3.17)
11/2" (40) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 89.6 (0.398) 3/8"-16 2.10 (3.17)
11/2" (40) 10 (3.05) 10 (3.05) I 20 (6.10) I 70.0 (0.311) 3/8"-16 2.10 (3.17)
11/2" (40) 12 (3.66) 12 (3.66) I 24 (7.32) I 84.0 (0.373) 3/8"-16 2.10 (3.17)

2" (50) 5 (1.52) 20 (6.10) I 35 (10.67) I 140.4 (0.624) 3/8"-16 3.37 (5.01)
2" (50) 6 (1.83) 18 (5.49) I 36 (10.97) I 148.3 (0.659) 3/8"-16 3.37 (5.01)
2" (50) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 143.8 (0.639) 3/8"-16 3.37 (5.01)
2" (50) 10 (3.05) 10 (3.05) I 20 (6.10) I 112.3 (0.499) 3/8"-16 3.37 (5.01)
2" (50) 12 (3.66) 12 (3.66) I 24 (7.32) I 134.8 (0.599) 3/8"-16 3.37 (5.01)

21/2" (65) 5 (1.52) 20 (6.10) I 40 (12.19) II 229.6 (1.021) 1/2"-13 4.92 (7.32)
21/2" (65) 6 (1.83) 18 (5.49) I 36 (10.97) II 216.5 (0.963) 1/2"-13 4.92 (7.32)
21/2" (65) 9 (2.74) 18 (5.49) II 36 (10.97) II 236.1 (1.050) 1/2"-13 4.92 (7.32)
21/2" (65) 10 (3.05) 20 (6.10) II 40 (12.19) II 262.4 (1.167) 1/2"-13 4.92 (7.32)
21/2" (65) 12 (3.66) 12 (3.66) I 24 (7.32) I 196.8 (0.875) 1/2"-13 4.92 (7.32)

Continued on following page.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 105 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 25

SUPPORT SPACING FOR SINGLE ROD HANGER PIPING


Table 2 - Maximum Hanger Spacing for Copper Tubing
Seismic Force Level (g’s) 1.0g (ASD)

Field Maximum Transverse Maximum Longitudinal Hanger &


Nominal Hanger Transverse Structure Longitudinal Structure Rod Water
Copper Spacing Support Connection Support Connection Loads Rod Filled
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)

3" (80) 5 (1.52) 20 (6.09) II 40 (12.19) III 324.8 (1.445) 1/2"-13 6.96 (10.35)
3" (80) 6 (1.83) 18 (5.49) II 36 (10.97) III 306.2 (1.362) 1/2"-13 6.96 (10.35)
3" (80) 8 (2.44) 16 (4.88) II 32 ( 9.75) III 296.9 (1.320) 1/2"-13 6.96 (10.35)
3" (80) 10 (3.05) 20 (6.09) II 40 (12.19) III 371.2 (1.651) 1/2"-13 6.96 (10.35)
3" (80) 12 (3.66) 12 (3.66) II 24 (7.32) II 278.4 (1.238) 1/2"-13 6.96 (10.35)

31/2" (90) 5 (1.52) 25 (7.62) III 50 (15.24) IV 511.1 (2.273) 1/2"-13 9.02 (13.42)
31/2" (90) 6 (1.83) 24 (7.32) III 48 ( 14.64) IV 505.1 (2.246) 1/2"-13 9.02 (13.42)
31/2" (90) 8 (2.44) 24 (7.32) III 48 ( 14.64) IV 529.1 (2.353) 1/2"-13 9.02 (13.42)
31/2" (90) 10 (3.05) 20 (6.09) III 40 (12.19) IV 481.0 (2.139) 1/2"-13 9.02 (13.42)
31/2" (90) 12 (3.66) 12 (3.66) III 24 (7.32) III 360.8 (1.605) 1/2"-13 9.02 (13.42)

4" (100) 5 (1.52) 25 (7.62) IV 50 (15.24) V 655.6 (2.916) 1/2"-13 11.57 (17.21)
4" ( 100) 6 (1.83) 24 (7.32) IV 48 ( 14.64) V 647.9 (2.882) 1/2"-13 11.57 (17.21)
4" ( 100) 8 (2.44) 24 (7.32) IV 48 ( 14.64) V 678.7 (3.019) 1/2"-13 11.57 (17.21)
4" ( 100) 10 (3.05) 20 (6.09) IV 40 (12.19) IV 617.0 (2.744) 1/2"-13 11.57 (17.21)
4" ( 100) 12 (3.66) 24 (7.32) IV 48 ( 14.64) V 740.4 (3.293) 1/2"-13 11.57 (17.21)

Notes:
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer
hanger spacing may be required when additional valves and fittings increase the load. For
electrical conduit support spacing and weight of conduit filled with conductors information,
see B-Line Strut Systems Catalog.
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for
brace attachment details
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity
and the additional seismic forces. Select a rod attachment detail from pages 39 thru 56 that meets
the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod
stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at
braced locations. Unbraced hangers never require rod stiffeners. Select a pipe hanger from pages
63 thru 71 that meets the hanger load requirements.
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.
5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See
Note E) on page 9.
6). Seismic forces include 1/3 of horizontal seismic force applied in vertical direction.
7). Charts on pages 103 - 106 are for 1.00g applications.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 106 of
Structural Engineer S 3913
**SRS2002-OSpg.82-107 (10/02) N 1/3/03 5:20 PM Page 26

This Page Has Been


Intentionally Left Blank

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 107 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 1

Appendix 2
Seismic Bracing Charts for Trapeze Supports

Pages 109 - 114 Tables 1 & 2 for Seismic Force Level 0.15g (ASD)

Pages 115 - 120 Tables 1 & 2 for Seismic Force Level 0.30g (ASD)

Pages 121 - 126 Tables 1 & 2 for Seismic Force Level 0.45g (ASD)

Pages 127 - 132 Tables 1 & 2 for Seismic Force Level 0.50g (ASD)

Pages 133 - 138 Tables 1 & 2 for Seismic Force Level 0.75g (ASD)

Pages 139 - 144 Tables 1 & 2 for Seismic Force Level 1.00g (ASD)

Page 145 Footnotes for Tables 1 & 2 found under Appendix 2

Table 1 - 2 Transverse and 2 Longitudinal Braces at each Location


Table 2 - 1 Transverse and 2 Longitudinal Braces at each Location

This Appendix contains bracing tables developed using allowable stress design
(ASD) for the following seismic force values (i.e. “g-values”): .15g (ASD),
.30g (ASD), .45g (ASD), .50g (ASD), .75g (ASD), and 1.0g (ASD). The
building code uses strength design which can be increased by a factor of 1.4. (See
page 1 for further information.) These charts cover the vast majority of seismic
requirements from coast to coast, from Zone 1 to Zone 4 applications, and take
into account the many codes which may be referenced for a specific project.

The seismic zone, building type, and other factors determine the level of
seismic force for a particular project. The project design professional should
determine the correct seismic force value using the appropriate building code and
local requirements. Use of the correct table is very important to ensure that the
correct brace spacing and anchorage is provided. See pages 1 - 8 for more
information.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 108 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 2

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 for Seismic Force Level 0.15g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 36 I 78 I 36 3/8 90 3/8

0 - 10 8 40 I 80 I 42 3/8 102 3/8

0 - 10 10 40 I 80 I 53 3/8 112 3/8

0 - 10 12 36 I 72 I 63 3/8 117 3/8

0 - 10 16 32 I 80 I 84 3/8 144 3/8

0 - 10 20 40 I 80 I 105 3/8 165 3/8

0 - 10 24 24 I 72 I 126 3/8 180 3/8

11 - 25 6 36 I 66 I 79 3/8 202 3/8


11 - 25 6 --- --- 78 II 79 3/8 225 3/8

11 - 25 8 40 I 64 I 105 3/8 225 3/8


11 - 25 8 --- --- 80 II 105 3/8 255 3/8

11 - 25 10 40 I 60 I 132 3/8 244 3/8


11 - 25 10 --- --- 80 II 132 3/8 281 3/8

11 - 25 12 36 I 60 I 158 3/8 270 3/8


11 - 25 12 --- --- 72 II 158 3/8 292 3/8

11 - 25 16 32 I 64 I 210 3/8 330 3/8


11 - 25 16 --- --- 80 II 210 3/8 360 3/8

11 - 25 20 40 I 60 I 263 3/8 375 3/8


11 - 25 20 --- --- 80 II 263 3/8 412 3/8

11 - 25 24 24 I 48 I 315 3/8 405 3/8


11 - 25 24 --- --- 72 II 315 3/8 450 3/8

26 - 50 6 30 I 30 I 158 3/8 270 3/8


26 - 50 6 36 II 54 II 158 3/8 360 3/8
26 - 50 6 --- --- 78 III 158 3/8 450 3/8

26 - 50 8 32 I 32 I 210 3/8 330 3/8


26 - 50 8 40 II 56 II 210 3/8 420 3/8
26 - 50 8 --- --- 80 III 210 3/8 510 3/8

26 - 50 10 30 I 30 I 263 3/8 375 3/8


26 - 50 10 40 II 50 II 263 3/8 450 3/8
26 - 50 10 --- --- 80 III 263 3/8 562 3/8

26 - 50 12 24 I 24 I 315 3/8 405 3/8


26 - 50 12 36 II 48 II 315 3/8 495 3/8
26 - 50 12 --- --- 72 III 315 3/8 585 3/8

26 - 50 16 32 I 32 I 420 3/8 540 3/8


26 - 50 16 --- --- 48 II 420 3/8 600 3/8
26 - 50 16 --- --- 80 III 420 3/8 720 1/2

26 - 50 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 109 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 3

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.15g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 20 20 I 20 I 525 3/8 600 3/8


26 - 50 20 40 II 40 II 525 3/8 675 1/2
26 - 50 20 --- --- 80 III 525 3/8 825 1/2

26 - 50 24 24 I 24 I 630 3/8 720 1/2


26 - 50 24 --- --- 48 II 630 3/8 810 1/2
26 - 50 24 --- --- 72 III 630 3/8 900 1/2

51 - 75 6 18 I 18 I 237 3/8 337 3/8


51 - 75 6 36 II 36 II 237 3/8 439 3/8
51 - 75 6 --- --- 54 III 237 3/8 540 3/8
51 - 75 6 --- --- 78 IV 237 3/8 675 1/2

51 - 75 8 16 I 16 I 315 3/8 405 3/8


51 - 75 8 32 II 32 II 315 3/8 495 3/8
51 - 75 8 40 III 56 III 315 3/8 630 1/2
51 - 75 8 --- --- 80 IV 315 3/8 765 1/2

51 - 75 10 20 I 20 I 394 3/8 506 3/8


51 - 75 10 30 II 30 II 394 3/8 562 3/8
51 - 75 10 40 III 50 III 394 3/8 675 1/2
51 - 75 10 --- --- 80 IV 394 3/8 844 1/2

51 - 75 12 12 I 12 I 473 3/8 540 3/8


51 - 75 12 36 II 36 II 473 3/8 675 1/2
51 - 75 12 --- --- 48 III 473 3/8 742 1/2
51 - 75 12 --- --- 72 IV 473 3/8 877 1/2

51 - 75 16 16 I 16 I 630 1/2 720 1/2


51 - 75 16 32 II 32 II 630 1/2 810 1/2
51 - 75 16 --- --- 48 III 630 1/2 900 1/2
51 - 75 16 --- --- 80 IV 630 1/2 1080 1/2

51 - 75 20 20 I 20 I 788 1/2 900 1/2


51 - 75 20 40 III 40 III 788 1/2 1012 1/2
51 - 75 20 --- --- 80 IV 788 1/2 1237 5/8

51 - 75 24 24 II 24 II 945 1/2 1080 1/2


51 - 75 24 --- --- 48 III 945 1/2 1215 5/8
51 - 75 24 --- --- 72 IV 945 1/2 1350 5/8

76 - 100 6 12 I 12 I 315 3/8 405 3/8


76 - 100 6 24 II 24 II 315 3/8 495 3/8
76 - 100 6 36 III 42 III 315 3/8 630 1/2
76 - 100 6 --- --- 60 IV 315 3/8 765 1/2
76 - 100 6 --- --- 78 V 315 3/8 900 1/2

76 - 100 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 110 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 4

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.15g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

76 - 100 8 16 I 16 I 420 3/8 540 3/8


76 - 100 8 24 II 24 II 420 3/8 600 3/8
76 - 100 8 40 III 40 III 420 3/8 720 1/2
76 - 100 8 --- --- 56 IV 420 3/8 840 1/2
76 - 100 8 --- --- 80 V 420 3/8 1020 1/2

76 - 100 10 10 I 10 I 525 3/8 600 3/8


76 - 100 10 20 II 20 II 525 3/8 675 1/2
76 - 100 10 40 III 40 III 525 3/8 825 1/2
76 - 100 10 --- --- 60 IV 525 3/8 975 1/2
76 - 100 10 --- --- 80 V 525 3/8 1125 1/2

76 - 100 12 12 I 12 I 630 1/2 720 1/2


76 - 100 12 24 II 24 II 630 1/2 810 1/2
76 - 100 12 36 III 36 III 630 1/2 900 1/2
76 - 100 12 --- --- 60 IV 630 1/2 1080 1/2
76 - 100 12 --- --- 72 V 630 1/2 1170 5/8

76 - 100 16 16 I 16 I 840 1/2 960 1/2


76 - 100 16 32 III 32 III 840 1/2 1080 1/2
76 - 100 16 --- --- 48 IV 840 1/2 1200 5/8
76 - 100 16 --- --- 80 V 840 1/2 1440 5/8

76 - 100 20 20 II 20 II 1050 1/2 1200 5/8


76 - 100 20 40 III 40 III 1050 1/2 1350 5/8
76 - 100 20 --- --- 60 IV 1050 1/2 1500 5/8
76 - 100 20 --- --- 80 V 1050 1/2 1650 5/8

76 - 100 24 24 II 24 II 1260 5/8 1440 5/8


76 - 100 24 --- --- 48 IV 1260 5/8 1620 5/8
76 - 100 24 --- --- 72 V 1260 5/8 1800 5/8

101 - 150 6 6 I 6 I 473 3/8 540 3/8


101 - 150 6 18 II 18 II 473 3/8 675 1/2
101 - 150 6 24 III 24 III 473 3/8 742 1/2
101 - 150 6 36 IV 42 IV 473 3/8 945 1/2
101 - 150 6 --- --- 60 V 473 3/8 1147 5/8

101 - 150 8 8 I 8 I 630 1/2 720 1/2


101 - 150 8 16 II 16 II 630 1/2 810 1/2
101 - 150 8 24 III 24 III 630 1/2 900 1/2
101 - 150 8 40 IV 40 IV 630 1/2 1080 1/2
101 - 150 8 --- --- 56 V 630 1/2 1260 5/8

101 - 150 10 10 I 10 I 788 1/2 900 1/2


101 - 150 10 20 III 20 III 788 1/2 1012 1/2
101 - 150 10 40 IV 40 IV 788 1/2 1237 5/8
101 - 150 10 --- --- 60 V 788 1/2 1462 5/8

101 - 150 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 111 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 5

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.15g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

101 - 150 12 12 II 12 II 945 1/2 1080 1/2


101 - 150 12 24 III 24 III 945 1/2 1215 5/8
101 - 150 12 36 IV 36 IV 945 1/2 1350 5/8
101 - 150 12 --- --- 60 V 945 1/2 1620 5/8

101 - 150 16 16 II 16 II 1260 5/8 1440 5/8


101 - 150 16 32 IV 32 IV 1260 5/8 1620 5/8
101 - 150 16 --- --- 48 V 1260 5/8 1800 5/8

101 - 150 20 20 III 20 III 1575 5/8 1800 5/8


101 - 150 20 40 IV 40 IV 1575 5/8 2025 3/4
101 - 150 20 --- --- 60 V 1575 5/8 2250 3/4

101 - 150 24 24 III 24 III 1890 3/4 2160 3/4


101 - 150 24 --- --- 48 V 1890 3/4 2430 3/4

151 - 200 6 6 I 6 I 630 1/2 720 1/2


151 - 200 6 12 II 12 II 630 1/2 810 1/2
151 - 200 6 18 III 18 III 630 1/2 900 1/2
151 - 200 6 30 IV 30 IV 630 1/2 1080 1/2
151 - 200 6 36 V 42 V 630 1/2 1260 5/8

151 - 200 8 8 I 8 I 840 1/2 960 1/2


151 - 200 8 16 III 16 III 840 1/2 1080 1/2
151 - 200 8 24 IV 24 IV 840 1/2 1200 5/8
151 - 200 8 40 V 40 V 840 1/2 1440 5/8

151 - 200 10 10 II 10 II 1050 1/2 1200 5/8


151 - 200 10 20 III 20 III 1050 1/2 1350 5/8
151 - 200 10 30 IV 30 IV 1050 1/2 1500 5/8
151 - 200 10 40 V 40 V 1050 1/2 1650 5/8

151 - 200 12 12 II 12 II 1260 5/8 1410 5/8


151 - 200 12 24 IV 24 IV 1260 5/8 1620 5/8
151 - 200 12 36 V 36 V 1260 5/8 1800 5/8

151 - 200 16 16 III 16 III 1680 5/8 1920 3/4


151 - 200 16 32 V 32 V 1680 5/8 2160 3/4

151 - 200 20 20 III 20 III 2100 3/4 2400 3/4


151 - 200 20 40 V 40 V 2100 3/4 2700 3/4

151 - 200 24 24 IV 24 IV 2520 3/4 2880 7/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 112 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 6

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 for Seismic Force Level 0.15g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 36 I 78 I 32 3/8 90 3/8

0 - 10 8 40 I 80 I 42 3/8 102 3/8

0 - 10 10 40 I 80 I 53 3/8 112 3/8

0 - 10 12 36 I 72 I 63 3/8 117 3/8

0 - 10 16 32 I 80 I 84 3/8 144 3/8

0 - 10 20 40 I 80 I 105 3/8 165 3/8

0 - 10 24 24 I 72 I 126 3/8 180 3/8

11 - 25 6 30 I 66 I 79 3/8 202 3/8


11 - 25 6 36 II 78 II 79 3/8 225 3/8

11 - 25 8 32 I 64 I 105 3/8 225 3/8


11 - 25 8 40 II 80 II 105 3/8 255 3/8

11 - 25 10 30 I 60 I 132 3/8 244 3/8


11 - 25 10 40 II 80 II 132 3/8 281 3/8

11 - 25 12 24 I 60 I 158 3/8 270 3/8


11 - 25 12 36 II 72 II 158 3/8 292 3/8

11 - 25 16 32 I 64 I 210 3/8 330 3/8


11 - 25 16 --- --- 80 II 210 3/8 360 3/8

11 - 25 20 20 I 60 I 263 3/8 375 3/8


11 - 25 20 40 II 80 II 263 3/8 412 3/8

11 - 25 24 24 I 48 I 315 3/8 405 3/8


11 - 25 24 --- --- 72 II 315 3/8 450 3/8

26 - 50 6 12 I 30 I 158 3/8 270 3/8


26 - 50 6 24 II 54 II 158 3/8 360 3/8
26 - 50 6 36 III 78 III 158 3/8 450 3/8

26 - 50 8 16 I 32 I 210 3/8 330 3/8


26 - 50 8 24 II 56 II 210 3/8 420 3/8
26 - 50 8 40 III 80 III 210 3/8 510 3/8

26 - 50 10 10 I 30 I 263 3/8 375 3/8


26 - 50 10 20 II 50 II 263 3/8 450 3/8
26 - 50 10 40 III 80 III 263 3/8 562 3/8

26 - 50 12 12 I 24 I 315 3/8 405 3/8


26 - 50 12 24 II 48 II 315 3/8 495 3/8
26 - 50 12 36 III 72 III 315 3/8 585 3/8

26 - 50 (Wt) continued on next page.

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 113 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 7

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 0.15g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 16 16 I 32 I 420 3/8 540 3/8


26 - 50 16 --- --- 48 II 420 3/8 600 3/8
26 - 50 16 32 III 80 III 420 3/8 720 1/2

26 - 50 20 --- --- 20 I 525 3/8 600 3/8


26 - 50 20 20 II 40 II 525 3/8 675 1/2
26 - 50 20 40 III 80 III 525 3/8 825 1/2

26 - 50 24 --- --- 24 I 630 1/2 720 1/2


26 - 50 24 24 II 48 II 630 1/2 810 1/2
26 - 50 24 --- --- 72 III 630 1/2 900 1/2

51 - 75 6 6 I 18 I 237 3/8 337 3/8


51 - 75 6 18 II 36 II 237 3/8 439 3/8
51 - 75 6 24 III 54 III 237 3/8 540 3/8
51 - 75 6 36 IV 78 IV 237 3/8 675 1/2

51 - 75 8 8 I 16 I 315 3/8 405 3/8


51 - 75 8 16 II 32 II 315 3/8 495 3/8
51 - 75 8 24 III 56 III 315 3/8 630 1/2
51 - 75 8 40 IV 80 IV 315 3/8 765 1/2

51 - 75 10 10 I 20 I 394 3/8 506 3/8


51 - 75 10 --- --- 30 II 394 3/8 562 3/8
51 - 75 10 20 III 50 III 394 3/8 675 1/2
51 - 75 10 40 IV 80 IV 394 3/8 844 1/2

51 - 75 12 --- --- 12 I 472 3/8 540 3/8


51 - 75 12 12 II 36 II 472 3/8 675 1/2
51 - 75 12 24 III 48 III 472 3/8 742 1/2
51 - 75 12 36 IV 72 IV 472 3/8 877 1/2

51 - 75 16 --- --- 16 I 630 1/2 720 1/2


51 - 75 16 16 II 32 II 630 1/2 810 1/2
51 - 75 16 --- --- 48 III 630 1/2 900 1/2
51 - 75 16 32 IV 80 IV 630 1/2 1080 1/2

51 - 75 20 --- --- 20 I 788 1/2 900 1/2


51 - 75 20 20 III 40 III 788 1/2 1012 1/2
51 - 75 20 40 IV 80 IV 788 1/2 1237 5/8

51 - 75 24 --- --- 24 II 945 1/2 1080 1/2


51 - 75 24 24 III 48 III 945 1/2 1215 5/8
51 - 75 24 --- --- 72 IV 945 1/2 1350 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 114 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 8

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 for Seismic Force Level 0.30g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 36 I 78 I 33 3/8 150 3/8

0 - 10 8 40 I 80 I 44 3/8 164 3/8

0 - 10 10 40 I 80 I 55 3/8 175 3/8

0 - 10 12 36 I 72 I 66 3/8 174 3/8

0 - 10 16 32 I 80 I 88 3/8 208 3/8

0 - 10 20 40 I 80 I 110 3/8 230 3/8

0 - 10 24 24 I 72 I 132 3/8 240 3/8

11 - 25 6 30 I 30 I 83 3/8 195 3/8


11 - 25 6 36 II 54 II 83 3/8 285 3/8
11 - 25 6 --- --- 78 III 83 3/8 375 3/8

11 - 25 8 32 I 32 I 110 3/8 230 3/8


11 - 25 8 40 II 56 II 110 3/8 320 3/8
11 - 25 8 --- --- 80 III 110 3/8 410 3/8

11 - 25 10 30 I 30 I 138 3/8 250 3/8


11 - 25 10 40 II 50 II 138 3/8 325 3/8
11 - 25 10 --- --- 80 III 138 3/8 437 3/8

11 - 25 12 24 I 24 I 165 3/8 255 3/8


11 - 25 12 36 II 48 II 165 3/8 345 3/8
11 - 25 12 --- --- 72 III 165 3/8 435 3/8

11 - 25 16 32 I 32 I 220 3/8 340 3/8


11 - 25 16 --- --- 48 II 220 3/8 400 3/8
11 - 25 16 --- --- 80 III 220 3/8 520 3/8

11 - 25 20 20 I 20 I 275 3/8 350 3/8


11 - 25 20 40 II 40 II 275 3/8 425 3/8
11 - 25 20 --- --- 80 III 275 3/8 575 3/8

11 - 25 24 24 I 24 I 330 3/8 420 3/8


11 - 25 24 --- --- 48 II 330 3/8 510 3/8
11 - 25 24 --- --- 72 III 330 3/8 600 3/8

26 - 50 6 12 I 12 I 165 3/8 255 3/8


26 - 50 6 24 II 24 II 165 3/8 345 3/8
26 - 50 6 36 III 42 III 165 3/8 480 3/8
26 - 50 6 --- --- 60 IV 165 3/8 615 1/2
26 - 50 6 --- --- 78 V 165 3/8 750 1/2

26 - 50 8 16 I 16 I 220 3/8 340 3/8


26 - 50 8 24 II 24 II 220 3/8 400 3/8
26 - 50 8 40 III 40 III 220 3/8 520 3/8
26 - 50 8 --- --- 56 IV 220 3/8 640 1/2
26 - 50 8 --- --- 80 V 220 3/8 820 1/2

26 - 50 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 115 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 9

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.30g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 10 10 I 10 I 275 3/8 350 3/8


26 - 50 10 20 II 20 II 275 3/8 425 3/8
26 - 50 10 40 III 40 III 275 3/8 575 3/8
26 - 50 10 --- --- 60 IV 275 3/8 725 1/2
26 - 50 10 --- --- 80 V 275 3/8 875 1/2

26 - 50 12 12 I 12 I 330 3/8 420 3/8


26 - 50 12 24 II 24 II 330 3/8 510 3/8
26 - 50 12 36 III 36 III 330 3/8 600 3/8
26 - 50 12 --- --- 60 IV 330 3/8 780 1/2
26 - 50 12 --- --- 72 V 330 3/8 870 1/2

26 - 50 16 16 I 16 I 440 3/8 560 3/8


26 - 50 16 32 III 32 III 440 3/8 680 1/2
26 - 50 16 --- --- 48 IV 440 3/8 800 1/2
26 - 50 16 --- --- 80 V 440 3/8 1040 1/2

26 - 50 20 20 II 20 II 550 3/8 700 1/2


26 - 50 20 40 III 40 III 550 3/8 850 1/2
26 - 50 20 --- --- 60 IV 550 3/8 1000 1/2
26 - 50 20 --- --- 80 V 550 3/8 1150 5/8

26 - 50 24 24 II 24 II 660 1/2 840 1/2


26 - 50 24 --- --- 48 IV 660 1/2 1020 1/2
26 - 50 24 --- --- 72 V 660 1/2 1200 5/8

51 - 75 6 6 I 6 I 248 3/8 315 3/8


51 - 75 6 18 II 18 II 248 3/8 450 3/8
51 - 75 6 24 III 24 III 248 3/8 517 3/8
51 - 75 6 36 IV 42 IV 248 3/8 720 1/2
51 - 75 6 --- --- 60 IV 248 3/8 922 1/2

51 - 75 8 8 I 8 I 330 3/8 420 3/8


51 - 75 8 16 II 16 II 330 3/8 510 3/8
51 - 75 8 24 III 24 III 330 3/8 600 3/8
51 - 75 8 40 IV 40 IV 330 3/8 780 1/2
51 - 75 8 --- --- 56 IV 330 3/8 960 1/2

51 - 75 10 10 I 10 I 413 3/8 525 3/8


51 - 75 10 20 III 20 III 413 3/8 637 1/2
51 - 75 10 40 IV 40 IV 413 3/8 862 1/2
51 - 75 10 --- --- 60 V 413 3/8 1087 1/2

51 - 75 12 12 II 12 II 495 3/8 630 1/2


51 - 75 12 24 III 24 III 495 3/8 765 1/2
51 - 75 12 36 IV 36 IV 495 3/8 900 1/2
51 - 75 12 --- --- 60 V 495 3/8 1170 5/8

51 - 75 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 116 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 10

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.30g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

51 - 75 16 16 II 16 II 660 3/8 840 1/2


51 - 75 16 32 IV 32 IV 660 3/8 1020 1/2
51 - 75 16 --- --- 48 V 660 3/8 1200 5/8

51 - 75 20 20 III 20 III 825 1/2 1050 1/2


51 - 75 20 40 IV 40 IV 825 1/2 1275 5/8
51 - 75 20 --- --- 60 V 825 1/2 1500 5/8

51 - 75 24 24 III 24 III 990 1/2 1260 5/8


51 - 75 24 --- --- 48 V 990 1/2 1530 5/8

76 - 100 6 6 I 6 I 330 3/8 420 3/8


76 - 100 6 12 II 12 II 330 3/8 570 3/8
76 - 100 6 18 III 18 III 330 3/8 600 3/8
76 - 100 6 30 IV 30 IV 330 3/8 780 1/2
76 - 100 6 36 V 42 V 330 3/8 960 1/2

76 - 100 8 8 I 8 I 440 3/8 560 3/8


76 - 100 8 16 III 16 III 440 3/8 680 1/2
76 - 100 8 24 IV 24 IV 440 3/8 800 1/2
76 - 100 8 40 V 40 V 440 3/8 1040 1/2

76 - 100 10 10 II 10 II 550 3/8 700 1/2


76 - 100 10 20 III 20 III 550 3/8 850 1/2
76 - 100 10 30 IV 30 IV 550 3/8 1000 1/2
76 - 100 10 40 V 40 V 550 3/8 1150 5/8

76 - 100 12 12 II 12 II 660 3/8 840 1/2


76 - 100 12 24 IV 24 IV 660 3/8 1020 1/2
76 - 100 12 36 V 36 V 660 3/8 1200 5/8

76 - 100 16 16 III 16 III 880 1/2 1120 1/2


76 - 100 16 32 V 32 V 880 1/2 1360 5/8

76 - 100 20 20 III 20 III 1100 1/2 1400 5/8


76 - 100 20 40 V 40 V 1100 1/2 1700 5/8

76 - 100 24 24 IV 24 IV 1320 5/8 1680 5/8

101 - 150 6 6 II 6 II 495 3/8 630 3/8


101 - 150 6 12 III 12 III 495 3/8 765 1/2
101 - 150 6 18 IV 18 IV 495 3/8 900 1/2
101 - 150 6 30 V 30 V 495 3/8 1170 1/2

101 - 150 8 8 II 8 II 660 3/8 840 1/2


101 - 150 8 16 IV 16 IV 660 3/8 1020 1/2
101 - 150 8 24 V 24 V 660 3/8 1200 5/8

101 - 150 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 117 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 11

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.30g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

101 - 150 10 10 III 10 III 825 1/2 1050 1/2


101 - 150 10 20 IV 20 IV 825 1/2 1275 5/8
101 - 150 10 30 V 30 V 825 1/2 1500 5/8

101 - 150 12 12 III 12 III 990 1/2 1260 5/8


101 - 150 12 24 V 24 V 990 1/2 1530 5/8

101 - 150 16 16 IV 16 IV 1320 5/8 1680 5/8

101 - 150 20 20 IV 20 IV 1650 5/8 2100 3/4

101 - 150 24 24 V 24 V 1980 3/4 2520 3/4

151 - 200 6 6 II 6 II 660 1/2 840 1/2


151 - 200 6 12 IV 12 IV 660 1/2 1020 1/2
151 - 200 6 18 V 18 V 660 1/2 1200 5/8

151 - 200 8 8 III 8 III 880 1/2 1120 1/2


151 - 200 8 16 V 16 V 880 1/2 1360 5/8

151 - 200 10 10 III 10 III 1100 1/2 1400 5/8


151 - 200 10 20 V 20 V 1100 1/2 1700 5/8

151 - 200 12 12 IV 12 IV 1320 5/8 1680 5/8

151 - 200 16 16 V 16 V 1760 5/8 2240 3/4

151 - 200 20 20 V 20 V 2200 3/4 2800 7/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 118 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 12

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 for Seismic Force Level 0.30g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 36 I 78 I 33 3/8 150 3/8

0 - 10 8 40 I 80 I 44 3/8 164 3/8

0 - 10 10 40 I 80 I 55 3/8 175 3/8

0 - 10 12 36 I 72 I 66 3/8 174 3/8

0 - 10 16 32 I 80 I 88 3/8 208 3/8

0 - 10 20 40 I 80 I 110 3/8 230 3/8

0 - 10 24 24 I 72 I 132 3/8 240 3/8

11 - 25 6 12 I 30 I 83 3/8 195 3/8


11 - 25 6 24 II 54 II 83 3/8 285 3/8
11 - 25 6 36 III 78 III 83 3/8 375 3/8

11 - 25 8 16 I 32 I 110 3/8 230 3/8


11 - 25 8 24 II 56 II 110 3/8 320 3/8
11 - 25 8 40 III 80 III 110 3/8 410 3/8

11 - 25 10 10 I 30 I 138 3/8 250 3/8


11 - 25 10 20 II 50 II 138 3/8 325 3/8
11 - 25 10 40 III 80 III 138 3/8 437 3/8

11 - 25 12 12 I 24 I 165 3/8 255 3/8


11 - 25 12 24 II 48 II 165 3/8 345 3/8
11 - 25 12 36 III 72 III 165 3/8 435 3/8

11 - 25 16 16 I 32 I 220 3/8 340 3/8


11 - 25 16 --- --- 48 II 220 3/8 400 3/8
11 - 25 16 32 III 80 III 220 3/8 520 3/8

11 - 25 20 --- --- 20 I 275 3/8 350 3/8


11 - 25 20 20 II 40 II 275 3/8 425 3/8
11 - 25 20 40 III 80 III 275 3/8 575 3/8

11 - 25 24 --- --- 24 I 330 3/8 420 3/8


11 - 25 24 24 II 48 II 330 3/8 510 3/8
11 - 25 24 --- --- 72 III 330 3/8 600 3/8

26 - 50 6 6 I 12 I 165 3/8 255 3/8


26 - 50 6 12 II 24 II 165 3/8 345 3/8
26 - 50 6 18 III 42 III 165 3/8 480 3/8
26 - 50 6 30 IV 60 IV 165 3/8 615 1/2
26 - 50 6 36 V 78 V 165 3/8 750 1/2

26 - 50 8 8 I 16 I 220 3/8 340 3/8


26 - 50 8 --- --- 24 II 220 3/8 400 3/8
26 - 50 8 16 III 40 III 220 3/8 520 3/8
26 - 50 8 24 IV 56 IV 220 3/8 640 1/2
26 - 50 8 40 V 80 V 220 3/8 820 1/2

26 - 50 10 --- --- 10 I 275 3/8 350 3/8


26 - 50 10 10 II 20 II 275 3/8 425 3/8
26 - 50 10 20 III 40 III 275 3/8 575 3/8
26 - 50 10 30 IV 60 IV 275 3/8 725 1/2
26 - 50 10 40 V 80 V 275 3/8 875 1/2

26 - 50 (Wt) continued on next page. * See note 2 on page 17. See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 119 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 13

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 0.30g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 12 --- --- 12 I 330 3/8 420 3/8


26 - 50 12 12 II 24 II 330 3/8 510 3/8
26 - 50 12 --- --- 36 III 330 3/8 600 3/8
26 - 50 12 24 IV 60 IV 330 3/8 780 1/2
26 - 50 12 36 V 72 V 330 3/8 870 1/2

26 - 50 16 --- --- 16 I 440 3/8 560 3/8


26 - 50 16 16 III 32 III 440 3/8 680 1/2
26 - 50 16 --- --- 48 IV 440 3/8 800 1/2
26 - 50 16 32 V 80 V 440 3/8 1040 1/2

26 - 50 20 --- --- 20 II 550 3/8 700 1/2


26 - 50 20 20 III 40 III 550 3/8 850 1/2
26 - 50 20 --- --- 60 IV 550 3/8 1000 1/2
26 - 50 20 40 V 80 V 550 3/8 1150 1/2

26 - 50 24 --- --- 24 II 660 1/2 840 1/2


26 - 50 24 24 IV 48 IV 660 1/2 1020 1/2
26 - 50 24 --- --- 72 V 660 1/2 1200 5/8

51 - 75 6 --- --- 6 I 248 3/8 315 3/8


51 - 75 6 6 II 18 II 248 3/8 450 3/8
51 - 75 6 12 III 24 III 248 3/8 517 3/8
51 - 75 6 18 IV 42 IV 248 3/8 720 1/2
51 - 75 6 30 V 60 V 248 3/8 922 1/2

51 - 75 8 --- --- 8 I 330 3/8 420 3/8


51 - 75 8 8 II 16 II 330 3/8 510 3/8
51 - 75 8 --- --- 24 III 330 3/8 600 3/8
51 - 75 8 16 IV 40 IV 330 3/8 780 1/2
51 - 75 8 24 V 56 V 330 3/8 960 1/2

51 - 75 10 --- --- 10 I 413 3/8 525 3/8


51 - 75 10 10 III 20 III 413 3/8 637 1/2
51 - 75 10 20 IV 40 IV 413 3/8 862 1/2
51 - 75 10 30 V 60 V 413 3/8 1087 1/2

51 - 75 12 --- --- 12 II 495 3/8 630 1/2


51 - 75 12 12 III 24 III 495 3/8 765 1/2
51 - 75 12 --- --- 36 IV 495 3/8 900 1/2
51 - 75 12 24 V 60 V 495 3/8 1170 1/2

51 - 75 16 --- --- 16 II 660 1/2 840 1/2


51 - 75 16 16 IV 32 IV 660 1/2 1020 1/2
51 - 75 16 --- --- 48 V 660 1/2 1200 5/8

51 - 75 20 --- --- 20 III 825 1/2 1050 1/2


51 - 75 20 20 IV 40 IV 825 1/2 1275 5/8
51 - 75 20 --- --- 60 V 825 1/2 1500 5/8

51 - 75 24 --- --- 24 III 990 1/2 1260 5/8


51 - 75 24 24 V 48 V 990 1/2 1530 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 120 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 14

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 for Seismic Force Level 0.45g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 36 I 54 I 35 3/8 156 3/8


0 - 10 6 --- --- 78 II 35 3/8 210 3/8

0 - 10 8 40 I 48 I 46 3/8 154 3/8


0 - 10 8 --- --- 80 II 46 3/8 226 3/8

0 - 10 10 40 I 50 I 58 3/8 170 3/8


0 - 10 10 --- --- 80 II 58 3/8 237 3/8

0 - 10 12 36 I 48 I 69 3/8 177 3/8


0 - 10 12 --- --- 72 II 69 3/8 231 3/8

0 - 10 16 32 I 48 I 92 3/8 200 3/8


0 - 10 16 --- --- 80 II 92 3/8 272 3/8

0 - 10 20 40 I 40 I 115 3/8 205 3/8


0 - 10 20 --- --- 80 II 115 3/8 295 3/8

0 - 10 24 24 I 48 I 138 3/8 246 3/8


0 - 10 24 --- --- 72 II 138 3/8 300 3/8

11 - 25 6 18 I 18 I 87 3/8 187 3/8


11 - 25 6 36 II 36 II 87 3/8 289 3/8
11 - 25 6 --- --- 54 III 87 3/8 390 1/2
11 - 25 6 --- --- 78 IV 87 3/8 525 1/2

11 - 25 8 16 I 16 I 115 3/8 205 3/8


11 - 25 8 32 II 32 II 115 3/8 295 3/8
11 - 25 8 40 III 56 III 115 3/8 430 1/2
11 - 25 8 --- --- 80 IV 115 3/8 565 1/2

11 - 25 10 20 I 20 I 144 3/8 256 3/8


11 - 25 10 30 II 30 II 144 3/8 312 3/8
11 - 25 10 40 III 50 III 144 3/8 425 1/2
11 - 25 10 --- --- 80 IV 144 3/8 594 1/2

11 - 25 12 12 I 12 I 173 3/8 240 3/8


11 - 25 12 36 II 36 II 173 3/8 375 3/8
11 - 25 12 --- --- 48 III 173 3/8 442 3/8
11 - 25 12 --- --- 72 IV 173 3/8 577 3/8

11 - 25 16 16 I 16 I 230 3/8 320 3/8


11 - 25 16 32 II 32 II 230 3/8 410 3/8
11 - 25 16 --- --- 48 III 230 3/8 500 3/8
11 - 25 16 --- --- 80 IV 230 3/8 680 1/2

11 - 25 20 20 I 20 I 288 3/8 400 3/8


11 - 25 20 40 III 40 III 288 3/8 512 3/8
11 - 25 20 --- --- 80 IV 288 3/8 737 1/2

11 - 25 24 24 II 24 II 345 3/8 480 3/8


11 - 25 24 --- --- 48 III 345 3/8 615 1/2
11 - 25 24 --- --- 72 IV 345 3/8 750 1/2

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 121 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 15

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.45g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 6 6 I 6 I 173 3/8 240 3/8


26 - 50 6 18 II 18 II 173 3/8 375 3/8
26 - 50 6 24 III 24 III 173 3/8 442 3/8
26 - 50 6 36 IV 42 IV 173 3/8 645 1/2
26 - 50 6 --- --- 60 V 173 3/8 847 5/8

26 - 50 8 8 I 8 I 230 3/8 320 3/8


26 - 50 8 16 II 16 II 230 3/8 410 3/8
26 - 50 8 24 III 24 III 230 3/8 500 3/8
26 - 50 8 40 IV 40 IV 230 3/8 680 1/2
26 - 50 8 --- --- 56 V 230 3/8 860 1/2

26 - 50 10 10 I 10 I 288 3/8 400 3/8


26 - 50 10 20 III 20 III 288 3/8 512 3/8
26 - 50 10 40 IV 40 IV 288 3/8 737 1/2
26 - 50 10 --- --- 60 V 288 3/8 962 1/2

26 - 50 12 12 II 12 II 345 3/8 480 3/8


26 - 50 12 24 III 24 III 345 3/8 615 1/2
26 - 50 12 36 IV 36 IV 345 3/8 750 1/2
26 - 50 12 --- --- 60 V 345 3/8 1020 1/2

26 - 50 16 16 II 16 II 460 3/8 640 1/2


26 - 50 16 32 IV 32 IV 460 3/8 820 1/2
26 - 50 16 --- --- 48 V 460 3/8 1000 1/2

26 - 50 20 20 III 20 III 575 3/8 800 1/2


26 - 50 20 40 IV 40 IV 575 3/8 1025 1/2
26 - 50 20 --- --- 60 V 575 3/8 1250 5/8

26 - 50 24 24 III 24 III 690 3/8 960 1/2


26 - 50 24 --- --- 48 V 690 3/8 1230 5/8

51 - 75 6 6 I 6 I 259 3/8 360 3/8


51 - 75 6 12 II 12 II 259 3/8 461 3/8
51 - 75 6 18 III 18 III 259 3/8 562 3/8
51 - 75 6 24 IV 24 IV 259 3/8 664 1/2
51 - 75 6 36 V 36 V 259 3/8 866 1/2

51 - 75 8 8 II 8 II 345 3/8 480 3/8


51 - 75 8 16 III 16 III 345 3/8 615 1/2
51 - 75 8 24 IV 24 IV 345 3/8 750 1/2
51 - 75 8 40 V 40 V 345 3/8 1020 1/2

51 - 75 10 10 II 10 II 431 3/8 600 3/8


51 - 75 10 20 IV 20 IV 431 3/8 769 1/2
51 - 75 10 40 V 40 V 431 3/8 1106 1/2

51 - 75 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 122 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 16

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.45g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

51 - 75 12 12 II 12 II 518 3/8 720 1/2


51 - 75 12 24 IV 24 IV 518 3/8 922 1/2
51 - 75 12 36 V 36 V 518 3/8 1125 1/2

51 - 75 16 16 III 16 III 690 1/2 960 1/2


51 - 75 16 32 V 32 V 690 1/2 1230 5/8

51 - 75 20 20 IV 20 IV 863 1/2 1200 5/8


51 - 75 20 40 V 40 V 863 1/2 1537 5/8

51 - 75 24 24 IV 24 IV 1035 1/2 1440 5/8

76 - 100 6 6 II 6 II 345 3/8 480 3/8


76 - 100 6 12 III 12 III 345 3/8 615 1/2
76 - 100 6 18 IV 18 IV 345 3/8 750 1/2
76 - 100 6 30 V 30 V 345 3/8 1020 1/2

76 - 100 8 8 II 8 II 460 3/8 640 1/2


76 - 100 8 16 IV 16 IV 460 3/8 820 1/2
76 - 100 8 24 V 24 V 460 3/8 1000 1/2

76 - 100 10 10 III 10 III 575 3/8 800 1/2


76 - 100 10 20 IV 20 IV 575 3/8 1025 1/2
76 - 100 10 30 V 30 V 575 3/8 1250 5/8

76 - 100 12 12 III 12 III 690 1/2 960 1/2


76 - 100 12 24 V 24 V 690 1/2 1230 5/8

76 - 100 16 16 IV 16 IV 920 1/2 1280 5/8

76 - 100 20 20 IV 20 IV 1150 5/8 1600 5/8

101 - 150 6 6 II 6 II 518 3/8 720 1/2


101 - 150 6 12 IV 12 IV 518 3/8 922 1/2
101 - 150 6 18 V 18 V 518 3/8 1125 1/2

101 - 150 8 8 III 8 III 690 1/2 960 1/2


101 - 150 8 16 V 16 V 690 1/2 1230 5/8

101 - 150 10 10 IV 10 IV 863 1/2 1200 5/8


101 - 150 10 20 V 20 V 863 1/2 1537 5/8

101 - 150 12 12 IV 12 IV 1035 1/2 1440 5/8

151 - 200 6 6 III 6 III 690 1/2 960 1/2


151 - 200 6 12 V 12 V 690 1/2 1230 5/8

151 - 200 8 8 IV 8 IV 920 1/2 1280 5/8

151 - 200 10 10 IV 10 IV 1150 5/8 1600 5/8

151 - 200 12 12 V 12 V 1380 5/8 1920 3/4

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 123 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 17

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 for Seismic Force Level 0.45g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 24 I 54 I 35 3/8 156 3/8


0 - 10 6 36 II 78 II 35 3/8 210 3/8

0 - 10 8 24 I 48 I 46 3/8 154 3/8


0 - 10 8 40 II 80 II 46 3/8 226 3/8

0 - 10 10 20 I 50 I 58 3/8 170 3/8


0 - 10 10 40 II 80 II 58 3/8 237 3/8

0 - 10 12 24 I 48 I 69 3/8 177 3/8


0 - 10 12 36 II 72 II 69 3/8 231 3/8

0 - 10 16 16 I 48 I 92 3/8 200 3/8


0 - 10 16 32 II 80 II 92 3/8 272 3/8

0 - 10 20 20 I 40 I 115 3/8 205 3/8


0 - 10 20 40 II 80 II 115 3/8 295 3/8

0 - 10 24 24 I 48 I 138 3/8 246 3/8


0 - 10 24 --- --- 72 II 138 3/8 300 3/8

11 - 25 6 6 I 18 I 87 3/8 187 3/8


11 - 25 6 18 II 36 II 87 3/8 289 3/8
11 - 25 6 24 III 54 III 87 3/8 390 3/8
11 - 25 6 36 IV 78 IV 87 3/8 525 1/2

11 - 25 8 8 I 16 I 115 3/8 205 3/8


11 - 25 8 16 II 32 II 115 3/8 295 3/8
11 - 25 8 24 III 56 III 115 3/8 430 3/8
11 - 25 8 40 IV 80 IV 115 3/8 565 1/2

11 - 25 10 10 I 20 I 144 3/8 256 3/8


11 - 25 10 --- --- 30 II 144 3/8 312 3/8
11 - 25 10 20 III 50 III 144 3/8 425 3/8
11 - 25 10 40 IV 80 IV 144 3/8 594 1/2

11 - 25 12 --- --- 12 I 173 3/8 240 3/8


11 - 25 12 12 II 36 II 173 3/8 375 3/8
11 - 25 12 24 III 48 III 173 3/8 442 3/8
11 - 25 12 36 IV 72 IV 173 3/8 577 3/8

11 - 25 16 --- --- 16 I 230 3/8 320 3/8


11 - 25 16 16 II 32 II 230 3/8 410 3/8
11 - 25 16 --- --- 48 III 230 3/8 500 3/8
11 - 25 16 32 IV 80 IV 230 3/8 680 1/2

11 - 25 20 --- --- 20 I 288 3/8 400 3/8


11 - 25 20 20 III 40 III 288 3/8 512 3/8
11 - 25 20 40 IV 80 IV 288 3/8 737 1/2

11 - 25 24 --- --- 24 II 345 3/8 480 3/8


11 - 25 24 24 III 48 III 345 3/8 615 1/2
11 - 25 24 --- --- 72 IV 345 3/8 750 1/2

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 124 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 18

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 0.45g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 6 --- --- 6 I 173 3/8 240 3/8


26 - 50 6 6 II 18 II 173 3/8 375 3/8
26 - 50 6 12 III 24 III 173 3/8 442 3/8
26 - 50 6 18 IV 42 IV 173 3/8 645 1/2
26 - 50 6 30 V 60 V 173 3/8 847 5/8

26 - 50 8 --- --- 8 I 230 3/8 320 3/8


26 - 50 8 8 II 16 II 230 3/8 410 3/8
26 - 50 8 --- --- 24 III 230 3/8 500 3/8
26 - 50 8 16 IV 40 IV 230 3/8 680 1/2
26 - 50 8 24 V 56 V 230 3/8 860 1/2

26 - 50 10 --- --- 10 I 288 3/8 400 3/8


26 - 50 10 10 III 20 III 288 3/8 512 3/8
26 - 50 10 20 IV 40 IV 288 3/8 737 1/2
26 - 50 10 30 V 60 V 288 3/8 962 1/2

26 - 50 12 --- --- 12 II 345 3/8 480 3/8


26 - 50 12 12 III 24 III 345 3/8 615 1/2
26 - 50 12 --- --- 36 IV 345 3/8 750 1/2
26 - 50 12 24 V 60 V 345 3/8 1020 1/2

26 - 50 16 --- --- 16 II 460 3/8 640 1/2


26 - 50 16 16 IV 32 IV 460 3/8 820 1/2
26 - 50 16 --- --- 48 V 460 3/8 1000 1/2

26 - 50 20 --- --- 20 III 575 3/8 800 1/2


26 - 50 20 20 IV 40 IV 575 3/8 1025 1/2
26 - 50 20 --- --- 60 V 575 3/8 1250 5/8

26 - 50 24 --- --- 24 III 690 1/2 960 1/2


26 - 50 24 24 V 48 V 690 1/2 1230 5/8

51 - 75 6 --- --- 6 I 259 3/8 360 3/8


51 - 75 6 6 II 12 II 259 3/8 461 3/8
51 - 75 6 --- --- 18 III 259 3/8 562 3/8
51 - 75 6 12 IV 24 IV 259 3/8 664 1/2
51 - 75 6 18 V 36 V 259 3/8 866 1/2

51 - 75 8 --- --- 8 II 345 3/8 480 3/8


51 - 75 8 8 III 16 III 345 3/8 615 1/2
51 - 75 8 --- --- 24 IV 345 3/8 750 1/2
51 - 75 8 16 V 40 V 345 3/8 1020 1/2

51 - 75 10 --- --- 10 II 432 3/8 600 3/8


51 - 75 10 10 IV 20 IV 432 3/8 769 1/2
51 - 75 10 20 V 40 V 432 3/8 1106 1/2

51 - 75 (Wt) continued on next page.

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 125 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 19

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 0.45g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

51 - 75 12 --- --- 12 II 518 3/8 720 1/2


51 - 75 12 12 IV 24 IV 518 3/8 922 1/2
51 - 75 12 --- --- 36 V 518 3/8 1125 1/2

51 - 75 16 --- --- 16 III 690 3/8 960 1/2


51 - 75 16 16 V 32 V 690 3/8 1230 5/8

51 - 75 20 --- --- 20 IV 863 1/2 1200 1/2


51 - 75 20 20 V 40 V 863 1/2 1537 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 126 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 20

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 for Seismic Force Level 0.50g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 36 I 48 I 35 3/8 155 3/8


0 - 10 6 --- --- 78 II 35 3/8 230 3/8

0 - 10 8 40 I 48 I 47 3/8 167 3/8


0 - 10 8 --- --- 80 II 47 3/8 247 3/8

0 - 10 10 40 I 40 I 59 3/8 158 3/8


0 - 10 10 --- --- 80 II 59 3/8 258 3/8

0 - 10 12 36 I 48 I 70 3/8 190 3/8


0 - 10 12 --- --- 72 II 70 3/8 250 3/8

0 - 10 16 32 I 48 I 94 3/8 213 3/8


0 - 10 16 --- --- 80 II 94 3/8 293 3/8

0 - 10 20 40 I 40 I 117 3/8 217 3/8


0 - 10 20 --- --- 80 II 117 3/8 317 3/8

0 - 10 24 24 I 48 I 140 3/8 260 3/8


0 - 10 24 --- --- 72 II 140 3/8 320 3/8

11 - 25 6 18 I 18 I 88 3/8 200 3/8


11 - 25 6 30 II 30 II 88 3/8 275 3/8
11 - 25 6 36 III 48 III 88 3/8 387 3/8
11 - 25 6 --- --- 72 IV 88 3/8 537 1/2
11 - 25 6 --- --- 78 V 88 3/8 575 1/2

11 - 25 8 16 I 16 I 117 3/8 217 3/8


11 - 25 8 32 II 32 II 117 3/8 317 3/8
11 - 25 8 40 III 48 III 117 3/8 417 3/8
11 - 25 8 --- --- 72 IV 117 3/8 567 1/2
11 - 25 8 --- --- 80 V 117 3/8 617 1/2

11 - 25 10 10 I 10 I 146 3/8 208 3/8


11 - 25 10 30 II 30 II 146 3/8 333 3/8
11 - 25 10 40 III 50 III 146 3/8 458 3/8
11 - 25 10 --- --- 70 IV 146 3/8 583 1/2
11 - 25 10 --- --- 80 V 146 3/8 646 1/2

11 - 25 12 12 I 12 I 175 3/8 250 3/8


11 - 25 12 24 II 24 II 175 3/8 325 3/8
11 - 25 12 36 III 48 III 175 3/8 475 3/8
11 - 25 12 --- --- 72 IV 175 3/8 625 1/2

11 - 25 16 16 I 16 I 233 3/8 333 3/8


11 - 25 16 32 II 32 II 233 3/8 433 3/8
11 - 25 16 --- --- 48 III 233 3/8 533 3/8
11 - 25 16 --- --- 64 IV 233 3/8 633 1/2
11 - 25 16 --- --- 80 V 233 3/8 733 1/2

11 - 25 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 127 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 21

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.50g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

11 - 25 20 20 II 20 II 292 3/8 417 3/8


11 - 25 20 40 III 40 III 292 3/8 542 3/8
11 - 25 20 --- --- 60 IV 292 3/8 667 1/2
11 - 25 20 --- --- 80 V 292 3/8 792 1/2

11 - 25 24 24 II 24 II 350 3/8 500 3/8


11 - 25 24 --- --- 48 III 350 3/8 650 1/2
11 - 25 24 --- --- 72 IV 350 3/8 800 1/2

26 - 50 6 6 I 6 I 175 3/8 250 3/8


26 - 50 6 12 II 12 II 175 3/8 325 3/8
26 - 50 6 24 III 24 III 175 3/8 475 3/8
26 - 50 6 36 IV 36 IV 175 3/8 625 1/2
26 - 50 6 --- --- 54 V 175 3/8 850 5/8

26 - 50 8 8 I 8 I 234 3/8 333 3/8


26 - 50 8 16 II 16 II 234 3/8 433 3/8
26 - 50 8 24 III 24 III 234 3/8 533 3/8
26 - 50 8 32 IV 32 IV 234 3/8 633 1/2
26 - 50 8 40 V 48 V 234 3/8 833 1/2

26 - 50 10 10 II 10 II 292 3/8 417 3/8


26 - 50 10 20 III 20 III 292 3/8 542 3/8
26 - 50 10 30 IV 30 IV 292 3/8 667 1/2
26 - 50 10 40 V 50 V 292 3/8 917 1/2

26 - 50 12 12 II 12 II 350 3/8 500 3/8


26 - 50 12 24 III 24 III 350 3/8 650 1/2
26 - 50 12 36 IV 36 IV 350 3/8 800 1/2
26 - 50 12 --- --- 48 V 350 3/8 950 1/2

26 - 50 16 16 II 16 II 467 3/8 667 1/2


26 - 50 16 32 IV 32 IV 467 3/8 867 1/2
26 - 50 16 --- --- 48 V 467 3/8 1067 1/2

26 - 50 20 20 III 20 III 584 3/8 833 1/2


26 - 50 20 40 V 40 V 584 3/8 1083 1/2

26 - 50 24 24 III 24 III 700 1/2 1000 1/2


26 - 50 24 --- --- 48 V 700 1/2 1300 5/8

51 - 75 6 6 I 6 I 263 3/8 375 3/8


51 - 75 6 12 III 12 III 263 3/8 487 3/8
51 - 75 6 24 IV 24 IV 263 3/8 712 1/2
51 - 75 6 36 V 36 V 263 3/8 937 1/2

51 - 75 8 8 II 8 II 350 3/8 500 3/8


51 - 75 8 16 III 16 III 350 3/8 650 1/2
51 - 75 8 24 IV 24 IV 350 3/8 800 1/2
51 - 75 8 32 V 32 V 350 3/8 950 1/2

51 - 75 (Wt) continued on next page.


* See note 2 on page 17. See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 128 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 22

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.50g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

51 - 75 10 10 II 10 II 438 3/8 625 3/8


51 - 75 10 20 IV 20 IV 438 3/8 812 1/2
51 - 75 10 30 V 30 V 438 3/8 1000 1/2

51 - 75 12 12 III 12 III 525 3/8 750 1/2


51 - 75 12 24 IV 24 IV 525 3/8 975 1/2
51 - 75 12 36 V 36 V 525 3/8 1200 1/2

51 - 75 16 16 III 16 III 700 1/2 1000 1/2


51 - 75 16 32 V 32 V 700 1/2 1300 5/8

51 - 75 20 20 IV 20 IV 875 1/2 1250 1/2

51 - 75 24 24 IV 24 IV 1050 1/2 1500 5/8

76 - 100 6 6 II 6 II 350 3/8 500 3/8


76 - 100 6 12 III 12 III 350 3/8 650 1/2
76 - 100 6 18 IV 18 IV 350 3/8 800 1/2
76 - 100 6 24 V 24 V 350 3/8 950 1/2

76 - 100 8 8 II 8 II 467 3/8 667 1/2


76 - 100 8 16 IV 16 IV 467 3/8 867 1/2
76 - 100 8 24 V 24 V 467 3/8 1067 1/2

76 - 100 10 10 III 10 III 584 3/8 833 1/2


76 - 100 10 20 V 20 V 584 3/8 1083 1/2

76 - 100 12 12 III 12 III 700 1/2 1000 1/2


76 - 100 12 24 V 24 V 700 1/2 1300 5/8

76 - 100 16 16 IV 16 IV 934 1/2 1333 5/8

76 - 100 20 20 V 20 V 1167 5/8 1667 5/8

76 - 100 24 24 V 24 V 1400 5/8 2000 3/4

101 - 150 6 6 III 6 III 525 3/8 750 1/2


101 - 150 6 12 IV 12 IV 525 3/8 975 1/2
101 - 150 6 18 V 18 V 525 3/8 1200 1/2

101 - 150 8 8 III 8 III 700 1/2 1000 1/2


101 - 150 8 16 V 16 V 700 1/2 1300 5/8

101 - 150 10 10 IV 10 IV 875 1/2 1250 5/8

101 - 150 12 12 IV 12 IV 1050 1/2 1500 5/8

101 - 150 16 16 V 16 V 1400 5/8 2000 3/4

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 129 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 23

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.50g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

151 - 200 6 6 III 6 III 700 1/2 1000 1/2


151 - 200 6 12 V 12 V 700 1/2 1300 5/8

151 - 200 8 8 IV 8 IV 934 1/2 1333 5/8

151 - 200 10 10 V 10 V 1167 5/8 1667 5/8

151 - 200 12 12 V 12 V 1400 5/8 2000 3/4

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 130 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 24

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 for Seismic Force Level 0.50g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 24 I 48 I 35 3/8 155 3/8


0 - 10 6 36 II 78 II 35 3/8 230 3/8

0 - 10 8 24 I 48 I 47 3/8 167 3/8


0 - 10 8 40 II 80 II 47 3/8 247 3/8

0 - 10 10 20 I 40 I 59 3/8 158 3/8


0 - 10 10 40 II 80 II 59 3/8 258 3/8

0 - 10 12 24 I 48 I 70 3/8 190 3/8


0 - 10 12 36 II 72 II 70 3/8 250 3/8

0 - 10 16 16 I 48 I 94 3/8 213 3/8


0 - 10 16 32 II 80 II 94 3/8 293 3/8

0 - 10 20 20 I 40 I 117 3/8 217 3/8


0 - 10 20 40 II 80 II 117 3/8 317 3/8

0 - 10 24 24 I 48 I 140 3/8 260 3/8


0 - 10 24 --- --- 72 II 140 3/8 320 3/8

11 - 25 6 6 I 18 I 88 3/8 200 3/8


11 - 25 6 12 II 30 II 88 3/8 275 3/8
11 - 25 6 24 III 48 III 88 3/8 387 3/8
11 - 25 6 36 IV 72 IV 88 3/8 537 1/2

11 - 25 8 8 I 16 I 117 3/8 217 3/8


11 - 25 8 16 II 32 II 117 3/8 317 3/8
11 - 25 8 24 III 48 III 117 3/8 417 3/8
11 - 25 8 32 IV 72 IV 117 3/8 567 1/2
11 - 25 8 40 V 80 V 117 3/8 617 1/2

11 - 25 10 --- --- 10 I 146 3/8 208 3/8


11 - 25 10 10 II 30 II 146 3/8 333 3/8
11 - 25 10 20 III 50 III 146 3/8 458 3/8
11 - 25 10 30 IV 70 IV 146 3/8 583 1/2
11 - 25 10 40 V 80 V 146 3/8 646 1/2

11 - 25 12 --- --- 12 I 175 3/8 250 3/8


11 - 25 12 12 II 24 II 175 3/8 325 3/8
11 - 25 12 24 III 48 III 175 3/8 475 3/8
11 - 25 12 36 IV 72 IV 175 3/8 625 1/2

11 - 25 16 --- --- 16 I 234 3/8 333 3/8


11 - 25 16 16 II 32 II 234 3/8 433 3/8
11 - 25 16 --- --- 48 III 234 3/8 533 3/8
11 - 25 16 32 IV 64 IV 234 3/8 633 1/2
11 - 25 16 --- --- 80 V 234 3/8 733 1/2

11 - 25 20 --- --- 20 II 292 3/8 417 3/8


11 - 25 20 20 III 40 III 292 3/8 542 3/8
11 - 25 20 --- --- 60 IV 292 3/8 667 1/2
11 - 25 20 40 V 80 V 292 3/8 792 1/2

11 - 25 24 --- --- 24 II 350 3/8 500 3/8


11 - 25 24 24 III 48 III 350 3/8 650 1/2
11 - 25 24 --- --- 72 IV 350 3/8 800 1/2

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 131 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 25

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 0.50g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 6 --- --- 6 I 175 3/8 250 3/8


26 - 50 6 6 II 12 II 175 3/8 325 3/8
26 - 50 6 12 III 24 III 175 3/8 475 3/8
26 - 50 6 18 IV 36 IV 175 3/8 625 1/2
26 - 50 6 24 V 54 V 175 3/8 850 5/8

26 - 50 8 --- --- 8 I 234 3/8 333 3/8


26 - 50 8 8 II 16 II 234 3/8 433 3/8
26 - 50 8 --- --- 24 III 234 3/8 533 3/8
26 - 50 8 16 IV 32 IV 234 3/8 633 1/2
26 - 50 8 24 V 48 V 234 3/8 833 1/2

26 - 50 10 --- --- 10 II 292 3/8 417 3/8


26 - 50 10 10 III 20 III 292 3/8 542 3/8
26 - 50 10 --- --- 30 IV 292 3/8 667 1/2
26 - 50 10 20 V 50 V 292 3/8 917 1/2

26 - 50 12 --- --- 12 II 350 3/8 500 3/8


26 - 50 12 12 III 24 III 350 3/8 650 1/2
26 - 50 12 --- --- 36 IV 350 3/8 800 1/2
26 - 50 12 24 V 48 V 350 3/8 950 1/2

26 - 50 16 --- --- 16 II 467 3/8 667 3/8


26 - 50 16 16 IV 32 IV 467 3/8 867 1/2
26 - 50 16 --- --- 48 V 467 3/8 1067 1/2

26 - 50 20 --- --- 20 III 583 3/8 833 1/2


26 - 50 20 20 V 40 V 583 3/8 1083 1/2

26 - 50 24 --- --- 24 III 700 3/8 1000 1/2


26 - 50 24 24 V 48 V 700 3/8 1300 5/8

51 - 75 6 --- --- 6 I 263 3/8 375 3/8


51 - 75 6 6 III 12 III 263 3/8 487 3/8
51 - 75 6 12 IV 24 IV 263 3/8 712 1/2
51 - 75 6 18 V 36 V 263 3/8 937 1/2

51 - 75 8 --- --- 8 II 350 3/8 500 3/8


51 - 75 8 8 III 16 III 350 3/8 650 1/2
51 - 75 8 --- --- 24 IV 350 3/8 800 1/2
51 - 75 8 16 V 32 V 350 3/8 950 1/2

51 - 75 10 --- --- 10 II 438 3/8 625 1/2


51 - 75 10 10 IV 20 IV 438 3/8 812 1/2
51 - 75 10 --- --- 30 V 438 3/8 1000 1/2

51 - 75 12 --- --- 12 III 525 3/8 750 1/2


51 - 75 12 12 IV 24 IV 525 3/8 975 1/2
51 - 75 12 --- --- 36 V 525 3/8 1200 5/8

51 - 75 16 --- --- 16 III 700 1/2 1000 1/2


51 - 75 16 16 V 32 V 700 1/2 1300 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 132 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 26

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 for Seismic Force Level 0.75g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 30 I 30 I 38 3/8 150 3/8


0 - 10 6 36 II 54 II 38 3/8 240 3/8
0 - 10 6 --- --- 78 III 38 3/8 330 1/2

0 - 10 8 32 I 32 I 50 3/8 170 3/8


0 - 10 8 40 II 56 II 50 3/8 260 3/8
0 - 10 8 --- --- 80 III 50 3/8 350 3/8

0 - 10 10 30 I 30 I 63 3/8 175 3/8


0 - 10 10 40 II 50 II 63 3/8 250 3/8
0 - 10 10 --- --- 80 III 63 3/8 362 3/8

0 - 10 12 24 I 24 I 75 3/8 165 3/8


0 - 10 12 36 II 48 II 75 3/8 255 3/8
0 - 10 12 --- --- 72 III 75 3/8 345 3/8

0 - 10 16 32 I 32 I 100 3/8 220 3/8


0 - 10 16 --- --- 48 II 100 3/8 280 3/8
0 - 10 16 --- --- 80 III 100 3/8 400 3/8

0 - 10 20 20 I 20 I 125 3/8 200 3/8


0 - 10 20 40 II 40 II 125 3/8 275 3/8
0 - 10 20 --- --- 80 III 125 3/8 425 3/8

0 - 10 24 24 I 24 I 150 3/8 240 3/8


0 - 10 24 --- --- 48 II 150 3/8 330 3/8
0 - 10 24 --- --- 72 III 150 3/8 420 3/8

11 - 25 6 12 I 12 I 94 3/8 206 3/8


11 - 25 6 18 II 18 II 94 3/8 262 3/8
11 - 25 6 30 III 30 III 94 3/8 375 3/8
11 - 25 6 36 IV 48 IV 94 3/8 544 3/8
11 - 25 6 --- --- 72 V 94 3/8 769 1/2

11 - 25 8 8 I 8 I 125 3/8 200 3/8


11 - 25 8 16 II 16 II 125 3/8 275 3/8
11 - 25 8 32 III 32 III 125 3/8 425 3/8
11 - 25 8 40 IV 48 IV 125 3/8 575 3/8
11 - 25 8 --- --- 72 V 125 3/8 800 1/2

11 - 25 10 10 I 10 I 157 3/8 250 3/8


11 - 25 10 20 II 20 II 157 3/8 344 3/8
11 - 25 10 30 III 30 III 157 3/8 437 3/8
11 - 25 10 40 IV 50 IV 157 3/8 625 1/2
11 - 25 10 --- --- 70 V 157 3/8 812 1/2

11 - 25 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 133 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 27

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.75g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

11 - 25 12 12 I 12 I 188 3/8 300 3/8


11 - 25 12 24 III 24 III 188 3/8 412 3/8
11 - 25 12 36 IV 48 IV 188 3/8 637 1/2
11 - 25 12 --- --- 72 V 188 3/8 862 1/2

11 - 25 16 16 II 16 II 250 3/8 400 3/8


11 - 25 16 32 III 32 III 250 3/8 550 3/8
11 - 25 16 --- --- 48 IV 250 3/8 700 1/2
11 - 25 16 --- --- 64 V 250 3/8 850 1/2

11 - 25 20 20 II 20 II 313 3/8 500 3/8


11 - 25 20 40 IV 40 IV 313 3/8 687 1/2
11 - 25 20 --- --- 60 V 313 3/8 875 1/2

11 - 25 24 24 III 24 III 375 3/8 600 3/8


11 - 25 24 --- --- 48 IV 375 3/8 825 1/2
11 - 25 24 --- --- 72 V 375 3/8 1050 1/2

26 - 50 6 6 I 6 I 188 3/8 300 3/8


26 - 50 6 12 III 12 III 188 3/8 412 3/8
26 - 50 6 24 IV 24 IV 188 3/8 637 1/2
26 - 50 6 36 V 36 V 188 3/8 862 5/8

26 - 50 8 8 II 8 II 250 3/8 400 3/8


26 - 50 8 16 III 16 III 250 3/8 550 3/8
26 - 50 8 24 IV 24 IV 250 3/8 700 1/2
26 - 50 8 32 V 32 V 250 3/8 850 1/2

26 - 50 10 10 II 10 II 313 3/8 500 3/8


26 - 50 10 20 IV 20 IV 313 3/8 687 1/2
26 - 50 10 30 V 30 V 313 3/8 875 1/2

26 - 50 12 12 III 12 III 375 3/8 600 3/8


26 - 50 12 24 IV 24 IV 375 3/8 825 1/2
26 - 50 12 36 V 36 V 375 3/8 1050 1/2

26 - 50 16 16 III 16 III 500 3/8 800 1/2


26 - 50 16 32 V 32 V 500 3/8 1100 1/2

26 - 50 20 20 IV 20 IV 625 3/8 1000 1/2

26 - 50 24 24 IV 24 IV 750 3/8 1200 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 134 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 28

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.75g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

51 - 75 6 6 II 6 II 282 3/8 450 3/8


51 - 75 6 12 IV 12 IV 282 3/8 619 1/2
51 - 75 6 24 V 24 V 282 3/8 956 1/2

51 - 75 8 8 III 8 III 375 3/8 600 3/8


51 - 75 8 16 IV 16 IV 375 3/8 825 1/2
51 - 75 8 24 V 24 V 375 3/8 1050 1/2

51 - 75 10 10 III 10 III 469 3/8 750 1/2


51 - 75 10 20 V 20 V 469 3/8 1031 1/2

51 - 75 12 12 IV 12 IV 563 3/8 900 1/2


51 - 75 12 24 V 24 V 563 3/8 1237 5/8

51 - 75 16 16 IV 16 IV 750 1/2 1200 5/8

51 - 75 20 20 V 20 V 938 1/2 1500 5/8

51 - 75 24 24 V 24 V 1125 1/2 1800 5/8

76 - 100 6 6 III 6 III 375 3/8 600 3/8


76 - 100 6 12 IV 12 IV 375 3/8 825 1/2
76 - 100 6 18 V 18 V 375 3/8 1050 1/2

76 - 100 8 8 III 8 III 500 3/8 800 1/2


76 - 100 8 16 V 16 V 500 3/8 1100 1/2

76 - 100 10 10 IV 10 IV 625 1/2 1000 1/2

76 - 100 12 12 IV 12 IV 750 1/2 1200 5/8

76 - 100 16 16 V 16 V 1000 1/2 1600 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 135 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 29

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 0.75g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

101 - 150 6 6 IV 6 IV 563 3/8 900 1/2


101 - 150 6 12 V 12 V 563 3/8 1237 5/8

101 - 150 8 8 IV 8 IV 750 1/2 1200 5/8

101 - 150 10 10 V 10 V 938 1/2 1500 5/8

101 - 150 12 12 V 12 V 1125 1/2 1800 5/8

151 - 200 6 6 IV 6 IV 750 1/2 1200 5/8

151 - 200 8 8 V 8 V 1000 1/2 1600 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 136 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:33 PM Page 30

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 for Seismic Force Level 0.75g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 12 I 30 I 38 3/8 150 3/8


0 - 10 6 24 II 54 II 38 3/8 240 3/8
0 - 10 6 36 III 78 III 38 3/8 330 1/2

0 - 10 8 16 I 32 I 50 3/8 170 3/8


0 - 10 8 24 II 56 II 50 3/8 260 3/8
0 - 10 8 40 III 80 III 50 3/8 350 3/8

0 - 10 10 10 I 30 I 63 3/8 175 3/8


0 - 10 10 20 II 50 II 63 3/8 250 3/8
0 - 10 10 40 III 80 III 63 3/8 362 3/8

0 - 10 12 12 I 24 I 75 3/8 165 3/8


0 - 10 12 24 II 48 II 75 3/8 255 3/8
0 - 10 12 36 III 72 III 75 3/8 345 3/8

0 - 10 16 16 I 32 I 100 3/8 220 3/8


0 - 10 16 --- --- 48 II 100 3/8 280 3/8
0 - 10 16 32 III 80 III 100 3/8 400 3/8

0 - 10 20 --- --- 20 I 125 3/8 200 3/8


0 - 10 20 20 II 40 II 125 3/8 275 3/8
0 - 10 20 40 III 80 III 125 3/8 425 3/8

0 - 10 24 --- --- 24 I 150 3/8 240 3/8


0 - 10 24 24 II 48 II 150 3/8 330 3/8
0 - 10 24 --- --- 72 III 150 3/8 420 3/8

11 - 25 6 6 I 12 I 94 3/8 206 3/8


11 - 25 6 --- --- 18 II 94 3/8 262 3/8
11 - 25 6 12 III 30 III 94 3/8 375 3/8
11 - 25 6 24 IV 48 IV 94 3/8 544 1/2
11 - 25 6 36 V 72 V 94 3/8 769 5/8

11 - 25 8 --- --- 8 I 125 3/8 200 3/8


11 - 25 8 8 II 16 II 125 3/8 275 3/8
11 - 25 8 16 III 32 III 125 3/8 425 3/8
11 - 25 8 24 IV 48 IV 125 3/8 575 1/2
11 - 25 8 32 V 72 V 125 3/8 800 5/8

11 - 25 10 --- --- 10 I 157 3/8 250 3/8


11 - 25 10 10 II 20 II 157 3/8 344 3/8
11 - 25 10 --- --- 30 III 157 3/8 437 3/8
11 - 25 10 20 IV 50 IV 157 3/8 625 1/2
11 - 25 10 30 V 70 V 157 3/8 812 5/8

11 - 25 12 --- --- 12 I 188 3/8 300 3/8


11 - 25 12 12 III 24 III 188 3/8 412 3/8
11 - 25 12 24 IV 48 IV 188 3/8 637 1/2
11 - 25 12 36 V 72 V 188 3/8 862 5/8

11 - 25 16 --- --- 16 II 250 3/8 400 3/8


11 - 25 16 16 III 32 III 250 3/8 550 3/8
11 - 25 16 --- --- 48 IV 250 3/8 700 1/2
11 - 25 16 32 V 64 V 250 3/8 850 1/2

11 - 25 (Wt) continued on next page. * See note 2 on page 17. See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 137 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 31

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 0.75g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

11 - 25 20 --- --- 20 II 313 3/8 500 3/8


11 - 25 20 20 IV 40 IV 313 3/8 687 1/2
11 - 25 20 --- --- 60 V 313 3/8 875 1/2

11 - 25 24 --- --- 24 III 375 3/8 600 3/8


11 - 25 24 24 IV 48 IV 375 3/8 825 1/2
11 - 25 24 --- --- 72 V 375 3/8 1050 1/2

26 - 50 6 --- --- 6 I 188 3/8 300 3/8


26 - 50 6 6 III 12 III 188 3/8 412 3/8
26 - 50 6 12 IV 24 IV 188 3/8 637 1/2
26 - 50 6 18 V 36 V 188 3/8 862 5/8

26 - 50 8 --- --- 8 II 250 3/8 400 3/8


26 - 50 8 8 III 16 III 250 3/8 550 3/8
26 - 50 8 --- --- 24 IV 250 3/8 700 1/2
26 - 50 8 16 V 32 V 250 3/8 850 1/2

26 - 50 10 --- --- 10 II 313 3/8 500 3/8


26 - 50 10 10 IV 20 IV 313 3/8 687 1/2
26 - 50 10 --- --- 30 V 313 3/8 875 1/2

26 - 50 12 --- --- 12 III 375 3/8 600 3/8


26 - 50 12 12 IV 24 IV 375 3/8 825 1/2
26 - 50 12 --- --- 36 V 375 3/8 1050 1/2

26 - 50 16 --- --- 16 III 500 3/8 800 1/2


26 - 50 16 16 V 32 V 500 3/8 1100 1/2

51 - 75 6 --- --- 6 II 282 3/8 450 3/8


51 - 75 6 6 IV 12 IV 282 3/8 619 1/2
51 - 75 6 12 V 24 V 282 3/8 956 1/2

51 - 75 8 --- --- 8 III 375 3/8 600 3/8


51 - 75 8 8 IV 16 IV 375 3/8 825 1/2
51 - 75 8 --- --- 24 V 375 3/8 1050 1/2

51 - 75 10 --- --- 10 III 469 3/8 750 1/2


51 - 75 10 10 V 20 V 469 3/8 1031 1/2

51 - 75 12 --- --- 12 IV 563 3/8 900 1/2


51 - 75 12 12 V 24 V 563 3/8 1237 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 138 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 32

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 for Seismic Force Level 1.0g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 24 I 24 I 40 3/8 160 3/8


0 - 10 6 36 II 42 II 40 3/8 250 3/8
0 - 10 6 --- --- 60 III 40 3/8 340 1/2
0 - 10 6 --- --- 78 IV 40 3/8 430 1/2

0 - 10 8 24 I 24 I 54 3/8 173 3/8


0 - 10 8 40 II 40 II 54 3/8 253 3/8
0 - 10 8 --- --- 56 III 54 3/8 333 3/8
0 - 10 8 --- --- 80 IV 54 3/8 453 1/2

0 - 10 10 20 I 20 I 67 3/8 167 3/8


0 - 10 10 40 II 40 II 67 3/8 267 3/8
0 - 10 10 --- --- 60 III 67 3/8 367 3/8
0 - 10 10 --- --- 80 IV 67 3/8 467 1/2

0 - 10 12 24 I 24 I 80 3/8 200 3/8


0 - 10 12 36 II 36 II 80 3/8 260 3/8
0 - 10 12 --- --- 60 III 80 3/8 380 3/8
0 - 10 12 --- --- 72 IV 80 3/8 440 1/2

0 - 10 16 16 I 16 I 107 3/8 187 3/8


0 - 10 16 32 II 32 II 107 3/8 267 3/8
0 - 10 16 --- --- 48 III 107 3/8 347 3/8
0 - 10 16 --- --- 80 IV 107 3/8 507 1/2

0 - 10 20 20 I 20 I 134 3/8 233 3/8


0 - 10 20 40 II 40 II 134 3/8 333 3/8
0 - 10 20 --- --- 60 III 134 3/8 433 3/8
0 - 10 20 --- --- 80 IV 134 3/8 533 1/2

0 - 10 24 24 I 24 I 160 3/8 280 3/8


0 - 10 24 --- --- 48 III 160 3/8 400 3/8
0 - 10 24 --- --- 72 IV 160 3/8 520 3/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 139 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 33

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 1.0g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

11 - 25 6 6 I 6 I 100 3/8 175 3/8


11 - 25 6 12 II 12 II 100 3/8 250 3/8
11 - 25 6 24 III 24 III 100 3/8 400 3/8
11 - 25 6 36 IV 36 IV 100 3/8 550 1/2
11 - 25 6 --- --- 54 V 100 3/8 775 5/8

11 - 25 8 8 I 8 I 137 3/8 233 3/8


11 - 25 8 16 II 16 II 137 3/8 333 3/8
11 - 25 8 24 III 24 III 137 3/8 433 3/8
11 - 25 8 32 IV 32 IV 137 3/8 533 1/2
11 - 25 8 40 V 48 V 137 3/8 733 1/2

11 - 25 10 10 II 10 II 167 3/8 292 3/8


11 - 25 10 20 III 20 III 167 3/8 417 3/8
11 - 25 10 30 IV 30 IV 167 3/8 542 3/8
11 - 25 10 40 V 50 V 167 3/8 792 1/2

11 - 25 12 12 II 12 II 200 3/8 350 3/8


11 - 25 12 24 III 24 III 200 3/8 500 3/8
11 - 25 12 36 IV 36 IV 200 3/8 650 1/2
11 - 25 12 --- --- 48 V 200 3/8 800 1/2

11 - 25 16 16 II 16 II 267 3/8 467 3/8


11 - 25 16 36 IV 32 IV 267 3/8 667 1/2
11 - 25 16 --- --- 48 V 267 3/8 867 1/2

11 - 25 20 20 III 20 III 334 3/8 583 3/8


11 - 25 20 40 V 40 V 334 3/8 833 1/2

11 - 25 24 24 III 24 III 400 3/8 700 1/2


11 - 25 24 --- --- 48 V 400 3/8 1000 1/2

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 140 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 34

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 1.0g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

26 - 50 6 6 II 6 II 200 3/8 350 3/8


26 - 50 6 12 III 12 III 200 3/8 500 3/8
26 - 50 6 18 IV 18 IV 200 3/8 650 1/2
26 - 50 6 24 V 24 V 200 3/8 800 1/2

26 - 50 8 8 II 8 II 267 3/8 467 3/8


26 - 50 8 16 IV 16 IV 267 3/8 667 1/2
26 - 50 8 24 V 24 V 267 3/8 867 1/2

26 - 50 10 10 III 10 III 334 3/8 583 3/8


26 - 50 10 20 V 20 V 334 3/8 833 1/2

26 - 50 12 12 III 12 III 400 3/8 700 1/2


26 - 50 12 24 V 24 V 400 3/8 1000 1/2

26 - 50 16 16 IV 16 IV 534 3/8 933 1/2

26 - 50 20 20 V 20 V 667 1/2 1167 5/8

26 - 50 24 24 V 24 V 800 1/2 1400 5/8

51 - 75 6 6 III 6 III 300 3/8 525 3/8


51 - 75 6 12 IV 12 IV 300 3/8 750 1/2
51 - 75 6 18 V 18 V 300 3/8 975 1/2

51 - 75 8 8 III 8 III 400 3/8 700 3/8


51 - 75 8 16 V 16 V 400 3/8 1000 1/2

51 - 75 10 10 IV 10 IV 500 3/8 875 1/2

51 - 75 12 12 IV 12 IV 600 3/8 1050 1/2

51 - 75 16 16 V 16 V 800 1/2 1400 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 141 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 35

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figures 9 & 10

Table 1 cont. for Seismic Force Level 1.0g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

76 - 100 6 6 III 6 III 400 3/8 700 1/2


76 - 100 6 12 V 12 V 400 3/8 1000 1/2

76 - 100 8 8 IV 8 IV 534 3/8 933 1/2

76 - 100 10 10 V 10 V 667 1/2 1167 5/8

76 - 100 12 12 V 12 V 800 1/2 1400 5/8

101 - 150 6 6 IV 6 IV 600 3/8 1050 1/2

101 - 150 8 8 V 8 V 800 1/2 1400 5/8

151 - 200 6 6 V 6 V 800 1/2 1400 5/8

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 142 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 36

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 for Seismic Force Level 1.0g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

0 - 10 6 12 I 24 I 40 3/8 160 3/8


0 - 10 6 18 II 42 II 40 3/8 250 3/8
0 - 10 6 30 III 60 III 40 3/8 340 1/2
0 - 10 6 36 IV 78 IV 40 3/8 430 1/2

0 - 10 8 8 I 24 I 54 3/8 173 3/8


0 - 10 8 16 II 40 II 54 3/8 253 3/8
0 - 10 8 24 III 56 III 54 3/8 333 3/8
0 - 10 8 40 IV 80 IV 54 3/8 453 1/2

0 - 10 10 10 I 20 I 67 3/8 167 3/8


0 - 10 10 20 II 40 II 67 3/8 267 3/8
0 - 10 10 30 III 60 III 67 3/8 367 3/8
0 - 10 10 40 IV 80 IV 67 3/8 467 1/2

0 - 10 12 12 I 24 I 80 3/8 200 3/8


0 - 10 12 --- --- 36 II 80 3/8 260 3/8
0 - 10 12 24 III 60 III 80 3/8 380 3/8
0 - 10 12 36 IV 72 IV 80 3/8 440 1/2

0 - 10 16 --- --- 16 I 107 3/8 187 3/8


0 - 10 16 16 II 32 II 107 3/8 267 3/8
0 - 10 16 --- --- 48 III 107 3/8 347 3/8
0 - 10 16 32 IV 80 IV 107 3/8 507 1/2

0 - 10 20 --- --- 20 I 134 3/8 233 3/8


0 - 10 20 20 II 40 II 134 3/8 333 3/8
0 - 10 20 --- --- 60 III 134 3/8 433 3/8
0 - 10 20 40 IV 80 IV 134 3/8 533 1/2

0 - 10 24 --- --- 24 I 160 3/8 280 3/8


0 - 10 24 24 III 48 III 160 3/8 400 3/8
0 - 10 24 --- --- 72 IV 160 3/8 520 3/8

11 - 25 6 --- --- 6 I 100 3/8 175 3/8


11 - 25 6 6 II 12 II 100 3/8 250 3/8
11 - 25 6 12 III 24 III 100 3/8 400 3/8
11 - 25 6 18 IV 36 IV 100 3/8 550 1/2
11 - 25 6 24 V 54 V 100 3/8 775 5/8

11 - 25 8 --- --- 8 I 133 3/8 233 3/8


11 - 25 8 8 II 16 II 133 3/8 333 3/8
11 - 25 8 --- --- 24 III 133 3/8 433 3/8
11 - 25 8 16 IV 32 IV 133 3/8 533 1/2
11 - 25 8 24 V 48 V 133 3/8 733 1/2

11 - 25 (Wt) continued on next page.


* See note 2 on page 17.
See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 143 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 37

TRAPEZE BRACING
Seismic Bracing Charts for Trapeze Supports - Figure 11

Table 2 cont. for Seismic Force Level 1.0g (ASD)

Hanger Rod Size


Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze
Total Support Brace Structure Brace Structure
Rod Minimum Rod Minimum
Weight Span Interval 3,4 Connection Interval 3,4 Connection
Load 5 Rod Size 6 Load 5 Rod Size 6
Wt Lt* Type 2 Type 2
lbs./ft. ft. ft. ft. lbs. in. lbs. in.

11 - 25 10 --- --- 10 II 167 3/8 292 3/8


11 - 25 10 10 III 20 III 167 3/8 417 3/8
11 - 25 10 --- --- 30 IV 167 3/8 542 3/8
11 - 25 10 20 V 50 V 167 3/8 792 1/2

11 - 25 12 --- --- 12 II 200 3/8 350 3/8


11 - 25 12 12 III 24 III 200 3/8 500 3/8
11 - 25 12 --- --- 36 IV 200 3/8 650 1/2
11 - 25 12 24 V 48 V 200 3/8 800 1/2

11 - 25 16 --- --- 16 II 267 3/8 467 3/8


11 - 25 16 16 IV 32 IV 267 3/8 667 1/2
11 - 25 16 --- --- 48 V 267 3/8 867 1/2

11 - 25 20 --- --- 20 III 334 3/8 583 3/8


11 - 25 20 20 V 40 V 334 3/8 833 1/2

11 - 25 24 --- --- 24 III 400 3/8 700 1/2


11 - 25 24 24 V 48 V 400 3/8 1000 1/2

26 - 50 6 --- --- 6 II 200 3/8 350 3/8


26 - 50 6 6 III 12 III 200 3/8 500 3/8
26 - 50 6 --- --- 18 IV 200 3/8 650 1/2
26 - 50 6 12 V 24 V 200 3/8 800 1/2

26 - 50 8 --- --- 8 II 267 3/8 467 3/8


26 - 50 8 8 IV 16 IV 267 3/8 667 1/2
26 - 50 8 --- --- 24 V 267 3/8 867 1/2

26 - 50 10 --- --- 10 III 334 3/8 583 3/8


26 - 50 10 10 V 20 V 334 3/8 833 1/2

26 - 50 12 --- --- 12 III 400 3/8 700 1/2


26 - 50 12 12 V 24 V 400 3/8 1000 1/2

51 - 75 6 --- --- 6 III 300 3/8 525 3/8


51 - 75 6 6 IV 12 IV 300 3/8 750 1/2
51 - 75 6 --- --- 18 V 300 3/8 975 1/2

51 - 75 8 --- --- 8 III 400 3/8 700 1/2


51 - 75 8 8 V 16 V 400 3/8 1000 1/2

* See note 2 on page 17.


See page 145 for footnotes.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 144 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 38

TRAPEZE BRACING

Footnotes
1. It is not necessary to install both transverse braces and longitudinal braces on the same trapeze support. For
example, it is common to install transverse braces on trapezes every 40 ft., and then install both transverse and
longitudinal braces every 80 ft.
2. The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for brace attachment
details.
3. Any combination of brace interval and structure connection type (anchor size) may be used for a given system
weight and support span. For example, it is not necessary to use structure connection type II for both transverse
and longitudinal braces. Often longitudinal braces are spaced at a greater distance, and would require a larger
anchor when attaching to structure.
4. The bracing intervals listed are maximums. They are rounded down to facilitate construction. For example, it is
common to use a longitudinal bracing interval that is twice the transverse spacing.
5. The rod load indicates the maximum tension in the rod due to gravity and 1/3 of the horizontal seismic force
applied in the vertical direction for “unbraced trapezes”. For trapezes with braces attached, the rod load also
includes additional seismic loads. Note that the rod loads at braced locations are significantly higher than
unbraced trapezes. Select a hanger rod attachment detail from pages 39 thru 56 that meets the load
requirements.
6. The minimum rod size is given for both braced and unbraced trapezes. Due to the additional seismic forces at
braced trapezes, the rod sizes may be significantly larger. Be sure to follow the guidelines on page 57 to see if a
rod stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at braced
locations. Unbraced trapezes never require rod stiffeners.
7. Seismic forces for charts in Appendix 2 (pages 109 - 144) include 1/3 of horizontal seismic force applied in
vertical direction.
8. Charts in Appendix 2 (pages 109 - 144) are for the seismic force levels (%g) listed on those
pages.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 145 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 39

Appendix 3
Proof Test Instructions For Concrete Anchors (CAN 1925B.3.5)
State of California Office of Statewide Health Planning and Development
TEST VALUES
Hardrock or Lightweight Concrete
Anchor Wedge Sleeve Shell
Dia. Load Torque Load Torque Load Torque
(in.) (lbs) (ft-lbs) (lbs) (ft-lbs) (lbs) (ft-lbs)
1/4 800 10 400 4 1000 --
5/16 -- -- 400 4 1400 --
3/8 1100 25 700 10 1800 --
1/2 2000 50 900 20 2700 --
5/8 2300 80 1100 45 3700 --
3/4 3700 150 1400 90 5400 --
1 5800 250 -- -- -- --
Notes
1. Anchor diameter refers to the thread size for the Wedge & Shell categories and to the anchor outside diameter for the Sleeve category.
2. Apply proof test loads to Wedge & Sleeve anchors without removing the nut if possible. If not, remove nut and install a threaded coupler
to the same tightness as the original nut using a torque wrench and apply load.
3. For Sleeve/Shell internally threaded categories, verify that the anchor is not prevented from withdrawing by a baseplate or other fixtures.
If restraint is found, loosen and shim or remove fixture(s) prior to testing.
4. Reaction loads from test fixtures may be applied close to the anchor being tested, provided the anchor is not restrained from withdrawing
by the fixture(s).
5. Shell type anchors should be tested as follows:
a. Visually inspect 25% for full expansion as evidenced by the location of the expansion plug in the anchor body. Plug location of a fully
expanded anchor should be as recommended by the manufacturer, or, in the absence of such recommendation, as determined on the
job site following the manufacturer’s installation instructions. At least 5% of the anchors shall be proof loaded as indicated in the table
above, but not less than three anchors per day for each different person or crew installing anchors, or;
b. Test 50% of the installed anchors per Section 1925B.3.5.
6. Test equipment (including torque wrenches) is to be calibrated by an approved testing laboratory in accordance with standard recognized
procedures.
7. Torque test values for Shell type anchors can occur on an case-by-case basis when test procedures are submitted and approved by the
enforcement agency.
8. The following criteria apply for the acceptance of installed anchors;
Hydraulic Ram Method: The anchor should have no observable movement at the applicable test load. For wedge and sleeve type
anchors, a practical way to determine observable movement is that the washer under the nut becomes loose.
Torque Wrench Method: The applicable test torque must be reached within the following limits;
Wedge or Sleeve type: One-half (1/2) turn of the nut.
One-quarter (1/4) turn of the nut for 3/8 inch sleeve anchor only.
9. Testing should occur a minimum of 24 hours after installation of the subject anchors.
10. If the manufacturer’s recommended installation torque is less than the test torque noted in the table, the manufacturer’s recommended
installation torque should be used in lieu of the tabulated values.

11. All tests shall be performed in the presence of the Inspector of Record.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 146 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 40

Appendix 4
2000 International Building Code
As defined in the 2000 International Building Code, Chapter 16, Section 1621, the seismic horizontal force, Fp,
may be calculated using the following formula:
0.4apSDSIp z
Fp = (1 + 2 • )Wp
Rp h

Except that: Fp shall not be less than 0.3 SDS Ip Wp and need not be more than 1.6 SDS Ip Wp.
Where:
Fp = Seismic Force Level
ap = Amplification Factor (Table 1621.3)
Rp = Component Response Modification Factor, (Table 1621.3) which varies from 1.0 to 5.0

= 1.5 for shallow embedded anchors where the embedment length-to-diameter ratio
is less than 8. (Table 1621.1.7)
i.e. a 1/2" diameter anchor embedded less than 4" in concrete.
Ip = Importance Factor (Table 1621.1.6)
= 1.5 for Life-safety components required to function after an earthquake, buildings
containing hazardous or flammable material, and for storage racks open to the
general public.
= 1.0 for all other occupancies
SDS= Design spectral response acceleration at short period several factors: Seismic zone,
Soil Property Type, and Distance from known fault. (Section 1615.1.3)
Where,
SDS = (2/3) SMS (Section 1615.1.3)
SMS = FaSS Maximum considered spectral response acceleration for short
period (Section 1615.1.2)
Fa = Site coefficient, which is a combination of the Mapped spectral
Acceleration SS and Site Class (Table 1615.1.2(1))
SS = Mapped Spectral Acceleration for short periods (Section 1615.1)
Site Class = Soil type, “A thru F” (Table 1615.1.1)
z = Element or component attachment elevation with respect to grade.
Note: (z) shall not be taken less than 0.0
h = Average structure roof elevation with respect to grade.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 147 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 41

Example: Deeply Embedded Anchors


In this example a cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical
center. The cable tray is actually suspended from the 2nd floor, which has an elevation of 20 feet
above grade. The location of the surgical center is in Memphis, TN with a rock soil profile.

0.4apSDSIp z
Fp = (1 + 2 • )Wp
Rp h

ap = (1.0) for a cable tray (Table 1621.3)


Rp = (3.5) for a cable tray system anchored with deep embedded anchors (Table 1621.3)
Ip = (1.5) for an essential facility in Seismic Use Group III which will require continued use
following an earthquake (Section 1621.1.6)
SDS = (0.4) extended calculations shown below (Section 1615.1.3)
Where,
SDS = (2/3) SMS = (0.4) (Section 1615.1.3)
SMS = FaSS = (0.6) (Section 1615.1.2)
Fa = (1.0) using straight line interpolation of the Mapped spectral Acceleration
(SS) and Site Class (Table 1615.1.2(1))
SS = (0.6) Mapped Spectral Acceleration for short periods (Section 1615.1)
Site Class = B for Rock (Table 1615.1.1)

z = 20 feet, for the elevation of the floor used to support the cable tray
h = 40 feet, for the average elevation of the structure roof

0.4(1.0)(0.40)(1.5) 20
Fp = (1 + 2 • )Wp = 0.14Wp = 0.14g
3.5 40

Check if value falls within the allowed limits:

Fp shall not be taken less than, 0.3SDSIpWp = 0.3(.40)(1.5)Wp = .18g


Fp shall not be greater than, 1.6SDSIpWp = 1.6(.40)(1.5)Wp = 0.96g

0.14g < 0.18g, thus requiring the use of 0.18g

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 148 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 42

To convert this Fp from a strength design, as just determined from the building code, to an
Allowable Stress Design (ASD) used in the Cooper B-Line Seismic Restraints Manual divide by 1.4.

0.18g
Fp = = 0.13g (ASD)
1.4

0.13g is the Allowable Stress Design Seismic Load Factor determined from 2000 International
Building Code.

Special Note: Installations using concrete anchors installed with an embedment length-to-diameter
ratio of less than 8, also referred to as shallow embedment anchors, have an adjusted Component
Response Factor. The adjusted factor being Rp = 1.5.

Example Two: Shallow Embedded Anchors


In this example a cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical
center in California. The cable tray is actually suspended from the 2nd floor, which has an
elevation of 20 feet above grade. The location of the surgical center is in seismic zone 4 with a
rock soil profile, however shallow embedded anchors (length-to-diameter ratio of less than 8) are
used at brace locations.
0.4apSDSIp z
Fp = (1 + 2 • )Wp
Rp h

ap = (1.0) for a cable tray (Table 1621.3)


Rp = (1.5) for a cable tray system anchored with shallow embedded anchors (Table 1621.3)
Ip = (1.5) for an essential facility in Seismic Use Group III which will require continued use
following an earthquake (Section 1621.1.6)
SDS = (0.4) extended calculations shown below (Section 1615.1.3)
Where,
SDS = (2/3) SMS = (0.4) (Section 1615.1.3)
SMS = FaSS = (0.6) (Section 1615.1.2)
Fa = (1.0) using straight line interpolation of the Mapped spectral Acceleration
(SS) and Site Class (Table 1615.1.2(1))
SS = (0.6) Mapped Spectral Acceleration for short periods (Section 1615.1)
Site Class = B for Rock (Table 1615.1.1)

z = 20 feet, for the elevation of the floor used to support the cable tray
h = 40 feet, for the average elevation of the structure roof
0.4(1.0)(0.40)(1.5) 20
Fp = (1 + 2 • )Wp = 0.32Wp = 0.32g
1.5 40

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 149 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 43

Check if value falls within the allowed limits:

Fp shall not be taken less than, 0.3SDSIpWp = 0.3(.40)(1.5)Wp = .18g


Fp shall not be greater than, 1.6SDSIpWp = 1.6(.40)(1.5)Wp = .96g

0.96g > 0.32g > 0.18g, thus allowing the use of 0.32g

To convert Fp from a strength design, as just determined from the building code, to an Allowable
Stress Design (ASD) as used in the Cooper B-Line Seismic Restraints Manual divide by 1.4.
0.32g
Fp = = 0.23g (ASD)
1.4

0.23g is the Allowable Stress Design Seismic Load Factor determined from 2000 International
Building Code.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 150 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 44

1999 Standard Building Code


As defined in the 1999 Standard Building Code, Chapter 16, Section 1607.6.4, the seismic horizontal force,
Fp, may be calculated using the following formula:

Fp = AvCcPacWc

Where,
Fp = Seismic Force Level
Av = Peak velocity-related acceleration (Section 1607.1.5)
Cc = Seismic coefficient for mechanical, electrical components and systems
(Table 1607.6.4A)
P = Performance criteria factor (Table 1607.6.4A)
ac = Attachment amplification factor (Table 1607.6.4B)
Wc = Operating weight of the mechanical, electrical component of system

Example
This example is for a primary cable tray system suspended in a surgical center in Memphis, TN.

Fp = AvCcPacWc

Av = (0.20) for the Memphis, TN area (Table 1607.1.5A)


Cc = (2.0) for a primary cable tray system (Table 1607.6.4A)
P = (1.5) for a primary cable tray system (Table 1607.6.4A)
- Group III for an essential Surgery or Emergency Treatment
Facility (Table 1607.1.6)
ac = Always (1.0) when using a fixed connection type (Table 1607.6.4B)

Fp = 0.2(2.0)(1.5)(1.0)Wc = .6Wc = .6g

To convert Fp from a strength design, as just determined from the building code, to an Allowable
Stress Design (ASD) as used in the Cooper B-Line Seismic Restraints Manual divide by 1.4.

0.60g
Fp = = 0.43g (ASD)
1.4

0.43g is the Allowable Stress Design Seismic Load Factor determined from 1999 Standard
Building Code.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 151 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 45

1997 Uniform Building Code


As defined in the 1997 Uniform Building Code, Chapter 16, Section 1632, the seismic horizontal force, Fp, may
be calculated using the following formula:

apCaIp h
Fp = (1 + 3 • x )Wp
Rp hr

Except that: Fp shall not be less than 0.7 Ca Ip Wp and need not be more than 4 Ca Ip Wp.

Where:
Fp = Seismic Force Level
ap = Amplification Factor (Table 16-O)
Rp = Component Response Modification Factor (Table 16-O)
= 3.0 for electrical, mechanical and plumbing equipment and associated
conduit, ductwork and piping.
= 1.5 for installations using concrete anchors with an embedment-to-diameter
ratio less than 8.
i.e. a 1/2" diameter concrete anchor with an embedment of less than 4" inches.
Ip = Importance Factor (Table 16-K)
= 1.5 for Essential facilities such as Hospitals, Fire Stations, Police Stations,
Aviation Control Towers, etc. consult Table 16-K in UBC for a detailed list.
= 1.0 for most other occupancies
Ca = Seismic Coefficient. This is an accumulation of several factors: (Table 16-Q)
Seismic Zone (Table 16-I), Soil Property Type (Table 16-J), and Distance from
known faults. (Table 16-S, and Table 16-U)
hx = Element or component attachment elevation with respect to grade.
Note: hx shall not be taken less than 0.0
hr = Structure Roof Elevation with respect to grade.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 152 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 46

Example One, Deeply Embedded Anchors:


Cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical center in California.
The cable tray is actually suspended from the bottom of the 2nd floor, which has an elevation of 20
feet above grade. Location of the surgical center is in seismic zone 4 with a rock soil profile.
apCaIp h
Fp = (1 + 3 • x )Wp
Rp hr

ap = 1.0 from Table 16-O


Ca = .40Na from Table 16A-Q, which is combination of Seismic Zone factor and Soil
profile type
Where,
Z = .40 for seismic zone 4 applications (Table 16-I)
Soil Profile Type = SB for rock sediment (Table 16-J)
Seismic Source Type = B for faults other than Type A & C (Table 16-U)
Na = 1.0, for 5 km from known seismic source (Table 16-S)
Ip = (1.5) for an essential surgery and emergency treatment area (Table 16-K)
Rp = (3.0) for cable trays supported with deep embedded anchors (Table 16-O)
hx = 20 feet, for the elevation of the floor used to support the cable tray
hr = 40 feet, for the elevation of the structure roof

(1.0)((0.40(1.0))(1.5) 20
Fp = (1 + 3 • )Wp = 0.50Wp = 0.50g
3.0 40

Check if value falls within limits:

Fp shall not be taken less than, 0.7CaIpWp = 0.7(.40)(1.5)Wp = .42g


Fp shall not be greater than, 4.0CaIpWp = 4.0(.40)(1.5)Wp = 2.4g

2.4g > .5 > 0.42g Therefore allowing the use of 0.50g

To convert this Fp from a strength design, as just determined from the building code, to an
Allowable Stress Design (ASD) used in the Cooper B-Line Seismic Restraints Manual divide by 1.4.
0.50g
Fp = = 0.36g (ASD)
1.4

0.36g is the Allowable Stress Design Seismic Load Factor determined from 1997 Uniform
Building Code.

Special Note: Installations using concrete anchors installed with an embedment length-to-diameter
ratio of less than 8, also referred as shallow embedment anchors, have an adjusted Component
Response Factor being Rp = 1.5.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 153 of Raafat S. Aboulhosn


Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 47

Example Two, Shallow Embedded Anchors:


In this example a cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical
center in California. The cable tray is actually suspended from the 2nd floor, which has an eleva-
tion of 20 feet above grade. Location of the surgical center is in seismic zone 4 with a rock soil
profile, however shallow embedment anchors (length-to-diameter ratio of less than 8) are used at
brace locations. a CI h
Fp = p a p (1 + 3 • x )Wp
Rp hr

ap = 1.0 from Table 16-O


Ca = (.40Na) which is combination of seismic zone factor and soil profile type
from (Table 16-Q)
Where,
Z = .40 for seismic zone 4 applications (Table 16-I)
Soil Profile type = SB for rock sediment (Table 16-J)
Seismic Source Type = B for faults other than Type A & C (Table 16-U)
Near Source Factor = 1.0 for 5 km from known seismic source (Table 16-S)
Ip = (1.5) for an essential surgery and emergency treatment areas (Table 16-K)
Rp = (1.5) for cable trays supported with shallow embedded anchors (Table 16-O)
hx = 20 feet, for the elevation of the floor used to support the cable tray
hr = 40 feet. for the elevation of the structure roof

(1.0)((0.40(1.0))(1.5) 20
Fp = (1 + 3 • )Wp = 1.0Wp = 1.0g
1.5 40

Check if value falls within limits:


Fp shall not be taken less than, 0.7CaIpWp = 0.7(.40)(1.5)Wp = .42g
Fp shall not be greater than, 4.0CaIpWp = 4.0(.40)(1.5)Wp = 2.4g

2.4g > 1.0g > 0.42g Therefore allowing the use of 1.0g

To convert this Fp from a strength design, as just determined from the building code, to an
Allowable Stress Design (ASD) used in the Cooper B-Line Seismic Restraints Manual divide by 1.4.
1.0g
Fp = = 0.71g (ASD)
1.4

0.71g is the Allowable Stress Design Seismic Load Factor determined from 1997 Uniform
Building Code for shallow embedment anchors.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

Raafat S. Aboulhosn
12 - 9 - 02 154 of
Structural Engineer S 3913
**SRS2002-OSpg.108-155(11/02) N 1/3/03 5:34 PM Page 48

1999 BOCA (Building Officials and Code Administrators)


As defined in the 1999 BOCA, Chapter 16, Section 1610.6.4, the seismic horizontal force, Fp, may be calcu-
lated using the following formula:
Fp = AvCcPacWc

Where,
Fp = Seismic Force Level
Av = Peak velocity-related acceleration (Section 1610.1.3)
Cc = Seismic coefficient for mechanical, electrical components and systems
(Table 1610.6.4(1))
P = Performance criteria factor (Table 1610.6.4(1))
ac = Attachment amplification factor (Table 1610.6.4(2))
Wc = Operating weight of the mechanical, electrical component of system

Example
This example is for a primary cable tray system suspended in a surgical center in St. Louis, MO.

Fp = AvCcPacWc

Av = (0.15) for the St. Louis, MO area (Figure 1610.1.3(1))


Cc = (2.0) for a primary cable tray system (Table 1610.6.4(1))
P = (1.5) for a primary cable tray system (Table 1610.6.4(1))
- Group III for an essential Surgery or Emergency Treatment
Facility (Table 1610.1.6)
ac = Always (1.0) when using a fixed connection type (Table 1610.6.4(2))

Fp = 0.15(2.0)(1.5)(1.0)Wc = .45Wc = .45g

To convert Fp from a strength design, as just determined from the building code, to an Allowable
Stress Design (ASD) as used in the Cooper B-Line Seismic Restraints Manual divide by 1.4.

0.45g
Fp = = 0.32g (ASD)
1.4

0.32g is the Allowable Stress Design Seismic Load Factor determined from the 1999 BOCA.

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 155 of Raafat S. Aboulhosn


Structural Engineer S 3913
Appendix 5
This page has been reserved for future professional engineering approvals. These additional stamps are beyond the
scope of OSHPD pre-approval and are not intended for use on hospital projects in the State of California.
A current version of this page with all available engineering approvals is available on our website at
http://www.cooperbline.com/pdf/catalogs/SRS02/appendix5.pdf

COOPER B-Line
509 West Monroe Street
Highland, Illinois 62249
Phone: 618-654-2184
Fax: 618-654-1917

Date: Page No. Sheet Number:

12 - 9 - 02 156 of
SRS-02

Additional B-Line Catalogs

Cable Tray Strut Pipe Hangers Cent-R-Rail Spring Steel


Systems Systems & Supports Systems Fasteners

Electrical E2 Electronic Non-Metallic Meter Mounting Anchors


Enclosures Enclosures Enclosures Equipment Systems

Customer Service
Address: Cooper B-Line Phone: 618-654-2184
509 West Monroe Street Fax: 618-654-1917
Highland, IL 62249

www.cooperbline.com

Questions, Comments, Suggestions?


““
B-VOCAL SSMM

with B-Line ”
Voice Of the Customer...Actively Listening
bvocal@cooperbline.com
618-654-2184 ext. 456

SYSTEMS THAT MAKE SENSE


101202