Article 1 This Standard is enacted pursuant to Article 6.1 of the Fire Act
(hereinafter referred to as “the Act”).
Article 2 (deleted)
Article 3 Before to use the fire safety equipments for which no domestic
national standards has been made or can’t be tested at home,
necessary documents like foreign standards, report of
examination (which may be made either at home or abroad), and
qualified test certificates or specification certificates shall
be submitted to the central regulating authority for approval.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 1/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(1)For a storey above the 11th floor, the total area of round
holes with an inscribed diameter more than 50cm shall occupy
1/30 of the floor area of the storey.
(2)For a storey under the 11th floor, the total area of round
holes with an inscribed diameter more than 50cm shall occupy
1/30 of the floor area of the storey, and there must be at least
two round holes with an inscribed diameter more than 1m or
openings with a width more than 75cm and a height more than
120cm.
1.The distance between the lower end of the opening and the
floor is less than 120cm.
2.A passage with the opening facing toward the road or with
width more than 1m.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 2/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 3/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 12
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 4/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Places are classified into the following categories pursuant to use and
occupancy:
1.Class A
(2)Bowling alleys, billiard halls, assembly halls, fitness and recreation centers
(including facilities offering Shiatsu massage services, sauna rooms, and other
weight-loss and body toning facilities), indoor pitch and putt golf course, game-
playing ground, electronic game centers, and information recreation grounds.
(3)Tourist hotels, hostels, inns, and rest houses (limited to lodging houses
only).
(5)Restaurants, food and beverage stores, coffee shops, and tea houses.
2.Class B
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 5/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(12)preschools.
3.Class C
4.Class D
5.Class E
(3)Underground building
2.Class B, C, and D places with the total floor area not less
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 6/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
than 150m2
5.Various places where there are boiler room, kitchen and other
equipments using fire in large amount.
1.High risk working place which floor area of the first floor
and the second floor of the building and storage area is more
than 3,000 square meters.
3.Low risk working place which floor area of the first floor and
the second floor of the building and storage area is more than
10,000m2.
4.Where there are three risk levels and the area of each risk
level doesn’t reach the standard in the former three clauses,
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 7/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
but the sum of the actual area of each risk level divided by the
standard area is greater than 1.
8.High-rise buildings.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 8/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
The place listed in 17.1(9) with the total floor area not less
than 1000m2, it is allowable to install sprinkler system
connected to the water supply , fire extinguishing equipments as
higher level effect or adopt measures declared by the central
regulating authority. Standard for Installation of Sprinkler
System Connected to The Water Supply will be prescribed by the
central fire agency.
┌──┬───────────┬───┬──┬────┬───┐
├──┼───────────┼───┼──┼────┼───┤
│1 │Helipad on housetop │ │○ │ │○ │
├──┼───────────┼───┼──┼────┼───┤
│ │200 m2. │ │ │ │ │
├──┼───────────┼───┼──┼────┼───┤
│3 │Garage or indoor │○ │○ │○ │○ │
│ │300 m2. │ │ │ │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 9/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├──┼───────────┼───┼──┼────┼───┤
│4 │Over-and-under │○ │○ │○ │○ │
├──┼───────────┼───┼──┼────┼───┤
│5 │Generator room, │○ │ │○ │○ │
│ │places containing │ │ │ │ │
│ │equipments with a │ │ │ │ │
├──┼───────────┼───┼──┼────┼───┤
│ │m2. │ │ │ │ │
├──┼───────────┼───┼──┼────┼───┤
│7 │Telecommunication │ │ │○ │○ │
│ │room, or telephone │ │ │ │ │
│ │exchanger room or │ │ │ │ │
├──┼───────────┼───┼──┼────┼───┤
│8 │Engine laboratory, │○ │○ │○ │○ │
│ │petrol laboratory, │ │ │ │ │
│ │other similar │ │ │ │ │
│ │dangerous working │ │ │ │ │
│ │m2. │ │ │ │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 10/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├──┴───────────┴───┴──┴────┴───┤
│Note: │
│ kcal/h. │
│3. Where the cars are parked in a row in a parking area and │
│ they can run out the door at the same time, this table │
└──────────────────────────────┘
1.Buildings with not more than 5 storeys: used for the purposes
listed in 12.1 and 12.2(12), the floor area of each storey is
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 11/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
not less than 300m2; used for the purposes listed in 12.2~4
(except 12.2(12)), the floor area of each storey is not less
than 500m2.
2.Buildings with more than 5 but less than 11 storeys where the
floor area of each storey is not less than 150m2.
5.Buildings used for the purposed listed in 12.5 (1), where the
total floor area reaches 500 m2 or more, among which the area of
Class A places accounts for 300m2.
6.Buildings used for the purposes listed in 12.1 and 12.5 (3),
where the total floor area reaches 300 m2 or more.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 12/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 22-1 119 fire notification device shall be equipped in the following
places:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 13/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
2.Various buildings where the height exceeds 31m, and the total
floor area amounts up to 15,000 m2
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 14/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
1.High-rise buildings.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 15/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(1)In places listed in 12.1 and 12.5, there shall be a unit fire
extinguishing efficiency for every 100m2 of the floor area
(including the last proportion less than 100m2) on each floor.
(3)In boiler room, kitchen and other places where fire is used
in large amounts, there shall be a unit fire extinguishing
efficiency for every 25m2 of the floor area (including the last
proportion less than 25 m2) on each floor.
Article 32 Piping and fittings for indoor hydrant and roof water tank shall
be equipped pursuant to the following provisions:
Piping
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 16/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
they are used togher with outdoor fire hyfrants, auto sprinkler
system, hoses and other extinguishing facilities and its funcion
can be realized individually, the matching pipes aren’t required
to use for the special purposes.
Roof Tank
(1)Water quantity in tank should be more than 0.5m3 for the type
I hydrant and 0.3m3 for the type II one. But if it is used
togther with other extinguishing facilities, the quantity should
be kept to the maximum.
Article 34 Except that the places listed in 12.2 (11) or 12.4 shall be
equipped with Type I hydrants, other places shall be equipped
with Type I or II hydrants pursuant to the following provisions:
(2)In any storey, when all the hydrants are used simultaneously,
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 17/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(2)In any storey, when all the hydrants are used simultaneously,
the aimer discharging pressure of each fire hydrant shall be
more than 1.7kgf/cm2 or 0.17Mpa, and the water output more than
80kg/min. But where there are more than two hydrants totally, it
shall be supposed two are used simultaneously for calculation.
Article 35 Indoor hydrant box shall comply with the following provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 18/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 36 The capacity of indoor fire hydrant equipments shall be not less
than the quantity of all the fire hydrants on the floor that has
the most indoor fire hydrants continuously discharging for 20
minutes. However, if the total number of fire hydrants on the
floor is more than 2, then 2 shall be used as the total number.
H = h1 + h2 + 17m
(2)The air in water tank shall be more than 1/3 of the capacity
of the tank, and the pressure more than the necessary pressure
of using fire hydrant at the highest point of the building to
maintain the prescribed discharging water pressure. Automatic
pressurization can be made when the pressure and liquid level
inside the tank lower down. Air compressor and pressurizing pump
shall be connected to emergency power source.
P = P1 + P2 + P3 + 1.7kgf/cm2
(2)The total pumping head of fire pump for fire hydrant shall be
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 19/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
H = h1 + h2 + h3 + 17m
Article 39 Articles 32.1 (1)~(5), 32.1 (7), 32.2, 33 and 38 shall apply to
piping, pressure test and emergency power source of outdoor fire
hydrant equipments.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 20/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
3.The outdoor hydrant switch shall not exceed the maximum height
of 1.5 meters above ground and be above the minimum height of
0.6 meter above ground. Where the hydrant is installed
underground, the fire hose joint position shall be at least 0.3
meter above ground.
(3)The fire hose house shall contain at least two pieces of fire
hoses having a length of at least 20 meters and a diameter of 63
mm, one dual-purpose beeline spray nozzle with a diameter of at
least 19 mm, and a valve-type hydrant switch.
Article 41 The capacity of outdoor fire hydrant equipment shall be not less
than the water output of two outdoor fire hydrants discharging
simultaneously for 30minutes.
H = h1 + h2 + 25m
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 21/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
P = P1 + P2 + P3 + 2.5kgf/cm2
(1)Water output of fire pump shall be more than 400 L/min each
fire hydrant. However, if the total number of fire hydrants
exceeds 2, the 2 shall be used as the total number.
(2)The total pumping head of fire pump shall be more than the
value computed using the following formula:
H = h1 + h2 + h3 + 25m
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 22/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 44 Piping and fittings of automatic sprinkler system and roof tank
shall comply with Article 32.1 and 32.2 and meet the following
provisions:
(1)Brach pipe shall incline 4cm every 10m, and main pipe 2cm
every 10m.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 23/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 24/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
The space within 45cm under the deflector of nozzle and within
horizontally 30cm shall be kept vacant.
┌──────────────┬──┬───┬────┬───┐
├──────────────┼──┼───┼────┼───┤
└──────────────┴──┴───┴────┴───┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 25/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
57
├──────────────┼─────────┤
│ <39℃ │ <75℃ │
├──────────────┼─────────┤
│ 39℃≦T<64℃ │ 75℃≦T<121℃ │
├──────────────┼─────────┤
│ 64℃≦T<106℃ │ 121℃≦T<162℃ │
├──────────────┼─────────┤
│ ≧106℃ │ ≧162℃ │
└──────────────┴─────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 26/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 50 The water output of a nozzle shall be more than 80L/min (those
installed in the overhead warehouse shall be 140L/min), and
pressure more than 1kgf/cm2 or 0.1Mpa. The water output of the
small separation nozzle shall be more than 50L/min.
The water output of the open type nozzle shall be more than
5L/min for every 1m2 of the protecting area, and more than
10L/min for every 1m2 of places where store flammable
substances.
Article 51 The automatic sprinkler system shall be equipped with water flow
detecting devices pursuant to the following provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 27/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
3,000m2, each floor shall be equipped with two sets. But where
each of two adjacent storeys has not more than 10 nozzles and
automatic fire alarm equipments installed shall be co-used that
very two storeys.
Article 54
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 28/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Discharge area of open type automatic sprinkler system shall comply with the
following provisions:
2.Where there are two or more discharge areas, the floor area of each discharge
area shall be not less than 100m2, and any two adjacent areas shall be mutually
overlapped so as to fight fire effectively.
4.Nozzle shall employ upward type unless matching pipe can take
effective measures.
Article 56 Check valve at the end of the automatic sprinkler system with
enclosed type nozzle shall be equipped pursuant to the following
provisions:
4.The height from the floor shall be less than 2.1m, and
discharge pipe shall be attached; and “End Check Valve” shall be
marked obviously.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 29/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌───────────────────┬──────────┐
│ ├────┬─────┤
│ │Quick- │Standard- │
│ │response│response │
├───────────────────┼────┼─────┤
│buildings │ │ │
├──────┬────────────┼────┼─────┤
│ ├────────────┼────┼─────┤
│ ├────────────┼────┼─────┤
│ │Others │8 │10 │
├──────┼────────────┼────┼─────┤
│ │other inflammable │ │ │
│ │materials │ │ │
│ ├────────────┼────┼─────┤
│ │other materials │ │ │
└──────┴────────────┴────┴─────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 30/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
discharge area.
4.Where fixed type nozzles are used, water source capacity shall
exceed an uninterrupted 20-minute water supply for all the
sprinklers in the largest discharge area. Where turret type
nozzles are used, water source capacity shall exceed an
uninterrupted 20-minute water supply to the sprinkler at maximum
discharge status.
(1)The horizontal distance between any point and the fire hose
connector shall not exceed 15 meters. However, this requirement
does not apply to places equipped with an automatic sprinkler
system complete with sprinklers.
(5)The distance between the floor and the switch valve shall be
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 31/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
H = h1 + 10m
P = P1 + P2 + 1 kgf/cm2
(2)The total head of the pump shall be set above that determined
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 32/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
H = h1 + h2 + 10m
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 33/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 64 The capacity of water source for water spray fire extinguishing
equipments shall be kept at not less than 20 m3. Where there are
two or more spraying areas, the capacity shall be kept at not
less than 40 m3.The capacity of water source for water spray
fire extinguishing equipments shall be kept at not less than 20
m3. Where there are two or more spraying areas, the capacity
shall be kept at not less than 40 m3.
1.Water output: more than 1,200 L/min. Where there are two or
more spraying areas, the figure shall be more than 2,000 l/min.
Article 66 The distance of water fog nozzle and matching pipe from high-
voltage electric equipments shall comply with the table below:
┌──────────┬──┬──┬──┬──┬───┬───┬
├─────┬────┼──┼──┼──┼──┼───┼───┼
│distance ├────┼──┼──┼──┼──┼───┼───┼
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 34/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
└─────┴────┴──┴──┴──┴──┴───┴───┴
───┬───┬───┬───┐
───┼───┼───┼───┤
───┼───┼───┼───┤
───┴───┴───┴───┘
Article 70 Proper foam outlet shall be selected for fixed foam fire
extinguishing equipments according to the actual expansion ratio
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 35/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌──────────┬────────────────┐
├──────────┼────────────────┤
├──────────┼────────────────┤
│(High frothing) │ │
└──────────┴────────────────┘
Article 72 The output value of foam nozzle shall comply with the following
provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 36/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Type of foam raw liquid Output value for every square meter of
floor area (l/min)
┌─────┬─────────┬──────────────┐
│ │ │(L) │
├─────┼─────────┼──────────────┤
│Hangar │80≦R<250 │ 2 │
│ │(hereinafter │ │
│ │referred to as │ │
│ │Type I) │ │
│ ├─────────┼──────────────┤
│ │250≦R<500 │ 0.5 │
│ │(hereinafter │ │
│ │referred to as │ │
│ │Type II) │ │
│ ├─────────┼──────────────┤
│ │500≦R<1000 │ 0.29 │
│ │(hereinafter │ │
│ │referred to as │ │
│ │Type III) │ │
├─────┼─────────┼──────────────┤
│ parking ├─────────┼──────────────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 37/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ garage ├─────────┼──────────────┤
├─────┼─────────┼──────────────┤
│ listed ├─────────┼──────────────┤
│ in │Type II │ 0.31 │
│ Article ├─────────┼──────────────┤
└─────┴─────────┴──────────────┘
Article 74 Articles 38, 44, 45, and 51~53 shall be applicable to emergency
power source, piping, fittings, roof tank, pressurization and
transmission test upon completion, water flow detecting device,
actuating device, and deluge valve of foam fire extinguishing
equipments.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 38/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 76 Water source for foam fire extinguishing equipments shall comply
with the following provisions:
┌────────────┬─────────────────┐
├────────────┼─────────────────┤
│Type I │ 0.04 │
├────────────┼─────────────────┤
│Type II │ 0.013 │
├────────────┼─────────────────┤
└────────────┴─────────────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 39/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(2) shall be added by the foam amount to fill the pipe and 20%
of total foam water solution.
(1)Water output: not less than 130 l/min where there is only one
foam fire hydrant box on a same floor, and not less than 260
l/min where there are two or more foam fire hydrant boxes on a
same floor.
Article 79 Concentration ratio of foam raw liquid mixing with water shall
comply with the following provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 40/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 41/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌──────┬───────┬───────────────┐
├──────┼───────┼───┼───┼───┼───┤
│Fire extin- │ │ │ │ │ │
│guishing │ │ │ │ │ │
│medium for │ │ │ │ │ │
│every cube │ │ │ │ │ │
│tected area │ │ │ │ │ │
│(kg/m3) │ │ │ │ │ │
├──────┼───────┼───┼───┼───┼───┤
│Additional │ 10 │ 5 │ 5 │ 5 │ 5 │
│quantity of │ │ │ │ │ │
│fire extin- │ │ │ │ │ │
│guishing │ │ │ │ │ │
│medium for │ │ │ │ │ │
│every square│ │ │ │ │ │
│meter of the│ │ │ │ │ │
│opening area│ │ │ │ │ │
│(kg/m2) │ │ │ │ │ │
├──────┼───────┼───┼───┼───┼───┤
│ity of fire │ │ │ │ │ │
│extinguish- │ │ │ │ │ │
│ing medium │ │ │ │ │ │
└──────┴───────┴───┴───┴───┴───┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 42/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Q = 8–6xa/A
┌──────┬──────────────────┬────┐
│ │exchanger room │ │
├──────┼──────────────────┼────┤
└──────┴──────────────────┴────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 43/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 86 Where total flooding is used, the opening part of the protected
area shall meet the following requirements:
1.Filling ratio shall be more than 1.5 and less than 1.9 for
high-pressure type, and more than 1.1 and less than 1.4 for low-
pressure type.
(2)In places where the temperature is lower than 40℃ and seldom
varies.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 44/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 90
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 45/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
1.Where there are two or more protected areas or objects on a same floor and the
storage container is shared by the areas or objects, each shall be equipped with
a selector valve.
4.Where storage container and nozzles are equipped with selector valve, safety
device or breaking plate shall be installed for matching pipe between container
and selector valve.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 46/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
1.A time delay not less than 20sec shall be provided between the
motion of the switch or tie rod of actuating device and the
opening of the valve of storage container.
Article 95 Emergency power source used for total flooding and local
application shall employ self-use generating equipments or
battery, the capacity of which shall be able to ensure
effectively running for at least 1 hour.
Article 96 In addition to 87.1, 87.2(2) and (3), 87.3 and 87.4, the
following provisions shall be applicable to moveable
application:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 47/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 98 Articles 82, 85, 86, 90, 91, 92, 93, 95, and 97 shall govern the
spraying pattern, venting device, opening of protected area,
selector valve, actuating device, voice alarm device, safety
device, emergency power source and indication specifications for
dry chemicals fire extinguishing equipments.
┌─────┬─────┬──────┬─────┬─────┐
│chemicals │ingredient│ingredient:│ingredient│ingredient│
│ │ │ │) │nate and │
│ │ │ │ │urea chem-│
│ │ │ │ │icals) │
├─────┼─────┼──────┼─────┼─────┤
│required │ │ │ │ │
│by every │ │ │ │ │
│square │ │ │ │ │
│meter of │ │ │ │ │
│protected │ │ │ │ │
│area │ │ │ │ │
│ (kg/m2) │ │ │ │ │
├─────┼─────┼──────┼─────┼─────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 48/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│quantity │ │ │ │ │
│for every │ │ │ │ │
│square │ │ │ │ │
│meter of │ │ │ │ │
│opening │ │ │ │ │
└─────┴─────┴──────┴─────┴─────┘
┌─────────┬─────┬───────┬──────┐
│medium │ │ │ │
├─────────┼─────┼───────┼──────┤
│meter of protected│ │ │ │
│object (kg/m2) │ │ │ │
├─────────┼─────┼───────┼──────┤
│tional quantity │ │ │ │
├─────────┼─────┴───────┴──────┤
└─────────┴────────────────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 49/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Q=X–Yxa/A
┌─────────┬─────┬───────┬──────┐
├─────────┼─────┼───────┼──────┤
├─────────┼─────┼───────┼──────┤
└─────────┴─────┴───────┴──────┘
┌─────────┬─────┬───────┬──────┐
├─────────┼─────┼───────┼──────┤
│extinguishing │ │ │ │
│medium (kg) │ │ │ │
└─────────┴─────┴───────┴──────┘
Article 100 Nozzles for total flooding and local application shall meet the
following requirements:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 50/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 101 Only Type III dry chemicals may be used as fire extinguishing
medium for indoor parking areas.
┌─────────┬─────┬───────┬──────┐
├─────────┼─────┼───────┼──────┤
│ │≦1.45 │ │ │
└─────────┴─────┴───────┴──────┘
(2)In places where the temperature is lower than 40℃ and seldom
varies.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 51/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
or carbon dioxide.
Article 105 Piping and valves of dry chemicals fire extinguishing equipments
shall be equipped pursuant to the following provisions:
1.Piping
(3)Where copper pipe is used, the copper pipe shall comply with
National Standard CNS No. 5127 or have the same or higher
strength, and be able to endure a pressure at least 1.5 times
the adjustment pressure or the highest pressure.
2.Valves
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 52/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 106 The distance between any part of the matching pipe of dry powder
fire extinguishing equipments from storage container and the
bending part shall be 20 times the pipe diameter or more, unless
effective measures have been taken to make the dry chemicals
never separated from pressurizing or pressure-maintaining gas.
Article 107 Pressure regulating device, which can adjust the pressure to
under 25kgf/cm2 or 2.5Mpa, shall be equipped for dry chemicals
fire extinguishing equipments.
Article 108 Pressure setting device for pressurized dry powder fire
extinguishing equipments shall be equipped pursuant to the
following provisions:
Article 110 Where gas-actuated type is used, the following provisions shall
be observed:
Article 111 Moveable application shall comply with the following provisions
in addition to Articles 102.1, 102.2 (2) and (3), 102.3 and
102.4.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 53/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌─────────┬─────┬───────┬──────┐
├─────────┼─────┼───────┼──────┤
│Quantity sprayed │ 45 │ 27 │ 18 │
│every minute │ │ │ │
│(kg/min) │ │ │ │
└─────────┴─────┴───────┴──────┘
Article 112 Fire alarm division in buildings equipped with automatic fire
alarm equipments shall be determined pursuant to the following
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 54/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
provisions:
1.Each fire alarm division may not cover more than one storey or
more than 600m2 floor area. However, where the total floor area
of tow adjacent storeys is not more than 500m2, the two storeys
may be allocated into a same division.
Article 113 In five-storey or higher buildings with a total floor area more
than 3000m2, the ringing mode of automatic fire alarm equipments
shall meet the following requirements:
2.When the fire is on the ground floor, only this storey and the
direct upper storey and the underground storeys shall make
alarm.
3.When the fire is underground, only the first storey and the
underground storeys shall make alarm.
4.The whole area should make alarm immediately when the alarm
previous mentioned are activated less than ten minutes or the
fire alarm signal receiving switchboard receives the fire signal
again.
Article 114 Proper detector shall be selected from the table below according
to the height of the mounting position. If the height of the
ceiling is different from that of the roof slab in a same room,
the mean value shall be used for
┌─────┬─────┬──────┬─────┬─────┐
│mounting │ │ │ │ │
│position │ │ │ │ │
│(H) │ │ │ │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 55/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├─────┼─────┼──────┼─────┼─────┤
│Type of │Different-│Differential│Different-│Type I │
│ │topical, │differential│distribut-│topical, │
│ │topical, │topical,Type│topical, │ │
│ │electrical│photo- │electrical│ │
│ │electrical│photo- │type │ │
│ │separated,│electrical │ │ │
└─────┴─────┴──────┴─────┴─────┘
Article 115 Mounting position of detector shall comply with the following
provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 56/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 117 Smoke detector or heat & smoke compound detector may not be
installed in the following occasions:
Proper detector shall be selected from the table below for the
places listed in the above two clauses.
┌─────────────┬────┬───┬───┬───┬
│Place │ 1 │ 2 │ 3 │ 4 │
│ ├────┼───┼───┼───┼
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 57/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │ │ │given │ │
│ │ │ │off │ │
├───┬────┬────┼────┼───┼───┼───┼
│detec-│topical │Type II │ ○ │ │ │ │
│tor ├────┼────┼────┼───┼───┼───┼
│ │Diffe- │Type I │ ○ │ │ ○ │ │
│ │rential ├────┼────┼───┼───┼───┼
│ │distri- │Type II │ ○ │ ○ │ ○ │ │
│ │buted │ │ │ │ │ │
│ ├────┼────┼────┼───┼───┼───┼
│ │Compen- │Type I │ ○ │ │ ○ │ │
│ │sated ├────┼────┼───┼───┼───┼
│ │topical │Type II │ ○ │ ○ │ ○ │ │
│ ├────┼────┼────┼───┼───┼───┼
│ │Fixed │Special │ ○ │ ○ │ ○ │ ○ │
│ │tempe- │Type │ │ │ │ │
│ │rature ├────┼────┼───┼───┼───┼
│ │ │Type I │ ○ │ ○ │ ○ │ ○ │
│ ├────┴────┼────┼───┼───┼───┼
│ │Flame type │ ○ │ │ │ │
├───┴─────────┴────┴───┴───┴───┴
│Note:
│ in place 1 should have the structure that dust and powder are
│ functions.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 58/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
└───────────────────────────────
────┬───┬───┬───┬─────┐
5 │ 6 │ 7 │ 8 │ 9 │
────┼───┼───┼───┼─────┤
│stay │ │ │outside │
────┼───┼───┼───┼─────┤
│ ○ │ ○ │ │ │
────┼───┼───┼───┼─────┤
│ ○ │ ○ │ │ │
────┼───┼───┼───┼─────┤
│ ○ │ ○ │ ○ │ │
────┼───┼───┼───┼─────┤
│ ○ │ ○ │ ○ │ │
│ │ │ │ │
────┼───┼───┼───┼─────┤
│ ○ │ ○ │ ○ │ │
────┼───┼───┼───┼─────┤
│ ○ │ ○ │ ○ │ │
────┼───┼───┼───┼─────┤
○ │ ○ │ ○ │ ○ │ ○ │
│ │ │ │ │
────┼───┼───┼───┼─────┤
○ │ ○ │ ○ │ ○ │ ○ │
────┼───┼───┼───┼─────┤
│ ○ │ │ │ │
────┴───┴───┴───┼─────┤
│ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 59/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
────────────────┴─────┘
Article 118 Detectors of smoke detecting type, smoke & heat compound type or
flame type may be selected for the places listed in the table
below:
┌─────┬────┬─────┬────┬─────┬
│ │ │described │ │of │
│ │ │12.5 │ │ │
├─────┼────┼─────┼────┼─────┼
│Smoke │ ○ │ ○ │ ○ │ ○ │
│detecting │ │ │ │ │
│type │ │ │ │ │
├─────┼────┼─────┼────┼─────┼
│Smoke and │ │ ○ │ │ │
│heat │ │ │ │ │
│compound │ │ │ │ │
│type │ │ │ │ │
├─────┼────┼─────┼────┼─────┼
│Flame │ │ │ │ ○ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 60/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│type │ │ │ │ │
├─────┼────┴─────┴────┴─────┴
│Note │
└─────┴──────────────────────
─────┬──────┐
ceiling │storeys, │
is higher │no-opening │
│and storeys │
│above the │
│11th floor │
│(only for │
│those │
│described │
│in Article │
│12.1, 12.2(2│
│(8)~(10) and│
│12.5.) │
─────┼──────┤
│ ○ │
│ │
│ │
─────┼──────┤
│ ○ │
│ │
│ │
│ │
─────┼──────┤
○ │ ○ │
│ │
─────┴──────┤
────────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 61/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 119 The detecting area of a detector refers to the space divided and
surrounded by columns with a net height of not less than 40cm or
other similar constructions around the mounting surface of the
detector. But for detectors of differential distributed and
smoke-detecting types, the net height shall be increased to not
less than 60cm.
┌─────────────────┬────────────
├─────────────────┼───────────┬
│ │buildings fireproof │
│ │construction. │
├─────┬──────┬────┼───────────┼
│Type of │Differential│Type I │ 90 │
│and │ │Type II │ 70 │
│effective ├──────┼────┼───────────┼
│ │ │Type II │ 70 │
│ ├──────┼────┼───────────┼
│ │Fixed │Special │ 70 │
│ │temperature │Type │ │
│ │topical ├────┼───────────┼
│ │ │Type I │ 60 │
│ │ ├────┼───────────┼
│ │ │Type II │ 20 │
└─────┴──────┴────┴───────────┴
─────┬──────────────────┐
│ 4m≦H<8m │
─────┼────────────┬─────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 62/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│construction │ │
─────┼────────────┼─────┤
50 │ 45 │ 30 │
─────┼────────────┼─────┤
40 │ 35 │ 25 │
─────┼────────────┼─────┤
50 │ 45 │ 30 │
─────┼────────────┼─────┤
40 │ 35 │ 25 │
─────┼────────────┼─────┤
40 │ 35 │ 25 │
│ │ │
─────┼────────────┼─────┤
30 │ 30 │ 15 │
─────┼────────────┼─────┤
15 │ -- │ -- │
─────┴────────────┴─────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 63/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌──────┬──────┬────────────────┐
│ │area │ │
├──────┼──────┼────────────────┤
│buildings or├──────┼────────────────┤
│construction│ │ │
├──────┼──────┼────────────────┤
│buildings ├──────┼────────────────┤
│ │ │than 18m2) │
└──────┴──────┴────────────────┘
┌──────┬──────┬────────────────┐
│ │ │ Type I │ Type II │
├──────┼──────┼───────┼────────┤
│H<8m │Fireproof │ 65 │ 36 │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 64/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │buildings or│ │ │
│ │buildings of│ │ │
│ │fireproof │ │ │
│ │construction│ │ │
│ ├──────┼───────┼────────┤
│ │Other │ 40 │ 26 │
│ │buildings │ │ │
├──────┼──────┼───────┼────────┤
│8m≦H<15m │Fireproof │ │ │
│ │buildings or│ │ │
│ │buildings of│ 50 │ -- │
│ │fireproof │ │ │
│ │construction│ │ │
│ ├──────┼───────┼────────┤
│ │Other │ 30 │ -- │
│ │buildings │ │ │
└──────┴──────┴───────┴────────┘
1.Where the ceiling of living room is not more than 2.3m above
the floor, or the floor area is not more than 40m2, detectors
shall be installed nearby the gateway.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 65/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
beams.
┌──────────┬───────────────────┐
│ ├──────────┬────────┤
├──────────┼──────────┼────────┤
│ H<4m │ 150 │ 50 │
├──────────┼──────────┼────────┤
│ 4m≦H<20m │ 75 │ -- │
└──────────┴──────────┴────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 66/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
7.The distance between the optical axis of the detector and the
alert area shall be not more than 7m.
Article 124 Flame type detector shall comply with the following provisions:
Article 125 Fire alarm signal receiving switchboard shall meet the following
requirements:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 67/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 126 The location of fire alarm signal receiving switchboard shall
meet the following requirements:
Article 127 Wiring of automatic fire alarm equipments shall comply with the
following provisions in addition to Regulations for Installation
of User's Electricity Device:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 68/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
and the earth, and in each fire alarm division the resistance
shall be not more than 0.1MΩ.
Article 128 Battery shall be used as emergency power source for automatic
fire alarm equipments, and the capacity of battery shall be able
to ensure the fire alarm equipment effectively run for 10
consecutive minutes.
Article 129 Each fire alarm division shall be equipped with fire alarms
pursuant to the following provisions:
4.The fire alarms installed out the door shall be provided with
waterproof functions.
Where two storeys share a same fire alarm division, the fire
alarms shall be installed separately in the two storeys. But the
division in stairways or between pipes isn’t required to install
an alarm.
Article 131 Fire alarm ring in places equipped with manual alarm equipments
shall be installed pursuant to the following provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 69/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 132 Manual alarm box, indicating lamp and fire alarm ring shall be
installed pursuant to the following provisions:
2.The height of manual alarm box shall be not less than 1.2m and
not more than 1.5m.
3.Indicating lamp and fire alarm ring shall be 2~2.5m high from
the floor, unless they are installed together with manual alarm
box.
┌────────┬────────┐
├────────┼────────┤
│Grade L │ ≧92db │
├────────┼────────┤
│Grade M │ 87db≦V<92db │
├────────┼────────┤
│Grade S │ 84db≦V<87db │
└────────┴────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 70/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
30m2, and the horizontal distance form the speaker in this area
to the speaker in the adjacent area less than 8m.
P=p+10log10(Q/4πr2+4(1-α/Sα)
(6)When the echoing sound is more than 3s, the distance between
the place 1m to the floorslabs and the speaker shall be
calculated depending on the following formula:
r=3/4√QSα/π(1-α)
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 71/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 137 Where used together with other equipments, the emergency
broadcasting equipments shall be enabled to shield the
broadcastings from others.
Article 138 Audio amplifier and operating device shall comply with CNS
No.10522, and installed pursuant to the following provisions:
2.The wire conduit may not be shared by other wires, unless the
electric wire inside the conduit is used for light current with
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 72/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 140 Where automatic fire alarm equipments for gas leakage are used,
fire alarm divisions shall be allocated under Article 112.
1.Natural gas.
(2)Where there are air inlets on the ceiling of the room where
the gas burning appliances are, detectors shall be installed
within 1.5m away from the air inlets separated by the beams with
a net height not less than 60cm or other similar constructions
between the gas burning appliances or the location the gas pipe
goes through the wall and the ceiling.
(2)For a position the gas pipe goes through the wall, the point
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 73/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
is the center of the gas pipe at the position the gas pipe goes
through the wall.
Article 142 Gas leakage signal receiving switchboard shall meet the
following requirements:
5.The tone color and volume of the main sound device shall be
different from other alarm sounds.
Article 143 Gas leakage alarm devices shall comply with the following
provisions:
2.In the area where gas leakage can be detected by the detector,
the alarm device inside this area shall make alarm upon
operation of the detector, and the volume shall be not less than
70db at the position 1m away, unless the detecting appliance is
provided alarm function, or it is installed in machine room or
other places not usually populated or at the position the gas
pipe goes through the wall.
Article 144 Wiring of automatic fire alarm equipments for gas leakage shall
comply with Regulations for Installation of User's Electricity
Device.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 74/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
not more than 150V, the resistance shall be not less than 0.1MΩ;
where the voltage to earth exceeds 150V, the resistance shall be
not less than 0.2MΩ. And 500V DC insulation ohmmeter shall also
be used to measure the insulation resistance between the wires
of the detector circuit as well as between the wire and the
earth, and the resistance shall be not less than 0.1MΩfor every
alarm division.
Article 145 Battery shall be used as emergency power source for automatic
fire alarm equipments for gas leakage, and the capacity of
battery shall be able to ensure the two loops effectively run at
least for 10 consecutive minutes, and other loops to supervise
at least for 10 minutes.
Article 145-1 119 fire notification devices shall comply with the following
requirements:
1.The main exits are easily recognizable from any point of the
living rooms and the travel distance between living rooms and
main exits complies with the following subparagraphs. This
provision does not apply to underground building, underground
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 75/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌─────┬────────┬────────┬──────┐
│ │ │ │4 │
├─────┼────────┼────────┼──────┤
│ │ │ │) │
└─────┴────────┴────────┴──────┘
3.Hall way and passages exits, leading to the main exit, and
being equipped with detector-linked automatic closing fire door
,and with indicating signs in addition to emergency lighting
equipment, to ensure the visibility of the signs, could be
exempted from installation of exit indicating lamps.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 76/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 146-1 Exit indicating lamps and direction indicating lamps that are
not installed in stairways and slopes are classified according
to the vertical dimension and luminous intensity of the lamp
face as follows:
┌────────────┬────────┬────────┐
│ │ │ (cd) │
├──────┬─────┼────────┼────────┤
│lamp ├─────┼────────┼────────┤
│ ├─────┼────────┼────────┤
├──────┼─────┼────────┼────────┤
│lamp ├─────┼────────┼────────┤
│ ├─────┼────────┼────────┤
└──────┴─────┴────────┴────────┘
Article 146-2 The effective range of exit indicating lamps and direction
indicating lamps is the travel distance toward the lamps that is
within the range specified by one of the following
subparagraphs. The effective range is 10 meters if the
indicating lamps are not easily recognizable.
┌─────────────────────────┬────┐
│Classification │Travel │
│ │distance│
│ │(meter) │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 77/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├──────┬────┬─────────────┼────┤
│ │ ├─────────────┼────┤
│ ├────┼─────────────┼────┤
│ │ │sign │ │
│ │ ├─────────────┼────┤
│ ├────┴─────────────┼────┤
│ │Class C │ 15 │
├──────┼──────────────────┼────┤
│Direction │Class A │ 20 │
│indicating ├──────────────────┼────┤
│lamps │Class B │ 15 │
│ ├──────────────────┼────┤
│ │Class C │ 10 │
└──────┴──────────────────┴────┘
D=kh,
┌─────────────────────────┬────┐
│Classification │K value │
├─────────┬───────────────┼────┤
│lamps ├───────────────┼────┤
├─────────┴───────────────┼────┤
└─────────────────────────┴────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 78/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
vestibules exist.
Article 146-5 When installed in the following occupancy, exit indicating lamps
and direction indicating lamps that are not located in stairways
and slopes, shall be class A or B. The face illumination of exit
indicating lamps shall be not less than 20cd or possess flash
function. The face illumination of the direction indicating
lamps shall be not less than 25 cd. The preceding restrictions
shall not apply to lamps that are installed in hallways, and
that are easily recognized within effective range thereof.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 79/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 146-6 The illuminance of the audience indicating lamp measured at the
horizon surface of passages in the auditorium, shall be not less
than 0.2 lx.
Article 146-7 Exit indicating lamps and direction indicating lamps shall be
illuminated at all times.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 80/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 154 Construction of indicating signs shall comply with CNS 10208.
Article 155 Storage batteries shall be used as emergency power source for
exit indicating lamp and direction indicating lamp, and the
capacity thereof shall be able to ensure the lamp continued
illumination for a duration of not less than 20 minutes.
However, for the lamps that are installed in the major
evacuation routes of the following occupancy, the capacity shall
be not less than 60 minutes, and the power source shall adopt
both storage batteries and emergency generators.
4. Stairways.
Article 156 Wiring of exit indicating lamp and direction indicating lamp
shall comply with Regulations for Installation of User's
Electricity Device and meet the following requirements:
Article 157 Refuge appliances shall be selected following the table below:
┌───────────────┬──────┬─────┬
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 81/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │storeys │storey │
├─┬─────────────┼──────┼─────┼
│ │100). │ │ │
├─┼─────────────┼──────┼─────┼
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 82/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├─┼─────────────┼──────┼─────┼
│ │accommodated people is │ │ │
│ │appliance shall be │ │ │
│ │200). │ │ │
├─┼─────────────┼──────┼─────┼
│ │number of accommodated │ │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 83/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├─┼─────────────┼──────┼─────┼
│ │listed in 12.1(1)~(3) on │ │ │
│ │accommodated people is │ │ │
│ │appliance shall be │ │ │
│ │100). │ │ │
├─┴─────────────┴──────┴─────┴
│ storey.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 84/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
└─────────────────────────────
──────┬─────┐
fifth storey│above │
──────┼─────┤
Refuge │Refuge │
bridge, │bridge, │
salvage bag,│salvage │
sliding │bag, │
platform │sliding │
│platform │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
──────┼─────┤
Refuge │Refuge │
ladder, │ladder, │
refuge │refuge │
bridge, │bridge, │
automatic │automatic │
descending │descending│
salvage bag,│salvage │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 85/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
sliding │bag, │
platform │sliding │
│platform │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
──────┼─────┤
Same as │Same as │
above │above │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
──────┼─────┤
Same as │Same as │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 86/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
above │above │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
──────┼─────┤
Same as │Same as │
above │above │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 87/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
──────┴─────┤
────────────┘
1.Where the places 1~5 in the table above meet the following
requirements, the number of accommodated people (100, 200, and
300) listed in the column of “quantity of refuge appliances” may
be doubled to recalculate the number of the required refuge
appliances.
(1)The net area of the flat roof is not less than 100m2.
(1)Fireproof construction
(3)May not be used for purposes other than refuge, passage and
conveyance.
Article 159 It is allowable that the required refuge appliances are not
installed where the storeys meet any of the following
requirements:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 88/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
equipped with a fireproof door which can resist the fire for at
least one hour (fireproof roller shutter door excluded) and is
able to be automatically closed, and the number of the
accommodated people is less than 30.
3.In storeys used for places listed in Article 12.2(6) and (10)
and 12.4, and the following requirements are satisfied:
(3) The travel distance between the center exits and any exit
that leads outdoors shall be less than 30 meters.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 89/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(3) If the Center has sleeping or resting areas, the areas shall
be located in fire compartment.
(2) The receiver of the automatic gas leakage fire alarm system.
┌─┬────────┬───────────────────┐
│ │ │accommodated people │
├─┼────────┼───────────────────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 90/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├─┼────────┼───────────────────┤
│ │ │shall be neglected). │
├─┼────────┼───────────────────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 91/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │ing field, │ │
│ │dining room, │ │
│ │catering shop, │ │
│ │coffee bar, │ │
│ │tearoom, and │ │
│ │other similar │ │
│ │places │ │
├─┼────────┼───────────────────┤
│ │field │ following: │
├─┼────────┼───────────────────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 92/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │ │ following: │
├─┼────────┼───────────────────┤
│ │house │ │
├─┼────────┼───────────────────┤
│ │ │ rooms. │
│ │ │ 3 m2. │
│ │ │ dated people. │
├─┼────────┼───────────────────┤
│ │dementia), elder│ │
│ │service │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 93/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │institutions │ │
│ │(day care, │ │
│ │temporary care │ │
│ │and short-term │ │
│ │protection │ │
│ │only), │ │
│ │children's │ │
│ │welfare house, │ │
│ │Preschools, │ │
│ │infant nursery │ │
│ │centers, nursing│ │
│ │home institution│ │
│ │and postpartum │ │
│ │nursing care │ │
│ │center │ │
├─┼────────┼───────────────────┤
│ │blind, deaf or │ │
│ │weak in intell- │ │
│ │igence, │ │
│ │remediation │ │
│ │classes, │ │
│ │training classes│ │
│ │, children and │ │
│ │youth welfare │ │
│ │institution, │ │
│ │study center │ │
│ │and guidance │ │
│ │class (art) │ │
├─┼────────┼───────────────────┤
│ │similar places │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 94/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├─┼────────┼───────────────────┤
├─┼────────┼───────────────────┤
│ │buildings, and │ │
│ │other similar │ │
│ │places │ │
├─┼────────┼───────────────────┤
│ │room, indoor │ │
│ │park, indoor │ │
│ │parking area, │ │
│ │photo studio, │ │
│ │TV broadcasting │ │
│ │filed, warehouse│ │
│ │, furniture │ │
│ │exhibition and │ │
│ │other working │ │
│ │places │ │
├─┼────────┼───────────────────┤
├─┴────────┴───────────────────┤
│Note: │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 95/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ following provisions: │
│5. The term of fixed seat refers to one that is installed in│
└──────────────────────────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 96/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 162 Necessary opening area shall be reserved for refuge appliances
following the table below:
┌──────────────┬───────────────┐
├──────────────┼───────────────┤
├──────────────┼───────────────┤
├──────────────┼───────────────┤
│ │platform │
├──────────────┼───────────────┤
│ │bridge │
└──────────────┴───────────────┘
Article 163 Necessary operating area shall be reserved for refuge appliances
following the table below, and there shall be no obstacles
affecting operation around the appliances:
Article 163.PDF
Article 164 Necessary descending space between the opening and the ground
shall be reserved for refuge appliances following the table
below:
Article 164.PDF
Article 165 Necessary open ground under the descending space as shown in the
table below shall be reserved for the refuge appliances:
Article 165.PDF
┌─────┬─────────┬────┬───┬─────┐
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 97/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│refuge │ │ │ │method │
│appliance │ │ │ │ │
│indicators│ │ │ │ │
├─────┼─────────┼────┼───┼─────┤
│ │ │ │back- │, each │
│ │ │ │ground│character │
│ │ │ │ │≧ 5 cm2. │
│ │ │ │ │For refuge│
│ │ │ │ │ladder and│
│ │ │ │ │other │
│ │ │ │ │popular- │
│ │ │ │ │ized │
│ │ │ │ │appliances│
│ │ │ │ │, the name│
│ │ │ │ │shall be │
│ │ │ │ │directly │
│ │ │ │ │marked. │
│ │ │width≧ │ │shall be │
│ │ │30cm │ │marked │
│ │ │ │ │under- │
│ │ │ │ │standably │
│ │ │ │ │with each │
│ │ │ │ │character │
│ │ │ │ │≧1 cm2 │
├─────┼─────────┼────┤ ├─────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 98/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │ │ │ │character │
│ │ │ │ │≧5cm2 │
└─────┴─────────┴────┴───┴─────┘
Article 167 Automatic descending life line shall meet the following
requirements:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 99/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(3)A distance not less than 10cm shall be kept between a fixed
ladder and the wall.
2.Where refuge ladder is installed in storeys above the fourth
floor, fixed ladder shall be used pursuant to the following
provisions:
(2)A distance not less than 10cm shall be kept between the
crossbars of the ladder and the wall when the ladder is being
used.
Article 172 Sliding rod and refuge cord shall comply with the following
provisions
2.The upper end and the lower end of a sliding rod shall be
fixed.
Article 173 Supporting device used for automatic descending life line or
salvage bag and fixed mount used for suspended ladder, sliding
rod or refuge cord shall comply with CNS No.2473 and No.4435, or
have the same or higher strength and endurance, and anti-
corrosive treatment shall have bee made to the materials.
Article 174
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 100/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Where screw bolts are used to fix the fixed mount or supporting device, the
following provisions shall be observed:
2.The depth and torque of the proportion of screw bolt embedded in the reinforced
concrete (the mortar layer excluded) shall comply with the table below:
┌────────┬────────────┬────────┐
│screw │ │ │
├────────┼────────────┼────────┤
├────────┼────────────┼────────┤
├────────┼────────────┼────────┤
└────────┴────────────┴────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 101/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 178 The level illumination of emergency lighting lamp on the ground
measured by photocell illuminometer used for low-illumination
measurement shall be more than 1 Lux on the floor surface of the
underground passage in underground buildings, and more than 2
Lux in other places. But more emergency lighting lamps shall be
installed at the turnings of aisles.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 102/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
6.A check valve and stop valve shall be installed at a spot near
the fire department connection for inspection and verification
convenience.
2.Matching pipes shall comply with CNS No. 6445 and No. 4626, or
have the same or higher strength, corrosion resistance and heat
endurance. If the design pressure of water delivery exceeds
10kgf/cm2, matching pipes complied with National Standard (CNS)
No. 4626, and with the Pipe Number SCH40 or above, or having the
same or higher strength, corrosion resistance and heat endurance
shall be used.
Article 182 A water hose box shall be equipped within 5m away from the water
outlet in every storey above the 11th floor. One straight water
fog double-purpose aimer and at least two pieces of 20m-long
water hoses shall be equipped inside the box, and the box shall
be deep enough to contain water hoses and aimer, and marked with
obvious text “Water Hose Box”, each character bigger than 20cm2,
and the surface area shall be more than 0.8m2.
The hose box mentioned above shall be made of steel sheets with
a thickness more than 1.6mm or other nonflammable materials with
the same characteristics.
Article 183 Where the building is higher than 60m, connecting delivery pipe
shall employ wet type, and the relay pump shall meet the
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 103/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
following requirements:
1.The total head of the relay pump shall be more than the
calculated value using the formula below:
Total head = water head loss by fire hose friction + water head
loss by matching pipe friction + drop height + water discharging
pressure
H = h1 + h2 + h3 + 60m
2.The water output of the relay pump shall be more than 2,400
L/min.
5.Roof tank shall have a capacity of more than 0.5m3, and relay
tank more than 2.5m3.
7.When the sum of shutoff head and net positive suction head is
more than 170m, additional pump shall be added to make serial
connection and running.
H = h1 + h2 + h3 + 60m
3.The quantity of water is 1,200 l/min for the top storey and
the second top storey, and 2,400 l/min for other storeys.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 104/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
4.The quantity of water is 600 l/min for the branch pipe of each
aimer.
Article 185 Fire fighting pool shall be equipped pursuant to the following
provisions:
(1)For those fire water pool equipped under Article 27.1 and
27.3, at least 20m3 shall be provided for every 7,500m2
(including the last proportion less than 7,500m2) of the total
floor area of the first and the second floor.
2.The horizontal distance from any fire water pool to any part
of the building shall be not more than 100m, and the effective
quantity of water shall be not less than 20m3.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 105/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌────────┬──────┬───────┬──────┐
├────────┼──────┼───────┼──────┤
│(L/min) │ │ │ │
├────────┼──────┼───────┼──────┤
│Water supply │ 1 │ 2 │ 3 │
│connection │ │ │ │
│quantity (pc.) │ │ │ │
└────────┴──────┴───────┴──────┘
2.The total head of the fire pump shall not fall below that
obtained from the following equation:
H = h1 + h2 + 15 m
3.The fire pump shall be equipped with actuating device and red
operating indicator near the Water supply connection. The
requirement is not applicable where the pump is connected to the
remote activating system of the Disaster Prevention Center,
which maintains communication link with the Water supply
connection.
Article 187 Indicating of fire water pool shall comply with the following
provisions:
1.Throw-in holes for inlet water pipe shall be marked with “Fire
Water Pool”.
Article 188 The smoke exhaust equipment set forth in Article 28, Paragraph 1
Subparagraph 1 to 4 shall be installed pursuant to the
following:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 106/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 107/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
installed.
10.The smoke exhaust vents that directly face outdoors and are
kept open at all times, shall not apply to the restrictions set
forth in Subparagraphs 6 and 9.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 108/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(2)Where the smoke exhaust ducts or supply air ducts cut across
a fire compartment, a fire damper shall be installed on the
intersection. The construction of the intersection juncture
where the duct crosses the fire compartment shall be fire
resistance rated as that of the fire compartment. Where duct
passes through other floor levels, the vertical duct shall be
installed at the fire compartmented shaft. Where the exhaust
duct has fire resistance performance, approved by the central
regulating authority, and the construction of the intersection
juncture where the duct crosses the fire compartment is fire
resistance rated as that of the fire compartment, the foregoing
requirement shall not apply.
(6)The smoke exhaust vent, supply air intake, smoke exhaust fan,
and supply air fan shall be connected to the emergency power
source, and power source capacity shall be enough to run the
system effectively for a period of at least 30 minutes.
Article 190 It is allowable that smoke control equipments are not equipped
in the following places:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 109/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
2.Living room parts of the storeys under the 10th floor (except
underground storeys) comply with the following provisions:
(2)The floor area is less than 100m2, and the ceiling and indoor
wall surfaces including the base are all decorated with
inflammable materials of Grade I.
Article 191 Emergency power sockets shall meet the following requirements:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 110/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(1)The long side and the short side of the boxes shall be
separately not less than 25cm and 20cm.
6.At lest two dedicated circuit loops from the main switchboard
shall be set up for each floor, and each loop may not connect
more than 10 sockets. (The capacity of each loop shall enable at
least two sockets to work simultaneously).
8.Each socket shall be equipped with a 110V 15A (or above) no-
fuse breaker.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 111/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 192-1 The disaster prevention center ,central management room or duty
room shall install disaster monitoring and controlling system to
monitor or operate the following fire safety equipment:
5.Emergency generator.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 112/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Part 4 Fire Safety Design and Equipments for Public Hazardous Goods, Inflammable
High-pressure Gas, Gas Station, Air Supply station, Storage Tank of Natural Gas,
and Other Places
Article 193 The rules specified in this part shall be applied to the
following places (referred as places of public hazardous
Materials in the following context):
2. Gas station.
3. LPS station.
(1) The total floor area is more than 1,000 square meters.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 113/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 114/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(1) The surface area of the liquid contained in the tank is more
than 40 m2.
(3) The room dedicated for the storage tank of the public
hazardous Materials with a flash point of more than 40℃ and less
than 70℃ shall be in buildings other than the one-story
building. However, this shall not apply if the building has no
opening and is separated by the walls and floor boards which can
resist fire for at least an hour.
(1) The surface area of the liquid contained in the tank is more
than 40 m2.
6. An indoor gas station with one side opened and the stories
above are used for other purposes.
(1) The total floor area is more than 600 m2 and less than 1,000
m2.
(3) The place which does not reach the subparagraph of paragraph
1 of the preceding Article and is used for painting, coating or
quenching or used as the operating place of boiler or oil
pressure device. However, this shall not apply to the storage
place of high flash point Materials or Category VI public
hazardous Materials with an operating temperature of less than
100℃.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 115/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
following subparagraphs:
6.An indoor gas station that does not have an obvious difficulty
in fire-suppression is included.
Article 196 Other places of difficulty in fire fighting include outdoor gas
stations and the places which do not reach the provision on the
places of obvious or common difficulty in fire fighting.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 116/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 200 For the Type V equipments other than fire extinguisher, the fire
extinguishing efficiency shall be calculated in accordance with
the following provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 117/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌──────────────┬───────────────┐
├──────────────┼───────────────┤
├────┬─────────┼───────────────┤
│ │over │hydrant. │
│ ├─────────┼───────────────┤
│ │ │Type II fire-suppression │
│ │ │fire-suppression equipment │
│ │ │based hydrant. │
├────┴─────────┼───────────────┤
│ │suppression equipments. │
│ │use. │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 118/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├────┬─────────┼───────────────┤
│tank ├─────────┼───────────────┤
│ │ │fire-suppression equipment. │
│ ├─────────┼───────────────┤
│ │ │suppression equipment. │
├────┼─────────┼───────────────┤
│tank ├─────────┼───────────────┤
│ │70℃ │ │
│ ├─────────┼───────────────┤
│ │ │suppression. Equipment │
├────┴─────────┼───────────────┤
└──────────────┴───────────────┘
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 119/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 204 In the places where electrical equipments are used, at least one
set of Type V fire extinguishing equipment shall be configured
for every 100m2 of area (including the mantissa less than
100m2).
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 120/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(2)The total floor area is not less than 150m2. However, this
shall not apply if there is no opening in every 150m2 and the
place is separated by the walls and floor boards which can
resist fire for a hour, or the total floor area of the storage
or processing place of Category II public hazardous goods other
than inflammable solid or Category IV public hazardous goods
with a flash point of not less than 70℃ is less than 500m2.
4.An indoor gas station, one side of which is opened and the
storeys above which are used for other purposes
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 121/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 206 For a building in which a gas station is located, if the storeys
above the second floor are used for other purposes, indicating
equipment shall be configured.
Places that possess floor area over 150 square meters for the
usage as prescribed in paragraph1 and 2 shall have outdoor fire
extinguishing hydrant in type I fire-suppression equipment
equipped. However, the distribution places prescribed in
paragraph 2 is exempted.
Article 209 Indoor fire hydrant shall comply with the following provisions:
4.When all the indoor fire hydrants on any floor are used at the
same time, the aimer discharging pressure of each hydrant sahll
be not less than 3.5kg/cm2 or 0.35MPa, and the water output not
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 122/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
5.The capacity of water source shall be not less than the water
output of all the fire hydrants, on the floor where the most
indoor fire hydrants are installed, continously discharging for
30 minutes.
The emergency power source of indoor fire hydrant shall meet the
provision of Article 38; and in addition, the power capacity
shall be enough to enable the equipment to work effectively for
at least 45 minutes.
Article 210 Outdoor hydrant shall comply with the following subparagraphs:
4. When cast iron pipe is used for piping, the iron pipes for
pressure pipelines as prescribed in CNS832 or other pipes with
equivalent strength shall be used and the nominal pressure shall
be more than 16kg/cm2 or 1.6Mpa.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 123/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 211 Automatic sprinkler system shall comply with the following
provisions:
(2)When open type sprinklers are used, the capacity shall be not
less than the water output of all sprinkers in the biggest
discharging area continuously discharing for 30 minutes.
Article 212 Water fog fire extinguishing equipment shall comply with the
following provisions:
2.Each spraying area shall be not less than 150m2. If the area
of the protected object is less than 150m2, the actual area
shall apply.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 124/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
4.When all the water fog sprinklers in the biggest spraying area
discharge water at the same time, the spraying pressure of each
sprinkler shall be not less than 3.5kg/cm2 or 0.35MPa.
Article 213 The fixed foam fire-suppression equipment set for oil tank shall
corrsspond to the following subparagraphs :
┌───────┬──────────────────────┐
│ structure and├────────┬──────┬──────┤
│ ├───┬────┼──────┼──────┤
│ │or II │or IV │ │ │
│Diameter of │ │ │ │ │
│storage tank │ │ │ │ │
├───────┼───┼────┼──────┼──────┤
│D<13m │1 │1 │2 │2 │
├───────┤ │ ├──────┼──────┤
│13m≦D<19m │ │ │3 │3 │
├───────┤ │ ├──────┼──────┤
│19m≦D<24m │ │ │4 │4 │
├───────┼───┼────┼──────┼──────┤
│24m≦D<35m │2 │2 │5 │5 │
├───────┼───┼────┼──────┼──────┤
│35m≦D<42m │3 │3 │6 │6 │
├───────┼───┼────┼──────┼──────┤
│42m≦D<46m │4 │4 │7 │7 │
├───────┼───┼────┼──────┼──────┤
│46m≦D<53m │5 │6 │7 │7 │
├───────┼───┼────┼──────┼──────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 125/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│53m≦D<60m │6 │8 │8 │8 │
├───────┼───┼────┼──────┼──────┤
│60m≦D<67m │8 │10 │ │9 │
├───────┼───┼────┤ ├──────┤
├───────┼───┼────┤ ├──────┤
├───────┼───┼────┤ ├──────┤
├───────┼───┼────┤ ├──────┤
├───────┼───┼────┤ ├──────┤
├───────┼───┼────┤ ├──────┤
├───────┼───┼────┤ ├──────┤
├───────┴───┴────┴──────┴──────┤
│Note: │
│ : │
│ the inner side of the side plate, prevents the foam from│
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 126/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ tank. │
│ foam. │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 127/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ exempted. │
│C.The Type III foam outlet in this table may be used only │
└──────────────────────────────┘
┌─────┬──────────┬──────────┬
│ Foam ├────┬─────┼────┬─────┼
│Public │ │ │ │ │
│Hazardous │ │ │ │ │
│Materials │ │ │ │ │
│Stored │ │ │ │ │
├─────┼────┼─────┼────┼─────┼
│IV public │ │ │ │ │
│hazardous │ │ │ │ │
│materials │ │ │ │ │
│with a │ │ │ │ │
│flash │ │ │ │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 128/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│point less│ │ │ │ │
│than 21℃ │ │ │ │ │
├─────┼────┼─────┼────┼─────┼
│IV public │ │ │ │ │
│hazardous │ │ │ │ │
│materials │ │ │ │ │
│with a │ │ │ │ │
│flash │ │ │ │ │
│point │ │ │ │ │
│higher │ │ │ │ │
│than 21℃ │ │ │ │ │
│and less │ │ │ │ │
│than 70℃ │ │ │ │ │
├─────┼────┼─────┼────┼─────┼
│IV public │ │ │ │ │
│hazardous │ │ │ │ │
│good with │ │ │ │ │
│a flash │ │ │ │ │
│point │ │ │ │ │
│higher │ │ │ │ │
│than 71℃ │ │ │ │ │
├─────┴────┴─────┴────┴─────┴
└────────────────────────────
──────────┬──────────┬
────┬─────┼────┬─────┼
solution│ │solution│ │
outlet │ │outlet │ │
│ │ │ │
│ │ │ │
│ │ │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 129/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │ │ │
────┼─────┼────┼─────┼
240 │8 │220 │4 │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
────┼─────┼────┼─────┼
160 │8 │120 │4 │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
────┼─────┼────┼─────┼
120 │8 │100 │4 │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
│ │ │ │
────┴─────┴────┴─────┴
──────────────────────
──────────┐
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 130/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Type Ⅳ │
────┬─────┤
Volume │Discharge │
of foam │rate │
solution│ │
outlet │ │
│ │
│ │
│ │
│ │
────┼─────┤
220 │4 │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
────┼─────┤
120 │4 │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
│ │
────┼─────┤
100 │4 │
│ │
│ │
│ │
│ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 131/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ │
│ │
│ │
────┴─────┤
──────────┘
┌──────────┬──────────┬─────
├────┬─────┼────┬─────┼────┬
├────┼─────┼────┼─────┼────┼
│一六○ │八 │二四○ │八 │ -- │
├────┴─────┴────┴─────┴────┴
│ manufacturer
└───────────────────────────
─────┬──────────┬──────────┐
─────┼────┬─────┼────┬─────┤
│solution│ │solution│ │
│outlet │ │outlet │ │
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 132/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
─────┼────┼─────┼────┼─────┤
─────┴────┴─────┴────┴─────┤
───────────────────────────┘
┌───────────────────────┬──────┐
│Materials │coefficient │
├─────┬─────────────────┤ │
├─────┼─────────────────┼──────┤
│ │cyclohexanol、furfuryl alcohol, │ │
│ ├─────────────────┼──────┤
│ │, 2-butyl alcohol │ │
│ ├─────────────────┼──────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 133/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
├─────┼─────────────────┼──────┤
│ ├─────────────────┼──────┤
│ ├─────────────────┼──────┤
│ │butyl ether │ │
├─────┼─────────────────┼──────┤
│ │ether │ │
├─────┼─────────────────┼──────┤
│ │exanol │ │
├─────┼─────────────────┼──────┤
│ │aldehyde), paraldehyde │ │
│ │ │ │
│ │Acetaldehyde │2.0 │
├─────┼─────────────────┼──────┤
│ │mine, 3-ethanolamine │ │
│ ├─────────────────┼──────┤
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 134/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
│ ├─────────────────┼──────┤
├─────┼─────────────────┼──────┤
│ │butyronitrile │ │
├─────┼─────────────────┼──────┤
│ │acid │ │
├─────┼─────────────────┼──────┤
│non- │ │ │
│insoluble │ │ │
│substances│ │ │
└─────┴─────────────────┴──────┘
條號:214
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 135/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
N=Aq/C
N=Aq/C
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 136/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
3.When the guns spray at the same time, the spraying quantity
shall be not less han 1,900l/min, and the effective horizontal
spraying distance not less than 30m.
2.The sprinkling pipe shall be set on the top of tank wall, and
the number of nozzles shall be calculated according to the
sprinkling angle and quantity. If the tank is equipped with
girder spike or reinforcement ring which encumbers the path of
water, additional sprinkling pipe and nozzle shall be installed
under the girder spike or reinforcement ring.
5.The capacity of water source shall be not less than the water
output of the biggest storage tank continously discharging for 4
hours.
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 137/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 217 Where foam nozzle is used, the following provisions shall be
observed:
2.A foam nozzle shall be set for every 9 square meters of the
surface area of the protected object (the floor area if it is a
building).
Article 219 The installation of foam based hydrant shall comply with the
following subparagraphs:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 138/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 220 The water source volume for foam fire-suppression equipment
shall be more than the water quantity required for the solution
prescribed below and the volume of solution required in the pipe
shall also be regarded.
4. The methods for calculating the water volume for the foam
fixed fire-suppression equipment used for storage tank are
stated as following:
(1) The water volume required for foam fixed outlet shall be
calculated by multiplying the quantity of foam solution
prescribed in the table under the Article 213.2 and 213.3by the
surface area of the liquid during maximum discharging volume.
(2) The necessary height drop in gravity tank shall be more than
the value calculated by the method provided below:
H=h1+h2+h3m
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 139/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
(2) The air in a water tank shall be more than 1/3 of the total
volume of the tank and the pressure more than the necessary
pressure of using hydrant installed in the highest point of the
building to maintain the required discharging water pressure.
The pressure tank shall be able to perform automatic
pressurization when the pressure and the liquid level inside the
tank lower down. Air compressor and pressurizing pump shall be
connected to emergency power source.
P = P1 + P2 + P3+P4
H = h1 + h2 + h3 + h4
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 140/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
┌───────┬──────────┬───────────┐
│ │protected area │ │
│ │(kg/m3) │ │
├───────┼──────────┼───────────┤
│V<5 │1.2 │ 1 │
├───────┼──────────┼───────────┤
│5≦V<15 │1.1 │ 6 │
├───────┼──────────┼───────────┤
│15≦V<50 │1.0 │ 17 │
├───────┼──────────┼───────────┤
│50≦V<15 │0.9 │ 50 │
├───────┼──────────┼───────────┤
├───────┼──────────┼───────────┤
└───────┴──────────┴───────────┘
Article 223 Dry powder fire extinguishing equipment shall comply with the
provisions of Article 98~111. However, for the dry powder fire
extinguishing equipment of total flooding mode, if public
hazardous goods is stored or processed in the protected area,
the dosage calculated under Article 99 shall be multiplied by
the coefficient listed in the table of Subparagraph 3 of the
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 141/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 224 The walking distance from a Type IV fire extinguishing equipment
to any point of the protected object shall be less than 30m.
However, this shall not apply if it is configured together with
Type I, Type II or Type III fire extinguishing equipment.
Article 226 Fire alarm equipment shall be configured in accordance with the
provisions of Articles 112~132.
Article 228 The fire extinguisher used in the places of inflammable high-
pressure gas, LPS station, storage tank of natural gas, and
inflammable high-pressure gas shall comply with the following
subparagraphs:
When the floor area is more than 200 meter squares, one set
shall be installed additionally for every 50 meter squares (<50
meter squares inclusive).
(1) More than four sets shall be equipped for the gas storage
tank area.
(2) More than one set shall be equipped for each gas filling
machine.
(3) More than one set shall be equipped in each place where fire
is used.
(4) Two sets shall be equipped in each floor that has floor area
less than 100 square meters. In floor that has the total area
more than 100 meter squares, one shall be configured
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 142/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
4.The volume of water source shall be more than the water volume
discharged by pressurization and driving device for 30
consecutive minutes.
5. The structure and the manual station shall apply mutais
mutandis to the case as referred to in Article 216.
Article 230 The protected area referred to in the preceding Article shall be
calculated in accordance with the following provisions:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 143/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 231 The outdoor hydrants used in the places of inflammable high-
pressure gas, LPS station, storage tank of natural gas, and
inflammable high-pressure gas shall comply with the following
subparagraphs:
Article 232 The installation and quantity of water discharging devices shall
comply with the following subparagraphs:
Article 233 The matching pipe, pressure test, pressurization and driving
device, and emergency power source of water shooting equipment
shall comply with the provisions of Article 39~42.
Article 234 Friction loss calculation of fire pump, motor, attachment and
matching pipe for indoor fire hydrant, outdoor fire hydrant,
automatic sprinkler, water fog fire extinguishing, foam fire
extinguishing, cooling water sprinkler, injecting device and
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 144/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 235 The wiring of the emergency power supply system shall comply
with Regulations for Installation of User's Electricity Device
and meet the following:
Article 236 The wiring of the fire safety equipment emergency power supply
system shall be pursuant to the flame-retardant or heat-
resistant protection prescribed in the following table:
(ATTACHMENT)
Article 236.pdf
Article 237 The electrical source of emergency power supply system shall
meet the following requirements:
https://law.moj.gov.tw/ENG/LawClass/LawAll.aspx?media=print&pcode=D0120029 145/146
1/9/23, 9:39 AM Standard for Installation of Fire Safety Equipments Based on Use and Occupancy - Article Content - Laws & Regulations Data…
Article 238 The Disaster Prevention Center shall have a floor area of at
least 40 m2 and shall comply with the following:
(3) The travel distance between the center exits and any exit
that leads outdoors shall be less than 30 meters.
(3) If the Center has sleeping or resting areas, the areas shall
be located in fire compartment.