You are on page 1of 10

International Journal of Refrigeration 122 (2021) 171–180

Contents lists available at ScienceDirect

International Journal of Refrigeration


journal homepage: www.elsevier.com/locate/ijrefrig

Free cooling potential for Brazilian data centers based on approach


point methodology
E.A. Amado, P.S. Schneider∗, C.S. Bresolin
Mechanical Engineering Department, Federal University of Rio Grande do Sul, Porto Alegre, RS, Brazil

a r t i c l e i n f o a b s t r a c t

Article history: Data centers cooling loads may reach about 40% of their electricity demands. The number of that type of
Received 9 November 2019 facility is continuously growing around worldwide and actions addressing energy saving are welcome to
Revised 14 November 2020
rationalize their operation. Free cooling appears as an effective solution to achieve energy savings, and the
Accepted 16 November 2020
present work proposes a methodology for assessing data center free cooling operation based on the heat
Available online 21 November 2020
exchanger approach point. The methodology can be applied to both airside and waterside economizer
Keywords: modes. The proposed methodology is applied to fourteen Brazilian state capitals that represent all coun-
Data center try climatic conditions. Free cooling environmental air temperature and humidity criteria are based on
Free cooling literature review and on ASHRAE thermal guidelines. Results show that cities such as Curitiba, São Paulo,
Air side economizer Porto Alegre and Brasília can potentially operate in both airside and waterside economizer modes for
Waterside economizer more than 30 0 0 h per year, even considering conservative data center thermal operating limits. Facilities
Approach point
placed on North and Northeast regions can only run under free cooling conditions if operational param-
ASHRAE TC 9.9 thermal guidelines
eters are to be relaxed to consider more flexible operating limits. It is shown that indirect economizers
are potentially more suitable to operate under ASHRAE recommended limits. The proposed methodology
is shaped for evaluating free cooling hours during system conception.
© 2020 Elsevier Ltd and IIR. All rights reserved.

Potentiel de refroidissement naturel basé sur la méthodologie des points


d’approche pour les centres de données brésiliens

Mots-clés: Centre de données; Refroidissement naturel; Économiseur câté air; Économiseur câté eau; Point d’approche; Directives thermiques TC 9.9 de l’ASHRAE

Abbreviations and symbols

Abbreviation
Ap : Approach Point [◦ C]
DC : Data Center DBT : Dry Bulb Temperature [◦ C]
ESD : Electrical Static Discharge DPT : Dew Point Temperature [◦ C]
FC : Free Cooling PUE : Power Usage Effectiveness [adim]
HX : Heat Exchanger RH : Relative Humidity [◦ C]
IT : Information Technology W BT : Wet Bulb Temperature [◦ C]
WCT : Water Cooling Tower Greek letters
Symbols γ : Summation of approach points [◦ C]
(continued on next page)


Corresponding author.
E-mail address: pss@mecanica.ufrgs.br (P.S. Schneider).

https://doi.org/10.1016/j.ijrefrig.2020.11.010
0140-7007/© 2020 Elsevier Ltd and IIR. All rights reserved.
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

ergy consumption from all non-computing devices of a data center


Subscripts
facility; such as lighting, power supply, communication and cool-
in : Indoor condition ing systems; would be zero. An average PUE is just below 2.0.
max : Maximum value
High-level energy performance in a DC is equivalent to reach low
PUE values, close to 1.2. Reducing the energy consumption of the
min : Minimum value
cooling system is the key factor to achieve a low PUE value and
out : Outdoors conditions improve a data center facility in both energetic and financial as-
pects. Santos et al. (2019) reviewed and discussed the most com-
mon metrics used to address DC energy performance. The authors
1. Introduction proposed the Energy Usage Effectiveness Designs – EUED as a new
index, which tried to correlate the local weather to the DC energy
Data centers (DCs) are dedicated facilities whose primary func- consumption on a year base.
tion is to house computer servers and offer data services. Reliabil- The use of free cooling strategies is, nowadays, one of the most
ity and availability are paramount for DCs since many companies used cooling efficiency techniques for data centers (Oró et al.,
rely heavily on a proper and uninterrupted data center operation 2015). According to The Green Grid (2012), it is estimated that the
all year round (ASHRAE, 2015). use of free cooling results in saving an average of 20% of money,
Digital information has experienced massive growth in the last energy and carbon emissions caused by cooling when compared to
decade, and data centers are the core infrastructure to support this DCs that do not use this technique. The following section describes
trend. Many countries are having rapid expansions of these facili- free cooling in detail.
ties to meet their demands for internet and cloud computing ser- Acknowledging the urge for energy savings in data centers, free
vices (Islam et al., 2015). Hence, DC financial and energetic impacts cooling potential studies have an important role in developing this
have drawn a lot of attention worldwide. technique and, consequently, in the increase of energy efficiency of
The DC market has increased at accelerated rates. According these facilities.
to Statista (2019), spending on DC systems worldwide has grown Methodologies have been proposed to assess the amount of
from US$ 140 billion in 2012 to US$ 202 billion in 2018, and it time that a DC can run compressor-free. Most of them re-
is expected to reach US$ 210 billion in 2019. Within the DC mar- lies on local weather data and specific system simulation. Local
ket, stands out the collocation sector. A collocation is a special data weather data and psychrometric operational criteria can suffice
center facility that rents infrastructure for customers to host their for designing simple systems based on direct airside economizers
servers and other computing hardware. This sector has grown even (Siriwardana et al., 2013; The Green Grid; The Green Grid, 2012),
faster than the average DC market. The collocation market should whether more complete thermal system simulation may be re-
reach a revenue of US$ 48 billion in 2021. quired when complex systems are to be conceived (Bi et al., 2017;
The collocation market spread has contributed to segment DC Gözcü et al., 2017; Lee and Chen, 2013a).
facilities worldwide (Shende, 2015). Partly driven by this, the Latin This work is motivated by the rising trend for energy efficiency
America DC market generated a turnover of US$ 2.87 billion in in data centers and aimed to develop criteria to estimate the DC
2017, and Brazil was responsible for 47.6% of this amount, which is free cooling potential of Brazilian reference cities applied to airside
expected to reach US$ 4.37 billion until 2021 (Dino, 2018). Some and waterside economizers. The proposed criteria were meant to
local environmental characteristics are desired to compete at a be general and flexible to be suitable for different DCs and regions
world scale, such as cheap electricity cost, cold climate and low- worldwide.
cost real estate. However, these characteristics are worthless unless
applied to high-level energy performance systems. 2. Free cooling
With respect to the energetic consequences of data centers, it is
fair to say that their energy consumption has increased at alarming Free cooling is a mode of operation defined as the use of a
rates all around the world. Between 20 0 0 and 20 05 this value has natural cold source (air or water) to cool an indoor environment
doubled, from 2005 to 2010 it increased another 56%, even though (Oró et al., 2015). When the cold source temperature is below
the world was facing an economic crisis (Zhang et al., 2014). DCs compared to the indoor operating temperature, it is possible to
were responsible for about 1.5% of worldwide electricity consump- cool the data center without a compressor based refrigeration cycle
tion in 2011, and an annual increase of 15–20% is expected in the (Amoabeng and Choi, 2016). This mode of operation is commonly
near future (Amoabeng and Choi, 2016). Furthermore, there is also known as economizer cycle (Zhang et al., 2014).
a major concern regarding data centers CO2 emissions. According Air conditioning compressors are the highest energy demanding
to Avgerinou et al. (2017), it is estimated that 2% of the global device of a cooling system. Free cooling systems can be arranged
CO2 is a result of energy usage in DCs. This value is expected to in parallel or in series with the conventional air conditioning sys-
increase at a 6% annual rate, and account for 12% of worldwide tem. Free cooling can be used either on full economizer mode, i.e.,
emissions by 2020. In this context, DC energy performance has also without the compressor; or in partial economizer mode as an aux-
become an important factor. iliary step to reduce the cooling load. Even so, free cooling still
As a result of all these factors, the trend in the IT and DC indus- relies on auxiliary power to drive system pumps and fans (Lee and
tries is to seek a high-level of reliability and availability followed Chen, 2013b), significant energy savings can be achieved whenever
by a reduction in energy consumption. The main responsible for compressors are turned off.
energy consumption in data centers are the servers and the re- The economizer modes can be divided into airside and water-
frigeration system, each of them accounting for about 40% of the side categories. The former rejects the DC heat to the air, and the
entire facility consumption (Rong et al., 2016). latter uses a water loop to transfer the DC heat outward.
From this perspective, Power Usage Effectiveness (PUE) index is Airside economizers cool the DC indoor environment using the
acknowledged as the most accepted metric to describe DC energy outdoor air directly or indirectly. In the direct category, filtered air
efficiency (Yuventi and Mehdizadeh, 2013). PUE is defined as the is supplied to the DC as in the outside condition by fans, Fig. 1a.
ratio of the total amount of energy used by an entire data cen- The outdoor air is drawn to the indoor environment without any
ter facility to the energy demanded only by the computing equip- air conditioning or humidity control. The advantage of this mode is
ment. PUE = 1 represents the hypothetical situation that the en- to be a less complex system that does not require a pump, cooling

172
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Fig. 3. Schematic of an air cooled waterside economizer system. Adapted from


Zhang et al. (2014).
Fig. 1. Air cooled economizer modes.

expensive because of increased water supply and disposal costs


(ASHRAE, 2016a).
Air cooled system is based on sensible heat exchangers to cool
down the circulating water when the outdoor air dry-bulb temper-
ature is favorable, Fig. 3. It is a simpler solution than the direct
water cooled one and avoids the environmental impact caused by
natural water consumption. On the other hand, its effectiveness is
lower (ASHRAE, 2016a), promoting fewer free cooling hours.
The cooling tower system uses an evaporative tower to reduce
Fig. 2. A schematic of a direct water cooled system. Adapted from Clidaras et al. the circulating water temperature, Fig. 3. Cooling tower type econ-
(2009).
omizers are the most widely used in the waterside category be-
cause they overcome most of the problems encountered by other
types. The water consumption rate of a cooling tower is only
towers or heat exchangers. The disadvantages are the risk of dust
about 5% of direct water system, making it more viable to op-
contamination and no humidity or temperature control can reduce
erate with purchased water. Furthermore, the amount of heated
DC reliability.
water discharged is very small, so the environmental harm is
Indirect airside economizer uses an intermediate air-air heat
greatly reduced if compared with the direct water cooled system
exchanger, between the indoor recirculating airflow and outdoor
(ASHRAE, 2016a).
airflow, Fig. 1b. The additional heat transfer step causes a reduc-
tion in the effectiveness of the whole system, usually allowing for
less free cooling hours when compared to direct airside economiz- 2.1. Free cooling potential
ers. On the other hand, it brings the advantages of preserving the
indoor air quality, saving the need for additional air filtering and Free cooling is considered an effective solution for reducing the
being less dependent on the outdoor humidity (ASHRAE, 2016b; energy consumption of cooling systems in the data center when its
Zhang et al., 2014). Besides, it can even provide more free cool- operation is viable for a high number of hours in a year. Thus, the
ing hours than a direct type for DCs in regions with constant high free cooling potential is defined as the number of hours in a year
humidity levels. that the DC can be cooled without compressor work (Malkamäki
The performance of direct type economizers depends only on and Ovaska, 2012; Oró et al., 2015; Siriwardana et al., 2013). The
the regional climate and indoor operating conditions, while the in- free cooling potential varies significantly depending on local cli-
direct type performance relies also on parameters related to the mate (Amoabeng and Choi, 2016).
heat exchanger. Thus, direct airside free cooling potential assess- In this context, free cooling potential assessments are studies
ments are more general and straightforward, making this kind of that evaluate the potential of a given city, region or country to cool
assessment a better starting point for DCs free cooling potential environments without mechanical cooling.
studies. There is an optimum supply air temperature for airside DC free cooling potential assessments commonly focus on gen-
economizer. As the supply temperature increases, the data center eral direct airside economizers. Siriwardana et al. (2013) investi-
free cooling hours increases as well, but after an optimum point, gated the potential of airside economizers in DCs housed in 20
the fan energy consumption exceeds the compressorless hours en- Australian cities, using weather data from 20 0 0 to 2011. The cities
ergy economy. The optimum supply temperatures are in the 18 o C– had their hourly dry-bulb temperature being compared with 15 ◦ C,
23 o C range, depending on operation conditions (Ham et al., 2015). which the set authors as the maximum allowed temperature for
Waterside economizer can be classified as direct water cooled the DC supplied air intake. The results showed that Melbourne pre-
system, air-cooled system and cooling tower system (Zhang et al., sented the highest free cooling potential from the cities assessed
2014). In direct water cooled system, natural cold water is used allowing for direct airside economizers to be used for more than
to cool the data center indoor air without any other steps of heat 50 0 0 h per year.
transfer, Fig. 2. This application is limited by the dependency either A thermo-economic analysis for three types of economizers
on purchasing water or on natural cold water availability, meaning done in ten Iranian cities (Deymi-Dashtebayaz and Namanlo, 2019)
that the DC must be located close to water sources. Nevertheless, concluded that the PUE can be improved up to 12% using com-
direct water cooled economizer is an efficient operating mode, able bined air or water economizer modes for most cities.
to maintain the facility temperature close to the average environ- Similarly, The Green Grid (2009) published the “Airside Free
ment temperature for 24 h a day. Cooling Maps”, evaluating the potential of direct airside economiz-
This system seems promising in Brazil, due to the country large ers for DCs in Europe, North America and Japan. These maps were
coastline, and its key cities near the ocean. However, cooling wa- updated in 2012 (The Green Grid, 2012) to take into account newer
ter drawn from natural sources may impact the local ecosystem and more relaxed operating ranges limits. The maps were made by
due to the increased temperature of the discharged water. Be- comparing bin data collected from the WeatherBank with maxi-
sides, water purchased from utilities for this purpose became very mum limits of dry-bulb and dew-point temperatures for data cen-

173
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Table 1 A3 and A4 classes, while the older ones are more suited to operate
Recommended and Allowable ranges for DC operation.
within the A1 and A2 classes.
Adapted from ASHRAE (2015).

Range DBT (◦ C) DPT (◦ C) RH (%)


3.2. Free cooling assessment for direct airside
Recommended 18 to 27 −9 to 15 60
Allowable A1 15 to 32 −12 to 17 8 to 80
Allowable A2 10 to 35 −12 to 21 8 to 80 The Recommended and Allowable envelopes are shown in
Allowable A3 05 to 40 −12 to 24 8 to 85 Fig. 4 are intended to describe operating limits of DCs while using
Allowable A4 05 to 45 −12 to 24 8 to 90 mechanical cooling. As free cooling does not depend on compres-
sor some of the envelope boundaries are not required. An in-depth
survey in the literature was carried out in this subsection to under-
ters. The Green Grid Airside Free Cooling Maps have become an stand which limits could be discarded while establishing the direct
important reference for DC operators and researchers in this field, airside free cooling criteria.
as it allows for a first estimate of the free cooling performance in Dry-bulb temperature The upper DBT limit is the most impor-
different regions. tant parameter for IT equipment operation and should be taken
Beaty et al. (2019) presented a waterside free cooling potential into account in this evaluation, as most of the failure mechanisms
assessment for several North American cities, by considering dif- of electronic components are intensified by increasing their opera-
ferent values for the supply air temperature, ranging from 14 ◦ C tional temperature (ASHRAE, 2016b). The maximum operating tem-
to 24 ◦ C. The approach between the outdoor wet-bulb temperature perature limit that an IT equipment should reach the chip level is
and the chilled water supply was assumed as 3.9 ◦ C and the tem- about 85 ◦ C (Amoabeng and Choi, 2016; Marcinichen et al., 2012).
perature difference between the chilled water supply and the sup- The heat removal in a data center must guarantee that this limit is
ply air temperature was assumed as 5.6 ◦ C. The author evaluated not surpassed. The lower boundary of DBT suggested ranges are in-
the hour percentage in a year in which a DC under those con- tended to prevent a very inefficient energetic operation under me-
ditions could operate under waterside free cooling, based on the chanical cooling. This boundary was discarded in the present work
local weather data. Denver displayed the highest potential among as it does not impact the free cooling potential assessment.
the assessed cities, with 53% of free cooling potential for the worst Lower humidity boundaries The RH and DP T parameters are
scenario. metrics to measure the relative and absolute humidity of the DC
In Brazil, works from Driemeyer (2016) and environment, respectively. Their lower limits were introduced by
Belizário (2018) modeled and assessed free cooling systems ASHRAE TC 9.9 (ASHRAE, 2015) to avoid the risk of electronic
as case studies, and Santos et al. (2019) applied their proposed discharges (ESD) in the IT equipment. The guideline reduced the
EUED index to select Brazilian cities. Nevertheless, there still is a lower RH limit from 25% to 8% after studies (Gao et al., 2015; Hy-
lack of general free cooling potential assessment for the country. deman and Swenson, 2010; Wan et al., 2013) had verified that this
reduction would not increase at high rates the ESD probability.
3. Free cooling assessment The assessment of Brazilian meteorological data (LABEE, 2018)
showed little occurrences of RH and DP T values below 8% and
To account for free cooling hours, an internal operation condi- −9 ◦ C respectively. Thus, it was decided to discard the lower RH
tion is needed for temperature and humidity, and compare it with and DP T limits while assessing the free cooling potential.
the outside weather condition. If the system has intermediate heat Higher humidity boundaries High humidity levels can cause wa-
exchangers, it is necessary to consider the temperature gap be- ter vapor to condensate on IT equipment, putting at risk their reli-
tween the hot and cold flows. Two ways to compute the free cool- ability (Oró et al., 2015). However, the RH parameter is difficult to
ing potential are proposed, one for direct air cooling, and other to be controlled inside a DC facility as it depends on both the abso-
waterside cooling tower. Also, a generalization for other indirect lute humidity content and the dry-bulb temperature. Nevertheless,
modes is proposed. its control can be performed by partially mixing exhaust air with
inlet air. DP T is a more stable parameter, as it is linked to the air
absolute humidity, which does not change significantly throughout
3.1. DC thermal operating conditions
the DC environment (Hydeman and Swenson, 2010). Therefore, the
upper DP T limit was taken into account while the upper RH limit
The latest ASHRAE thermal guidelines (ASHRAE, 2015) displays
was discarded in the present assessment.
the required conditions for reliable DC operation. Ranges of dry-
Based on these assumptions, only two parameters among those
bulb temperature (DBT ), relative humidity (RH) and dew-point
presented in the operating ranges suggested by ASHRAE were con-
temperature (DP T ) were featured for different classes of IT equip-
sidered to evaluate the free cooling potential for direct airside:
ment in this guideline as shown in Table 1 and Fig. 4.
upper dry-bulb temperature limit (DBTin,max ) and upper dew-point
The Recommended range is defined as a reference, as it is
temperature limit (DP Tin,max ), defined by the upper right corner of
the safest one and the most accepted by DC operators (Lee and
envelopes in Fig. 4. Thus, the free cooling is considered possible
Chen, 2013b). The other four are called Allowable ranges, with dif-
for the hourly step accounted by the double condition imposed in
ferent limits according to the IT equipment class. An equipment
Eq. (1),
class is a definition for IT manufacturers to design their products.
When it was first created, the Recommended range was in- DBTout ≤ DBTin,max
tended to be the most reliable, acceptable and reasonable power- ∴ Direct Airside Free cooling is possible. (1)
DP Tout ≤ DP Tin,max
efficient operation zone, but it was never meant to be the abso-
lute limits of operation. As a result of the growing need for en- for the hourly outdoor dry-bulb DBTout and dew-point DP Tout
ergy efficiency, and consequently, the interest to use economizers temperatures in respect to the desired limits for DBTin,max and
as much as possible during a year, the Allowable ranges were pro- DP Tin,max . It was assumed that the air temperature remains un-
posed, reinforcing the idea that it is acceptable to operate outside changed along with its intake through the cold face of IT equip-
the Recommended range for short periods of time without affect- ment.
ing the overall reliability of the IT equipment. It is worth noticing A graphical representation was made to illustrate the criteria
that new equipment allowed for a more relaxed operation, toward established on a psychrometric chart. Fig. 5 presents the free cool-

174
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Fig. 4. Recommended and Allowable operating envelopes on a psychrometric chart.

Fig. 5. Free cooling zone considering the Recommended range limits on a psychrometric chart.

175
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Fig. 6. Free cooling zones considering Allowable ranges limits.

ing zone considering the free cooling criteria applied to the Rec- transfer resistance is taken into account by the approach point,
ommended range limits for DBTin,max and DP Tin,max . which is the minimum temperature difference between hot and
The green color represents the zone where free cooling is cold fluid flows. The use of the approach point to refine the free-
achievable (Zone I), the red color means that the free cooling is cooling potential assessment is shown as follows applied to a wa-
not possible due to the high DBT level (Zone II), the red color rep- terside economizer with a cooling tower to be later expanded to
resents that free cooling is not possible due to the high DP T level other indirect modes.
(Zone III), and the orange zone is where free cooling is not practi- To calculate the W BTout,max , the approach point from the heat
cal due to both: DBT and DP T parameters (Zone IV). exchanger and cooling tower ApWCT are discounted from the max-
Free cooling zones for Allowable ranges limits A1, A2, A3 and imum internal dry-bulb temperature DBTin,max ,
A4 were similarly plotted as shown in Fig. 6.
W BTout,max = DBTin,max − ApHX − ApWCT (2)
3.3. Free cooling methodology for waterside cooling tower the approach values can be evaluated through an energy balance
in the heat exchanger, using the inlet and outlet temperature dif-
Differently from direct airside economizer mode, indirect ferences and effectiveness. The ApWCT is defined as the difference
modes use heat exchangers. Heat exchanger can be modeled as between the cooling tower outlet cold water and the outdoor wet-
a resistance device. To offset the resistance, the cold source tem- bulb temperature W BTout . The ApHX is defined in the cold side of
perature should be lower than the DC internal required tempera- a counter-current heat exchanger. Eq. (2) is an expression to find
ture, reducing the free-cooling available hours. That additional heat the maximum outdoor wet-bulb temperature which guarantees

176
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Table 2 ASHRAE Climate Zone. Dry-bulb and dew-point temperatures were


Free cooling potential criteria summary.
employed to find the number of hours that each city could poten-
Category Type Criteria tially operate on free cooling along a year period (8760 h).
Airside Direct DBTout ≤ DBTin,max
DP Tout ≤ DP Tin,max 4.1. Airside direct results
Indirect DBTout ≤ DBTin,max − ApHX
Waterside Direct water cooled DBTout ≤ DBTin,max − ApHX
The direct type economizers performance depends only on
Air cooled DBTout ≤ DBTin,max − ApHX,out − ApHX,in
Cooling tower W BTout ≤ DBTin,max
b
− ApHX − ApWCT the regional climate and indoor operating conditions. Thus, direct
airside free cooling potential assessments are more general and
straightforward, making a better starting point for DCs free cool-
ing potential studies.
DBTin,max as the indoor supply air temperature considering that
Table 4 summarizes the airside free cooling potential assess-
all DC restrictive parameters had been set. Therefore, free cooling
ment results for the 14 Brazilian capitals listed in Table 3. Limits
is considered possible when the outdoor wet-bulb temperature is
from all ranges (Recommended and Allowable A1, A2, A3, A4) were
less than or equal to this maximum calculated value (Eq. (3)).
considered. Reddish tones represent lower free cooling potential,
W BTout ≤ W BTout,max ∴ Free cooling is possible. (3) while bluish tones represent higher potential.
Curitiba displayed the best performance among all cities, being
The heat exchangers were taken as adiabatic, so the cooling
capable to operate inside Zone I (Fig. 5) for 5575 h considering the
tower rejects the total dissipated heat from the IT equipment. Both
Recommended range limits. Capital cities such as São Paulo, Porto
indoor air and water loops were modeled as systems with no need
Alegre and Brasília presented free cooling potential for more than
for fluid make-up. There are no other heat sources along the air
30 0 0 h considering the Recommended range. Most of the North
path from intake to the IT cold face. The hot and cold aisles are
and Northeast cities displayed a negligible number of free cooling
perfectly separated. The DBTin,max is the main parameter to be
hours for both Recommended and A1 range limits.
monitored whenever indirect waterside economizers are used. The
Overall better results were achieved when considering more
ASHRAE thermal guidelines limits presented in Table 1 were used
flexible ranges (A2, A3 and A4). Curitiba, São Paulo and Brasília can
as a reference to evaluate this parameter.
operate in free cooling considering A2 range for almost the entire
3.4. Graphical procedure year (80 0 0+ hours), and all cities aside from Fortaleza are able to
operate inside Zone I for 7800+ hours in a year when A3 or A4
A graphical procedure was made to define the free cooling zone ranges were considered.
on a psychrometric chart. The customized psychrometric chart pre- By looking exclusively at the free cooling hours, one cannot find
sented in Fig. 7(a) displays the “γ isolines”. With γ being defined whether the excess of DBT or the excess of DP T were responsible
as the sum of approaches from the cooling tower and heat ex- to prevent more free cooling hours. An expanded assessment based
changer as shown in Eq. (4). only on the DP T criterion was performed on the 14 capital cities to
investigate whether the DBT criterion was really required (Table 5).
γ ≡ ApHX + ApWCT (4) Results presented in Table 5 corroborate with the hypothesis
that DP T is indeed the critical parameter to the free cooling po-
W BTout,max = DBTin,max − γ (5) tential assessment in Brazil. The DBT criterion was only relevant
while assessing the Recommended range limits and for a few cities
For values of DBTin,max and γ , one can trace a constant DBT line such as Brasília and São Paulo, which displayed a variation in the
from the DBTin,max until it reaches the set γ value and then mark free cooling hours of 9.94% and 3.12%, respectively. Maceió had a
this point. The W BT of this point is the W BTout,max . Thus, the free 62.50% variation in its free cooling hours, but the absolute num-
cooling zone can be defined as the entire zone below a constant ber is negligible since it raised from 8 to 13 h. All cities displayed
W BT line which has that point as shown in Fig. 7(b). This pro- slightly increases or even no changes at all while considering the
cedure is useful to create free cooling zones and compare them limits of the Allowable ranges, which indicates that the direct air-
with weather data graphically. Fig. 7(c) and (d) presents applica- side free cooling assessment could be performed based only on the
tions of this graphical procedure to create different free cooling DP T criterion without causing major changes in the free cooling
zones, relying on different system parameters, but considering the potential hours of the 14 Brazilian cities.
same weather data occurrences.
4.2. Cooling tower waterside results
3.5. Generalization for other indirect types
The free cooling potential results for 14 Brazilian capitals are
Similar criteria to the ones developed for the cooling tower presented in Table 6 for an average scenario considering γ = 10 ◦ C.
economizer can be proposed to the indirect air, direct water and As reference values, Beaty et al. (2019) and Belizário (2018) used,
air cooled water types since they are all indirect. Table 2 brings respectively, an equivalent value to γ = 9, 5 ◦ C and γ = 8 ◦ C in
the criteria for all the five main types in the airside and waterside their work. All of the ASHRAE thermal guidelines operating range
categories. limits (Table 1) were taken into consideration to set the DBTin,max
values in this assessment.
4. Results Curitiba displayed the best performance among all cities, as
6301 h per year were found of free cooling potential considering
To explore the proposed methodology, the free cooling poten- the Recommended range limit. Capital cities such as São Paulo,
tial for fourteen capital cities were selected based on the avail- Porto Alegre and Brasília came right after, with more than 30 0 0 h
able Test Reference Year (TRY) weather data (LABEE, 2018). The se- in a year on the same range limit.
lected cities are the major economic centers in their regions. Al- Most of the North and Northeast regions of the country dis-
most all cities are in the ASHRAE Climate Zone 1 in Brazil. All played a negligible potential to free cooling considering Rec-
country regions were covered (South, Southeast, Midwest, North- ommended and A1 limit, with exception of Salvador and Ma-
east and North). Table 3 presents the selected cities by Region and

177
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Fig. 7. Graphical representation of the waterside free cooling potential criteria.

Table 3
Capital cities assessed by country region. Weather data obtained from LABEE (2018).

Region ASHRAE climate zone City (state)

South 2 Porto Alegre (RS), Florianópolis (SC), Curitiba (PR)


Southeast 2 São Paulo (SP)
1 Rio de Janeiro (RJ), Vitória (ES)
Midwest 2 Brasília (DF)
Northeast 1 Salvador (BA), Maceió (AL), Recife (PE),
Natal (RN), Fortaleza (CE), São Luís (MA)
North 1 Belém (PA)

ceió which achieved more than 40 0 0 h in the A1 limit. Over- were excluded from the assessment. Free cooling is possible for
all better results were found when considering more flexible the entire year for all the 14 cities when A3 or A4 limits were
limits. considered.
All the 14 assessed cities displayed at least 5900 free cool- This assessment was performed over an average of γ = 10 ◦ C.
ing hours with the waterside economizer mode when consid- Results are very sensitive to changes on γ , and W BT cumulative
ering the A2 range limits, and that number can reach at least frequency distributions can aid to assess the free cooling potential
8300 h (almost the entire year) if Fortaleza, São Luís and Belém of a given city considering variations of γ .

178
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

Table 4
Free cooling potential in 14 Brazilian capitals.

Free Cooling (FC) hours FC hours FC hours FC hours FC hours


considering considering A1 considering A2 considering A3 considering
City State Latitude Recommended range range range range A4 range

Porto Alegre RS 30◦ 02’S 3783 5309 7927 8735 8735


Florianópolis SC 27◦ 36’S 1925 3760 7004 8470 8470
Curitiba PR 25◦ 26’S 5575 7299 8726 8760 8760
São Paulo SP 23◦ 33’S 4259 6418 8665 8760 8760
Rio de Janeiro RJ 22◦ 54’S 255 1134 5481 8555 8555
Vitória ES 20◦ 19’S 447 1417 5304 8494 8494
Brasília DF 15◦ 47’S 3028 5079 8745 8760 8760
Salvador BA 12◦ 58’S 17 261 5061 8729 8729
Maceió AL 9◦ 40’S 8 130 5795 8759 8759
Recife PE 8◦ 03’S 0 4 2521 8694 8694
Natal RN 5◦ 48’S 0 6 3048 8697 8697
Fortaleza CE 3◦ 43’S 0 1 221 6657 6657
São Luís MA 2◦ 32’S 0 1 168 8141 8141
Belém PA 1◦ 27’S 0 2 387 7888 7888

Table 5
Free cooling hours while assessing only the dew-point temperature criterion and its percentage growth in relation to the assessment
considering the two criteria.

Free Cooling (FC) hours FC hours FC hours FC hours FC hours


considering considering considering considering considering
City State Latitude Recommended range A1 range A2 range A3 range A4 range

Porto Alegre RS 30◦ 02’S 3836 (+1.40%) 5323 7939 8735 (=) 8735 (=)
(+0.26%) (+0.15%)

Florianópolis SC 27 36’S 1929 (+0.21%) 3760 (=) 7004 (=) 8470 (=) 8470 (=)
Curitiba PR 25◦ 26’S 5615 (+0.72%) 7299 (=) 8726 (=) 8760 (=) 8760 (=)
São Paulo SP 23◦ 33’S 4392 (+3.12%) 6425 8665 (=) 8760 (=) 8760 (=)
(+0.11%)
Rio de Janeiro RJ 22◦ 54’S 259 (+1.57%) 1134 (=) 5487 8555 (=) 8555 (=)
(+0.11%)
Vitória ES 20◦ 19’S 447 (=) 1417 (=) 5304 (=) 8494 (=) 8494 (=)
Brasília DF 15◦ 47’S 3329 (+9.94%) 5086 8745 (=) 8760 (=) 8760 (=)
(+0.14%)
Salvador BA 12◦ 58’S 17 (=) 261 (=) 5061 (=) 8729 (=) 8729 (=)
Maceió AL 9◦ 40’S 13 (+62.50%) 130 (=) 5795 (=) 8759 (=) 8759 (=)
Recife PE 8◦ 13’S 0 (=) 4 (=) 2521 (=) 8694 (=) 8694 (=)
Natal RN 5◦ 48’S 0 (=) 6 (=) 3048 (=) 8697 (=) 8697 (=)
Fortaleza CE 3◦ 43’S 0 (=) 1 (=) 221 (=) 6657 (=) 6657 (=)
São Luís MA 2◦ 32’S 0 (=) 1 (=) 168 (=) 8141 (=) 8141 (=)
Belém PA 1◦ 27’S 0 (=) 2 (=) 387 (=) 7888 (=) 7888 (=)

Table 6
Free cooling potential hours in 14 Brazilian capitals considering the average scenario (γ = 10 ◦ C).

Free Cooling (FC) hours FC hours FC hours FC hours FC hours


considering considering considering considering considering
City State Latitude Recommended range A1 range A2 range A3 range A4 range

Porto Alegre RS 30◦ 02’S 4291 7700 8613 8760 8760


Florianópolis SC 27◦ 36’S 2600 7077 8389 8752 8760
Curitiba PR 25◦ 26’S 6301 8664 8760 8760 8760
São Paulo SP 23◦ 33’S 5117 8569 8754 8760 8760
Rio de Janeiro RJ 22◦ 54’S 578 5238 8242 8760 8760
Vitória ES 20◦ 19’S 832 5215 8261 8760 8760
Brasília DF 15◦ 47’S 3032 8660 8760 8760 8760
Salvador BA 12◦ 58’S 79 4113 8553 8760 8760
Maceió AL 9◦ 40’S 34 5051 8700 8760 8760
Recife PE 8◦ 03’S 0 1726 8613 8760 8760
Natal RN 5◦ 48’S 0 2302 8380 8760 8760
Fortaleza CE 3◦ 43’S 0 309 5939 8760 8760
São Luís MA 2◦ 32’S 0 132 6922 8760 8760
Belém PA 1◦ 27’S 0 609 6875 8760 8760

5. Conclusion compressor-free. The heat exchanger resistance was used as a pa-


rameter within the approach point method, which allowed it to be
The present work presented a methodology for free-cooling of general to use with airside and waterside categories of econo-
potential assessment able to incorporate system limitations. The mizers.
methodology uses the heat exchanger approach point applied The maximum dry-bulb (DBTin,max ) and dew-point (DP Tin,max )
to criteria from ASHRAE thermal guidelines with local weather temperatures of the supplied intake air were considered as cri-
data to estimate the number of hours that a DC can be cooled teria to estimate the direct airside free cooling potential. Results

179
E.A. Amado, P.S. Schneider and C.S. Bresolin International Journal of Refrigeration 122 (2021) 171–180

showed that Curitiba displayed the highest free cooling potential Bi, Y., Wang, Y., Ma, X., Zhao, X., 2017. Investigation on the energy saving potential
in this category, achieving 5575 economizer hours in a year, even of using a novel dew point cooling system in data centres. Energies 10, 1732.
doi:10.3390/en10111732.
considering the most conservative operating limit. Cities such as Clidaras, J., Stiver, D.W., Hamburgen, W., 2009. Water-Based Data Center.
Porto Alegre, São Paulo and Brasília also showed the potential to Patent US7525207B2; 2009. https://patentimages.storage.googleapis.com/b6/d0/
free cooling, displaying more than 30 0 0 economizer hours in those d6/d1f4357032fea5/US7525207.pdf.
Deymi-Dashtebayaz, M., Namanlo, S.V., 2019. Potentiometric and economic analysis
limits. Cities from North and Northeast did not show the potential of using air and water-side economizers for data center cooling based on vari-
to free cooling considering conservative operating limits. However, ous weather conditions. Int. J. Refrig. 99, 213–225. doi:10.1016/j.ijrefrig.2019.01.
when considering more flexible ranges such as Allowable A3 and 011.
Dino. https://www.terra.com.br/noticias/dino/com- receita- de- us- 28- bilhoes- na-
A4 limits more than 70 0 0 economizer hours were achieved. A fur-
america- latina- mercado- de- data- centers- demanda- investimento- brasileiro,
ther analysis detailing these results showed that the DP T parame- e86e110777ea555792ccb818a87d4421eedextcb.html.
ter was the critical criterion in this assessment. Driemeyer, R., 2016. Projeto de Melhoria de um Data Center com Ênfase em In-
fraestrutura e Melhoria Energética. Universidade do Vale do Taquari, Lajeado,
The waterside free cooling potential assessment was made con-
RS - Brazil Master’s thesis.
sidering a cooling tower economizer type. The criteria to free cool- Gao, X., Talebzadeh, A., Moradian, M., Han, Y., Swenson, D., Pommerenke, D., 2015.
ing proposed in this category considered the maximum supply Dependence of ESD charge voltage on humidity in data centers: Part III – esti-
air temperature (DBTin,max ) and the system approaches (ApCT and mation of ESD-related risk in data centers using voltage level extrapolation and
Chebyshev’s inequality. ASHRAE Trans. 121, 49–57.
ApHX ) as parameters to compare with the outdoor wet-bulb tem- Gözcü, O., Özada, B., Carfi, M.U., Erden, H.S., 2017. Worldwide energy analysis of ma-
perature (W BTout ). A graphical representation was developed to il- jor free cooling methods for data centers. In: Proceedings of the 16th IEEE Inter-
lustrate the criteria dependence with the sum of the system ap- society Conference on Thermal and Thermomechanical Phenomena in Electronic
Systems (ITherm), pp. 968–976. doi:10.1109/ITHERM.2017.7992592.
proaches (γ ) on a psychrometric chart. Ham, S.-W., Park, J.-S., Jeong, J.-W., 2015. Optimum supply air temperature ranges
The waterside free cooling criteria were evaluated and dis- of various air-side economizers in a modular data center. Appl. Therm. Eng. 77,
cussed considering an average scenario of γ = 10 ◦ C based on lit- 163–179. doi:10.1016/j.applthermaleng.2014.12.021.
Hydeman, M., Swenson, D., 2010. Humidity controls for data centers are they nec-
erature values. The results behaved similarly to the airside free essary. ASHRAE J. 52, 48–55.
cooling potential assessment. Curitiba displayed the highest free Islam, M.A., Mahmud, H., Ren, S., Wang, X., 2015. Paying to save: reducing cost
cooling potential in this category, achieving 6301 economizer of colocation data center via rewards. In: Proceedings of the 21st Interna-
tional Symposium on High Performance Computer Architecture (HPCA). IEEE,
hours in a year considering the most conservative operating lim-
Burlingame, CA, USA.
its. Porto Alegre, São Paulo and Brasília also showed potential LABEE, 2018. Climatic data files, 2018. https://labeee.ufsc.br/downloads/
for free cooling displaying more than 30 0 0 economizer hours in arquivos- climaticos/formato- try- swera- csv- bin.
Lee, K.-P., Chen, H.-L., 2013a. Analysis of energy saving potential of air-side free
that limit. North and Northeast cities of the country only pre-
cooling for data centers in worldwide climate zones. Energy Build. 64, 103–112.
sented the potential to free cooling considering Allowable A2 limits doi:10.1016/j.enbuild.2013.04.013.
onwards. Lee, K.-P., Chen, H.-L., 2013b. Analysis of energy saving potential of air-side free
cooling for data centers in worldwide climate zones. Energy Build. 64, 103–112.
doi:10.1016/j.enbuild.2013.04.013.
Declaration of Competing Interest Malkamäki, T., Ovaska, S.J., 2012. Solar energy and free cooling potential in European
data centers. Proc. Comput. Sci. 10, 10 04–10 09. doi:10.1016/j.procs.2012.06.138.
The authors declare that they have no known competing finan- Marcinichen, J.B., Olivier, J.A., Thome, J.R., 2012. On-chip two-phase cooling of dat-
acenters: cooling system and energy recovery evaluation. Appl. Therm. Eng. 41,
cial interests or personal relationships that could have appeared to 36–51. doi:10.1016/j.applthermaleng.2011.12.008.
influence the work reported in this paper. Oró, E., Depoorter, V., Garcia, A., Salom, J., 2015. Energy efficiency and renewable
energy integration in data centres. Strategies and modelling review. Renew. Sus-
tain. Energy Rev. 42, 429–445. doi:10.1016/j.rser.2014.10.035.
Acknowledgments Rong, H., Zhang, H., Xiao, S., Li, C., Hu, C., 2016. Optimizing energy consumption for
data centers. Renew. Sustain. Energy Rev. 58, 674–691. doi:10.1016/j.rser.2015.
Amado acknowledges Coordenação de Aperfeiçoamento de Pes- 12.283.
Santos, A.F., Gaspar, P.D., Souza, H.J.d., 2019. Evaluation of the heat and en-
soal de Nível Superior (CAPES) for his MSc grant; Smith Schneider
ergy performance of a datacenter using a new efficiency index: energy us-
acknowledges Conselho Nacional de Desenvolvimento Científico e age effectiveness design - eued. Braz. Arch. Biol. Techonol. 62. doi:10.1590/
Tecnológico for his research grant (CNPq-PQ 301619/2019-0). 1678- 4324- smart- 2019190021.
Statista, 2019. Worldwide it Spending Data Center Systems 2012–2020 Statis-
tic. Available at: <https://www.statista.com/statistics/496373/datacenter-
References
colocation-revenueworldwide/>, Statista, 2019.
Shende, S., 2015. Colocation Market by Type (retail Colocation and Wholesale Colo-
Amoabeng, K.O., Choi, J.M., 2016. Review on cooling system energy consumption cation), End-User (Large Enterprises and Small and Medium Enterprises) and
in internet data centers. Int. J. Air-Cond. Refrig. 24 (04), 1630 0 08. doi:10.1142/ Industry Vertical (BFSI, Government & Public Sector, Telecom & IT, healthcare
S201013251630 0 081. & Life Sciences, Energy) – Global Opportunity Analysis and Industry Forecast,
ASHRAE, 2015. ASHRAE Thermal Guidelines for Data Processing Environments, 2014–2020.
fourth American Society of Heating, Refrigerating and Air-Conditioning Engi- Siriwardana, J., Jayasekara, S., Halgamuge, S.K., 2013. Potential of air-side economiz-
neers, Inc, Atlanta, GA. ers for data center cooling: a case study for key Australian cities. Appl. Energy
ASHRAE, 2016a. ASHRAE Handbook: HAVC Systems and Equipment, SI Edition. 104, 207–219. doi:10.1016/j.apenergy.2012.10.046.
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc, The Green Grid. Updated air-side free cooling maps: the impact of ASHRAE 2011 Al-
Atlanta, GA. lowable Ranges White Paper #46. 2012. Available at https://datacenters.lbl.gov/
ASHRAE, 2016b. Data Center Power Equipment Thermal Guidelines and Best Prac- sites/default/files/WP46UpdatedAirsideFreeCoolingMapsTheImpactofASHRAE2011
tices. Technical Report. American Society of Heating, Refrigerating and Air-Con- AllowableRanges.pdf.
ditioning Engineers, Inc. The Green Grid, 2009. Air-Side Free Cooling Maps.
Avgerinou, M., Bertoldi, P., Castellazzi, L., 2017. Trends in data centre energy con- Wan, F., Swenson, D., Hillstrom, M., Stayer, C., Pommerenke, D., 2013. The effect of
sumption under the european code of conduct for data centre energy efficiency. humidity on static electricity induced reliability issues of ICT equipment in data
Energies 10 (10), 1470. doi:10.3390/en10101470. centers – motivation and setup of the study. ASHRAE Trans. 119, 341–358.
Beaty, D.L., Quirk, D.P., Morrison, F.T., 2019. Designing data center waterside econo- Yuventi, J., Mehdizadeh, R., 2013. A critical analysis of power usage effectiveness
mizers. ASHRAE J. 57–61. and its use in communicating data center energy consumption. Energy Build.
Belizário, A.C., 2018. Avaliação Energética e Financeira para Utilização de Sistemas 64, 90–94.
de ar Condicionado Acionados por Energia Solar em Ambientes de Missão Zhang, H., Shao, S., Xu, H., Zou, H., Tian, C., 2014. Free cooling of data centers: a
Crítica Para Diferentes Regiões Climáticas. Universidade de São Paulo, São Paulo review. Renew. Sustain. Energy Rev. 35, 171–182. doi:10.1016/j.rser.2014.04.017.
Ph.D. thesis.

180

You might also like