Professional Documents
Culture Documents
Conductor
Considerations
A Conductor
Chapter
number 3of Considerations
facts are considered when determining ampacity of three single-insulated conductors rated
the amount of current a conductor can carry safely 0–2000 volts, 150° to 250° C, in a raceway or cable
and economically. Conductor size is basic for deter- based on an ambient air temperature of 40°C. Table
mining conductor ampacity, or current-carrying ca- 310.19 covers the ampacities of single-insulated
pacity, as are conductor material and type of conductors rated 0–2000 volts, 150° to 250°C, in free
insulation. Examples of common conductor types air based on ambient air temperature of 40°C. In
are shown in Figure 3–1. (See Article 100, “Defini- each case, another determining factor is the ambient
tions.”) These three facts are used in the NEC® for temperature in which the conductors are installed.
making the determination. NEC® 310.2 states that NEC® 310.15(A) through 310.15(C) and Tables
conductors shall be insulated, except where bare or 310.15(B)(2) and 310.15(B)(6) list other determin-
covered conductors are permitted elsewhere in the ing factors, which may limit conductor ampacity to
NEC®. Conductor material, when referred to in the values less than those given in these tables. Other
NEC®, shall be of aluminum, copper-clad alumi- factors to consider are the number of conductors in
a raceway, whether the load is continuous or inter-
num, or copper unless otherwise specified. Where
mittent, the physical length of the circuit, and the
installed in raceways, conductors of trade size 8
ambient air temperature where the conductor is lo-
AWG and larger shall be stranded. The minimum
cated. All these factors are discussed in these sec-
size of conductors is listed in Table 310.5 of the
tions and must be considered. Tables 310.61 through
NEC®. Conductor material and size and the insula-
310.84 cover the allowable ampacities for medium-
tion are three of the determining factors in develop-
or high-voltage cables up to 35,000 volts.
ing the 0- to 2000-volt tables. These tables are
310.16 through 310.19.
Table 310.16 covers the ampacity of insulated
AMBIENT TEMPERATURE
conductors rated 0–2000 volts, 60° to 90° C, with not
more than three conductors in a raceway or cable or CONSIDERATIONS
in the earth (directly buried), based on an ambient NEC® 310.10 states that no conductor shall be
temperature of 30°C (86°F). Table 310.17 covers the used in such a manner that its operating temperature
ampacity of single-insulated conductors rated will exceed that designated for the type of insulated
0–2000 volts in free air based on an ambient air conductor involved, and in no case shall conductors
temperature of 30°C (86°F). Table 310.18 covers the be associated together in such a way, with respect to
27
28 Chapter 3
Ampacities
For ambient temperature other than 30°C (86°F), multiply the ampaci-
ties shown above by the appropriate factor shown below.
Ambient
Temp. °C Temperature Rating of Conductor
*For dry and damp locations only. See 75° column for wet locations.
testing agency directories, product testing standards, termination ratings for the equipment involved in the
and manufacturers’ literature, but most do not con- circuit.
sult these sources until it is too late.
Example: Using a circuit breaker with
75°C terminations and a 150-ampere load, if a
Why Are Temperature Ratings Important?
THHN (90°C) conductor is selected for the job,
Conductors carry a specific temperature rating based from Table 310.16 select a conductor that will
on the type of insulation employed on the conductor. carry the 150 amperes. Although Type THHN
Common insulation types can be found in Table has a 90°C ampacity rating, the ampacity from
310.13 of the NEC®, and corresponding ampacities the 75°C column must be selected because the
can be found in Table 310.16. circuit-breaker termination is rated at 75°C.
Looking at the table, a 1/0 copper conductor is
acceptable. The installation would be as shown
Example: A 1/0 copper conductor ampac- in Figure 3–3, with proper heat dissipation at
ity based on different conductor insulation the termination and along the conductor length.
types: If the temperature rating of the termination had
not been considered, a 1 AWG conductor based
on the 90°C ampacity may have been selected,
Temperature
Insulation Type Rating Ampacity which may have led to overheating at the termi-
nation or premature opening of the overcurrent
TW 60°C 125 amperes
THW 75°C 150 amperes
device because of the smaller conductor size.
THHN 90°C 170 amperes (See Figure 3–4.)
Although the wire size has not changed In the example above, a conductor with a 75°C
(1/0 Cu) the ampacity has changed due to the insulation type (THW, RHW, USE, and so forth) also
temperature rating of the insulation on the con- would be acceptable because the termination is rated at
ductor. Higher-rated insulation allows a smaller 75°C. A 60°C insulation type (TW or perhaps UF) is not
conductor to be used at the same ampacity as a acceptable because the temperature at the termination
larger conductor with lower-rated insulation, could rise to a value greater than the insulation rating.
and, as a result, the amount of copper and even
the number of conduit runs needed for the job
may be reduced. General Rules for Application
When applying equipment with conductor termina-
tions, the following two basic rules apply:
One common misapplication of conductor
temperature ratings occurs when the rating of the • Rule 1 [NEC® 110.14(C)(1)(a)]—Termination
provisions for equipment rated 100 am-
equipment termination is ignored. Conductors
peres or less or equipment that is marked
must be sized by considering where they will ter- for 14 to 1 AWG conductors are rated for
minate and how that termination is rated. If a ter- use with conductors rated 60°C. (See Fig-
mination is rated for 75°C, this means the ure 3–5.)
temperature at that termination may rise to 75°C • Rule 2 [NEC® 110.14(C)(1)(b)]—Termina-
when the equipment is loaded to its ampacity. If tion provisions for equipment rated greater
60°C insulated conductors were employed in this than 100 amperes or equipment termina-
example, the additional heat at the connection tions marked for conductors larger than 1
above the 60°C conductor insulation rating could AWG are for use with conductors rated
result in failure of the conductor insulation. 75°C. (See Figure 3–6.)
When a conductor is selected to carry a spe- There are exceptions to the rules. Two impor-
cific load, the user/installer or designer must know tant exceptions are:
Conductor Considerations 31
1/0 Cu 90˚C or
75˚C Insulation
Circuit
150 Amperes breaker 150 Amperes
Conductor properly
sized based on termination
75˚C Rated terminations
rating of circuit breaker
Figure 3–3
1 AWG Cu
90˚C Insulation
Circuit
breaker 150 Amperes
150 Amperes
Figure 3–4
20
20-ampere conductor
based on 60˚C ampacity
Figure 3–5
32 Chapter 3
125-Ampere conductor
125-Ampere based on 75˚C ampacity
Equipment
Circuit breaker
Breaker terminations
rated and marked for 75˚C
Figure 3–6
listed distribution or utilization equipment that is terminate. Significant changes in the product testing/
listed and identified for the use of 90°C wire at its listing standards also would have to occur.
90°C ampacity. This includes distribution equip- A final note about equipment is that, generally,
ment, wiring devices, transformers motor control de- equipment requiring the conductors to be terminated
vices, and utilization equipment such as HVAC, in the equipment has an insulation rating of 90°C but
motors, and luminaires (light fixtures). Installers and has an ampacity based on 75°C or 60°C. This type of
designers who do not know this fact have been faced equipment might include 100%-rated circuit break-
with jobs that do not comply with the NEC®, and jobs ers, fluorescent luminaires (lighting fixtures), and so
have been turned down by the electrical inspectors. on, and will include a marking to indicate such a
requirement. Check with the equipment manufac-
Example: A 90°C wire can be used at turer to see if there are any special considerations.
its 90°C ampacity (see Figure 3–7). Note
that the 2 AWG 90°C-rated conductor does
not terminate directly in the distribution Higher-Rated Conductors and Derating
equipment but in a terminal or tap box with Factors
90°C-rated terminations. One advantage to conductors with higher insulation
ratings is noted when derating factors are applied.
Frequently, manufacturers are asked when distri- Derating factors can be required because of the
bution equipment will be available with terminations number of conductors in a conduit, higher ambient
that will permit 90°C conductors at the 90°C ampacity. temperatures, or possibly internal design require-
The answer is complex, as such equipment requires not ments for a facility. By beginning the derating proc-
only significant equipment redesign (to handle the ad- ess at the conductor ampacity based on the higher
ditional heat) but also coordination of the downstream insulation value, upsizing the conductors to compen-
equipment where the other end of the conductor will sate for the derating may not be required.
2 AWG
90˚C Insulated
conductors sized
based on 90˚C
ampacity
Tap box enclosure with
termination lugs or splices
rated for 90˚C terminations
Figure 3–7
34 Chapter 3
For the following example of this derating proc- required, a 3/0 copper conductor would have
ess, consider these two positions: met these requirements.
1. The ampacity value determined after apply- Using a 90°C conductor such as THHN:
ing the derating factors must be equal to or 250-kcmil copper has a 90°C ampacity of
less than the ampacity of the conductor, 290 amperes. Using the factors from above, the
based on the temperature limitations at its calculations are:
terminations.
2. The derated ampacity becomes the allow- 290 × .8 × .91 = 211 amperes
able ampacity of the conductor, and the con-
ductor must be protected against overcurrent 211 amperes is less than the 75°C ampacity of a
in accordance with this allowable ampacity. 250-kcmil copper conductor (255 amperes), so
the 211 amperes would now be the allowable
Example for the derating process. Assume ampacity of the 250-kcmil conductor. If the
a 480Y/277 VAC, 3-phase, 4-wire feeder circuit calculation resulted in a number larger than the
to a panelboard supplying 200 amperes of fluo- 75°C ampacity, the actual 75°C ampacity would
rescent lighting load, and assume that the con- have been required to be used as the allowable
nectors will be in a 40°C ambient temperature. ampacity of the conductor. This is critical because
Also, assume the conductors originate and ter- the terminations are rated at 75°C.
minate in equipment with 75°C terminations.
1. Because the phase and neutral conductors Note: The primary advantage to using 90°C con-
will be in the same conduit, the issue of ductors is exemplified by this example. The con-
conduit fill must be considered. The neutral ductor is permitted to be reduced by one size
(300 kcmil to 250 kcmil) and still accommodate all
must be considered to be a current-carrying
required derating factors for the circuit.
conductor because it is supplying electric-
discharge lighting. (NEC®310.15(B)(4))
2. With four current-carrying conductors in In summary, when using 90°C wire for derating
the raceway, an 80% reduction in the con- purposes, begin by derating at the 90°C ampacity.
ductor ampacity based on four to six cur- Compare the result of the calculation with the am-
rent-carrying conductors in the raceway pacity of the conductor based on the termination
applies. (NEC® 310.15(B)(2)) rating (60°C or 75°C). The smaller of the two num-
3. The correction factors at the bottom of bers then becomes the allowable ampacity of the
Table 310.16 also must be applied. And conductor. Note that if the load dictates the size of the
adjustment of .88 for 75°C and .91 for required overcurrent device (i.e., continuous load ×
90°C is required where applicable. 125%), then the conductor allowable ampacity must
Now the calculations: be protected by the required overcurrent device. (See
NEC® 240.3 that permits the conductor to be pro-
Using a 75°C conductor such as THWN: tected by the next higher standard size overcurrent
300-kcmil copper has a 75°C ampacity of device as per 240.6.) This may require moving to a
285 amperes. Using the factors from above, the larger conductor size and beginning the derating. In
calculations are: the example, if the 200 amperes of load were con-
tinuous, a 250-ampere overcurrent device would be
285 × .80 × .88 = 201 amperes
required. The 201 or 211 amperes from the calcula-
Thus, 201 amperes is now the allowable tions would not be protected by the 250-ampere
ampacity of the 300-kcmil copper conductor overcurrent device, so we would be required to move
for this circuit. If the derating factors for con- to a larger conductor meeting these requirements to
duit fill and ambient temperatures had not been begin the derating process.
Conductor Considerations 35
must have sufficient working space around electrical copper conductors having different temperature rat-
equipment of 600 volts nominal or less; that we must ings as given in NEC® Table 310.16 are as follows:
have clearances in front and above; that we must
have headroom to work on the equipment and proper Conductor Temperature Rating
illumination; and that all live parts must be guarded (Size kcmil) 60°C 75°C 85°C 90°C
against accidental contact. Article 110 reminds us (140°F) (167°F) (185°F) (194°F)
that warning signs must be placed and that electrical 250 215 255 275 290
500 320 380 415 430
equipment must be protected from physical damage.
1000 455 545 590 615
NEC® 110.22 states that each disconnecting means
for motors and appliances, and service, feeders, or
Although 500-kcmil conductors have twice the
branch-circuits at the point where these originate,
cross-sectional area of 250-kcmil conductors, their
must be legibly identified to indicate their purpose
ampacity is only about half again as much. The am-
and that the identifying markings must be suffi-
pacities of 1000-kcmil conductors are only about
ciently durable to withstand the environment in-
45% more than 500-kcmil conductors. The size of
volved. Where circuits and fuses are installed with a
the conductors, particularly for large ampacities, has
series combination rating “Caution—Series Rated
a definite bearing on the efficient use of both conduc-
System,” the equipment enclosure shall be legibly
tor material and raceways. Because large conductors
marked in the field to indicate the equipment has
are less flexible than small ones, they are more diffi-
been applied with a series combination rating. Over
cult to handle and pull through raceways, particularly
600-volts-requirements are found in Part II of Article
those having offsets and bends. Paralleling of two or
110. These requirements are specific about entrance
more smaller conductors per phase allows higher
and access to working space, guarding barriers, en-
ampacities than could be obtained with a single large
closures for electrical installations, and separation
conductor. Even though allowable raceway fill for
from other circuitry. Over-600-volts installations
multiple conductors is less than a single conductor
must be located in locked rooms or enclosures, ex-
(NEC® Chapter 9, Table 1), there is often no need to
cept where under the observation of qualified per-
use a larger raceway to obtain the needed ampacity.
sons at all times. Table 110.34(E) covers the
Conductors carry loads continuously; however,
elevation of unguarded live parts above working ®
NEC Article 210 Part II and 220.19 generally limit
space for nominal voltages 601 and above.
the conductors to be loaded to no more than 80% of
their rated ampacities. This limitation ensures over-
CONDUCTOR AMPACITY current devices are not subjected to loads of more
than 80% of their rating. Unlike the conductors,
ADJUSTMENT FACTORS
overcurrent devices may open prematurely if fully
The NEC® defines ampacity in Article loaded for long periods, unless specifically designed
100—Definitions as “The current in amperes a con- to carry full current rating continuously. Where over-
ductor can carry continuously under the conditions current devices in their enclosures are listed for con-
of use without exceeding its temperature rating.”* tinuous operation at 100% load, this 80% correction
Ampacity is used with this meaning throughout this factor does not apply to panelboards, overcurrent
manual in referring to wire and conductor sizes; the devices, or conductors.
NEC® abbreviations of cmil for circular mil and
kcmil for thousand circular mils are used. These
supersede the abbreviations of cm and mcm, respec-
ALLOWABLE CONDUCTOR FILL
tively, though the latter still can be found on many
terminals and conductors made prior to 1990. The (More than Three Conductors
ampacity of a conductor does not increase in direct in a Raceway)
proportion to its size. The ampacity ratings of three Where the number of conductors in a raceway or
cable exceed three, or where single conductors or mul-
*Reprinted with permission from NFPA 70-2002. ticonductor cables are stacked or bundled without
Conductor Considerations 37
(2) Selection of Ampacity. Where more than one calculated or tabulated ampacity could
apply for a given circuit length, the lowest value shall be used.
Exception: Where two different ampacities apply to adjacent portions of a circuit, the higher
ampacity shall be permitted to be used beyond the point of transition, a distance equal to 3.0 m
(10 ft) or 10 percent of the circuit length figured at the higher ampacity, whichever is less.
FPN: See 110.14(C) for conductor temperature limitations due to termination provisions.
(B) Tables. Ampacities for conductors rated 0 to 2000 volts shall be as specified in the
Allowable Ampacity Tables 310.16 through 310.19 and Ampacity Tables 310.20 through 310.23
as modified by (1) through (6).
FPN: Tables 310.16 through 310.19 are application tables for use in determining conductor
sizes on loads calculated in accordance with Article 220. Allowable ampacities result from
consideration of one or more of the following:
(1) Temperature compatibility with connected equipment, especially the connection points.
(2) Coordination with circuit and system overcurrent protection.
(3) Compliance with the requirements of product listings or certifications. See 110.3(B).
(4) Preservation of the safety benefits of established industry practices and standardized
procedures.
(1) General. For explanation of type letters used in tables and for recognized sizes of
conductors for the various conductor insulations, see 310.13. For installation requirements, see
310.1 through 310.10 and the various articles of this Code. For flexible cords, see Tables 404.04,
400.5(A), and 400.5(B).
(a) More than Three Current-Carrying Conductors in a Raceway or Cable. Where the
number of current-carrying conductors in a raceway or cable exceeds three, or where single
conductors or multiconductor cables are stacked or bundled longer than 600 mm (24 in.) without
maintaining spacing and are not installed in raceways, the allowable ampacity of each conductor
shall be reduced as shown in Table 310.15(B)(2)(a).
38 Chapter 3
FPN: See Annex B, Table B.310.11, for adjustment factors for more than three current-
carrying conductors in a raceway or cable with load diversity.
Exception No. 1: Where conductors of different systems, as provided in 300.3, are installed
in a common raceway or cable, the derating factors shown in Table 310.15(B)(2)(a) shall apply to
the number of power and lighting conductors only (Articles 210, 215, 220, and 230).
Exception No. 2: For conductors installed in cable trays, the provisions of 392.11 shall apply.
Exception No. 3: Derating factors shall not apply to conductors in nipples have a length not
exceeding 600 mm (24 in.)
Exception No. 4: Derating factors shall not apply to underground conductors entering or
leaving an outdoor trench if those conductors have physical protection in the form of rigid metal
conduit, intermediate metal conduit, or rigid nonmetallic conduit having a length not exceeding
3.05 m (10 ft) and the number of conductors does not exceed four.
Exception No. 5: Adjustment factors shall not apply to Type AC cable or to Type MC cable
without an overall outer jacket under the following conditions:
(a) Each cable has not more than three current-carrying conductors
(b) The conductors are 12 AWG copper
(c) Not more than 20 current-carrying conductors are bundled, stacked, or supported on
"bridle rings"
A 60 percent adjustment factor shall be applied where the current-carrying conductors in
these cables that are stacked or bundled longer than 600 mm (24 in.) without maintaining
spacing exceeds 20.
(b) More than One Conduit, Tube, or Raceway. Spacing between conduits, tubing, or
raceways shall be maintained.
Percent of Values in
Tables 310.16 through 310.19
Number of Current- as Adjusted for Ambient
Carrying Conductors Temperature if Necessary
4–6 80
7–9 70
10 – 20 50
21 – 30 45
31 – 40 40
41 and above 35
(3) Bare or Covered Conductors. Where bare or covered conductors are used with
insulated conductors, their allowable ampacities shall be limited to those permitted for the
adjacent insulated conductors.
Conductor Considerations 39
(a) A neutral conductor that carries only the unbalanced current from other conductors of the
same circuit shall not be required to be counted when applying the provisions of 310.15(B)(2)(a).
(b) In a 3-wire circuit consisting of two phase wires and the neutral of a 4-wire, 3-phase
wye-connected system, a common conductor carries approximately the same current as the
line-to-neutral load currents of the other conductors and shall be counted when applying the
provisions of 310.15(B)(2)(a).
(c) On a 4-wire, 3-phase wye circuit where the major portion of the load consists of nonlinear
loads, harmonic currents are present in the neutral conductor; the neutral shall therefore be
considered a current-carrying conductor.
(6) 120/240-Volt, 3-Wire, Single-Phase Dwelling Services and Feeders. For dwelling
units, conductors, as listed in Table 310.15(B)(6), shall be permitted as 120/240-volt, 3-wire,
single-phase service-entrance conductors, service lateral conductors, and feeder conductors
that serve as the main power feeder to a dwelling unit and are installed in raceway or cable with
or without an equipment grounding conductor. For application of this section, the main power
feeder shall be the feeder(s) between the main disconnect and the lighting and appliance
branch-circuit panelboard(s). The feeder conductors to a dwelling unit shall not be required to be
larger than their service-entrance conductors. The grounded conductor shall be permitted to be
smaller than the ungrounded conductors, provided the requirements of 215.2, 220.22, and
230.42 are met.
Conductor
(AWG or kcmil)
Aluminum or Service or
Copper-Clad Feeder Rating
Copper Aluminum (Amperes)
4 2 100
3 1 110
2 1/0 125
1 2/0 150
1/0 3/0 175
2/0 4/0 200
3/0 250 225
4/0 300 250
250 350 300
350 500 350
400 600 400
TC − (TA + ∆TD )
I=
RDC(1 + YC )RCA
Where:
TC = Conductor temperature in degrees Celsius (°C)
TA = Ambient temperature in degrees Celsius (°C)
∆TD = Dielectric loss temperature rise
RDC = dc resistance of conductor at temperature TC
YC = Component ac resistance resulting from skin effect and proximity effect
RCA = Effective thermal resistance between conductor and surrounding ambient
maintaining spacing and are not installed in race- Example: Determine the ampacity of three
ways, the maximum allowable load current on each 1/0 AWG, three 2 AWG, and six 4 AWG Type
conductor must be reduced as shown in the box that THW conductors in a 3-phase, 3-wire delta sys-
follows. tem (no neutral wire) for operation at a tempera-
The table is based on the following formula: ture of 40°C (104°F). The maximum operating
temperature for THW wire from NEC® Table
A2 = (the square root of) 0.5N/E × (A1)
310.13 is 75°C (104°F). According to Table
where A1 = table ampacity multiplied by factor from 310.15(B)(2), ampacities must be reduced to 50%
Table 310.15(B)(2)(a), N = total number of conductors of the values listed in the tables. According to the
used to obtain factor from Table 310.15(B)(2)(a), E = Correction Factors below Table 310.16, ampaci-
desired number of energized conductors, and A2 = ties also must be reduced by a correction factor of
ampacity limit for energized conductors. 88% for ambient temperature. Derating factors
These reductions are to minimize heat buildup are as follows:
in the raceway, stack, bundle, or cable that may tend Wire Ampacity × Factor for × Factor for = Net
to damage the insulation over a long period of time. Size More than Temperature Ampacity
3 over 30°C
Allowable ampacities of multiple conductors in a Conductors
raceway after applying these derating factors, as they in a
Raceway
are called, are shown in the preceding table. Addi-
1/0 150 50% .88 66
tional correction factors may be necessary to avoid
2 115 50% .88 50.6
prolonged overheating of conductors and insulation 4 85 50% .88 37.4
from outside sources.
The following example illustrates the use of the NEC® 310.15 states that the ampacity for con-
derating and temperature correction factors: ductors rated 0–2000 volts shall be as specified in
Conductor Considerations 41
Tables 310.16 through 310.21 and their accompany- a matter of information, the NEC® states in FPNs, as
ing notes. The ampacity for solid dielectric insulated listed above, the following: “Conductors for branch
conductors rated 2001 through 35,000 volts shall be circuits or feeders as defined in Article 100 should be
as specified in Tables 310.69 through 310.84 and sized to prevent voltage drop exceeding 3% at the
their accompanying notes. However, under engineer- farthest outlet of power, heating, and luminaire
ing supervision, ampacity may be calculated by the (lighting) loads or combinations of such loads, and
following general formula. Examples of these calcu- where the maximum total voltage drop on both feed-
lations and the formula applications can be found in ers and branch circuits to the farthest outlet does not
Annex B of the 2002 NEC®. However, the annex is exceed 5% will provide reasonable efficiency of op-
not a part of the requirements of the NEC® and is eration.”* This means that the voltage drop must be
included for informational purposes only. Therefore, fairly equally divided between the feeder and the
the AHJ may determine the application of this mate- branch-circuit conductors. If the branch-circuit volt-
rial for complying with NEC® 310.15. age drop is 3% of the rated voltage, the voltage drop
in the feeder should not exceed 2%. A voltage drop
greater than 5% of line voltage can result in a vari-
VOLTAGE DROP ation greater than 10% from designed operating volt-
age, as in the case of a 240-volt motor connected to a
The resistance, or impedance, of conductors 208-volt branch-circuit having an excessive voltage
may cause a substantial difference between the volt- drop.
age measured at the service entrance of a facility and Available heat from an electric heating appli-
the point of use at the equipment utilizing the said ance is proportional to the square of the applied
voltage. It is necessary to minimize the voltage drop voltage. If a heating unit is rated at 240 volts and the
in conductors to ensure good service. Excessive volt- terminal voltage is 5% less, or 228 volts, the heat
age drop impairs the operation of electrical equip- generated at the appliance is reduced by 10%. At a
ment. Lower-than-rated voltage results not only in 10% reduction, or 216 volts, the heat generated at the
decreased light output from fluorescent lighting, but appliance is reduced by nearly 20%.
also may cause starting and operating difficulties. It is important, therefore, to take proper precau-
The total lumen output for a 2-lamp, rapid-start fluo- tions to avoid excessive voltage drop in all types of
rescent luminaire (fixture) in general varies about circuits, whether for luminaires (lighting), power, or
1% for each percent change in line voltage. A similar heating. The basic formula for determining voltage
voltage drop of 1% causes about 3 1/2% loss in drop in a 2-wire, dc circuit; a 2-wire, single-phase
lumen output for filament-type lamps. circuit; or a 3-wire, single-phase, alternating-current
Although motors generally are designed for a (ac) circuit with a balanced load at 100% power
10% overall voltage variation, they operate more factor (where reactance is negligible) is:
efficiently at nameplate voltages. Excessive voltage
drop (more than 5% of the line voltage) can cause
serious motor overheating. If the overheating is 2×R×L×I
Voltage Drop =
serious enough, it could cause a fire if the overcur- Circular Mils
rent or thermal protective devices fail to operate
properly. where R = resistivity of conductor material (12 ohms
Although the NEC® does not make mandatory per circular mil foot for copper, 19 ohms per circular
requirements to govern voltage drop, it would be a mil foot for aluminum); L = one-way length of cir-
violation of 110.3(B) to supply voltage to equipment cuit (ft), and I = current in one conductor (amperes)
at less than the nameplate rating. NEC® 210.19 in- (see Table A-15 in annex).
cludes a fine print note (FPN 4), which includes For 3-phase, 4-wire, ac circuits, the voltage drop
guides to the allowable voltage drop in branch- between 1-phase wire and the neutral is one-half of
circuit conductors; NEC® 215.2 includes a similar
FPN for feeder conductors. Adherence to these FPNs
will provide a reasonable efficiency of operation. As *Reprinted with permission from NFPA 70-2002.
42 Chapter 3
Impedance Factors for Finding Voltage Drop in Copper Conductors ing formula does not apply. For example, where mo-
tors are a major part of a circuit load, the power
Single-phase AC, Power Factor
Wire
factor may be considerably less than one. Determin-
Size
100 90 80 70 60 DC
ing voltage drop in circuits having a load of less than
AWG
unity power factor requires a more complicated for-
14 .5880 .5360 .4790 .4230 .3650 .5880
mula. Figure 3–8 lists impedance factors developed
12 .3690 .3330 .3030 .2680 .2320 .3690
10 .2320 .2150 .1935 .1718 .1497 .2320 from this formula for single-phase circuits.
8 .1462 .1373 .1248 .1117 .0981 .1462 For 3-phase circuits, the voltage drop may be
computed by multiplying the single-phase voltage
6 .0918 .0882 .0812 .0734 .0653 .0918
drop by .86. Should the voltage drop so determined
4 .0578 .0571 .0533 .0489 .0440 .0578
2 .0367 .0379 .0361 .0337 .0309 .0363 be greater than the suggested desirable percentage of
1 .0291 .0311 .0299 .0284 .0264 .0288 the circuit voltage, a larger-size conductor should be
used, the circuit length should be shortened, or the
1/0 .0233 .0257 .0252 .0241 .0227 .0229
circuit load should be reduced until the voltage drop
2/0 .0187 .0213 .0212 .0206 .0196 .0181
3/0 .0149 .0179 .0181 .0177 .0171 .0144 is within the required or desired limits.
4/0 .0121 .0152 .0156 .0155 .0151 .0114
Example: Find the voltage drop in a 300-
Wire
Size, ft (91.4-m) circuit using 4/0 AWG Type TW
kcmil copper conductors in a 3-phase circuit. Allow-
250 .0102 .0136 .0143 .0143 .0141 .0097
300 .0086 .0121 .0128 .0131 .0130 .0081
able ampacity (NEC® Table 310.16) is 195;
350 .0074 .0109 .0118 .0122 .0122 .0069 power factor, 80%. Voltage drop = 195 × 3.00 ×
400 .0066 .0101 .0111 .0115 .0116 .0060 0.0l56 × 0.86 = 7.9 volts.
500 .0054 .0089 .0099 .0105 .0108 .0048
600 .0047 .0083 .0093 .0099 .0103 .0040
700 .0041 .0077 .0088 .0094 .0098 .0034 CONDUCTORS RUN IN PARALLEL
750 .0039 .0075 .0086 .0093 .0097 .0032
When large ampacities are required, the use of
800 .0037 .0073 .0084 .0091 .0095 .0030 parallel conductors should be carefully investigated.
900 .0034 .0069 .0081 .0088 .0093 .0027
1000 .0031 .0067 .0079 .0086 .0091 .0021
Conductors larger than 500 kcmil generally are con-
sidered questionable from the standpoint of ease of
Voltage drop in two wires of a single-phase ac or dc circuit is equal to installation and operating economies. NEC® 310.4
current × length of run in hundreds of ft × impedance factor. states that conductors of size 1/0 or larger compris-
Impedance factors in table multiplied by 0.86 will give phase-to-phase ing each phase, neutral, or equipment grounding
voltage drop for 3-phase ac circuits.
conductor are permitted to be connected in parallel
(electrically joined to form a single conductor) only
Figure 3–8 Impedance factors for voltage drop
if the following requirements are met: all parallel
(Courtesy of American Iron & Steel Institute)
conductors are of the same length, are of the same
conductor material, have the same circular mil area,
have the same insulation type, and are terminated in
the same manner. Although paralleling of conductors
the value derived from this formula. For 3-phase
may prove more practical and economical than using
circuits at 100% power factor, the voltage drop be-
one larger conductor, the voltage drop in parallel
tween any 2-phase wires is 0.866 × the voltage drop
conductors in a 3-phase, ac circuit at 100% power
calculated by the formula. factor may be greater than the voltage drop in a
In circuits where each phase and neutral con- single large conductor. In a circuit at 90% power
ductor consists of two or more wires, the voltage factor, the voltage drop is about equal for single and
drop is determined by using the current in only one parallel conductors.
wire of a phase conductor and the neutral. For loads If all parallel conductors are to be installed in a
of other than 100% (unity) power factor, the preced- single raceway, as in Figure 3–9 and Figure 3–10, it
Conductor Considerations 43
Where conductors are run in parallel in One trade size 3 (78) Rigid or IMC Steel Conduit
multiple raceways or cables as permitted by
NEC® 310.4, the equipment grounding conduc-
tor when required shall be run in parallel. Each Three 500-kcmil conductors
500-ft (150m) run
parallel equipment grounding conductor shall
Ampacity 320
be sized based on the overcurrent device. dc resistance 0.0216 ohms/1000 ft (300m)
Factor for ac 1.13
Example: With a 1000-ampere overcur-
Voltage drop = 320 ∞ 500 ∞ 0.0216/100 ∞ 1.13 = 3.9 volts
rent device protecting a feeder run in three indi- per conductor (7.8 volts for two conductors)
vidual nonmetallic conduits or Type MC cable,
Table 250.122 requires that a 2/0 copper or 4/0 Two trade size 2 (53) Rigid or IMC Steel Conduit
aluminum equipment grounding conductor be
run in each conduit or cable. Note: Most cable
manufacturers include a reduced equipment
grounding conductor, and where cable is speci- Three 3/0 AWG 60 C conductors
fied the cable may have to be special-ordered to in each 500-ft (150m) run
get the properly sized equipment grounding. Ampacity 165
dc resistance 0.642 ohms/1000 ft (300m)
Factor for ac 1.04
Voltage drop = 320 ∞ 500 ∞ 0.642/100 ∞ 1.04 = 5.5 volts
is necessary to derate them as per NEC® Article 310, per conductor (11.0 volts for two conductors)
Table 310.15(B)(2), when more than three conduc- The voltage drops are computed for loads at 100%
power factor. The differences decrease as power
tors are installed in a raceway. Hence, it is better in factors become less than 100%.
many cases to use two or more smaller raceways.
Therefore, when conductors having different insula- Figure 3–9 Voltage drop in single and paralleled con-
tion materials are added to conductors already in a ductors
raceway, the new conductors must have an equal or
higher temperature rating than the existing ones, but
the lower ampacity rating of the two insulation types system with two wires connected in parallel for each
must be used for all conductors, as per NEC® 300.3. phase and for the neutral, requiring two raceways
When more than one raceway is used, NEC® with four wires in each. Where two or more raceways
300.3(B) applies, with exceptions stating that each enclose conductors in parallel, they are required by
raceway shall contain all phase conductors, the neu- NEC® 310.4 to have the same physical charac-
tral, and the equipment grounding conductor if pre- teristics. (Otherwise, the raceways enclosing the dif-
sent. There is another exception in NEC® 300.5(I) ferent conductors might have a different electrical
that permits an isolated phase in nonmetallic race- characteristic, such as unequal inductive reactance.)
ways. This requirement is clarified in 300.20: Where Currents in the conductors are in individual reac-
conductors carrying alternating current are installed tance, and currents in the conductors in the individ-
in metal enclosures or metal raceways, they are ar- ual raceways would not be in phase at their common
ranged so as to avoid heating the surrounding metal terminal. This condition must be avoided for proper
by induction. operation of multiphase equipment such as motors.
To accomplish this, all phase conductors and, Inductive heating caused by improper installation of
where used, the neutral and all equipment grounding conductors in steel raceways and enclosures is dis-
conductors are grouped together. For example, if cussed in Chapter 5.
three wires are in parallel for each phase, three race- Although derating factors will provide for safe
ways are required. This would result in three wires in installation of large numbers of conductors in a race-
each raceway for a single-phase, 3-wire system, and way, there are some drawbacks to this practice. The
four wires in each raceway for a 3-phase, 4-wire more conductors enclosed in a raceway, the greater
system. Figure 3–11 illustrates a 3-phase, 4-wire the chance of a serious breakdown. Where continuity
44 Chapter 3
C A
a. Single raceway Single-phase or
polyphase loads
not connected to
Trade size 2 1/2 (63) conduit
AB the neutral do not
C affect the size of
N the neutral.
N B
b. Parallel raceways (a) A neutral conductor that carries only the unbal-
anced current from other conductors of the same circuit
need not be counted when applying the provisions of
Trade size 2 (53) conduits AB
CN NEC® 310–15(B)(2)(a).
AB
CN (b) In a 3-wire circuit consisting of 2-phase wires and
Three 3/0 AWG 60˚C conductors the neutral of a 4-wire, 3-phase, wye-connected sys-
in each 500-ft (150m) run tem, a common conductor carries approximately the
same current as the line-to-neutral load currents of the
other conductors and shall be counted when applying
For three current-carrying conductors plus one neutral in the provisions of NEC® 310.15(B)(2)(a).
each raceway, no derating is necessary. At 150 amperes per
conductor, 1/0 AWG 75°C conductors may be used for both
phase and neutral wires. Conductors for each phase and (c) On a 4-wire, 3-phase wye circuit where the major
neutral must be in each raceway. For parallel runs, two trade portion of the load consists of nonlinear loads, there
size 2 (53) conduits are required. are harmonic currents present in the neutral conductor,
and the neutral shall be considered to be a current-
carrying conductor.
Figure 3–10 Multiple conductors in parallel as in Figure 3–11 Size of neutral conductor as in NEC®
NEC® 310.4 (Courtesy of American Iron & Steel 220.22 (Courtesy of American Iron & Steel Institute)
Institute)
Conductor Considerations 45
of service is important, it usually is advisable to conductors has distinct advantages, great care must
install circuit conductors in separate conduits or be taken to avoid conductor current imbalance and
raceways. Also, derating conductors may not provide inductive heating.
the most effective use of the conductor material. It is
very important when employing parallel conductor
runs that all conductors be installed using the same NEUTRAL CONDUCTOR
wiring method throughout the parallel run. For in- (GROUNDED CONDUCTOR)
stance, if parallel conductors are installed in individ-
ual metallic conduits enclosing each phase Most neutral systems are divided into two gen-
conductor and the neutral conductor, the same wiring eral categories, either solidly grounded or impedance
method should be used from the point of origin to the grounded. Examples of solidly grounded neutral sys-
termination point. Changing wiring methods, such as tems are shown in Figure 3–12. Impedance-
terminating the raceways in a wireway or auxiliary grounded neutral systems can be divided into several
gutter and extending the grouped parallel conductors subcategories. The system ground point always
to the termination point, may result in excessive should be at the power source. An archaic concept of
inductive heating. Although paralleling of circuit grounding at the load or at other points of the system
250.118 Steel
conduit or EMT
as equipment
Main service grounding conductor
disconnect
A
N
B
Neutral (identified
System 250.25 grounded
ground of conductor)
transformer Grounding
electrode
Grounding conductor
electrode 250.62 and
250.64 and Table 250.66
Requirements for grounding electrode conductor, grounded system as per Part III
Article 250, Grounded System
250.92
Main Main Rigid Steel Conduit or
service bonding Distribution EMT as grounding
switch jumper panel conductor for
equipment served
250.118
Grounding- Equipment-
electrode bonding
conductor* jumper
Grounding
electrode
*Grounds both the identified grounded conductor and the equipment grounding
conductor. It is connected to the grounded metallic cold water piping on premises,
or other available grounding electrode, such as metal building frame if effectively
grounded, or a made electrode. NEC ® 250.50 and 250.52.
Figure 3–12 Grounding principles (Courtesy of American Iron & Steel Institute)
46 Chapter 3
because of availability or convenience is not recom- 120/240-volt circuit should be the total of the 120-
mended because of problems caused by multiple volt load between the neutral and the more heavily
ground paths and the danger that the system could be loaded ungrounded conductor, as the more lightly
left ungrounded and unsafe. The NEC® recognizes loaded conductor could be carrying no current at all.
this danger and prohibits system grounding at any Because 240-volt loads are not connected to the neu-
place except the source or service equipment. The tral, they would not affect the commutation of its
neutral conductor is defined in 310.15(B)(4) of the size. The same applies in general to 3-phase loads on
NEC®. The size of the required neutral for an electri- 3-phase, 4-wire circuits. For a feeder supplying
cal system is found in 220.22. household electric ranges and other cooking appli-
The basic rule is that the neutral conductor must ances, the maximum unbalanced load is considered
have sufficient ampacity to carry the maximum pos- to be 70% of the load on the ungrounded conductors,
sible imbalance of the connected load between the as determined in the allowance with NEC® Table
neutral and any of the ungrounded conductors of the 220.19. For 3-wire dc; 3-wire, single-phase, ac; and
circuit. Although 310.15(B)(4)(c) only requires that 4-wire, 3-phase, ac feeds, a further demand factor of
the neutral be full size, where the effects of harmon- 70% may be applied to that portion of the unbal-
ics are present, good engineering practices dictate anced load that exceeds 200 amperes.
that the neutral conductor be sized to the maximum No demand factor can be applied, and hence
possible current on the electrical system, which may no reduction in the size of the neutral can be made,
require a neutral 1.5 to 2 times the size of the un- for that portion of the feeder or circuit supplying
grounded conductors of the system. In many cases, electric-discharge lamps, such as fluorescent lumi-
on 3-phase, 4-wire wye systems, typically 208/120- naires (fixtures). Neutral conductors are approxi-
volt systems, each ungrounded conductor should have mately equal to phase currents on these circuits
its own full-size neutral when supplying personal com- because of third harmonics developed by the lamp
puters and other data processing equipment. ballast.
In common inductive-resistant systems, such as
residential and commercial store buildings, a 3-wire,
Example: Given a 3-phase load, not Example: A new 3-phase, 4-wire, wye-
connected to neutral, of 200 amperes per phase connected feeder is connected by an existing
conductor and single-phase unbalanced loads junction box to three single-phase plus neutral
(phase-to-neutral) of 50, 100, and 150 amperes. circuits, each consisting of 2-phase conductors
Then, the load in amperes divides as follows: and a neutral. Two of these circuits are in one
conduit, the third is in another. Single-phase
Max. Current per Conductor circuit conductors are all 2 AWG Type THW
Phase Neutral copper. Determine the ampacity of each single-
conductor conductor phase circuit and the required size of the new
3-phase load 200 0
service.
Single-phase loads 150 150*
Total 350 150
• If electric-discharge ballasts are in the
The minimum size of copper 75°C wire is circuit, the load is considered continuous
650 kcmil for the phase conductor and 1/0 (3 hours or more continuous operation).
See definition in NEC® Article 100 for
AWG for the neutral. Good design, however,
“continuous load.”
calls for larger conductors.
• Neutrals in these circuits must be counted
*Maximum possible neutral load is 150 amperes. With all as current-carrying conductors. Refer to
loads connected, resultant current in the neutral would be 87
amperes. NEC® 310.15(B)(4)(b), Ampacity Tables of
0–2000 Volts.
Conductor Considerations 47
FPN No. 1: A second fault that occurs (3) Bonding of Electrically Conductive
through the equipment enclosures and bonding is Materials and Other Equipment. Electrically
considered a ground fault. conductive materials that are likely to become
FPN No. 2: See Figure 250.4 for information energized shall be connected together and to the
on the organization of Article 250. supply system grounded equipment in a manner
that creates a permanent, low-impedance path for
The IEEE STD 142 Green Book reminds us that ground-fault current that is capable of carrying the
equipment grounding conductors are installed to maximum fault current likely to be imposed on it.
• Reduce shock hazard to personnel
• Provide adequate current-carrying capability, (4) Path for Fault Current. Electrical equip-
both in magnitude and duration to accept the
ment, wiring and other electrically conductive ma-
ground-fault current permitted by the overcur-
terial likely to become energized shall be installed
rent protection system without creating a fire or
explosive hazard to building or contents in a manner that creates a permanent, low imped-
ance circuit from any point on the wiring system to
• Provide a low-impedance return path for
ground-fault current necessary for timely op- the electrical supply source to facilitate the opera-
eration of the overcurrent protective system tion of overcurrent devices should a second fault
occur on the wiring system. The earth shall not be
used as the sole equipment grounding conductor
250.4 General Requirements for Ground- or effective fault-current path.
ing and Bonding.
The following general requirements identify
what grounding and bonding of electrial systems FPN No. 1: A second fault that occurs
are required to accomplish. The prescriptive meth- through the equipment enclosures and bonding is
ods contained in Article 250 shall be followed to considered a ground fault.
comply with the performance requirements of this FPN No. 2: See Figure 250.4 for information
section. on the organization of Article 250.
Conductor Considerations 49
NEC® 250.90 and 250.96 require bonding to en- conductor to carry any fault currents directly to the
sure continuity and the capacity to safely carry the fault grounded point on the secondary, so that such fault
currents likely to be imposed. NEC® 250.118(B) lists currents will not have to travel along the high imped-
the acceptable types of equipment grounding con- ance path through the earth. This special grounded-
ductors. NEC® 250.122 lists the minimum size of grounding conductor, in furnishing a low-impedance
equipment-grounding conductors, with exceptions. path for fault current, facilitates the operation of the
There are three basic components of a complete overcurrent device on ungrounded circuits.
grounding system. Each is composed of one or more On a grounded system using a grounded neu-
parts that have different, but related, functions. tral, or a grounded phase conductor, the common
The first component is the grounded conductor. grounding-electrode conductor connects both the
This may be a grounded neutral or, on a 3-phase, equipment grounding conductor and the service en-
3-wire, delta-connected system, a grounded phase closure, and the grounded-circuit, or system, con-
conductor. The latter sometimes is called a corner- ductor to the grounding electrode.
grounded system. In all cases, the grounded conduc-
tor must be white, gray, or with three continuous Equipment Ground: The grounding con-
white stripes on other than green insulation, or be ductor must be bare, green, or green with one or
identified at the terminals and junction boxes at in- more yellow stripes.
stallation. NEC® 200.6 covers the requirements for
installing and marking these grounded conductors. The finish may be, and usually is, covered only
The second component, identified as the grounding and must not be relied on as insulation. The color
conductor, consists of both the equipment grounding coding is required by the NEC® only for equipment
conductor and the grounding-electrode conductor. grounding conductors, but in some jurisdictions it is
The equipment grounding conductor is connected to required for grounding conductors as well.
the noncurrent-carrying metal parts of the equipment The third component of a grounding or grounded
and to the grounding terminals of grounding-type system is the bonding jumper. An equipment-bonding
receptacles. The grounding conductor also extends to jumper connects two or more equipment grounding
the service equipment enclosure. Metal raceways, conductors or two or more noncurrent-carrying metal
Rigid Metal Conduit (RMC) or Intermediate Metal parts where continuity and adequate ampacity of
Conduit (IMC), and Electrical Metallic Tubing equipment grounding cannot otherwise be ensured or
(EMT) may serve as equipment grounding conduc- relied upon. Examples of this are a flush box and the
tors in accordance with NEC® 250.118. See Appen- grounding terminal of the grounding-type receptacle
dix Figures A–16 through A–20 for tables giving the (unless the receptacle has an integral device designed
maximum safe lengths of conductors and conduits and approved for this purpose), or a service-entrance
used as equipment grounding conductors. raceway and a service-entrance enclosure. These bond-
The grounding-electrode conductor, where used ing jumpers must be bare, green, or green with one or
on a system that does not have a grounded circuit more yellow stripes. A main bonding jumper bonds the
(system) conductor, such as a 3-phase, 3-wire un- service enclosure to the grounded bus of a grounded
grounded system, connects the service enclosure of system such as that shown in Figure 3–13. A circuit-
such a system to the grounding electrode. Where such bonding jumper is a current-carrying conductor, usu-
a grounded circuit is supplied by a transformer secon- ally a wire or strap, that bonds two or more parts of a
dary that is grounded at any point, the grounded con- circuit, whether grounded or ungrounded. An instance of
ductor must extend to the service-equipment enclosure, this is an expansion joint in which the ampacity of the
even though it will not be used as a circuit conductor circuit cannot otherwise be ensured around the joint. A
on the premises of the facility. circuit-bonding jumper is not part of the grounding
The grounding-electrode conductor in this case system. It is mentioned here only because of its simi-
connects the service enclosure and the special larity in name with other types of bonding jumpers.
grounded conductor to the grounding electrode. This The grounding-electrode conductor is con-
special grounded conductor functions as a grounding nected to the grounding electrode. The grounding
50 Chapter 3
Service equipment
Main
disconnecting
means
Service entrance Distribution
250.52(A)(1)
Supplementary
grounding electrode
Grounding-electrode
conductor (may be
connected to main
switch enclosure)
A A
B B
C C
3-phase, 3-wire, corner-ground
N delta
3-phase, 4-wire delta
Figure 3–15 Example of ac systems that are required to be grounded by NEC® 250.20 and 250.21 (Courtesy of
American Iron & Steel Institute)
ductors do not exceed 150 volts; (2) where the sys- grounded to the nearest building steel or nearest
tem is 3-phase, 4-wire, wye-connected in which the available other grounding electrodes in accordance
neutral is used as a circuit conductor; (3) where the to Part III of Article 250.
system is 3-phase, 4-wire, delta-connected in which The grounding rules in the NEC® deserve spe-
the midpoint of one phase is used as a circuit conduc- cial emphasis. The electrode-grounding connec-
tor; (4) where a grounded service conductor is per- tions at the transformer and at the service
mitted to be uninsulated. equipment provide parallel paths to ground for
Examples of common distribution voltages and fault currents. Two parallel paths have much less
the grounding requirements are shown in Fig- resistance than either separately. Thus, they pro-
ure 3–15. There are exceptions to these general rules. vide a low-resistance connection, essential for
Alternating-current systems of 1 kV and over sup- minimum impressed voltage should a fault occur.
plying mobile or portable equipment shall be For example, if a temporary fault current is 100
grounded as specified in NEC® 250.188. Where sup- amperes and the total impedance of the ground-
plying other than portable equipment, such systems fault path is 10 ohms, the voltage drop (difference
shall be permitted to be grounded. Where such sys- of potential) across the fault path will reach 1000
tems are grounded, they shall comply with the appli- volts. If a 2-ohm grounding path is achieved using
cable provisions of this article. Separately derived the underground-water-pipe grounding connection
systems with power derived from a generator, a plus the transformer-electrode-grounding connec-
transformer, or converter windings and that have no tion (utility), the voltage drop is held to 200 volts. A
direct electrical connections, including a solidly con- fault current of 25 amperes has a voltage drop of 50
nected grounded circuit conductor to supply conduc- volts across the 2-ohm ground. Thus, the grounding
tors originating in another system, if required to be connection at the transformer not only lessens the
grounded, as in NEC® Article 250, shall be grounded effects of the fault, but also helps to ground a fault
as specified in 250.30, which requires that they be on the source side of the service equipment.
52 Chapter 3
raceway not only lowers the total impedance of the carrying equipment at any point on the load side of
grounding path, but carries 95% or more of the cur- the service equipment.
rent. Furthermore, the raceway provides the addi- If the grounded-circuit conductor is not insu-
tional protection of a grounding shield. For instance, lated from the noncurrent-carrying equipment on the
in the unlikely event that a phase conductor becomes load side of the service equipment, then the raceways
damaged within a raceway and an uninsulated spot and possibly the piping and ducts will carry continu-
resulting from the damage comes in contact with a ously a portion of the neutral current on systems
grounded raceway, the resulting fault current would having a grounded neutral, and a portion of the phase
be carried to the grounded service-equipment enclo- current on systems having a grounded phase conduc-
sure through the main bonding jumper to the system tor. If this section of the grounded conductor be-
and the overcurrent device. comes open-circuited, the full circuit-to-ground
By contrast, a damaged phase conductor in a voltage is impressed upon such noncurrent-carrying
nonmetallic raceway could remain exposed to acci- equipment in the event of a fault-to-ground.
dental contact indefinitely. A fault within a non- The flow of such currents over raceways and
metallic raceway may or may not provide a other equipment can be a serious fire hazard. If a
low-impedance return path to trip the overcurrent raceway is in casual contact with a pipe, duct, or
device protecting the circuit. Some designers prefer building structure member, arcing may present a
only bare-equipment grounding conductors in non- shock hazard. For these reasons, the grounded circuit
metallic raceways to facilitate early detection when conductor must be insulated throughout its length, as
conductor insulation damage occurs. would an ungrounded circuit conductor. After World
An equipment grounding conductor and a War II, NEC® 250.140 permitted the grounded con-
grounded-circuit conductor are not the same electri- ductor to be used for grounding the frames of ranges,
cally. It is unsafe to connect the grounded-circuit wall-mounted cooking units, and clothes dryers un-
conductor to the raceway or to any other noncurrent- der some conditions, but this was changed. This
54 Chapter 3
practice was permitted for existing installations prior to Equipment intended to interrupt current at
the adoption of the 1996 NEC®; however, all new other than fault levels shall have an inter-
installations of these appliances are required to be rupting rating at nominal circuit voltage suf-
wired in accordance with all the requirements of fiecient for the current that must be
interrupted.
Article 250. The frames and all noncurrent-carry-
ing parts are now required to be grounded with a • NEC® 110.10. Circuit Impedance and
Other Characteristics. The overcurrent pro-
separate equipment grounding conductor; the
tective devices, the total impedance, the
grounded conductor will not be permitted to be component short-circuit current ratings, and
used for this purpose. This change requires that all other characteristics of the circuit to be pro-
ranges, counter-mounted cooking equipment, and tected shall be selected and coordinated to
clothes dryers be connected with a 4-wire cord and permit the circuit-protective devices used to
receptacle. clear a fault to do so without extensive dam-
See Appendix Figures A–16 through A–20 for age to the electrical components of the cir-
maximum lengths for raceways and conductors used cuit. This fault shall be assumed to be either
for equipment grounding. between two or more of the circuit conduc-
tors, or between any circuit conductor and
the grounding conductor or enclosing metal
CAPABLE OF CARRYING THE raceway. Listed products applied in accord-
AVAILABLE FAULT CURRENT ance with their listing shall be considered to
meet the requirements of this section.
Short-Circuit Calculations
Throughout the NEC®, as well as in industry These tough code requirements mean that we
standards, you will find references to fault currents, need to know the available fault currents at the main
short-circuit currents, ground-fault currents, interrupt- service equipment as well as at all points in the
ing ratings, impedances of transformers, and the like. system. Too often, engineers, electricians, and con-
tractors look for adequate interrupting ratings of the
• NEC® 110.9. Interrupting Rating. Equip- fuses or breakers in the main service equipment only.
ment intended to interrupt current at fault This is wrong. The Code tells us to observe available
levels shall have an interrupting rating suffi- fault currents throughout the electrical system. This
cient for the nominal circuit voltage and the means panelboards, motor controllers, motor control
current that is available at the line termnals
centers, distribution centers, and so on.
of the equipment.
Conductor Considerations 55
Step 1. Determine the full-load rating of the transformer—in amperes—from the transformer
nameplate, tables, or the following formulas:
a) For 3-phase transformers:
KVA × 1 000
I FLA =
E L − L × 1.73
where EL-L = line-to-line voltage
b) For single-phase transformers:
KVA × 1 000
I FLA =
E L−L
Step 2. Find the percent impedance (Z) on nameplate of the transformer.
Step 3. Find the transformer multiplier “M1”:
100
M1 =
transformer % impedance ( Z ) × 0.9
(Note: Because the marked transformer impedance can vary +/– 10% per the UL
standard, the 0.9 factor above takes this into consideration to show “worst-case” conditions.)
Step 4. Determine the transformer let-through short-circuit current at the secondary terminals
of the transformer. Use tables or the following formula:
The L-N fault current is higher than the L-L fault current at the secondary terminals of a
single-phase, center-tapped transformer. At some distance from the terminals, depending on
the wire size, the L-N fault current is lower than the L-L fault current. This can vary from 1.33
to 1.67 times. These figures are based on the change in the turns ratio between primary and
secondary, infinite-source impedance, a distance of zero feet from the terminals of the
56 Chapter 3
transformer, and 1.2 times oX (reactance) and 1.5 times oX (resistance) for the L-N versus
L-L resistance and reactance values.
For simplicity, in step 4c we used an approximate multiplier of 1.5. First, do the L-N
calculation at the transformer secondary terminals, step 4c, then proceed with the point-to-
point method.
1.73 × L × I
f=
N × C × E L−L
2×L×I
f=
N × C × E L−L
2×L×I
f=
N × C × E L−N
where
L = the length of the circuit to the fault, in ft.
I = the available fault-current—in amperes—at the beginning of the circuit.
C = the constant derived from the “C” tables (see the following pages of text) for the
specific type of conductors and wiring method.
E = the voltage, line-to-line or line-to-neutral. See step 4a, b, and c to decide which
voltage to use.
N = the number of conductors in parallel.
X = the fault current in amperes at the transformer terminals.
Step 6. After finding the “f” factor, refer to Chart M (see the following pages of text) to
determine the appropriate value of the multiplier “M2” for the specific “f” value. Or, calculate
1
as follows: M 2 =
1+ f
Step 7. Multiply the available fault current at the beginning of the circuit by the multiplier
“M2” to determine the available symmetrical fault current at the fault.
CHART M (Multiplier)
f M f M
“C”Values—Busways
High-Impedance
Ampacity Plug-In Busway Feeder Busway Busway
Review Questions
1. Conductors may be installed in raceways in both solid or stranded configurations. What is the
largest solid conductor that may be installed in a raceway?
3. Insulated conductor types are clearly identified by which letter when they are designed and
approved for installations in wet locations?
4. When installing six 12 AWG Type THWN conductors in a trade size 3/4 (21) Rigid Metal
Conduit, what is the percentage of ampacity adjustment required by the NEC®?
5. When installing three 4 AWG Type THW conductors, three 10 AWG Type THWN conduc-
tors, and three 12 AWG Type THWN conductors, what ampacity adjustment is required and
what is the allowable ampacity for these three sizes of conductors?
7. What is generally the smallest conductor size for the grounded neutral and the ungrounded
phase conductors to be run in parallel?
8. A small commercial building is supplied by two services, a 480-volt/277-volt service used for
power and lighting and a 208-volt/120-volt service used for appliance and branch-circuit
loads. What color must the grounded neutral conductor be on these two systems?
9. Where circuits are run in parallel, what is the minimum size equipment grounding conductor
required to be run in each parallel raceway?
10. NEC® 250.4(A)(5) requires the equipment grounding conductor to be capable of carrying the
available fault current that may be applied to a circuit. How many amperes will a 12 AWG
solid conductor carry for five seconds?
11. For how many seconds will a 2 AWG copper conductor carry 10,000 amperes before it burns
off?