USER MANUAL

REFRIGERATED DRYERS
RD—DIGITAL CYCLING

PART NUMBER:
02250201-297 R01
KEEP FOR
FUTURE
REFERENCE

WARRANTY NOTICE
©SULLAIR CORPORATION
The information in this manual is current
as of its publication date, and applies to
Failure to follow the instructions dryer serial number:
and procedures in this manual or,
misuse of this equipment will (RD) 0711SA0263
VOID its warranty!
AIR CARE SEMINAR TRAINING
Sullair Air Care Seminars are courses that provide hands-on instruction for the proper operation, maintenance,
and servicing of Sullair products. Individual seminars on Stationary compressors and compressor electrical
systems are offered at regular intervals throughout the year at Sullair’s corporate headquarters training facility
located at Michigan City, Indiana.

Instruction includes training on the function and installation of Sullair service parts, troubleshooting common
faults and malfunctions, and actual equipment operation. These seminars are recommended for maintenance,
contractor maintenance, and service personnel.

For detailed course outlines, schedule, and cost information contact:

SULLAIR TRAINING DEPARTMENT

1-888-SULLAIR or
219-879-5451 (ext. 5623)
www.sullair.com
training@sullair.com
- Or Write -
Sullair Corporation
3700 E. Michigan Blvd.
Michigan City, IN 46360
Attn: Service Training Department.
TABLE OF CONTENTS
SECTION 1—SAFETY
7 1.1 SAFETY INFORMATION

SECTION 2—RD SERIES DRYER


9 2.1 INTRODUCTION
9 2.2 SPECIFICATIONS
10 2.3 SAFETY INSTRUCTIONS
10 2.4 ISSUES TO AVOID
10 2.5 RECEIVING AND INSPECTION
10 2.6 TRANSPORTATION
11 2.7 INSTALLATION LAYOUT REQUIREMENTS
11 2.8 ENVIRONMENTAL PROTECTION
11 2.9 PRODUCT DESCRIPTION
11 2.10 PRODUCT FEATURES
12 2.11 PRINCIPLE OF OPERATION
13 2.12 COMPRESSED AIR HEAT EXCHANGER
14 2.13 PIPE/CONNECTION REQUIREMENTS
14 2.14 ELECTRICAL CONNECTION REQUIREMENTS
14 2.15 OPERATING PRECAUTIONS
14 2.16 INSTALLATION
16 2.17 STEPS TO UNDERTAKE BEFORE OPERATING
16 2.18 OPERATING PROCEDURES
17 2.19 STARTUP AND SHUT DOWN PROCEDURE
18 2.20 MAINTENANCE
19 2.21 TROUBLESHOOTING
25 2.22 SETTINGS

SECTION 3—CONTROLLER
31 3.1 OPERATION

SECTION 4—
40 4.1 ED/SPARE PARTS—RD400 AIR COOLED
TABLE OF CONTENTS

42 4.2 ED/SPARE PARTS—RD500 AIR COOLED


44 4.3 ED/SPARE PARTS—RD700 AIR COOLED
46 4.4 ED/SPARE PARTS—RD700 WATER COOLED
48 4.5 ED/SPARE PARTS—RD850 AIR COOLED
50 4.6 ED/SPARE PARTS—RD850 WATER COOLED
52 4.7 ED/SPARE PARTS—RD1000 AIR COOLED
54 4.8 ED/SPARE PARTS—RD1000 WATER COOLED
56 4.9 ED/SPARE PARTS—RD1200 AIR COOLED
58 4.10 ED/SPARE PARTS—RD1200 WATER COOLED
60 4.11 ED/SPARE PARTS—RD1600 AIR COOLED
62 4.12 ED/SPARE PARTS—RD1600 WATER COOLED
64 4.13 ED/SPARE PARTS—RD2000 AIR COOLED
66 4.14 ED/SPARE PARTS—RD2000 WATER COOLED
68 4.15 ED/SPARE PARTS—RD2400 AIR COOLED
70 4.16 ED/SPARE PARTS—RD2400 WATER COOLED
72 4.17 ED/SPARE PARTS—RD3000 AIR COOLED
74 4.18 ED/SPARE PARTS—RD3000 WATER COOLED
76 4.19 ED/SPARE PARTS—RD3800 AIR COOLED
78 4.20 ED/SPARE PARTS—RD3800 WATER COOLED
80 4.21 ED/SPARE PARTS—RD5000 AIR COOLED
82 4.22 ED/SPARE PARTS—RD5000 WATER COOLED
84 4.23 ED/SPARE PARTS—RD6000 AIR COOLED
86 4.24 ED/SPARE PARTS—RD6000 WATER COOLED
88 4.25 ID—RD400
90 4.26 ID—RD500-850
92 4.27 ID—RD1000-1200
94 4.28 ID—RD1600-2000
96 4.29 ID—RD2400
98 4.30 ID—RD3000
100 4.31 ID—RD3800
102 4.32 ID—RD5000
104 4.33 ID—RD6000
106 4.34 P&I—RD400
108 4.35 P&I—RD500-850
110 4.36 P&I—RD700-850 WATER COOLED
112 4.37 P&I—RD1000-6000
114 4.38 P&I—RD1000-6000 WATER COOLED
116 4.39 WIRING DIAGRAM—RD400 (230-3-60-A)
120 4.40 WIRING DIAGRAM—RD400 (460-3-60-A, 400-3-50-A)
124 4.41 WIRING DIAGRAM—RD500/700 (230-3-60-A)
128 4.42 WIRING DIAGRAM—RD (500/700/850-1000-1200-1600-2000-2400-
3000-3800-5000-6000)-460-3-60-A, 400-3-50-A
132 4.43 WIRING DIAGRAM—RD700-850 (230-3-60-W)
TABLE OF CONTENTS

136 4.44 WIRING DIAGRAM—RD (700-850-1000-1200-1600-2000-2400-3000-


3800-5000-6000) 460-3-60-W, 400-3-50-W
140 4.45 CONTROL CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-
3000-3800-5000-6000
142 4.46 POWER CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-
3000-3800-5000-6000
TABLE OF CONTENTS
SAFETY

Section 1

SAFETY
The dryer has been designed and constructed in 1.1 SAFETY INFORMATION
accordance with the generally recognized rules
pertaining to refrigeration technology as well as The end user and operator must observe all National,
industrial safety and accident prevention regulations. State, and Local industrial and safety regulations
dealing with the operation of pressure vessels under
The equipment design, development, production,
compressed air service. Also all “end user” safety
assembly and customer service fall under the Sullair
rules for the same type of service must be adhered
quality control system.
to. The following points list some of the important
The dryer is state of the art. There are, however, factors dealing with this type of equipment.
hazards to the body, equipment and life
• Never make any constructional changes to
accompanying this type of product if it is not operated
the equipment
for the purpose which it is intended by trained and
specialized personnel. • Use only original spare parts and accessories
• Never weld on any pressure vessel or mod-
The equipment supplied is intended exclusively for
ify it in any way
drying compressed air. Any other use or one
exceeding this is considered unauthorized. Sullair • All maintenance on “pressure parts” must
cannot be held liable for damages resulting from be carried out with the equipment shut-
incorrect or unauthorized use of the equipment. Any down, depressurized and locked out. Any
such risk is carried solely by the end user. in plant procedures or work permits regard-
ing pressure vessels are to be adhered to.
Authorized use means complete compliance with all
• Do not operate the equipment with the con-
of the conditions of operation, servicing and
trol panel door open, the electrical system
maintenance prescribed by Sullair in this Instruction
energized and live parts exposed.
and Operation Manual.
• Disconnect the dryer from the electrical
The dryer is only to be operated, serviced and supply when any electrical work is per-
repaired by trained personnel who are familiar with formed. Lock out the safety disconnect and
this type of equipment and understand fully its obtain any required work permits.
operation and any potential dangers.

7
NOTES

8
PRODUCT USER MANUAL

Section 2

RD SERIES DRYER
2.1 INTRODUCTION conditions. Warm dry air will not affect the piping nor
the tools and the result is extended tool life. In
The Sullair Non-cycling Refrigerated air dryers are addition, applications that require clean dry air can
designed for constant full load operation. They use rely upon Sullair’s non-cycling refrigerated air dryers
specially designed heat exchangers with integrated to provide dry air at full load continuously.
components to provide consistent dewpoint and
trouble-free service for years to come. 2.2 SPECIFICATIONS
The dryers remove the moisture, from the
Pay attention to the Minimum and Maximum
compressed air stream. By using basic refrigeration,
operating conditions before installing and operating
the hot saturated air is cooled in the highly efficient
the dryer.
heat-exchangers and the moisture is condensed and
removed. Additional filtration eliminates other
contaminants and particles. Normal Operating Pressure 100 PSIG / 6.89 Bar

Water (moisture) is one of the greatest enemies of air Normal Operating Temperature 100°F / 38°C
tools and piping. Left untreated in the compressed air
Normal Ambient Temperature 100°F / 38°C
stream, this moisture will deteriorate the tools,
equipment and piping with corrosion, pipe scaling, Maximum Operating Pressure 230 PSIG / 15.86 Bar
freezing and a host of other problems that will
diminish the life of your entire compressed air Minimum Operating Pressure 75 PSIG / 5.17 Bar
system. With a Sullair refrigerant dryer, you can be Maximum Ambient Temperature 120°F / 49°C
assured of clean, dry air with consistent dewpoint
between 36 and 40°F / 2 and 4°C. The unique three- Minimum Ambient Temperature 40°F / 4°C
in-one heat exchanger combination—
Maximum Operating Temperature 150°F / 66°C
• Air to Air (pre-cooler/re-heater Heat Exchanger)
• Air to Refrigerant (high efficiency Heat RD dryer capacities are designed in accordance to
Exchanger) CAGI standards. Variances from standards will
• Integrated Separator (located at the coldest point directly affect performance.
to maximize moisture extraction)
If your application does not match the above criteria,
heats up the exiting air, thereby eliminating the contact your Sullair distributor and they will be able to
chances of freezing even in relatively cooler ambient provide the right dryer for your application.

9
PRODUCT USER MANUAL SECTION 2

2.3 SAFETY INSTRUCTIONS 3. Do not operate the dryer at pressures, tem-


peratures of flow other than the ones men-
SAFETY REGULATIONS: tioned on the data label.
1. When operating the air dryer, the operator
must adopt safe working methods and 2.5 RECEIVING AND
observe all local safety instructions and rele- INSPECTION
vant regulations.
Sullair dryers are factory tested prior to shipment.
2. Prior to installation, the dryer and the com- However, during shipment, there are chances that
pressed air system are to be depressurized the dryer was mishandled or certain parts were
and disconnected from the electrical main broken or might have come loose. In order to ensure
supply. that the dryer you have received is fit for installation
and operation, we recommend you take a few
3. The user is responsible for safe operating
minutes to inspect the dryer for any physical abuse
conditions. Parts and accessories must be
or damage during shipment.
replaced if inspection shows that it is unsafe
to operate the dryer. If you notice any damage to the shipment, or if the
blue beads in the Tip-n-Tell label are in the arrow
4. Installation, operation, maintenance and
(read instructions on the label attached to the box)
repair are only to be performed by autho-
we recommend you take the following steps to
rized, trained and skilled technicians.
ensure proper arrangements can be made to
5. The minimum and maximum values listed on address the issue.
the data label must be strictly followed. If
1. Immediately file a complaint with the ship-
your application does not fall within the
ping company.
parameters indicated on the data label–
STOP. Contact your Sullair representative/ 2. Contact Sullair or Sullair distributor and
distributor and clarify the issue before pro- inform them of the damage. (Email or fax the
ceeding or operating the dryer. copy of the shipper claim and acknowledge-
ment)
6. All safety procedures and practices men-
tioned in this manual must be observed, as If there is no physical damage to the dryer –
well as all of the federal, state and local
1. Remove all the crating and packaging.
safety precautions.
2. Inspect the dryer for electrical and piping
7. If any statement in this manual does not
connection and make sure that they are all
comply with the local legislation, the stron-
tight.
gest standard is to be applied.
3. Check the data label, your packing slip and
2.4 ISSUES TO AVOID make sure that it is the correct unit you had
ordered.
1. Any structural changes made to the dryer
4. Follow the recommended safety procedures
without the advise of Sullair or Sullair repre-
and get the dryer ready for installation.
sentatives will void all warranty.
2. Compressed air from this dryer does not 2.6 TRANSPORTATION
meet the OSHA standards for breathing and
hence it should not be used for breathing 1. Use care and caution when transporting the
purposes. dryer. Avoid sudden jerks, tilting, dropping
and other physical abuse.
None of the protective alarms, equipment or
2. A forklift can be used to transport the dryer
devices should be tampered with. These pro-
provided the forks are long enough to sup-
tective items have been designed and
port the full width or length. Caution must be
installed on this dryer for your safety.
used throughout the move.

10
SECTION 2 PRODUCT USER MANUAL

2.7 INSTALLATION LAYOUT The minimum and maximum values stated must be
REQUIREMENTS observed, as well as the safety precautions
described in this manual.
1. The dryer must be installed horizontally. A
minimum of at least 1.5 feet / 0.5 meters
clearance around the dryer is necessary to
allow free air circulation and easy access for 2.10 PRODUCT FEATURES
servicing.
2.10.1 REFRIGERANT COMPRESSOR
2. The ambient temperature in the room should
not exceed 120°F / 49°C and should not be The refrigerant compressor is fully hermetically
below 40°F / 4°C, taking into account the sealed and requires no maintenance.
heat radiated by the dryer. (About 18 watts 2.10.2 CONDENSER
for each SCFM under ISO 7183-5 condition
or 40 watt for each liter/sec under ISO 7183- 1. Air cooled models: The refrigerant con-
A condition). denser is equipped with fans that are cycled
on and off to maintain a minimum high side
2.8 ENVIRONMENTAL pressure.
PROTECTION 2. Water-cooled dryers Utilize a water control
valve piloted by a sensing bulb that reacts to
1. US/EU laws protect the environment against the high side refrigerant pressure controlling
refrigerant being released into the atmo- the water flow Maintain a minimum high side
sphere. pressure.
2. An annual leak control test at less than 5.0
2.10.3 REFRIGERANT CIRCUIT PROTECTION
gr/year should be performed by a qualified
engineer if the refrigerant dryer contains 1. High/Low pressure safety switch:
more than 4.4 lbs / 2 kg of refrigerant. This
control test has to be done twice a year if the Refrigerant circuits are protected against
dryer contains more than 66 lbs / 30 kg. excessive pressure by a safety switch that
stops the compressor in cases of high or low
3. Prior to dryer disposal, the refrigerant must
refrigerant pressure. If this safety switch has
be properly recovered by a qualified engi-
tripped out on high refrigerant pressure, it
neer.
has to be manually reset before the dryer
can be restarted. A low pressure trip will
2.9 PRODUCT DESCRIPTION automatically reset.
This refrigerated compressed air dryer has been 2.10.4 FILTER DRIER
designed to remove water vapor from industrial
compressed air that is free of any aggressive Total water removal in the refrigerant circuit is
contaminants like ammonia, gaseous acid, dust, rust, achieved by a filter drier who also traps any solid
liquid condensate, any other chemical or mineral particles that may have migrated into the circuit
substances capable of attacking or clogging the heat during assembly.
exchanger(s). 2.10.5 CRANKCASE HEATER
The optional, water-cooled condenser is not 3-Phase dryers are equipped with an electric
designed for use with seawater or water containing crankcase heater. The heater provides preliminary
aggressive contaminants. pre-heating of the refrigerant compressor to
Please contact your factory representative for further evaporate liquid refrigerant possibly condensed in
questions on this issue. This dryer has been the crankcase. This will prevent liquid shock that can
designed for indoor operation only.

11
PRODUCT USER MANUAL SECTION 2

damage the compressor. point. Maximum condensation of moisture


occurs at the coldest point and it is at that
exact junction that the moisture is removed
and drained.
WARNING
2.10.9 DEW POINT INDICATOR
Never run the dryer before heating the
The Dew point indicator is a standard on all dryer
crankcase. Allow 2 hours the heater to heat
models and is located in the control panel and
the compressor of the dryers after a long
provides an idea for the pressure dew point (PDP)
shut-down period.

2.10.6 REFRIGERANT CIRCUIT REGULATION IN


RD-0400 – RD-6000 2.10.10 HIGH TEMPERATURE SWITCH—
1. The liquid refrigerant is injected into the Located inside the dryer, this high temperature
evaporator through a metering device trying switch stops the dryers if the compressor suction line
to maintain the refrigerant in the evaporator temperature is above 113°F / 45°C.
at a constant pressure 2.10.1 MICROPROCESSOR DEVICE
2. The evaporating pressure is kept constant by This device is supplied on all models. The
a controlled injection of hot gas from the Microprocessor allows the dryer to save energy
high-pressure side into the low-pressure when there is no flow in the dryer. It is possible to
section of the circuit through a hot gas by- monitor major dryer failures on the Microprocessor. It
pass valve. This constant pressure corre- allows the operators to monitor the following:
sponds to a stable evaporating temperature
adjusted as close to 32°F / 0°C as possible. • Evaporation temperature
• Inlet air temperature
3. The mixture of hot gas from the by-pass valve
and cold gas from the evaporator is called • Ambient temperature
superheat and is adjusted at 50 ± 5°F / 10± • Refrigerant gas high and low temperatures
5°C. • Fan is working properly
2.10.7 CONDENSATE DRAIN—TRAP • Compressor is working properly
ASSEMBLY • Condenser is blocked
Dismantling the drain is easy because it can be • Power Phases are correctly connected
isolated from the air circuit under pressure with a ball • Drain function
valve. Always isolate the drain before disassembly. • Total working hours
Membrane disc may need to be replaced time to time
• Total economy hours
due to contamination in the air circuit. Contact Sullair
or its distributer if there is any drain blockage issues. • Real date and time

2.10.8 HEAT EXCHANGER, MODULAR DESIGN Microprocessor can be remotely controlled and any
alarm contacts can be connected to any external
The dryers are equipped with compact, modular devices.
design heat exchangers. This assembly has been
specially designed to dry compressed air and 2.11 PRINCIPLE OF OPERATION
consists of:
The refrigerant circuit can be divided in 3 parts:
1. An air/air heat exchanger which pre-cools
the entering hot air with the exiting chilled air. 1. Low pressure section with an evaporator
(heat exchanger)
2. An evaporator which is an air/refrigerant heat
exchanger which cools down the com- 2. High pressure section including: Condenser,
pressed air liquid receiver, (if installed) and the filter
dryer.
3. An integral separator that separates the
moisture from the air stream at the coldest

12
SECTION 2 PRODUCT USER MANUAL

3. Control circuit including: Compressor, meter- gaseous refrigerant into the low pressure refrigerant
ing device, hot gas by-pass valve (if circuit.
installed), fan pressure switch, safety high/
low pressure switch. Water cooled dryers are 2.12 COMPRESSED AIR HEAT
equipped with a water flow control EXCHANGER
valve.Refrigeration Heat Exchanger
1. The saturated, hot compressed air flows into
The compressor compresses gaseous refrigerant.
the air/air heat exchanger where it is pre
The hot refrigerant gas condenses in the condenser cooled by the out going chilled air.
and once liquefied it passes through the liquid
2. The compressed air then enters the evapo-
receiver (optional)
rator where it is cooled to the desired dew
The liquid refrigerant leaves the liquid receiver and is point.
injected into the evaporator (heat exchanger) by a
3. The cooled compressed air passes through
metering device (expansion valve).
the air/water separator where the liquid con-
This metering device is protected by a filter dryer, densate is removed by the centrifugal sepa-
that retains particles and humidity that could be in the ration and drained away by the automatic
circuit trap. The outgoing, chilled air is then warmed
up in the air/air heat exchanger by the hot
The injected liquid evaporates (changes states from
incoming air. This energy efficient air-to-air
liquid to gas) by absorbing heat from the compressed
heat exchanger significantly reduces the
air. The gaseous refrigerant is sucked into the
load on the compressor.
compressor and the cycle carries on.
4. As long as the compressed air temperature
In order to keep the evaporation pressure steady,
does not drop below dew point, there will be
and maintain the refrigerant temperature in the heat
no further condensation in the compressed
exchanger, a hot gas by-pass valve injects hot
air piping.

Figure 2-1: Typical Installation Diagram

13
PRODUCT USER MANUAL SECTION 2

2.13 PIPE/CONNECTION 2.14 ELECTRICAL CONNECTION


REQUIREMENTS REQUIREMENTS
Refer to Product Models and Specifications— The owner shall furnish all labor, materials,
Table 2-2, Table 2-3, Table 2-4, Table 2-5. equipment and services necessary for and
reasonably incidental to complete the installation of
all electrical as shown on the drawings.
The electrical installation and connection shall be
made in strict accordance with the requirements of
any and all City, County, State or Federal codes of
Law having jurisdiction, the requirements and
recommendations of the Board of Fire Underwriters,
including all amendments and / or additions to the
said codes, laws, requirements, and
recommendations, the requirements and
recommendations of the local utility, the Owner, and
the Standard Building Code.
The installer shall obtain all permits and inspections
required for the work, and shall pay all costs and fees
thereof.

2.15 OPERATING PRECAUTIONS

WARNING
Verify that the operating parameters match
with the nominal values stated on the data
nameplate of the dryer (voltage, frequency,
air pressure, air temperature, ambient tem-
perature, etc.).

This dryer has been thoroughly tested, packaged


and inspected prior to shipment. Nevertheless, the
unit could be damaged during transportation, check
the integrity of the dryer during first start-up and
monitor operation during the first hours of operation
Qualified personnel must perform the first start-up.
When installing and operating this equipment,
comply with all National Electrical Code and any
applicable federal, state and local codes.
Who is operating the unit is responsible for the
proper and safe operation of the dryer.
Never operate equipment with panels removed.

2.16 INSTALLATION
In addition to the general mechanical construction
procedures and local regulations, the following
instructions need to be emphasized:

14
SECTION 2 PRODUCT USER MANUAL

1. Only authorized, trained and skilled engi- (coalescing filter) that can act as a backup
neers should install the compressed air during short periods when the by-pass valve
dryer. is open to perform maintenance on the dryer.
Contact your Sullair representative/dealer for
2. Safety devices, protecting covers or insula-
suitable filters.
tions in the dryer are never to be removed or
modified. Each pressure vessel or accessory
installed outside the dryer with compressed
air (Any pressure above atmospheric pres-
sure) must be fitted with individual pressure
relief safety valves.
3. Install one (1) air by-pass valve and two (2)
switch off valves in the line to isolate the
dryer to allow easy maintenance and for pos-
sible isolation of the dryer without interrupt-
ing the compressed air flow.

5. Water Filter: For dryers with water cooled


condensers, a water filter should be installed
in the supply water piping. (Water Cooled
Units Only)
6. The interconnecting piping must be of the
correct size, pressure rating and match that
of the dryer Inlet and Outlet pipe sizes. DO
NOT use pipes of lesser diameter as this will
lead to additional pressure loss and will
affect the performance of your air dryer. If
4. In Line Filters: install one compressed air fil- you are in doubt, contact your Sullair distrib-
ter in line (particulate filter) before the dryer utor. It is recommended to use the same pipe
to protect it against dirt and possible clog- size as that of the dryer Inlet and Outlet.
ging of heat exchanger. Install an After-filter

15
PRODUCT USER MANUAL SECTION 2

2.17 STEPS TO UNDERTAKE 6. Remove any packaging and other material


BEFORE OPERATING which could obstruct the area around the
dryer.
1. Read this manual completely.
7. Activate the mains switch.
2. Review all safety precautions.
8. Turn on the main switch - pos. 1 on the con-
3. Use recommended pipe sizes as per specifi- trol panel.
cations.
9. Check that the mains power light of the ON/
4. DO NOT operate the dryer at pressures OFF button is ON.
above the maximum specified on the dryer
10. Wait at least two hours before starting the
label (check the technical specifications).
dryer (compressor crankcase heater must
5. DO NOT operate the dryer in temperatures heat the oil of the compressor)
above 120°F / 50°C degrees
11. Ensure the cooling water flow and tempera-
6. DO NOT operate the dryer with inlet air tem- ture is adequate (Water-Cooled).
peratures above 150°F / 65°C.
12. Switch ON the dryer pressing the button "I -
ON" of the ON/OFF switch on the digital con-
2.18 OPERATING PROCEDURES troller
This procedure should be followed on first start-up, 13. Ensure the data plate flow rate match with
after periods of extended shutdown or following plant consumption.
maintenance procedures. Qualified personnel must
14. If the dryer does not start to run check the
perform the start-up.
monitor on the Microprocessor. If the Phase
SEQUENCE OF OPERATIONS error is mentioned on the screen change the
Phases and re-start the dryer.
1. Ensure that all the steps of the “Installation”
chapter have been observed. 15. Allow the dryer temperature to stabilize 10-
15 minutes
2. Ensure that the connection to the com-
pressed air system is correct and that the 16. Slowly open the air inlet valve.
piping is suitably fixed and supported.
17. Slowly open the air outlet valve.
3. Ensure that the condensate drain pipe is
18. Slowly close the central by-pass valve of the
properly fastened and connected to a collec-
system (if optional By-pass valves are
tion system.
installed).
4. Ensure that the by-pass system (if installed)
19. Check the piping for air leakage.
is closed and the dryer is isolated.
20. Ensure the drain is regularly cycling - wait for
5. Ensure that the manual valve of the conden-
its first interventions.
sate drain circuit is open.

16
SECTION 2 PRODUCT USER MANUAL

2.19 STARTUP AND SHUT DOWN SEC 3.24 SHUT DOWN


PROCEDURE 1. Shut down the air compressor.
2. After few minutes, shut down the dryer
pressing the button "0 - OFF" of the digital
WARNING controller

For short periods of inactivity, (max 2-3


days) we recommend that power is main- NOTE
tained to the dryer and the control panel.
Otherwise, before re-starting the dryer, it is A Dew Point within 32° F and 50°F/0°C and
necessary to wait at least 2-3 hours for the +10°C displayed on Air Dryer Controller is
compressor crankcase heater to heat the oil correct according to the possible working
of the compressor. conditions (flow-rate, temperature of the
incoming air, ambient temperature, etc.).
SEC 3.23 START-UP:
1. Check the condenser for cleanliness (Air- During the operation, the refrigeration compressor
Cooled). will cycle ON/OFF on RD series. The dryer must
remain ON during the full usage period of the
2. Ensure the cooling water flow and tempera- compressed air, even if the air compressor works
ture is adequate (Water-Cooled).
intermittently.
3. Check that the mains Disconnect ON/OFF
switch is ON.
4. Switch ON the dryer pressing the button "I - WARNING
ON" of the ON/OFF switch
5. Ensure that electronic Monitor is ON. The number of start/stop must be no more
than 6 time per hour. The dryer must stop
6. Wait a few minutes; verify that the Dew Point running for at least 5 minutes before being
temperature displayed on electronic instru- started up again.
ment is dropping and condensate drain is
discharging . The user is responsible for compliance with
these rules. Frequent start/Stop may cause
irreparable damage to refrigeration com-
pressor.

17
PRODUCT USER MANUAL SECTION 2

2.20 MAINTENANCE 2.20.2 MAINTENANCE BY THE USER


1. Keep the dryer clean.
2.20.1 MAINTENANCE BY AN ENGINEER/
TECHNICIAN 2. In case of more than 4 pounds of refrigerant,
the dryer should be regularly checked to be
1. Maintenance and repairs should only be per- leak free by qualified refrigerant engineer.
formed when the air dryer is shut down and Refer to section “Environmental protection”
depressurized and when the main power of this manual.
switch is turned OFF.
3. Every six months - check the correct opera-
2. Use only the appropriate tools for mainte- tion of the condenser drain trap. Replace
nance and repair. timer or solenoid valve in case of clogging or
malfunctioning.
3. Before dismantling any part that has been
pressurized, disconnect the pressure 4. Every six months - check and clean the drain
sources and depressurize the system com- strainer by undoing the access screw and
pletely. Shut off all valves and isolate the rinsing the filter with tap water to remove the
dryer. trapped dirt from the inside.
4. Proceed carefully during maintenance and 5. Every month clean the air condenser with a
repair. Prevent dirt from entering by covering brush or compressed air as soon as it’s dirty
parts and orifices with a clean cloth, paper or or clogged. Take extra care not to bend the
tape. fins of the condenser heat exchanger.
5. Receiver tanks should never be welded or 6. Check the troubleshooting list in case of
modified in any way. maintenance issues.
6. Never leave tools, loose parts or cleaning 7. Check operating pressures, temperatures
rags in or on the air dryer. and time settings after maintenance. If oper-
ating and safety devices function properly,
7. Before connecting the dryer back online,
the air dryer may be used.
check the setting of the control and safety
devices as well as the pressure and the tem- 8. For water-cooled condensers—Use only
perature of the compressed air circuit. clean water when cleaning the condenser.
Water should be jet-streamed from the outlet
8. For dryers with water-cooled condensers—
side to the inlet side.
End caps of water condenser can be disas-
sembled for cleaning with help of a water jet.

Table 2-1: Recommended Maintenance


Semi-
Recommended Maintenance Activity Weekly Monthly Annual
Annual

Air Condenser Cleaning X


Water condenser cleaning X
Replacement of Filter Element X
Refrigerant Gas Leak
X
(for dryers containing more then 4 lb / 1.49 kg of gas)
Refrigerant Gas Leak
X
(for dryers containing more then 66 lb / 24.63 kg of gas)
Drain control X
Cleaning drain strainer inside drain ball valve X
Cleaning or replacing drain membrane valve
X
(250CFM / 7.08 CMM and larger models)
Monitoring working conditions X

18
SECTION 2 PRODUCT USER MANUAL

2.21 TROUBLESHOOTING
Problem Possible Cause Repair Comments
Dryer is switched on, The connection has Invert two phases 3-phase dryers are equipped with
indicator light is lit but the inverted phases a phase controller to avoid the
refrigerant compressor fans from turning in the opposite
does not turn on. direction.
Refrigeration unit is not Check refrigeration compres- Several factors can cause com-
functioning sor pressor failure. A qualified refrig-
eration technician needs to check
all the electrical and refrigerant
circuit and controls.
The refrigerant high pres- The refrigerant safety high The dryer is protected against
sure protection has pressure switch has tripped. excessively high refrigerant pres-
tripped sure. If the condenser efficiency
has reduced, the switch will trip.
Manually reset the switch
In case of water cooled con-
densers, check the water con-
trol valve
Excessive ambient tem- Be sure that dryer is working A high ambient temperature may
perature in temperatures lower than the cause the refrigerant system to
design conditions. Designed operate at higher than normal
conditions and correction fac- pressures. Results will be higher
tors are described in this man- than normal evaporator tempera-
ual . ture. Important: adequate air cir-
culation around the dryer, and
proper ventilation in the equip-
ment room should guarantee a
low enough ambient temperature.
Dryer is switched on but Excessive temperature on Allow time to compressor to Compressor is protected against
the refrigerant compres- crankcase of compressor. cool down. Reason may be a overly high temperatures of the
sor does not turn on. possible incorrect adjustment crankcase by a thermal switch.
of hot gas bypass valve or
shortage of refrigerant
Excessive compressed Be sure that dryer is working The dryer is designed for working
air inlet temperature. in temperatures lower than in calculated conditions (see
design conditions. description in this manual). If con-
ditions are exceeded, the dryer
will be overflowed, dew point will
go up and protecting devices can
switch off.

19
PRODUCT USER MANUAL SECTION 2

Problem Possible Cause Repair Comments


Dryer is switched on but Clogged condenser fins Clear fins or water The clogged fins in the con-
the refrigerant compres- or clogged water condenser of all denser will restrict the air pas-
sor does not turn on. condenser. obstructions. sage and reduce the refrigeration
capacity, causing high tempera-
Possible high crankcase ture in the evaporator. Same will
temperature occur if water condenser is
clogged with mud or dirt. Air con-
Possible loss of phase denser and water condenser
should be periodically checked
Possible low voltage caus- and cleaned. Protect water circuit
ing overload trip by an adapted filter.

Possible failed compres-


sor
Too much compressed air Check actual flow This dryer is designed for a maxi-
flow. through the dryer. mum air flow at design condi-
tions. If too much air is pumped
into the dryer, water removal
capacity may not be sufficient,
resulting in liquid carryover down-
stream. Check the rated output
the air compressor.
Faulty electrical wiring Inspect the circuit The compressor-on light should
be wired into the refrigerant
compressor circuit. See wiring
diagrams in this manual.
One electrical protection Reset the protection or The dryer is protected against
has tripped. replace the blown fuse. high amp draw by fuse and/or
overload relay that can trip in
case of need. Reset or replace
fuse once, but do not persist if it
trips again, request assistance
from a qualified refrigeration con-
tractor.
Dryer is switched on but Fan has to run if refriger- Check that compressed air Fan operates automatically to
fan is not running. ant high pressure reaches flows through the dryer. Check keep refrigerant pressure below
upper set point. that fan blades are free to the maximum value. The fan can
move. Check the fan pressure stop if pressure is under
switch. the recommended setting.
When compressor starts, Compressor is slugging Be sure the pre-heating period Refrigerant may move between
it vibrates a lot and liquid refrigerant at start- of at least 2 hours is receivers when refrigerant com-
makes mechanical noise. up. respected pressor is stopped and not
heated, especially if stopped for a
long time. This migration may
cause liquid shock (slugging) in
valves specially on large dryers
containing more refrigerant.

20
SECTION 2 PRODUCT USER MANUAL

Problem Possible Cause Repair Comments


Water in system Compressed Air Inlet and Check inlet and outlet connec- This dryer is designed for air flow
outlet connections are tions. in one direction only. Inlet and
reversed. outlet directions are identified on
the dryer.
Drain system is clogged Restore a free flow Drain system is timed solenoid
or inoperative. of water condensate. valve, pneumatically assisted
Check water which has to be adjusted in
evacuation. accordance with values listed in
this manual.
The Solenoid valve includes a
strainer that has to be periodically
checked and cleaned. Mem-
branes of pneumatically assisted
drain have to be checked or
replaced every 6 months.
Bypass system is open Check the valves Important: Bypass piping should
be installed around the dryer so
the dryer can be isolated for ser-
vice without shutting down the air
supply. During dryer operation,
valves must be set so all air goes
into the system. Check tightness
of the bypass system.
Free moisture remains in Blow out the system Before the dryer is first started all
pipe lines. free moisture should be blown
out of the system.
Excessive air flow Check actual flow This dryer is designed for a maxi-
through the dryer. mum air flow. If too much air is
pumped into the dryer, water
removal capacity may not be suf-
ficient, resulting in liquid Carry-
over downstream. Check the
rated flow of the air compressor.

21
PRODUCT USER MANUAL SECTION 2

Problem Possible Cause Repair Comments


Water in system Excessive free moisture Check the separator In some system there may be an
and drain system and com- accumulation of free moisture in
pressor after cooler the line ahead of the dryer. If this
ahead of the dryer. moisture is pumped into the dryer
intermittently, the water removal
capacity may not be sufficient. A
water separator should be
installed in the line before the
dryer.
Excessive compressed Be sure that dryer is working The dryer is designed to work for
air inlet temperature. lower than design conditions calculated design conditions.
Should the conditions be
exceeded, the dryer will be over-
flowed, dew point will go up and
protecting devices can switch off.
Clogged condenser fins Clear fins of all The clogged fins in the con-
obstructions denser will restrict air passage
and reduce refrigerant capacity
causing water downstream. Fins
should be periodically checked
and cleaned.
Shortage of refrigerant Fix the leak and add a Loss of refrigerant will cause
charge of refrigerant. improper functioning. A qualified,
refrigeration specialist should
perform the necessary repairs, or
factory should be contacted if the
unit is in warranty.
Refrigeration system is Check to be certain To check if the compressor is run-
not functioning refrigerant compressor ning, check compressor-on light.
is running It is possible for the fan to be
operating but not the compressor.
Compressor not running can be
caused by several factors. A
qualified refrigeration technician
should check all refrigerant and
electrical controls
Excessive pressure Readjust refrigerant The refrigerant pressure adjust-
dew point evaporating pressure ment should be done by a quali-
fied refrigeration engineer. This is
a very sensitive device and incor-
rect settings may create other
failures.

22
SECTION 2 PRODUCT USER MANUAL

Problem Possible Cause Repair Comments


High pressure drop Excessive compressed Check actual This dryer is designed for a
air flow or too low air inlet pressure and flow maximum air flow. If too much
pressure. through the dryer. air is pumped into the dryer,
water removal capacity may
not be sufficient, resulting in
liquid carry-over downstream.
Check the rated flow of the
air compressor.
Freeze up Check that compressor room Frosting of the lines is an indica-
ambient is above 41°F. tion that controls are set too low.
The following should be done by
an experienced refrigeration
technician.
Fan switch could have failed Controls may be adjusted in the
in closed position keeping fan fields by means of the hot gas
on. bypass valve. This is to be done
by a qualified refrigerant techni-
cian.
Clogged heat exchanger Clean heat exchanger Dryer are supposed to be used
with a reverse air flow. with compressed air free of any
aggressive contaminants. Some
contamination may require extra
maintenance of the heat
exchanger. Contact your Sullair
Distributor.
The unit will not run or Line disconnect switch is Close the start or disconnect If the dryer is not operating,
cycles off and on. open. switch. check the disconnect switch or
circuit breaker to be certain it is
on.
Fuse or breaker is open Replace fuse or reset breaker. The fuse to the power line should
be checked and replaced if
needed. Never replace a burnt
fuse with an oversized fuse.
Faulty refrigerant Determine the cause Failure of compressor to run may
compressor or controls. and make correction be caused by several factors. A
qualified refrigeration specialist
should check all electrical and
refrigeration controls, or factory
should be contacted if unit is in
warranty.

23
PRODUCT USER MANUAL SECTION 2

Problem Possible Cause Repair Comments


The unit will not run or Excessive compressed air Design conditions and correc- The dryer is designed for working
cycles off and on. inlet temperature. tion factors are described in into calculated design conditions.
this manual. Should the conditions be
Be sure that dryer is working exceeded, the dryer will be over-
in ambient temperatures flowed, dew point will go up and
below design conditions. protecting devices may trip.
Excessive ambient tem- Designed conditions and cor- A high ambient temperature may
perature rection factors are described cause the refrigerant system to
in dryer . Be sure that dryer is operate at higher than normal
working lower than design pressures. Results will be a
conditions. higher than normal evaporator
temperature.
Important: there should be ade-
quate air circulation around the
dryer, and proper ventilation in
the equipment room should guar-
antee a low enough ambient tem-
perature.
Clogged condenser fins Clear fins of all obstructions. The clogged fins in the con-
denser will restrict the air pas-
sage and reduce the refrigeration
capacity, causing high tempera-
ture in the evaporator.
Fins should be periodically
checked and cleaned.
Shortage of refrigerant Fix the leak and add a charge Loss of refrigerant will cause
of refrigerant. improper functioning. Dryers are
equipped with a temperature
switch which maintains the
amount of refrigerant to maintain
proper cooling of the compressor.
A shortage of refrigerant may
cause suction line to become
very hot, causing the temperature
switch to trip.
A qualified refrigeration specialist
should perform the necessary
repairs.
Error sign occurs on The dew point is too low or Check refrigerant gas and If there is not enough refrigerant-
digital temperature too high. make sure that the working gas or if the working temperature-
control device conditions are within the cor- and inlet temperatures are very
rect range. high, the dew point will increase.

24
2.22 SETTINGS

SECTION 2
Ideal value that should
No Temperature Set Points Page What does it show? Set Points (°C / °F)
be seen (°C/°F)
1- Inlet Air Temp. - Low Alarm Setpoint The bottom limit of the Dryer air inlet temperature 0 / 32
35 / 95
2- Inlet Air Temp. - High Alarm Setpoint The top limit of the Dryer air inlet temperature 55 / 131
3- Exchanger Temp. - Low Alarm Setpoint The bottom limit of the refrigerant gas temperature in the Evaporator (-)3 / 26,6
2-10 / 36-50
4- Exchanger Temp. - High Alarm Setpoint The top limit of the refrigerant gas temperature in the Evaporator 20 / 68
The bottom limit of the refrigerant gas temperature in the
5- Low Pressure Line Temp. - Low Alarm Setpoint (-)5 / 23
Low pressure side of the refrigerant circuit
7-20 / 45-68
The top limit of the refrigerant gas temperature in the
6- Low Pressure Line Temp. - High Alarm Setpoint 45 / 113
Low pressure side of the refrigerant circuit
The bottom limit of the refrigerant gas temperature in the
7- High Pressure Line Temp. - Low Alarm Setpoint 0 / 32
High pressure side of the refrigerant circuit
40-80 / 104-176
The top limit of the refrigerant gas temperature in the High pressure
8- High Pressure Line Temp. - High Alarm Setpoint 90 / 194
side of the refrigerant circuit
The bottom limit of the Ambient air temperature
9- Ambient Temperature - Low Alarm Setpoint 0 / 32
(Dryer room temperature)
25 / 77
The top limit of the Ambient air temperature
10- Ambient Temperature - High Alarm Setpoint 55 / 131
(Dryer room temperature)
Dryer stops automatically when the evaporation
11- Exchanger Temp. - ECO Start Setpoint 2 / 36
temperature goes below that temperature
Dryer starts automatically when the evaporation
12- Exchanger Temp. - ECO End Setpoint 8 / 46
temperature goes above that temperature
13- Condenser Temp. - Dif. Setpoint Temperature between refrigerant inlet and outlet of the condenser 5/5

No Time Parameters Page Set Points


When the dryer is turned on Controller does not read evaporator temperature for sometime
1- Exchanger Temp. - Alarm Delay (Minute) 20

PRODUCT USER MANUAL


until the refrigerant circuit stabilizes
Controller does not stop the dryer during that time after the evaporation temperature goes
2- ECO Start Delay (Minute) 10
below the set temperature
When the dryer is turned on the controller does not measure Low and High temperatures
3- Low Pressure Line Temp. - High Alarm Delay (Minute) 10
for a period of time
4- Restart Delay (Second) When the dryer stops it does not re-start for some seconds because of safety 30
5- Drain Off Time (Minute) Timer drain is "off" during that time 3
6- Drain On Time (Second) Timer drain is "on" during that time 5
7- Filter Change Period (Hour) Warning to the customer to replace the elements of their filters 8000
8- General Maintenance Period (Hour) Warning to the customer to get a service from Sullair 20000
25
26

PRODUCT USER MANUAL


Table 2-2: DP Power 60H

Rated
STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbed
GROUP SULLAIR PART SULLAIR PART Flow Port Size
VOLTAGE Rated Conditions REF MODEL REF Drop Power
[1]

scfm (psid) (kW) (in)


Non-
230/3/60 400 RD-0400-230-60-A 02250193-849 400 2.7 1.92 2" NPT-F
Cycling
Non-
460/3/60 400 RD-0400-460-60-A 02250193-981 400 2.7 1.92 2" NPT-F
Cycling
Non-
575/3/60 400 RD-0400-575-60-A 02250194-136 400 2.7 1.92 2" NPT-F
Cycling
Non-
230/3/60 500 RD-0500-230-60-A 02250193-850 500 3.9 2.35 2" NPT-F
Cycling
Non-
460/3/60 500 RD-0500-460-60-A 02250193-982 500 3.9 2.35 2" NPT-F
Cycling
Non-
575/3/60 500 RD-0500-575-60-A 02250194-137 500 3.9 2.35 2" NPT-F
Cycling
Non-
230/3/60 700 RD-0700-230-60-A 02250193-851 RD-0700-230-60-W 02250193-861 700 3.1 3.45 3" NPT-M
Cycling
Non-
460/3/60 700 RD-0700-460-60-A 02250193-983 RD-0700-460-60-W 02250194-107 700 3.1 3.45 3" NPT-M
Cycling
Non-
575/3/60 700 RD-0700-575-60-A 02250194-138 RD-0700-575-60-W 02250194-161 700 3.1 3.45 3" NPT-M
Cycling
Non-
230/3/60 850 RD-0850-230-60-A 02250193-852 RD-0850-230-60-W 02250193-862 850 2.4 3.53 3" NPT-M
Cycling
Non-
460/3/60 850 RD-0850-460-60-A 02250193-984 RD-0850-460-60-W 02250194-108 850 2.4 3.53 3" NPT-M
Cycling
Non-
575/3/60 850 RD-0850-575-60-A 02250194-139 RD-0850-575-60-W 02250194-162 850 2.4 3.53 3" NPT-M
Cycling
Non-
575/3/60 1000 RD-1000-575-60-A 02250194-140 RD-1000-575-60-W 02250194-163 1000 2.8 3.64 3" NPT-M
Cycling
Non-
460/3/60 1220 RD-1200-460-60-A 02250193-986 RD-1200-460-60-W 02250194-110 1250 2.95 4.65 3" NPT-M
Cycling
Non-
575/3/60 1250 RD-1200-575-60-A 02250194-141 RD-1200-575-60-W 02250194-164 1250 2.95 4.65 3" NPT-M
Cycling
Non-
460/3/60 1600 RD-1600-460-60-A 02250193-988 RD-1600-460-60-W 02250194-113 1600 3.1 5.45 4" FLG
Cycling
Non-
575/3/60 1600 RD-1600-575-60-A 02250194-142 RD-1600-575-60-W 02250194-165 1600 3.1 5.45 4" FLG
Cycling
Non-
460/3/60 2000 RD-2000-460-60-A 02250193-989 RD-2000-460-60-W 02250194-114 2000 3.4 7.72 4" FLG
Cycling

SECTION 2
Non-
575/3/60 2000 RD-2000-575-60-A 02250194-143 RD-2000-575-60-W 02250194-166 2000 3.4 7.72 4" FLG
Cycling
Non-
460/3/60 2500 RD-2400-460-60-A 02250193-990 RD-2400-460-60-W 02250194-115 2500 3.2 9.22 6" FLG
Cycling
27

PRODUCT USER MANUAL


Table 2-2: DP Power 60H

Rated
STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbed
GROUP SULLAIR PART SULLAIR PART Flow Port Size
VOLTAGE Rated Conditions REF MODEL REF Drop Power
[1]

scfm (psid) (kW) (in)


Non-
575/3/60 2500 RD-2400-575-60-A 02250194-144 RD-2400-575-60-W 02250194-167 2500 3.2 9.22 6" FLG
Cycling
Non-
460/3/60 3000 RD-3000-460-60-A 02250193-991 RD-3000-460-60-W 02250194-116 3000 2.6 12.25 6" FLG
Cycling
Non-
575/3/60 3000 RD-3000-575-60-A 02250194-145 RD-3000-575-60-W 02250194-168 3000 2.6 12.25 6" FLG
Cycling
Non-
460/3/60 3800 RD-3800-460-60-A 02250193-992 RD-3800-460-60-W 02250194-117 3800 2.8 14.62 6" FLG
Cycling
Non-
575/3/60 3800 RD-3800-575-60-A 02250194-146 RD-3800-575-60-W 02250194-169 3800 2.8 14.62 6" FLG
Cycling
Non-
460/3/60 5000 RD-5000-460-60-A 02250193-993 RD-5000-460-60-W 02250194-118 5000 3.5 18.78 8" FLG
Cycling
Non-
575/3/60 5000 RD-5000-575-60-A 02250194-147 RD-5000-575-60-W 02250194-170 5000 3.5 18.78 8" FLG
Cycling
Non-
460/3/60 6000 RD-6000-460-60-A 02250193-994 RD-6000-460-60-W 02250194-119 6000 3.5 22.27 8" FLG
Cycling
Non-
575/3/60 6000 RD-6000-575-60-A 02250194-148 RD-6000-575-60-W 02250194-171 6000 3.5 22.27 8" FLG
Cycling

Table 2-3: DP Power 50H

Rated
STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbe
GROUP SULLAIR PART SULLAIR PART Flow Port Size
VOLTAGE Rated Conditions REF MODEL REF Drop d Power
[1]

scfm (psid) (kW) (in)


Non-Cycling 400/3/50 400 RD-0400-400-50-A 02250193-917 400 3.4 1.92 2" NPT-F
Non-Cycling 400/3/50 500 RD-0500-400-50-A 02250193-918 500 3.9 2.35 2" NPT-F
Non-Cycling 400/3/50 700 RD-0700-400-50-A 02250193-919 RD-0700-400-50-W 02250193-947 700 2.5 3.45 3" NPT-M
Non-Cycling 400/3/50 850 RD-0850-400-50-A 02250193-920 RD-0850-400-50-W 02250193-948 850 2.8 3.64 3" NPT-M
Non-Cycling 400/3/50 1000 RD-1000-400-50-A 02250193-921 RD-1000-400-50-W 02250193-949 1000 3.1 3.64 3" NPT-M

SECTION 2
Non-Cycling 400/3/50 1200 RD-1200-400-50-A 02250193-922 RD-1200-400-50-W 02250193-950 1200 3.5 4.5 3" NPT-M
Non-Cycling 400/3/50 1600 RD-1600-400-50-A 02250193-923 RD-1600-400-50-W 02250193-951 1600 3.1 5.54 4" FLG
Non-Cycling 400/3/50 2000 RD-2000-400-50-A 02250193-924 RD-2000-400-50-W 02250193-953 2000 2.5 7.72 4" FLG
Non-Cycling 400/3/50 2400 RD-2400-400-50-A 02250193-925 RD-2400-400-50-W 02250193-954 2400 2.5 9.22 6" FLG
SECTION 2
Table 2-3: DP Power 50H

Rated
STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbe
GROUP SULLAIR PART SULLAIR PART Flow Port Size
VOLTAGE Rated Conditions REF MODEL REF Drop d Power
[1]

scfm (psid) (kW) (in)


Non-Cycling 400/3/50 3000 RD-3000-400-50-A 02250193-926 RD-3000-400-50-W 02250193-955 3000 2.8 12.25 6" FLG
Non-Cycling 400/3/50 3800 RD-3800-400-50-A 02250193-927 RD-3800-400-50-W 02250193-956 3800 2.8 14.62 6" FLG
Non-Cycling 400/3/50 5000 RD-5000-400-50-A 02250193-928 RD-5000-400-50-W 02250193-958 5000 3.5 18.78 8" FLG
Non-Cycling 400/3/50 6000 RD-6000-400-50-A 02250193-929 RD-6000-400-50-W 02250193-959 6000 3.5 22.27 8" FLG

Table 2-4: Models 60HZ


Capacity
WATER Rated Pressure Absorbed
GROUP STANDARD
SCFM @ AIR COOLED SULLAIR SULLAIR
COOLED Flow Port Size Width Height Depth Weight
VOLTAGE Rated MODEL REF PART PART Drop Power
MODEL REF [1]
Conditions

scfm (psid) (kW) (in) in mm in mm in mm lbs kg


Non- 230/3/60 400 RD-0400-230-3-60-A 02250193-849 400 2.7 2.13 2" NPT 23.5 595 49.6 1260 28.3 718 341 155
Cycling
Non-
460/3/60 400 RD-0400-460-3-60-A 02250193-981 400 2.7 2.19 2" NPT 23.5 595 49.6 1260 28.3 718 341 155
Cycling
Non-
575/3/60 400 RD-0400-575-3-60-A 02250194-136 400 2.7 2.1 2" NPT 23.5 595 49.6 1260 28.3 718 341 155
Cycling
Non-
230/3/60 500 RD-0500-230-3-60-A 02250193-850 500 3.9 2.7 2" NPT 31.9 810 58.9 1495 45.9 1166 1056 480
Cycling
Non- 460/3/60 500 RD-0500-460-3-60-A 02250193-982 500 3.9 2.88 2" NPT 31.9 810 58.9 1495 45.9 1166 1056 480
Cycling
Non-
575/3/60 500 RD-0500-575-3-60-A 02250194-137 500 3.9 2.6 2" NPT 31.9 810 58.9 1495 45.9 1166 1056 480
Cycling
Non- RD-0700-230-
230/3/60 700 RD-0700-230-3-60-A 02250193-851 3-60-W 02250193-861 700 3.1 3.92 3" NPT 31.9 810 58.9 1495 45.9 1166 1056 480
Cycling
Non- RD-0700-460-

PRODUCT USER MANUAL


460/3/60 700 RD-0700-460-3-60-A 02250193-983 3-60-W 02250194-107 700 3.1 3.88 3" NPT 31.9 810 58.9 1495 45.9 1166 1056 480
Cycling
Non- 575/3/60 700 RD-0700-575-3-60-A 02250194-138 RD-0700-575-
Cycling 3-60-W 02250194-161 700 3.1 3.7 3" NPT 31.9 810 58.9 1495 45.9 1166 1056 480
Non- RD-0850-230-
230/3/60 850 RD-0850-230-3-60-A 02250193-852 3-60-W 02250193-862 850 2.4 4.38 3" NPT 31.9 810 58.9 1495 45.9 1166 1100 500
Cycling
Non- RD-0850-460-
460/3/60 850 RD-0850-460-3-60-A 02250193-984 3-60-W 02250194-108 850 2.4 4.48 3" NPT 31.9 810 58.9 1495 45.9 1166 1100 500
Cycling
Non- RD-0850-575-
575/3/60 850 RD-0850-575-3-60-A 02250194-139 3-60-W 02250194-162 850 2.4 4.4 3" NPT 31.9 810 58.9 1495 45.9 1166 1100 500
Cycling
Non- RD-1000-460-
Cycling 460/3/60 1000 RD-1000-460-3-60-A 02250193-985 3-60-W 02250194-109 1000 2.8 5.28 3" NPT 31.9 810 73.8 1875 45.9 1166 1122 510
Non- RD-1000-575-
575/3/60 1000 RD-1000-575-3-60-A 02250194-140 3-60-W 02250194-163 1000 2.8 5.12 3" NPT 31.9 810 73.8 1875 45.9 1166 1122 510
Cycling
Non- RD-1200-460-
460/3/60 1250 RD-1200-460-3-60-A 02250193-986 3-60-W 02250194-110 1250 2.95 5.28 3" NPT 31.9 810 73.8 1875 45.9 1166 1122 510
Cycling
Non- RD-1200-575-
575/3/60 1250 RD-1200-575-3-60-A 02250194-141 02250194-164 1250 2.95 5.12 3" NPT 31.9 810 73.8 1875 45.9 1166 1122 510
28

Cycling 3-60-W
29

PRODUCT USER MANUAL


Table 2-4: Models 60HZ
Capacity
WATER Rated Pressure Absorbed
GROUP STANDARD
SCFM @ AIR COOLED SULLAIR SULLAIR
COOLED Flow Port Size Width Height Depth Weight
VOLTAGE Rated MODEL REF PART PART Drop Power
Conditions MODEL REF [1]

scfm (psid) (kW) (in) in mm in mm in mm lbs kg


Non- 460/3/60 1600 RD-1600-460-3-60-A 02250193-988 RD-1600-460-
3-60-W 02250194-113 1600 3.1 7.3 4" FLG 45.9 1166 79.9 2030 61.0 1550 1672 760
Cycling
Non- 575/3/60 1600 RD-1600-575-3-60-A 02250194-142 RD-1600-575-
Cycling 3-60-W 02250194-165 1600 3.1 7.2 4" FLG 45.9 1166 79.9 2030 61.0 1550 1672 760
Non- RD-2000-460-
460/3/60 2000 RD-2000-460-3-60-A 02250193-989 3-60-W 02250194-114 2000 3.4 9 4" FLG 45.9 1166 79.9 2030 61.0 1550 1705 775
Cycling
Non- 575/3/60 2000 RD-2000-575-3-60-A 02250194-143 RD-2000-575-
3-60-W 02250194-166 2000 3.4 8.8 4" FLG 45.9 1166 79.9 2030 61.0 1550 1705 775
Cycling
Non- 460/3/60 2500 RD-2400-460-3-60-A 02250193-990 RD-2400-460-
Cycling 3-60-W 02250194-115 2500 3.2 9.8 6" FLG 45.9 1166 79.9 2030 82.7 2100 1925 875
Non- RD-2400-575-
Cycling 575/3/60 2500 RD-2400-575-3-60-A 02250194-144 3-60-W 02250194-167 2500 3.2 9.6 6" FLG 45.9 1166 79.9 2030 82.7 2100 1925 875
Non- 460/3/60 3000 RD-3000-460-3-60-A 02250193-991 RD-3000-460-
3-60-W 02250194-116 3000 2.6 11.2 6" FLG 45.9 1166 79.9 2030 82.7 2100 2156 980
Cycling
Non- 575/3/60 3000 RD-3000-575-3-60-A 02250194-145 RD-3000-575-
Cycling 3-60-W 02250194-168 3000 2.6 11 6" FLG 45.9 1166 79.9 2030 82.7 2100 2156 980
Non- RD-3800-460-
Cycling 460/3/60 3800 RD-3800-460-3-60-A 02250193-992 3-60-W 02250194-117 3800 2.8 13.9 6" FLG 45.9 1166 79.9 2030 110.3 2800 2409 1095
Non- RD-3800-575-
575/3/60 3800 RD-3800-575-3-60-A 02250194-146 3-60-W 02250194-169 3800 2.8 13.7 6" FLG 45.9 1166 79.9 2030 110.3 2800 2409 1095
Cycling
Non- RD-5000-460-
460/3/60 5000 RD-5000-460-3-60-A 02250193-993 3-60-W 02250194-118 5000 3.5 18.2 8" FLG 45.9 1166 79.9 2030 110.3 2800 2420 1100
Cycling
Non- RD-5000-575-
Cycling 575/3/60 5000 RD-5000-575-3-60-A 02250194-147 3-60-W 02250194-170 5000 3.5 18 8" FLG 45.9 1166 79.9 2030 110.3 2800 2420 1100
Non- 460/3/60 6000 RD-6000-460-3-60-A 02250193-994 RD-6000-460-
3-60-W 02250194-119 6000 3.5 22.27 8" FLG 45.9 1166 79.9 2030 118.1 3000 2750 1250
Cycling
Non- RD-6000-575-
575/3/60 6000 RD-6000-575-3-60-A 02250194-148 3-60-W 02250194-171 6000 3.5 22.27 8" FLG 45.9 1166 79.9 2030 118.1 3000 2750 1250
Cycling

Table 2-5: Models 50Hz

Capacity SCFM Rated


STANDARD AIR COOLED MODEL SULLAIR WATER COOLED SULLAIR Pressure Absorbed Port
GROUP @ Rated Flow Width Height Depth Weight
VOLTAGE REF PART MODEL REF PART Drop Power Size
Conditions [1]

scfm (psid) (kW) (in) in mm in mm in mm lbs kg

Non-Cycling 400/3/50 400 RD-0400-400-3-50-A 02250193-917 400 3.4 1.92 2" 23.5 595 49.6 1260 28.3 718 341 155

Non-Cycling 400/3/50 500 RD-0500-400-3-50-A 02250193-918 500 3.9 2.35 2" 31.9 810 58.9 1495 45.9 1166 1056 480

Non-Cycling 400/3/50 700 RD-0700-400-3-50-A 02250193-919 RD-0700-400-3-50-W 02250193-947 700 2.5 3.45 3" 31.9 810 58.9 1495 45.9 1166 1056 480

Non-Cycling 400/3/50 850 RD-0850-400-3-50-A 02250193-920 RD-0850-400-3-50-W 02250193-948 850 2.8 3.64 3" 31.9 810 58.9 1495 45.9 1166 1100 500

SECTION 2
Non-Cycling 400/3/50 1000 RD-1000-400-3-50-A 02250193-921 RD-1000-400-3-50-W 02250193-949 1000 3.1 3.64 3" 31.9 810 73.8 1875 45.9 1166 1122 510

Non-Cycling 400/3/50 1200 RD-1200-400-3-50-A 02250193-922 RD-1200-400-3-50-W 02250193-950 1200 3.5 4.5 3" 31.9 810 73.8 1875 45.9 1166 1122 510

Non-Cycling 400/3/50 1600 RD-1600-400-3-50-A 02250193-923 RD-1600-400-3-50-W 02250193-951 1600 3.1 5.54 4”FLG 45.9 1166 79.9 2030 61.0 1550 1672 760
SECTION 2
Table 2-5: Models 50Hz

Capacity SCFM Rated


STANDARD AIR COOLED MODEL SULLAIR WATER COOLED SULLAIR Pressure Absorbed Port
GROUP @ Rated Flow Width Height Depth Weight
VOLTAGE REF PART MODEL REF PART Drop Power Size
Conditions [1]

scfm (psid) (kW) (in) in mm in mm in mm lbs kg

Non-Cycling 400/3/50 2000 RD-2000-400-3-50-A 02250193-924 RD-2000-400-3-50-W 02250193-953 2000 2.5 7.72 4"FLG 45.9 1166 79.9 2030 61.0 1550 1705 775

Non-Cycling 400/3/50 2400 RD-2400-400-3-50-A 02250193-925 RD-2400-400-3-50-W 02250193-954 2400 2.5 9.22 6"FLG 45.9 1166 79.9 2030 82.7 2100 1925 875

Non-Cycling 400/3/50 3000 RD-3000-400-3-50-A 02250193-926 RD-3000-400-3-50-W 02250193-955 3000 2.8 12.25 6"FLG 45.9 1166 79.9 2030 82.7 2100 1925 875

Non-Cycling 400/3/50 3800 RD-3800-400-3-50-A 02250193-927 RD-3800-400-3-50-W 02250193-956 3800 2.8 14.62 6"FLG 45.9 1166 79.9 2030 110.3 2800 2409 1095

Non-Cycling 400/3/50 5000 RD-5000-400-3-50-A 02250193-928 RD-5000-400-3-50-W 02250193-958 5000 3.5 18.78 8"FLG 45.9 1166 79.9 2030 110.3 2800 2420 1100

Non-Cycling 400/3/50 6000 RD-6000-400-3-50-A 02250193-929 RD-6000-400-3-50-W 02250193-959 6000 3.5 22.27 8"FLG 45.9 1166 79.9 2030 118.1 3000 2750 1250

PRODUCT USER MANUAL


30
CONTROLLER FOR REFRIGERANT DRYERS

Section 3
CONTROLLER
E-680 is designed as a controller for refrigerant type The front panel of the controller contains a four line
compressed air dryers. The controller has 8 20 character LCD display and 10 buttons that are
temperature sensor inputs. Each channel can be used in configuration and manual control operations.
configured for type J, type K thermocouple or Pt-100
The dimensions of the controller are 3.8 x 7.6 in / 96
resistance thermometer. These inputs are used to
x 192 mm (front panel) with a depth of 4.3 in / 110
measure the temperatures at various points in the
mm. The panel cutout should be 3.5 x 7.2 in / 90x185
dryer. The controller has also 8 digital (relay) outputs
mm. The operating voltage of the controller is 20 -
and 16 digital inputs. The digital outputs are taken
60V AC or 20 - 85V DC.
through the normally open contacts of the output
relays. The contact rating of the output relays are
10A at 250 V AC Digital inputs are activated by 24V 3.1 OPERATION
DC or AC.
The front panel view of E-680 controller is given in
The controller has an RS-485 communication Figure 3-1. The front panel of the controller contains
interface that can be used for remotely monitoring a four line 20 character LCD display, 9 buttons and
channel temperatures, set points, input and output one alarm indicator LED.
states. Modbus RTU protocol is used for
communication.

Figure 3-1: The Front Panel View of E-680 Controller

The buttons below the LCD display ( , , , output. While in normal operation, the drain output is
and ) are used in configuration operations. controlled according to the configured “drain on” and
“drain off” periods. When button is pressed the
button is used for manual control of the drain drain output is activated even if the dryer is in off state.

31
CONTROLLER FOR REFRIGERANT DRYERS SECTION 3

The dryer is automatically stopped if an anomaly is and buttons are used for starting and stopping
detected. In that case, the alarm output and the alarm the dryer respectively. If the dryer is stopped
indicator LED on the front panel become activated. In manually, it can not be started before “restart delay”
order to restart the dryer, alarm should be period is timed out.
acknowledged and “restart delay” period should be
timed out. Pressing button acknowledges the alarm
3.1.1 1. EXTERNAL CONNECTIONS
and de-energizes the alarm output and alarm LED. The back panel view and the connection terminals of
E-680 controller are given in Figure 3-2.

-01+ -02+ -03+ -04+ -05+ -06+ -07+ -08+

Figure 3-2: The Backpanel View of E-680 Controller

TERMINALS IN THE UPPER ROW TERMINALS IN THE MIDDLE ROW


These terminals are used for temperature sensors These terminals are used for digital outputs and
(Pt-100). digital inputs. The names and the functions in the
order of the terminal numbers are given in the
01 Inlet Air Temperature. following table.
02 Exchanger Temperature.
T.No Name Function
03 Low Pressure Line Temperature.
04 High Pressure Line Temperature. 1 COMM. For D. Out 1-4
2 COMM. For D. Out 1-4
05 Ambient Temperature.
3 D. OUTPUT 1 Compressor Motor
06 Auxiliary Channel Temperature. This tempera-
ture can be monitored, but sensor break has no 4 D. OUTPUT 2 Drain Output (Normal)
effect on the operation of the controller. 5 D. OUTPUT 3 Dryer is Running.
07 Spare Channel 1. 6 D. OUTPUT 4 Dryer is Stopped. In case of
fault, the output flashes.
08 Spare Channel 2.
7 -

Spare channels are measured by the controller, but 8 COMM. For D. Out 5-8
can not be monitored and sensor break for these 9 COMM. For D. Out 5-8
channels has no effect on the operation of the 10 D. OUTPUT 5 Drain Output (Inverted)
controller. 11 D. OUTPUT 6 Spare
12 D. OUTPUT 7 Spare

32
SECTION 3 CONTROLLER FOR REFRIGERANT DRYERS

T.No Name Function


TERMINALS IN THE LOWER ROW

13 D. OUTPUT 8 Alarm Output (Horn) The first 3 terminals are for operating voltage.
14 -
(Phase, Neutral and Ground) The ground terminal
should be connected to the chassis of the dryer.
15 COMM. For D. INPUTS
16 COMM. For D. INPUTS The last 3 terminals are for RS-485 communication
17 COMM. For D. INPUTS
line.
18 D. INPUT 1 Remote Start (Press and 3.1.2 NORMAL OPERATION
Release)
19 D. INPUT 2 Remote Stop (Press and
When the controller is powered on it displays the
Release) type and version message and then normal
20 D. INPUT 3 Compressor Fault
operation screen is displayed as shown below.
21 D. INPUT 4 Compressor Overload
22 D. INPUT 5 Fan Fault
23
24
D. INPUT 6
D. INPUT 7
Fan Overload
Phase Sequence Error
SULLAIR
25 D. INPUT 8 Remote Disable
26 D. INPUT 9 Fan Motor is On DEW POINT . 16°C
READY
27 D. INPUT 10 Configuration Enable
28 D. INPUT 11 Spare
29 D. INPUT 12 Spare
30 D. INPUT 13 Spare
31 D. INPUT 14 Spare The exchanger temperature and operation state of
32 D. INPUT 15 Spare the dryer is displayed in this screen. Sequentially
33 D. INPUT 16 Spare pressing button display other info related to the
dryer in 8 different screens. While one screen is
The contact rating of each output relay is 10A at 250 displayed, pressing button reverts to the normal
V AC. operation screen. The views of the screens in
Digital inputs are activated by 24V DC or AC. sequence of the appearance are shown below.

33
CONTROLLER FOR REFRIGERANT DRYERS SECTION 3

........

INLET AIR TEMP. TOTAL TIME : 22.2


20°C ECO TIME : 8.1
EXCHANGER.TEMP. RUN TIME : 22.2
18°C HIGH FILTER TIME: 22.2

LOW PRES.LINE TEMP. 1. REMOTE DISABLE


18°C 2. INLET AIR TEMP.HI
HIGH PRES.LINE TEMP. 3. EXCH TEMP.LO
18°C 4. COMPRESSOR FAULT

AMBIENT TEMPERATURE DATE : 22.03.10


19°C TIME : 12.30.45
AUXILIARY TEMP. DAY : MONDAY
18°C

COMPRESSOR OK D.INPUT1: LLLLLLLL


FAN MOTOR OK D.INPUT2: LLLLLLLL
PHASE SEQUENCE OK D.OUTPUT: LLLHHLLL
REMOTE CONTROL OK

34
SECTION 3 CONTROLLER FOR REFRIGERANT DRYERS

In the first 3 screens the sensor temperatures are If the drain output is activated, ‘DRAIN ON’ message
displayed. If the measured temperatures are is displayed at the end of the last line. While the fan
between their low and high limits, only the motor is running, ‘FAN MOTOR IS ON’ message is
temperature value is displayed, otherwise ‘LOW’ or displayed in the second line. In ECO mode the
‘HIGH’ message is added in the end of the line. In appearance of the display is given below.
case of sensor break, only ‘SENSOR BREAK’
message is displayed.
The fourth screen displays the states of the
compressor motor, fan motor, the phase sequence
and remote disable. This information is compiled
SULLAIR
from the digital inputs. (Digital Inputs 3 to 8) ECO(SEC.) : 234
In the first two line of the fifth screen the total and DEW POINT 8°C
ECO operation durations of the dryer are displayed. RUNNING
These values can not be reset. The third line displays
the run time since the last maintenance. The fourth
line indicates the filter usage time. If these times
exceed their set values (see section 2.3.3.), i.e.
The value at the end of the second row indicates the
general maintenance period and filter change period,
time in seconds since beginning of the ECO mode.
a flashing warning with a message ‘MAINTENANCE’
or ‘REPLACE FILTER’ is displayed in the fourth line If the dryer is stopped automatically because of an
of the display. anomaly, or manually by using button, the normal
operating screen is displayed as shown below.
The sixth screen displays the last four events that
caused the dryer to be stopped automatically.
The seventh screen displays the date and time.
The eighth screen displays the states of the digital SULLAIR
inputs and digital outputs. The letters ‘L’ and ‘H’
stands for ‘not activated’ and ‘activated’ states
respectively. DEW POINT 16°C
In order to start the dryer, all the temperatures except DISABLED 127
the exchanger temperature must be between their
low and high limits. The low pressure line
temperature can be ‘HIGH’. Digital inputs 3 to 8
should not be activated. If this is not the case,
The number at the end of the last line indicates the
instead of ‘READY’ message, ‘DISABLED’ message
remaining time in seconds from the restart delay. If
is displayed in the normal operation screen.
this number becomes zero and there is no anomaly,
When the dryer is started, the normal operation the dryer can be restarted.
screen is displayed as shown below..
button is used to change the temperature unit
from ºC to ºF or vice versa. When this button is
pressed, the control operation stops about 3 seconds
and all the temperature values are converted to the
SULLAIR selected unit.
The first line in the normal operation display
(MIKROPOR) is user configurable.
DEW POINT . 16°C
READY

35
CONTROLLER FOR REFRIGERANT DRYERS SECTION 3

3.1.3 CONFIGURATION MODE 4. Exchanger Temp. / High Alarm Setpoint


(68°F/20°C)
In order to enter into configuration mode, button
must be pressed at least 3 second duration. After this 5. Low Pressure Line Temp. / Low Alarm Setpoint
operation security code is asked. Security code is (23°F/-5°C)
adjusted by and buttons. After adjusting the 6. Low Pressure Line Temp. / High Alarm Setpoint
security code and pressing button, accesses the (113°F/45°C)
“General Parameters Page”. Here, and buttons 7. High Pressure Line Temp. / Low Alarm Setpoint
can be used to select the other pages. When a page (32°F/0°C)
is selected, pressing button accesses the first
8. High Pressure Line Temp. / High Alarm Setpoint
parameter in that page. Successively pressing
(194°F/90°C)
button will display the other parameters in that page.
After the last parameter or pressing button more than 9. Ambient Temperature / Low Alarm Setpoint
two seconds, reverts to the top of that page where a (32°F/0°C)
different page can be selected. When a parameter is
10. Ambient Temperature / High Alarm Setpoint
selected, its value can be edited by and (131°F/55°C)
buttons. In anywhere in the configuration pages,
pressing button quits the configuration mode and 11. Exchanger Temp. / ECO Start Setpoint
reverts to the normal operation. (36°F/2°C)

If the entered security code is not correct, all the 12. Exchanger Temp. / ECO End Setpoint
parameters except “Security Code” parameter in the (46°F/8°C)
“General Parameters Page” can be accessed but no 13. Condensor Temp. Diff. Set Point
modification is allowed. (5°F/5°C)
The value of the security code is determined by the TIME PARAMETERS PAGE
parameter “Security Code” in the “General
Parameters Page”. The factory setting of the security 1. Exchanger Temp. / Alarm Delay (Minute)
code is “10”. 2. ECO Start Delay (Minute)
The Configuration Pages and the parameters in the 3. Low Pressure Line Temp. / High Alarm Delay
configuration pages are given below. (Minute)
GENERAL PARAMETERS PAGE 4. Restart Delay (Second)
1. Language 5. Drain Off Time (Minute)
2. Communication Address 6. Drain On Time (Second)
3. Baud Rate 7. Filter Change Period (Hour)
4. Parity 8. General Maintenance Period (Hour)
5. Message Text DATE-TIME ADJUST PAGE
6. Security Code 1. Minutes
TEMPERATURE SET POINTS PAGE 2. Hours
(FACTORY SETTINGS)
3. Date
1. Inlet Air Temp. / Low Alarm Setpoint
(32°F/0°C) 4. Month

2. Inlet Air Temp. / High Alarm Setpoint 5. Year


(131°F/55°C) 6. Confirm (Y/N)
3. Exchanger Temp. / Low Alarm Setpoint ANALOG INPUT PARAMETERS PAGE
(27°F/-3°C)
1. 1. Channel Offset
2. 2. Channel Offset

36
SECTION 3 CONTROLLER FOR REFRIGERANT DRYERS

3. 3. Channel Offset 3. Ambient Temp. Cal. (Channel 1)


4. 4. Channel Offset 4. 1. RT Cal. (390 ohm)
5. 5. Channel Offset 5. 2. RT Cal. (390 ohm)
6. 6. Channel Offset 6. 3. RT Cal. (390 ohm)
7. 7. Channel Offset 7. 4. RT Cal. (390 ohm)
8. 8. Channel Offset 8. 5. RT Cal. (390 ohm)
9. 1. Channel Input Type 9. 6. RT Cal. (390 ohm)
10. 2. Channel Input Type 10. 7. RT Cal. (390 ohm)
11. 3. Channel Input Type 11. 8. RT Cal. (390 ohm)
12. 4. Channel Input Type The 7th and 8th Parameters in the “Time Parameters
Page” (Filter Change Period and Maintenance
13. 5. Channel Input Type
Period) and all the parameters in “Calibration Page”
14. 6. Channel Input Type can not be edited unless the Digital Input 10 is
activated (Configuration Enable).
15. 7. Channel Input Type
While ‘Filter Change Period’ parameter is selected,
16. 8. Channel Input Type
pressing the buttons and simultaneously, resets the
2.3.6. CALIBRATION PAGE FILTER TIME to 0.0.
1. 50mV Cal (Channel 1) While ‘Maintenance Period’ parameter is selected,
pressing the buttons and simultaneously, resets the
2. 0°C Cal. (Channel 1)
RUN TIME to 0.0.

37
NOTES

38
Section 4

TECHNICAL DRAWINGS

39
4.1 ED/SPARE PARTS—RD400 AIR COOLED
40

SECTION 4
02250196-586 R03
4.1 ED/SPARE PARTS—RD400 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-NUT-1200 CAGE NUT AND SCREW 27
2 M-CON-0400 CONDENSOR 1 30 M-SCR-6000 SCREW TYPE 2 16
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 31 M-TRF-6000 TRANSFORMER 1
4 M-DRI-1200 DRYER-DEHYDRATOR 1 32 M-PPR-6000 PHASE PROTECTION RELAY 1
5 M-EXC-0850 HEAT EXCHANGER 2 33 M-CNT-0400-400-3-50 CONTACTOR 1
6 M-EXV-0500 EXPANSION VALVE 1 34 M-FCN-1200 FAN CONTACTOR 1
7 M-BYV-1200 BY PASS VALVE 1 COMPRESSOR OVERLOAD
8 M-RCV-0700 LIQUID RECEIVER 1 35 SEE REF. TABLE PROTECTOR 1
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-FOP-0850-230-3-60-A FAN OVERLOAD PROTECTOR 1
10 M-FNS-6000 FAN ON/OFF SWITCH 1 37 M-SNS-6000 SENSOR PROBE 6
11 M-LPS-6000 LOW PRESSURE SWITCH 1 38 M-DBV-6000 DRAIN BALL VALVE 1
12 M-MKP-1200 MIKROPROCESSOR 1 39 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 4
13 M-MNS-1200 MAIN SWITCH 1 T CONNECTION FOR SWITCH
40 M-TSC-6000 CAPILLARY 1
14 M-SLV-6000-24 SOLENOID VALVE 1
41 M-CLP-1200 DRYER CLAMP 1
15 M-MMV-6000 MEMBRANE VALVE 1
42 M-BPC-1000 BY-PASS CLAMP 1
16 M-MMM-6000 MEMBRANE 1
43 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
17 M-CFR-0400 CABINET FRONT 1
44 M-CCB-0400 CONDUIT FOR CONTROL BOX 1
18 M-CSI-0400 CABINET SIDE 2
45 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
19 M-CRE-0400 CABINET REAR 1
46 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CTO-0400 CABINET TOP 1
47 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 7
21 M-CBA-0400 CABINET BASE 1
48 M-PWC-1200 POWER CONNECTOR 1
22 M-CBL-0400 CABINET LEG 4
49 M-CCK-0850 CONTACTOR CONNECTION KIT 1
23 M-HP1-0400 CABINETHORIZONTAL PROFILE 1 2
50 M-DFD-1200 DRAIN FIXING DEVICE 1
24 M-HP2-0400 CABINET HORIZONTAL PROFILE 2 2
51 M-SCP-0400 CAPILLARY FOR SWITCH 1
25 M-CTC-6000 CABINET TOP CORNER 4
CAPILLARY FOR SWITCH HIGH/LOW
26 M-CPS-6000 CABINET HANDLE 8
52 M-HLC-0400 PRESSURE 2
27 M-STU-6000 CABINET STUD AND NUT 12
53 M-REV-6000 RELIEF VALVE 1
28 M-FAS-6000 CABINET FASTENER 12

DRYER PART POWER COMPRESSOR OVERLOAD KIT FOR ELECTRICAL PANEL


DECAL CAPACITY NUMBER RATINGS COOLING COMPRESSOR (1) FAN MOTOR (3) PROTECTOR (35) (45)

RD400 400 CFM 02250193-825 230V/3Ph/60Hz AIR COOLED M-CMP-0400-230-3-60 M-FMT-0700-460-3-60 M-COP-0850 M-KEP-0400-230-3-60

RD400 400 CFM 02250193-906 430V/3Ph/50Hz AIR COOLED M-CMP-0400-460-3-60 M-FMT-0700-460-3-60 M-COP-0400 M-KEP-0400
RD400 400 CFM 02250193-965 430V/3Ph/60Hz AIR COOLED M-CMP-0400-400-3-50 M-FMT-0700-400-3-60 M-COP-0400 M-KEP-0400

RD400 400 CFM 02250194-123 575V/3Ph/60Hz AIR COOLED M-CMP-0400-575-3-60 M-FMT-0700-575-3-60 M-COP-0400 M-KEP-0400
41
4.2 ED/SPARE PARTS—RD500 AIR COOLED
42

SECTION 4
02250196-588 R03
4.2 ED/SPARE PARTS—RD500 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 31 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-0500 CONDENSOR 1 32 M-TRF-6000 TRANSFORMER 1
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-DRI-1200 DRIER-DEHYDRATOR 1 34 SEE REF. TABLE CONTACTOR 1
5 M-EXC-0850 HEAT EXCHANGER 2 35 M-FCN-1200 FAN CONTACTOR 1
6 M-EXV-0500 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
7 M-BYV-1200 BY PASS VALVE 1 36 SEE REF. TABLE PROTECTOR 1
8 M-SPR-1200 SEPARATOR 1 37 M-FOP-0850-230-3-60 FAN OVERLOAD PROTECTOR 2
9 M-RCV-0700 LIQUID RECEIVER 1 38 M-SNS-6000 SENSOR PROBE 6
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 1
11 M-FNS-6000 FAN ON/OFF SWITCH 1 ELBOW FOR HEAT EXCHANGER
40 M-EHH-0850 HOSE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1
T CONNECTION FOR SWITCH
13 M-MKP-6000 MIKROPROCESSOR 1
41 M-TSC-6000 CAPILLARY 1
14 M-MNS-1200 MAIN SWITCH 1
42 M-CLP-1200 DRYER CLAMP 1
15 M-SLV-6000-24 SOLENOID VALVE 1
43 M-BPC-1000 BY-PASS CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1
44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
17 M-MMM-6000 MEMBRANE 1
45 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
18 M-CFR-0850 CABINET FRONT 1
46 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
19 M-CSI-0850 CABINET SIDE 2
47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CRE-0850 CABINET REAR 1
48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CTO-0700 CABINET TOP 1
49 M-PWC-1200 POWER CONNECTOR 1
22 M-CBA-0850 CABINET BASE 1
50 M-CCK-0850 CONTACTOR CONNECTION KIT 2
23 M-CBL-0850 CABINET LEG 4
51 M-DFD-1200 DRAIN FIXING DEVICE 2
24 M-HP1-0850 CABINETHORIZONTAL PROFILE 1 2
52 M-SCP-0850 CAPILLARY FOR SWITCH 2
25 M-HP2-0850 CABINET HORIZONTAL PROFILE 2 2
CAPILLARY FOR SWITCH HIGH/LOW
26 M-CTC-6000 CABINET TOP CORNER 4
53 M-HLC-0850 PRESSURE 2
27 M-CPS-6000 CABINET HANDLE 8
54 M-REV-6000 RELIEF VALVE 1
28 M-STU-6000 CABINET STUD AND NUT 13
55 M-DSC-5000 CLAMP FOR DISTRIBUTOR 1
29 M-FAS-6000 CABINET FASTENER 13
30 M-NUT-1200 CAGE NUT AND SCREW 29

COMPRESSOR
DRYER PART POWER OVERLOAD KIT FOR ELECTRICAL
DECAL CAPACITY NUMBER RATINGS COOLING COMPRESSOR (1) FAN MOTOR (3) CONTACTOR (34) PROTECTOR (36) PANEL (45)

RD500 500 CFM 02250193-826 230V/3Ph/60Hz AIR COOLED M-CMP-0500-230-3-60 M-FMT-0700-230-3-60 M-CNT-2400-460-3-60 M-COP-1600 M-KEP-0850-230-3-60

RD500 500 CFM 02250193-907 430V/3Ph/50Hz AIR COOLED M-CMP-0500-460-3-50 M-FMT-0700-400/460-3-50/60 M-CNT-0850-400-3-50 M-COP-0850 M-KEP-0850

RD500 500 CFM 02250193-966 430V/3Ph/60Hz AIR COOLED M-CMP-0500-400-3-60 M-FMT-0700-400/460-3-50/60 M-CNT-0850-400-3-50 M-COP-0850 M-KEP-0850
43

RD500 500 CFM 02250194-124 575V/3Ph/60Hz AIR COOLED M-CMP-0500-575-3-60 M-FMT-0700-575-3-60 M-CNT-0850-400-3-50 M-COP-0850 M-KEP-0850
4.3 ED/SPARE PARTS—RD700 AIR COOLED
44

SECTION 4
02250196-590 R3
4.3 ED/SPARE PARTS—RD700 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 31 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-0700 CONDENSOR 1 32 M-TRF-6000 TRANSFORMER 1
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-DRI-1200 DRIER-DEHYDRATOR 1 34 SEE REF. TABLE CONTACTOR 1
5 M-EXC-0850 HEAT EXCHANGER 2 35 M-FCN-1200 FAN CONTACTOR 2
6 M-EXV-0700 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
7 M-BYV-1200 BY PASS VALVE 1 36 SEE REF. TABLE PROTECTOR 1
8 M-SPR-1200 SEPARATOR 1 37 SEE REF. TABLE FAN OVERLOAD PROTECTOR 2
9 M-RCV-0700 LIQUID RECEIVER 1 38 M-SNS-6000 SENSOR PROBE 6
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 1
11 M-FNS-6000 FAN ON/OFF SWITCH 1 ELBOW FOR HEAT EXCHANGER
12 M-LPS-6000 LOW PRESSURE SWITCH 1 40 M-EHH-0850 HOSE 6
13 M-MKP-6000 MIKROPROCESSOR 1 T CONNECTION FOR SWITCH
14 M-MNS-1200 MAIN SWITCH 1 41 M-TSC-6000 CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-1200 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-1000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CFR-0850 CABINET FRONT 1 45 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
19 M-CSI-0850 CABINET SIDE 2 46 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
20 M-CRE-0850 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-0700 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-0850 CABINET BASE 1 49 M-PWC-1200 POWER CONNECTOR 1
23 M-CBL-0850 CABINET LEG 4 50 M-CCK-0850 CONTACTOR CONNECTION KIT 3
24 M-HP1-0850 CABINETHORIZONTAL PROFILE 1 2 51 M-DFD-1200 DRAIN FIXING DEVICE 2
25 M-HP2-0850 CABINET HORIZONTAL PROFILE 2 2 52 M-SCP-0850 CAPILLARY FOR SWITCH 2
26 M-CTC-6000 CABINET TOP CORNER 4 CAPILLARY FOR SWITCH HIGH/LOW
53 M-HLC-0850 PRESSURE 2
27 M-CPS-6000 CABINET HANDLE 8
54 M-REV-6000 RELIEF VALVE 1
28 M-STU-6000 CABINET STUD AND NUT 13
29 M-FAS-6000 CABINET FASTENER 13 55 M-DSC-5000 CLAMP FOR DISTRIBUTOR 1
56 M-CAC-0850 CLAMP AIR COLLECTOR 2
30 M-NUT-1200 CAGE NUT AND SCREW 29

COMPRESSOR KIT FOR


DRYER PART POWER FAN OVERLOAD
DECAL CAPACITY COOLING COMPRESSOR FAN MOTOR CONTACTOR OVERLOAD ELECTRICAL
NUMBER RATINGS PROTECTOR
PROTECTOR PANEL
230V/3Ph/ AIR M-CNT-2400-
RD 700 700 CFM 02250193-827 M-CMP-0700-230-3-60 M-FMT-0700-460-3-60 M-COP-1600 M-FOP-1200-230-3-60 M-KEP-0850-230-3-60
60Hz COOLED 460-3-60
430V/3Ph/ AIR M-CNT-0850-
RD 700 700 CFM 02250193-908 M-CMP0-700-460-3-60 M-FMT-0700-400-3-60 M-COP-0850 M-FOP-1200-460-3-60 M-KEP-0850
50Hz COOLED 460-3-60
460V/3Ph/ AIR M-CNT-0850-
RD 700 700 CFM 02250193-967 M-CMP-0700-460-3-60 M-FMT-0700-460-3-60 M-COP-0850 M-FOP-1200-460-3-60 M-KEP-0850
60Hz COOLED 460-3-60
575V/3Ph/ AIR M-CNT-0850-
RD 700 700 CFM 02250194-125 M-CMP-0700-575-3-60 M-FMT-0700-575-3-60 M-COP-0850 M-FOP-1200-460-3-60 M-KEP-0850
60Hz COOLED 460-3-60
45
4.4 ED/SPARE PARTS—RD700 WATER COOLED
46

SECTION 4
02250196-618 R03
4.4 ED/SPARE PARTS—RD700 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-0700-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-0850 HEAT EXCHANGER 3 32 SEE REF. TABLE CONTACTOR 2
5 M-EXV-0850 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-1200 BY PASS VALVE 1 33 SEE REF. TABLE PROTECTOR 1
7 M-SPR-1200 SEPARATOR 1 34 M-WVF-0850 WATER VALVE 2
8 M-RCV-0700 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-0850 HOSE 6
12 M-MNS-1200 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000-24 SOLENOID VALVE 1 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 3 39 M-CLP-1200 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 3 40 M-BPC-1000 BY-PASS CLAMP 1
16 M-CFR-0850 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
17 M-CSI-0850 CABINET SIDE 2 42 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
18 M-CRE-0850-W CABINET REAR 1 43 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
19 M-CTO-0700W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-0850 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CBL-0850 CABINET LEG 4 46 M-PWC-1200 POWER CONNECTOR 1
22 M-HP1-0850 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-0850 CONTACTOR CONNECTION KIT 1
23 M-HP2-0850 CABINET HORIZONTAL PROFILE 2 2 48 M-DFD-1200 DRAIN FIXING DEVICE 2
24 M-CTC-6000 CABINET TOP CORNER 4 CAPILLARY FOR SWITCH HIGH/LOW
49 M-HLC-0850 PRESSURE 2
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 13 50 M-REV-6000 RELIEF VALVE 1
51 M-DSC-5000 CLAMP FOR DISTRIBUTOR 1
27 M-FAS-6000 CABINET FASTENER 13
52 M-CAC-0850 CLAMP AIR COLLECTOR 2
28 M-NUT-1200 CAGE NUT AND SCREW 29

COMPRESSOR KIT FOR


DRYER PART POWER
DECAL CAPACITY COOLING COMPRESSOR (1) CONTACTOR (3) OVERLOAD ELECTRICAL PANEL
NUMBER RATINGS
PROTECTOR (35) (43)
230V/3Ph/ WATER
RD 700 700 CFM 02250193-861 60Hz COOLED M-CMP-0700-230-3-60 M-CNT-2400-460-3-60 M-COP-1600 M-KEP-0850-230-3-60-W
430V/3Ph/ WATER
RD 700 700 CFM 02250193-947 50Hz COOLED M-CMP-0700-460-3-60 M-CNT-0850-460-3-60 M-COP-0850 M-KEP-0850-W
460V/3Ph/ WATER
RD 700 700 CFM 02250194-107 60Hz COOLED M-CMP-0700-460-3-60 M-CNT-0850-460-3-60 M-COP-0850 M-KEP-0850-W
575V/3Ph/ WATER
47

RD 700 700 CFM 02250194-161 60Hz COOLED M-CMP-0700-575-3-60 M-CNT-0850-460-3-60 M-COP-0850 M-KEP-0850-W
4.5 ED/SPARE PARTS—RD850 AIR COOLED
48

SECTION 4
02250196-591 R03
4.5 ED/SPARE PARTS—RD850 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 13
2 M-CON-0850 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 13
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-6000 CAGE NUT AND SCREW 29
4 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-0850 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-0850 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-1200 BY PASS VALVE 1 34 M-CNT-0850 CONTACTOR 1
8 M-SPR-1200 SEPARATOR 1 35 M-FCN-1200 FAN CONTACTOR 2
9 M-RCV-1200 LIQUID RECEIVER 1 36 SEE REF. TABLE COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-1200 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 1
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-0850 ELBOW FOR HEAT EXCHANGER HOSE 8
14 M-MNS-1200 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000 SOLENOID VALVE 1 42 M-CLP-1200 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-1000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CFR-0850 CABINET FRONT 1 45 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
19 M-CSI-0850 CABINET SIDE 2 46 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
20 M-CRE-0850 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-0850 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-0850 CABINET BASE 1 49 M-PWC-0850 POWER CONNECTOR 1
23 M-CBL-0850 CABINET LEG 4 50 M-CCK-0850 CONTACTOR CONNECTION KIT 3
24 M-HP1-0850 CABINETHORIZONTAL PROFILE 1 2 51 M-DFD-1200 DRAIN FIXING DEVICE 3
25 M-HP2-0850 CABINET HORIZONTAL PROFILE 2 2 52 M-SCP-0850 CAPILLARY FOR SWITCH 2
26 M-CTC-6000 CABINET TOP CORNER 4 53 M-HLC-0850 CAPILLARY FOR SWITCH HIGH/LOW PRESS 2
27 M-CPS-6000 CABINET HANDLE 8 54 M-REV-6000 RELIEF VALVE 1
55 M-CAC-0850 CLAMP FOR AIR COLLECTOR 2

COMPRESSOR
DRYER PART POWER KIT FOR ELECTRICAL
DECAL CAPACITY COOLING COMPRESSOR (1) FAN MOTOR (3) CONTACTOR (34) OVERLOAD
NUMBER RATINGS PANEL (46)
PROTECTOR (36)
230V/3Ph/ AIR M-CMP-0850-230- M-FMT-1200-400/ M-CNT-1600-460-
RD 850 850 CFM 02250193-828 60Hz COOLED 3-60 460-3-50/60 360 M-COP-1600 M-KEP-0850-230-3-60
430V/3Ph/ AIR M-CMP-1000-460- M-FMT-1200-400/ M-CNT-0850-460-
RD 850 850 CFM 02250193-909 50Hz COOLED 3-60 460-3-50/60 360 M-COP-0850 M-KEP-0850
430V/3Ph/ AIR M-CMP-1000-460- M-FMT-1200-400/ M-CNT-0850-460-
RD 850 850 CFM 02250193-968 60Hz COOLED 3-60 460-3-50/60 360 M-COP-0850 M-KEP-0850
575V/3Ph/ AIR M-CMP-1000-575- M-FMT-1200-575-3- M-CNT-0850-460-
RD 850 850 CFM 02250194-126 60Hz COOLED 3-60 60 360 M-COP-0850 M-KEP-0850
49
4.6 ED/SPARE PARTS—RD850 WATER COOLED
50

SECTION 4
02250196-619 R03
4.6 ED/SPARE PARTS—RD850 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-1000-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-0850 HEAT EXCHANGER 4 32 M-CNT-0850 CONTACTOR 1
5 M-EXV-1000 EXPANSION VALVE 2 COMPRESSOR OVERLOAD
6 M-BYV-1200 BY PASS VALVE 1 33 SEE REF. TABLE PROTECTOR 1
7 M-SPR-1200 SEPARATOR 1 34 M-WVF-0850 WATER VALVE 2
8 M-RCV-1200 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-0850 HOSE 8
12 M-MNS-1200 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000-24 SOLENOID VALVE 1 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 1 39 M-CLP-1200 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 1 40 M-BPC-1000 BY-PASS CLAMP 1
16 M-CFR-0850 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
17 M-CSI-0850 CABINET SIDE 2 42 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
18 M-CRE-0850 CABINET REAR 1 43 SEE REF. TABLE KIT FOR ELECTRICAL PANEL 1
19 M-CTO-0850W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-0850 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CBL-0850 CABINET LEG 4 46 M-PWC-1200 POWER CONNECTOR 1
22 M-HP1-0850 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-0850 CONTACTOR CONNECTION KIT 1
23 M-HP2-0850 CABINET HORIZONTAL PROFILE 2 2 48 M-DFD-1200 DRAIN FIXING DEVICE 3
24 M-CTC-6000 CABINET TOP CORNER 4 CAPILLARY FOR SWITCH HIGH/LOW
49 M-HLC-0850 PRESSURE 2
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 13 50 M-REV-6000 RELIEF VALVE 1
51 M-CAC-0850 CLAMP FOR AIR COLLECTOR 2
27 M-FAS-6000 CABINET FASTENER 13
28 M-NUT-1200 CAGE NUT AND SCREW 29

COMPRESSOR KIT FOR


DRYER PART POWER
DECAL CAPACITY COOLING COMPRESSOR (1) CONTACTOR (32) OVERLOAD ELECTRICAL PANEL
NUMBER RATINGS
PROTECTOR (35) (43)
230V/3Ph/ WATER
RD 850 850 CFM 02250193-862 60Hz COOLED M-CMP-0850-230-3-60 M-CNT-1600-460-3-60-A M-COP-1600-230-3-60-A M-KEP-0850-230-3-60
430V/3Ph/ WATER
RD 850 850 CFM 02250193-948 50Hz COOLED M-CMP-1000-460-3-60 M-CNT-0850-460-3-60-A M-COP-0850-460-3-60-A M-KEP-0850
460V/3Ph/ WATER
RD 850 850 CFM 02250194-108 60Hz COOLED M-CMP-1000-460-3-60 M-CNT-0850-460-3-60-A M-COP-0850-460-3-60-A M-KEP-0850
575V/3Ph/ WATER
RD 850 850 CFM 02250194-162 60Hz COOLED M-CMP-1000-575-3-60 M-CNT-0850-460-3-60-A M-COP-0850-575-3-60-A M-KEP-0850
51
4.7 ED/SPARE PARTS—RD1000 AIR COOLED
52

SECTION 4
02250196-592 R03
4.7 ED/SPARE PARTS—RD1000 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 22
2 M-CON-1000 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 22
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-1200 CAGE NUT AND SCREW 29
4 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-1000 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-1200 BY PASS VALVE 1 34 M-CNT-1200 CONTACTOR 1
8 M-SPR-1200 SEPARATOR 1 35 M-FCN-1200 FAN CONTACTOR 1
9 M-RCV-1200 LIQUID RECEIVER 1 36 M-COP-1200 COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-1200 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 1
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 6
14 M-MNS-1200 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-1200 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-1000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
18 M-CFR-1000 CABINET FRONT 1 45 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
19 M-CSI-1000 CABINET SIDE 2 46 M-KEP-1200 KIT FOR ELECTRICAL PANEL 1
20 M-CRE-1000 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-1000 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-1000 CABINET BASE 1 49 M-PWC-1200 POWER CONNECTOR 1
23 M-CBL-1000 CABINET LEG 4 50 M-CCK-1600 CONTACTOR CONNECTION KIT 2
24 M-HP1-1000 CABINETHORIZONTAL PROFILE 1 2 51 M-DFD-1200 DRAIN FIXING DEVICE 2
25 M-HP2-1000 CABINET HORIZONTAL PROFILE 2 2 52 M-SCP-1200 CAPILLARY FOR SWITCH 2
26 M-CTC-6000 CABINET TOP CORNER 4 53 M-HLC-1200 CAPILLARY FOR SWITCH HIGH/LOW PRESS 2
27 M-CPS-6000 CABINET HANDLE 8 54 M-REV-6000 RELIEF VALVE 1

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR (1) FAN MOTOR (3)
NUMBER RATINGS

RD 1000 1000 CFM 02250193-921 400V/3Ph/50Hz AIR COOLED M-CMP-1000-460-3-60 M-FMT-1200-400/460-3-50/60


RD 1000 1000 CFM 02250193-985 460V/3Ph/60Hz AIR COOLED M-CMP-1000-460-3-60 M-FMT-1200-400/460-3-50/60
RD 1000 1000 CFM 02250194-140 575V/3Ph/60Hz AIR COOLED M-CMP-1000-575-3-60 M-FMT-1200-575-3-60
53
4.8 ED/SPARE PARTS—RD1000 WATER COOLED
54

SECTION 4
02250196-620 R03
4.8 ED/SPARE PARTS—RD1000 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-1000-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-6000 HEAT EXCHANGER 2 32 M-CNT-1200 CONTACTOR 1
5 M-EXV-1000 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-1200 BY PASS VALVE 1 33 M-COP-1200 PROTECTOR 1
7 M-SPR-1200 SEPARATOR 1 34 M-WVF-1200 WATER VALVE 1
8 M-RCV-1200 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-6000 HOSE 2
12 M-MNS-1200 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000-24 SOLENOID VALVE 1 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 2 39 M-CLP-1200 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 2 40 M-BPC-1000 BY-PASS CLAMP 1
16 M-CFR-1000 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
17 M-CSI-1000 CABINET SIDE 2 42 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
18 M-CRE-1000 CABINET REAR 1 43 M-KEP-1600-W KIT FOR ELECTRICAL PANEL 1
19 M-CTO-1000-W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-1000 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CBL-1000 CABINET LEG 4 46 M-PWC-1200 POWER CONNECTOR 1
22 M-HP1-1000 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-1600 CONTACTOR CONNECTION KIT 3
23 M-HP2-1000 CABINET HORIZONTAL PROFILE 2 2 48 M-DFD-1200 DRAIN FIXING DEVICE 1
24 M-CTC-6000 CABINET TOP CORNER 4 CAPILLARY FOR SWITCH HIGH/LOW
49 M-HLC-1200 PRESSURE 2
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 22 50 M-REV-6000 RELIEF VALVE 1
27 M-FAS-6000 CABINET FASTENER 22
28 M-NUT-6000 CAGE NUT AND SCREW 29

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR (1)
NUMBER RATINGS

RD 1000 1000 CFM 02250193-949 400V/3Ph/50Hz WATER COOLED M-CMP-1000-460-3-60


RD 1000 1000 CFM 02250193-109 460V/3Ph/60Hz WATER COOLED M-CMP-1000-460-3-60

RD 1000 1000 CFM 02250194-163 575V/3Ph/60Hz WATER COOLED M-CMP-1000-575-3-60


55
4.9 ED/SPARE PARTS—RD1200 AIR COOLED
56

SECTION 4
02250196-593 R03
4.9 ED/SPARE PARTS—RD1200 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 22
2 M-CON-1200 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 22
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-1200 CAGE NUT AND SCREW 29
4 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-1200 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-1200 BY PASS VALVE 1 34 M-CNT-1200 CONTACTOR 1
8 M-SPR-1200 SEPARATOR 1 35 M-FCN-1200 FAN CONTACTOR 2
9 M-RCV-1200 LIQUID RECEIVER 1 36 M-COP-1200 COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-1200 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 1
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 2
14 M-MNS-1200 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-1200 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-1000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
18 M-CFR-1200 CABINET FRONT 1 45 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
19 M-CSI-1200 CABINET SIDE 2 46 M-KEP-1200 KIT FOR ELECTRICAL PANEL 1
20 M-CRE-1200 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-1200 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-1200 CABINET BASE 1 49 M-PWC-1200 POWER CONNECTOR 1
23 M-CBL-1200 CABINET LEG 4 50 M-CCK-1600 CONTACTOR CONNECTION KIT 3
24 M-HP1-1200 CABINETHORIZONTAL PROFILE 1 2 51 M-DFD-1200 DRAIN FIXING DEVICE 1
25 M-HP2-1200 CABINET HORIZONTAL PROFILE 2 2 52 M-SCP-1200 CAPILLARY FOR SWITCH 2
26 M-CTC-6000 CABINET TOP CORNER 4 53 M-HLC-1200 CAPILLARY FOR SWITCH HIGH/LOW PRESS 2
27 M-CPS-6000 CABINET HANDLE 8 54 M-REV-6000 RELIEF VALVE 1

DRYER PART
DECAL CAPACITY POWER RATINGS COOLING COMPRESSOR FAN MOTOR (3)
NUMBER

RD 1200 1200 CFM 02250193-922 400V/3Ph/50Hz AIR COOLED M-CMP-1600-460-3-60 M-FMT-1200-400/460-3-50/60


RD 1200 1200 CFM 02250193-986 460V/3Ph/60Hz AIR COOLED M-CMP-1600-460-3-60 M-FMT-1200-400/460-3-50/60
RD 1200 1200 CFM 02250194-141 575V/3Ph/60Hz AIR COOLED M-CMP-1600-575-3-60 M-FMT-1200-460-3-60
57
4.10 ED/SPARE PARTS—RD1200 WATER COOLED
58

SECTION 4
02250196-621 R03
4.10 ED/SPARE PARTS—RD1200 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-1200-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-1200 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-6000 HEAT EXCHANGER 3 32 M-CNT-1200 CONTACTOR 1
5 M-EXV-1200 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-1200 BY PASS VALVE 1 33 M-COP-1200 PROTECTOR 1
7 M-SPR-1200 SEPARATOR 1 34 M-WVF-1200 WATER VALVE 1
8 M-RCV-1200 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-6000 HOSE 3
12 M-MNS-1200 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000-24 SOLENOID VALVE 3 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 3 39 M-CLP-1200 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 1 40 M-BPC-6000 BY-PASS CLAMP 1
16 M-CFR-1200 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 10
17 M-CSI-1200 CABINET SIDE 2 42 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
18 M-CRE-1200 CABINET REAR 1 43 M-KEP-1600-W KIT FOR ELECTRICAL PANEL 1
19 M-CTO-1200-W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-1200 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CBL-1200 CABINET LEG 4 46 M-PWC-1200 POWER CONNECTOR 1
22 M-HP1-1200 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-1600 CONTACTOR CONNECTION KIT 3
23 M-HP2-1200 CABINET HORIZONTAL PROFILE 2 2 48 M-DFD-1200 DRAIN FIXING DEVICE 2
24 M-CTC-6000 CABINET TOP CORNER 4 CAPILLARY FOR SWITCH HIGH/LOW
49 M-HLC-1200 PRESSURE 2
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 22 50 M-REV-6000 RELIEF VALVE 1
27 M-FAS-6000 CABINET FASTENER 22
28 M-NUT-1200 CAGE NUT AND SCREW 29

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 1200 1200 CFM 02250193-950 400V/3Ph/50Hz WATER COOLED M-CMP-1600-460-3-60


RD 1200 1200 CFM 02250193-110 460V/3Ph/60Hz WATER COOLED M-CMP-1600-460-3-60

RD 1200 1200 CFM 02250194-174 575V/3Ph/60Hz WATER COOLED M-CMP-1600-575-3-60


59
4.11 ED/SPARE PARTS—RD1600 AIR COOLED
60

SECTION 4
02250196-594 R03
4.11 ED/SPARE PARTS—RD1600 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 28
2 M-CON-1600 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 28
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-6000 CAGE NUT AND SCREW 44
4 M-DRI-2400 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-1600 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-6000 BY PASS VALVE 1 34 M-CNT-1600 CONTACTOR 1
8 M-SPR-6000 SEPARATOR 1 35 M-FCN-6000 FAN CONTACTOR 2
9 M-RCV-6000 LIQUID RECEIVER 1 36 M-COP-1600 COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-2400 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 5
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 4
14 M-MNS-2400 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-2400 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-1000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CFR-2000 CABINET FRONT 1 45 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
19 M-CSI-2000 CABINET SIDE 2 46 M-KEP-1600 KIT FOR ELECTRICAL PANEL 1
20 M-CRE-2000 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-2000 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-2000 CABINET BASE 1 49 M-PWC-2400 POWER CONNECTOR 1
23 M-CBL-2000 CABINET LEG 4 50 M-CCK-1600 CONTACTOR CONNECTION KIT 3
24 M-HP1-2000 CABINETHORIZONTAL PROFILE 1 2 51 M-SCP-2000 CAPILLARY FOR SWITCH 2
25 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 52 M-HLC-2000 CAPILLARY FOR SWITCH HIGH/LOW PRESSURE 2
26 M-CTC-6000 CABINET TOP CORNER 4 53 M-REV-6000 RELIEF VALVE 1
27 M-CPS-6000 CABINET HANDLE 8

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR FAN MOTOR
NUMBER RATINGS

RD 1600 1600 CFM 02250193-923 400V/3Ph/50Hz AIR COOLED M-CMP-1600-460-3-60 M-FMT-1600-460-3-60


RD 1600 1600 CFM 02250193-988 460V/3Ph/60Hz AIR COOLED M-CMP-1600-460-3-60 M-FMT-1600-460-3-60
RD 1600 1600 CFM 02250194-142 575V/3Ph/60Hz AIR COOLED M-CMP-1600-575-3-60 M-FMT-1600-575-3-60
61
4.12 ED/SPARE PARTS—RD1600 WATER COOLED
62

SECTION 4
02250196-622 R03
4.12 ED/SPARE PARTS—RD1600 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-1600-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-2400 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-6000 HEAT EXCHANGER 4 32 M-CNT-1600 CONTACTOR 1
5 M-EXV-1600 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-6000 BY PASS VALVE 1 33 M-COP-1600 PROTECTOR 1
7 M-SPR-6000 SEPARATOR 1 34 M-WVF-3800 WATER VALVE 1
8 M-RCV-6000 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 5
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-6000 HOSE 4
12 M-MNS-2400 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000-24 SOLENOID VALVE 1 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 5 39 M-CLP-2400 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 5 40 M-BPC-6000 BY-PASS CLAMP 1
16 M-CFR-2000 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
17 M-CSI-2000 CABINET SIDE 2 42 M-CCB-1600 CONDUIT FOR CONTROL BOX 1
18 M-CRE-2000 CABINET REAR 1 43 M-KEP-1600-W KIT FOR ELECTRICAL PANEL 1
19 M-CTO-2000-W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-2000 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CBL-2000 CABINET LEG 4 46 M-PWC-2400 POWER CONNECTOR 1
22 M-HP1-2000 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-1600 CONTACTOR CONNECTION KIT 3
23 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
48 M-HLC-2000 PRESSURE 2
24 M-CTC-6000 CABINET TOP CORNER 4
49 M-REV-6000 RELIEF VALVE 1
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 28
27 M-FAS-6000 CABINET FASTENER 28
28 M-NUT-6000 CAGE NUT AND SCREW 44

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 1600 1600 CFM 02250193-951 400V/3Ph/50Hz WATER COOLED M-CMP-1600-460-3-60

RD 1600 1600 CFM 02250193-113 460V/3Ph/60Hz WATER COOLED M-CMP-1600-460-3-60

RD 1600 1600 CFM 02250194-165 575V/3Ph/60Hz WATER COOLED M-CMP-1600-575-3-60


63
4.13 ED/SPARE PARTS—RD2000 AIR COOLED
64

SECTION 4
02250196-595 R03
4.13 ED/SPARE PARTS—RD2000 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 28
2 M-CON-2400 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 28
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-6000 CAGE NUT AND SCREW 44
4 M-DRI-2400 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-2400 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-6000 BY PASS VALVE 1 34 M-CNT-2400 CONTACTOR 1
8 M-SPR-6000 SEPARATOR 1 35 M-FCN-6000 FAN CONTACTOR 2
9 M-RCV-6000 LIQUID RECEIVER 1 36 M-COP-2400 COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-2400 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 5
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 4
14 M-MNS-2400 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-2400 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-6000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CFR-2000 CABINET FRONT 1 45 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
19 M-CSI-2000 CABINET SIDE 2 46 M-KEP-2400 KIT FOR ELECTRICAL PANEL 1
20 M-CRE-2000 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-2000 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-2000 CABINET BASE 1 49 M-PWC-2400 POWER CONNECTOR 1
23 M-CBL-2000 CABINET LEG 4 50 M-CCK-5000 CONTACTOR CONNECTION KIT 3
24 M-HP1-2000 CABINETHORIZONTAL PROFILE 1 2 51 M-SCP-2000 CAPILLARY FOR SWITCH 2
25 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
26 M-CTC-6000 CABINET TOP CORNER 4 52 M-HLC-2000 PRESSURE 2
27 M-CPS-6000 CABINET HANDLE 8 53 M-REV-6000 RELIEF VALVE 1

DRYER PART
DECAL CAPACITY POWER RATINGS COOLING COMPRESSOR FAN MOTOR
NUMBER

RD 2000 2000 CFM 02250193-924 400V/3Ph/50Hz AIR COOLED M-CMP-2000-460-3-60 M-FMT-6000-460-3-60


RD 2000 2000 CFM 02250193-989 460V/3Ph/60Hz AIR COOLED M-CMP-2000-460-3-60 M-FMT-6000-460-3-60
RD 2000 2000 CFM 02250194-143 575V/3Ph/60Hz AIR COOLED M-CMP-2000-575-3-60 M-FMT-6000-575-3-60
65
4.14 ED/SPARE PARTS—RD2000 WATER COOLED
66

SECTION 4
02250196-623 R03
4.14 ED/SPARE PARTS—RD2000 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 27 M-FAS-6000 CABINET FASTENER 28
2 M-CON-2000-W CONDENSOR 1 28 M-NUT-6000 CAGE NUT AND SCREW 44
3 M-DRI-2400 DRIER-DEHYDRATOR 1 29 M-SCR-6000 SCREW TYPE 2 16
4 M-EXC-6000 HEAT EXCHANGER 4 30 M-TRF-6000 TRANSFORMER 1
5 M-EXV-2400 EXPANSION VALVE 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
6 M-BYV-6000 BY PASS VALVE 1 32 M-CNT-2400 CONTACTOR 1
7 M-SPR-6000 SEPARATOR 1 COMPRESSOR OVERLOAD
8 M-RCV-6000 LIQUID RECEIVER 1 33 M-COP-2400 PROTECTOR 1
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 34 M-WVF-3800 WATER VALVE 1
10 M-LPS-6000 LOW PRESSURE SWITCH 1 35 M-SNS-6000 SENSOR PROBE 6
11 M-MKP-6000 MIKROPROCESSOR 1 36 M-DBV-6000 DRAIN BALL VALVE 5
12 M-MNS-2400 MAIN SWITCH 1 ELBOW FOR HEAT EXCHANGER
37 M-EHH-6000 HOSE 4
13 M-SLV-6000 SOLENOID VALVE 1
T CONNECTION FOR SWITCH
14 M-MMV-6000 MEMBRANE VALVE 5
38 M-TSC-6000 CAPILLARY 1
15 M-MMM-6000 MEMBRANE 5
39 M-CLP-2400 DRYER CLAMP 1
16 M-CFR-2000 CABINET FRONT 1
40 M-BPC-6000 BY-PASS CLAMP 1
17 M-CSI-2000 CABINET SIDE 2
41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CRE-2000 CABINET REAR 1
42 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
19 M-CTO-2000W CABINET TOP 1
43 M-KEP-5000-W KIT FOR ELECTRICAL PANEL 1
20 M-CBA-2000 CABINET BASE 1
44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CBL-2000 CABINET LEG 4
45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-HP1-2000 CABINETHORIZONTAL PROFILE 1 2
46 M-PWC-2400 POWER CONNECTOR 1
23 M-HP2-2000 CABINET HORIZONTAL PROFILE 2 2
47 M-CCK-5000 CONTACTOR CONNECTION KIT 3
24 M-CTC-6000 CABINET TOP CORNER 4
CAPILLARY FOR SWITCH HIGH/LOW
25 M-CPS-6000 CABINET HANDLE 8 48 M-HLC-2000 PRESSURE 2
26 M-STU-6000 CABINET STUD AND NUT 28 49 M-REV-6000 RELIEF VALVE 1

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 2000 2000 CFM 02250193-953 400V/3Ph/50Hz WATER COOLED M-CMP-2000-460-3-60

RD 2000 2000 CFM 02250193-114 460V/3Ph/60Hz WATER COOLED M-CMP-2000-460-3-60

RD 2000 2000 CFM 02250194-166 575V/3Ph/60Hz WATER COOLED M-CMP-2000-575-3-60


67
4.15 ED/SPARE PARTS—RD2400 AIR COOLED

SECTION 4
02250196-596 R03
68
4.15 ED/SPARE PARTS—RD2400 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 40
2 M-CON-2400 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 40
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-6000 CAGE NUT AND SCREW 60
4 M-DRI-2400 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-2400 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-6000 BY PASS VALVE 1 34 M-CNT-2400 CONTACTOR 1
8 M-SPR-6000 SEPARATOR 1 35 M-FCN-6000 FAN CONTACTOR 2
9 M-RCV-6000 LIQUID RECEIVER 1 36 M-COP-2400 COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-2400 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 6
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 10
14 M-MNS-2400 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-2400 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 6 43 M-BPC-6000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 6 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CFR-3000 CABINET FRONT 1 45 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
19 M-CSI-3000 CABINET SIDE 2 46 M-KEP-2400 KIT FOR ELECTRICAL PANEL 1
20 M-CRE-3000 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-3000 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-3000 CABINET BASE 1 49 M-PWC-2400 POWER CONNECTOR 1
23 M-CBL-3000 CABINET LEG 4 50 M-CCK-5000 CONTACTOR CONNECTION KIT 3
24 M-HP1-3000 CABINETHORIZONTAL PROFILE 1 2 51 M-SCP-3000 CAPILLARY FOR SWITCH 2
25 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
26 M-CTC-6000 CABINET TOP CORNER 4 52 M-HLC-3000 PRESSURE 2
27 M-CPS-6000 CABINET HANDLE 8 53 M-REV-6000 RELIEF VALVE 1

DECAL CAPACITY DRYER PART NUMBER POWER RATINGS COOLING COMPRESSOR FAN MOTOR

RD 2400 2400 CFM 02250193-925 400V/3Ph/50Hz AIR COOLED M-CMP-2400-460-3-60 M-FMT-6000-460-3-60


RD 2400 2400 CFM 02250193-990 460V/3Ph/60Hz AIR COOLED M-CMP-2400-460-3-60 M-FMT-6000-460-3-60
RD 2400 2400 CFM 02250194-144 575V/3Ph/60Hz AIR COOLED M-CMP-2400-575-3-60 M-FMT-6000-575-3-60
69
4.16 ED/SPARE PARTS—RD2400 WATER COOLED
70

SECTION 4
02250196-624 R03
4.16 ED/SPARE PARTS—RD2400 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-2400-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-2400 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-6000 HEAT EXCHANGER 5 32 M-CNT-2400 CONTACTOR 1
5 M-EXV-2400 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-6000 BY PASS VALVE 1 33 M-COP-2400 PROTECTOR 1
7 M-SPR-6000 SEPARATOR 1 34 M-WVF-3800 WATER VALVE 1
8 M-RCV-6000 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 6
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-6000 HOSE 10
12 M-MNS-2400 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000-24 SOLENOID VALVE 1 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 6 39 M-CLP-2400 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 6 40 M-BPC-6000 BY-PASS CLAMP 1
16 M-CFR-3000 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
17 M-CSI-3000 CABINET SIDE 2 42 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
18 M-CRE-3000 CABINET REAR 1 43 M-KEP-5000-W KIT FOR ELECTRICAL PANEL 1
19 M-CTO-3000W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-3000 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
21 M-CBL-3000 CABINET LEG 4 46 M-PWC-2400 POWER CONNECTOR 1
22 M-HP1-3000 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-5000 CONTACTOR CONNECTION KIT 3
23 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
48 M-HLC-3000 PRESSURE 2
24 M-CTC-6000 CABINET TOP CORNER 4
49 M-REV-6000 RELIEF VALVE 1
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 40
27 M-FAS-6000 CABINET FASTENER 40
28 M-NUT-6000 CAGE NUT AND SCREW 60

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 2400 2400 CFM 02250193-954 400V/3Ph/50Hz WATER COOLED M-CMP-2400-460-3-60


RD 2400 2400 CFM 02250193-115 460V/3Ph/60Hz WATER COOLED M-CMP-2400-460-3-60

RD 2400 2400 CFM 02250194-167 575V/3Ph/60Hz WATER COOLED M-CMP-2400-575-3-60


71
4.17 ED/SPARE PARTS—RD3000 AIR COOLED

SECTION 4
02250196-597 R03
72
4.17 ED/SPARE PARTS—RD3000 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-STU-6000 CABINET STUD AND NUT 44
2 M-CON-3000 CONDENSOR 1 29 M-FAS-6000 CABINET FASTENER 44
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 30 M-NUT-6000 CAGE NUT AND SCREW 60
4 M-DRI-5000 DRIER-DEHYDRATOR 1 31 M-SCR-6000 SCREW TYPE 2 16
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-TRF-6000 TRANSFORMER 1
6 M-EXV-3000 EXPANSION VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
7 M-BYV-6000 BY PASS VALVE 1 34 M-CNT-3000 CONTACTOR 1
8 M-SPR-6000 SEPARATOR 1 35 M-FCN-6000 FAN CONTACTOR 2
9 M-RCV-6000 LIQUID RECEIVER 1 36 M-COP-3000 COMPRESSOR OVERLOAD PROTECTOR 1
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-FOP-6000 FAN OVERLOAD PROTECTOR 2
11 M-FNS-6000 FAN ON/OFF SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-DBV-6000 DRAIN BALL VALVE 6
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 12
14 M-MNS-3800 MAIN SWITCH 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-CLP-3800 DRYER CLAMP 1
16 M-MMV-6000 MEMBRANE VALVE 1 43 M-BPC-6000 BY-PASS CLAMP 1
17 M-MMM-6000 MEMBRANE 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
18 M-CFR-3000 CABINET FRONT 1 45 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
19 M-CSI-3000 CABINET SIDE 2 46 M-KEP-3000 KIT FOR ELECTRICAL PANEL 1
20 M-CRE-3000 CABINET REAR 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CTO-3000 CABINET TOP 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBA-3000 CABINET BASE 1 49 M-PWC-3800 POWER CONNECTOR 1
23 M-CBL-3000 CABINET LEG 4 50 M-CCK-5000 CONTACTOR CONNECTION KIT 3
24 M-HP1-3000 CABINETHORIZONTAL PROFILE 1 2 51 M-SCP-3000 CAPILLARY FOR SWITCH 2
25 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
26 M-CTC-6000 CABINET TOP CORNER 4 52 M-HLC-3000 PRESSURE 2
27 M-CPS-6000 CABINET HANDLE 8 53 M-REV-6000 RELIEF VALVE 1

DECAL CAPACITY DRYER PART NUMBER POWER RATINGS COOLING COMPRESSOR FAN MOTOR
RD 3000 3000 CFM 02250193-926 400V/3Ph/50Hz AIR COOLED M-CMP-3000-460-3-60 M-FMT-6000-460-3-60
RD 3000 3000 CFM 02250193-991 460V/3Ph/60Hz AIR COOLED M-CMP-3000-460-3-60 M-FMT-6000-460-3-60
RD 3000 3000 CFM 02250194-145 575V/3Ph/60Hz AIR COOLED M-CMP-3000-575-3-60 M-FMT-6000-575-3-60
73
4.18 ED/SPARE PARTS—RD3000 WATER COOLED
74

SECTION 4
02250196-625 R03
4.18 ED/SPARE PARTS—RD3000 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-3000-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-5000 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-6000 HEAT EXCHANGER 6 32 M-CNT-3000 CONTACTOR 1
5 M-EXV-3000 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-6000 BY PASS VALVE 1 33 M-COP-3000 PROTECTOR 1
7 M-SPR-6000 SEPARATOR 1 34 M-WVF-3800 WATER VALVE 1
8 M-RCV-6000 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 7
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-6000 HOSE 12
12 M-MNS-3800 MAIN SWITCH 1 T CONNECTION FOR SWITCH
38 M-TSC-6000 CAPILLARY 1
13 M-SLV-6000-24 SOLENOID VALVE 1
39 M-CLP-3800 DRYER CLAMP 1
14 M-MMV-6000 MEMBRANE VALVE 7
40 M-BPC-6000 BY-PASS CLAMP 1
15 M-MMM-6000 MEMBRANE 7
41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 18
16 M-CFR-3000 CABINET FRONT 1
42 M-CCB-3000 CONDUIT FOR CONTROL BOX 1
17 M-CSI-3000 CABINET SIDE 2
43 M-KEP-5000-W KIT FOR ELECTRICAL PANEL 1
18 M-CRE-3000 CABINET REAR 1
44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
19 M-CTO-3000W CABINET TOP 1
45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
20 M-CBA-3000 CABINET BASE 1
46 M-PWC-3800 POWER CONNECTOR 1
21 M-CBL-3000 CABINET LEG 4
47 M-CCK-5000 CONTACTOR CONNECTION KIT 1
22 M-HP1-3000 CABINETHORIZONTAL PROFILE 1 2
CAPILLARY FOR SWITCH HIGH/LOW
23 M-HP2-3000 CABINET HORIZONTAL PROFILE 2 2
48 M-HLC-3000 PRESSURE 2
24 M-CTC-6000 CABINET TOP CORNER 4
49 M-REV-6000 RELIEF VALVE 1
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 44
27 M-FAS-6000 CABINET FASTENER 44
28 M-NUT-6000 CAGE NUT AND SCREW 60

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 3000 3000 CFM 02250193-955 400V/3Ph/50Hz WATER COOLED M-CMP-3000-460-3-60

RD 3000 3000 CFM 02250193-116 460V/3Ph/60Hz WATER COOLED M-CMP-3000-460-3-60

RD 3000 3000 CFM 02250194-168 575V/3Ph/60Hz WATER COOLED M-CMP-3000-575-3-60


75
4.19 ED/SPARE PARTS—RD3800 AIR COOLED
76

SECTION 4
02250196-598 R03
4.19 ED/SPARE PARTS—RD3800 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 27 M-CPS-6000 CABINET HANDLE 8
2 M-CON-3800 CONDENSOR 1 28 M-STU-6000 CABINET STUD AND NUT 40
3 SEE REF. TABLE FAN MOTOR ASSEMBLY 1 29 M-FAS-6000 CABINET FASTENER 40
4 M-DRI-5000 DRIER-DEHYDRATOR 1 30 M-NUT-6000 CAGE NUT AND SCREW 56
5 M-EXC-6000 HEAT EXCHANGER 2 31 M-SCR-6000 SCREW TYPE 2 16
6 M-EXV-3800 EXPANSION VALVE 1 32 M-TRF-6000 TRANSFORMER 1
7 M-BYV-6000 BY PASS VALVE 1 33 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-SPR-6000 SEPARATOR 1 34 M-CNT-5000 CONTACTOR 1
9 M-RCV-6000 LIQUID RECEIVER 1 35 M-FCN-6000 FAN CONTACTOR 4
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-COP-3800 COMPRESSOR OVERLOAD PROTECTOR 1
11 M-FNS-6000 FAN ON/OFF SWITCH 1 37 M-FOP-6000 FAN OVERLOAD PROTECTOR 4
12 M-LPS-6000 LOW PRESSURE SWITCH 1 38 M-SNS-6000 SENSOR PROBE 6
13 M-MKP-6000 MIKROPROCESSOR 1 39 M-DBV-6000 DRAIN BALL VALVE 7
14 M-MNS-3800 MAIN SWITCH 1 40 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 12
15 M-SLV-6000-24 SOLENOID VALVE 1 41 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
16 M-MMV-6000 MEMBRANE VALVE 1 42 M-CLP-3800 DRYER CLAMP 1
17 M-MMM-6000 MEMBRANE 1 43 M-BPC-6000 BY-PASS CLAMP 1
18 M-CFR-3000 CABINET FRONT 1 44 M-CCP-6000 CONDUIT FOR CONTROL PANEL 23
19 M-CSI-3800 CABINET SIDE 2 45 M-CCB-3800 CONDUIT FOR CONTROL BOX 1
20 M-CRE-3800 CABINET REAR 1 46 M-KEP-5000 KIT FOR ELECTRICAL PANEL 1
21 M-CTO-3800 CABINET TOP 1 47 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
22 M-CBA-3800 CABINET BASE 1 48 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 7
23 M-CBL-3800 CABINET LEG 4 49 M-PWC-3800 POWER CONNECTOR 1
24 M-HP1-3800 CABINETHORIZONTAL PROFILE 1 2 50 M-CCK-5000 CONTACTOR CONNECTION KIT 3
25 M-HP2-3800 CABINET HORIZONTAL PROFILE 2 2 51 M-SCP-3800 CAPILLARY FOR SWITCH 3
26 M-CTC-6000 CABINET TOP CORNER 4 52 M-HLC-3800 CAPILLARY FOR SWITCH HIGH/LOW PRESS 2
53 M-REV-6000 RELIEF VALVE 1

DECAL CAPACITY DRYER PART NUMBER POWER RATINGS COOLING COMPRESSOR FAN MOTOR

RD 3800 3800 CFM 02250193-927 400V/3PH/50HZ AIR COOLED M-CMP-3800-460-3-60 M-FMT-6000-460-3-60


RD 3800 3800 CFM 02250193-992 460V/3PH/60HZ AIR COOLED M-CMP-3800-460-3-60 M-FMT-6000-460-3-60
RD 3800 3800 CFM 02250194-146 575V/3PH/60HZ AIR COOLED M-CMP-3800-575-3-60 M-FMT-6000-575-3-60
77
4.20 ED/SPARE PARTS—RD3800 WATER COOLED
78

SECTION 4
02250196-626 R03
4.20 ED/SPARE PARTS—RD3800 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-SCR-6000 SCREW TYPE 2 16
2 M-CON-3800-W CONDENSOR 1 30 M-TRF-6000 TRANSFORMER 1
3 M-DRI-5000 DRIER-DEHYDRATOR 1 31 M-PPR-6000 PHASE PROTECTION RELAY 1
4 M-EXC-6000 HEAT EXCHANGER 6 32 M-CNT-5000 CONTACTOR 1
5 M-EXV-3800 EXPANSION VALVE 1 COMPRESSOR OVERLOAD
6 M-BYV-6000 BY PASS VALVE 1 33 M-COP-3800 PROTECTOR 1
7 M-SPR-6000 SEPARATOR 1 34 M-WVF-3800 WATER VALVE 1
8 M-RCV-6000 LIQUID RECEIVER 1 35 M-SNS-6000 SENSOR PROBE 6
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-DBV-6000 DRAIN BALL VALVE 7
10 M-LPS-6000 LOW PRESSURE SWITCH 1 ELBOW FOR HEAT EXCHANGER
11 M-MKP-6000 MIKROPROCESSOR 1 37 M-EHH-6000 HOSE 12
12 M-MNS-3800 MAIN SWITCH 1 T CONNECTION FOR SWITCH
13 M-SLV-6000 SOLENOID VALVE 1 38 M-TSC-6000 CAPILLARY 1
14 M-MMV-6000 MEMBRANE VALVE 7 39 M-CLP-3800 DRYER CLAMP 1
15 M-MMM-6000 MEMBRANE 7 40 M-BPC-6000 BY-PASS CLAMP 1
16 M-CFR-3800 CABINET FRONT 1 41 M-CCP-6000 CONDUIT FOR CONTROL PANEL 23
17 M-CSI-3800 CABINET SIDE 1 42 M-CCB-5000 CONDUIT FOR CONTROL BOX 1
18 M-CRE-3800 CABINET REAR 1 43 M-KEP-5000-W KIT FOR ELECTRICAL PANEL 1
19 M-CTO-3800-W CABINET TOP 1 44 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
20 M-CBA-3800 CABINET BASE 1 45 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 7
21 M-CBL-3800 CABINET LEG 4 46 M-PWC-3800 POWER CONNECTOR 1
22 M-HP1-3800 CABINETHORIZONTAL PROFILE 1 2 47 M-CCK-5000 CONTACTOR CONNECTION KIT 2
23 M-HP2-3800 CABINET HORIZONTAL PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
48 M-HLC-3800 PRESSURE 2
24 M-CTC-6000 CABINET TOP CORNER 4
49 M-REV-6000 RELIEF VALVE 1
25 M-CPS-6000 CABINET HANDLE 8
26 M-STU-6000 CABINET STUD AND NUT 40
27 M-FAS-6000 CABINET FASTENER 40
28 M-NUT-6000 CAGE NUT AND SCREW 56

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 3800 3800 CFM 02250193-927 400V/3Ph/50Hz AIR COOLED M-CMP-3800-460-3-60


RD 3800 3800 CFM 02250193-992 460V/3Ph/60Hz AIR COOLED M-CMP-3800-460-3-60

RD 3800 3800 CFM 02250194-146 575V/3Ph/60Hz AIR COOLED M-CMP-3800-575-3-60


79
4.21 ED/SPARE PARTS—RD5000 AIR COOLED
80

SECTION 4
02250196-599 R03
4.21 ED/SPARE PARTS—RD5000 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 28 M-CPS-6000 CABINET HANDLE 8
2 M-CON-6000 CONDENSOR 1 29 M-STU-6000 CABINET STUD AND NUT 48
3 SEE REF. TABLE FAN MOTOR 6 30 M-FAS-6000 CABINET FASTENER 48
4 M-DRI-5000 DRIER-DEHYDRATOR 1 31 M-NUT-6000 CAGE NUT AND SCREW 64
5 M-EXC-6000 HEAT EXCHANGER 7 32 M-SCR-6000 SCREW TYPE 2 16
6 M-EXV-5000 EXPANSION VALVE 1 33 M-TRF-6000 TRANSFORMER 1
7 M-BYV-6000 BY PASS VALVE 1 34 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-SPR-6000 SEPARATOR 1 35 M-CNT-5000 CONTACTOR 1
9 M-RCV-6000 LIQUID RECEIVER 1 36 M-FCN-6000 FAN CONTACTOR 4
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-COP-5000 COMPRESSOR OVERLOAD PROTECTOR 1
11 M-FNS-6000 FAN ON/OFF SWITCH 3 38 M-FOP-6000 FAN OVERLOAD PROTECTOR 4
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-SNS-6000 SENSOR PROBE 6
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-DBV-6000 DRAIN BALL VALVE 8
14 M-MNS-5000 MAIN SWITCH 1 41 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 14
15 M-SLV-6000-24 SOLENOID VALVE 1 42 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
16 M-MMV-6000 MEMBRANE VALVE 8 43 M-CLP-5000 DRYER CLAMP 1
17 M-MMM-6000 MEMBRANE 8 44 M-BPC-1000 BY-PASS CLAMP 1
18 M-CFR-5000 CABINET FRONT 1 45 M-CCP-6000 CONDUIT FOR CONTROL PANEL 23
19 M-CSI-5000 CABINET SIDE-RIGHT 2 46 M-CCB-5000 CONDUIT FOR CONTROL BOX 1
20 M-CSI-5000 CABINET SIDE-LEFT 47 M-KEP-5000 KIT FOR ELECTRICAL PANEL 1
21 M-CRE-5000 CABINET REAR 1 48 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
22 M-CTO-5000 CABINET TOP 1 49 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
23 M-CBA-5000 CABINET BASE 1 50 M-PWC-5000 POWER CONNECTOR 1
24 M-CBL-5000 CABINET LEG 4 51 M-CCK-5000 CONTACTOR CONNECTION KIT 3
25 M-HP1-5000 CABINETHORIZONTAL PROFILE 1 2 52 M-SCP-5000 CAPILLARY FOR SWITCH 3
26 M-HP2-5000 CABINET HORIZONTAL PROFILE 2 2 53 M-HLC-5000 CAPILLARY FOR SWITCH HIGH/LOW PRESS 2
27 M-CTC-5000 CABINET TOP CORNER 4 54 M-REV-6000 RELIEF VALVE 1
55 M-REV-6000 CLAMP FOR DISTRIBUTER 1

DRYER PART
DECAL CAPACITY POWER RATINGS COOLING COMPRESSOR FAN MOTOR
NUMBER
RD 5000 5000 CFM 02250193-928 400V/3PH/50HZ AIR COOLED M-CMP-5000-460-3-60 M-FMT-6000-460-3-60
RD 5000 5000 CFM 02250193-993 460V/3PH/60HZ AIR COOLED M-CMP-5000-460-3-60 M-FMT-6000-460-3-60
RD 5000 5000 CFM 02250194-147 575V/3PH/60HZ AIR COOLED M-CMP-5000-575-3-60 M-FMT-6000-575-3-60
81
4.22 ED/SPARE PARTS—RD5000 WATER COOLED
82

SECTION 4
02250196-627 R03
4.22 ED/SPARE PARTS—RD5000 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 2 26 M-CPS-6000 CABINET HANDLE 8
2 M-CON-5000-W CONDENSOR 1 27 M-STU-6000 CABINET STUD AND NUT 48
3 M-DRI-5000 DRIER-DEHYDRATOR 1 28 M-FAS-6000 CABINET FASTENER 48
4 M-EXC-6000 HEAT EXCHANGER 7 29 M-NUT-6000 CAGE NUT AND SCREW 64
5 M-EXV-5000 EXPANSION VALVE 1 30 M-SCR-6000 SCREW TYPE 2 16
6 M-BYV-6000 BY PASS VALVE 1 31 M-TRF-6000 TRANSFORMER 1
7 M-SPR-6000 SEPARATOR 1 32 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-RCV-6000 LIQUID RECEIVER 1 33 M-CNT-5000 CONTACTOR 1
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 34 M-COP-5000 COMPRESSOR OVERLOAD PROTECTOR 2
10 M-LPS-6000 LOW PRESSURE SWITCH 1 35 M-WVF-5000 WATER VALVE 1
11 M-MKP-6000 MIKROPROCESSOR 1 36 M-SNS-6000 SENSOR PROBE 6
12 M-MNS-5000 MAIN SWITCH 1 37 M-DBV-6000 DRAIN BALL VALVE 8
13 M-SLV-6000-24 SOLENOID VALVE 1 38 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 14
14 M-MMV-6000 MEMBRANE VALVE 8 39 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 1
15 M-MMM-6000 MEMBRANE 8 40 M-CLP-5000 DRYER CLAMP 1
16 M-CFR-5000 CABINET FRONT 1 41 M-BPC-6000 BY-PASS CLAMP 1
17 M-CSI-5000 CABINET SIDE-LEFT 1 42 M-CCP-6000 CONDUIT FOR CONTROL PANEL 23
18 M-CSR-5000 CABINET SIDE-RIGHT 1 43 M-CCB-5000 CONDUIT FOR CONTROL BOX 1
19 M-CRE-5000 CABINET REAR 1 44 M-KEP-5000-W KIT FOR ELECTRICAL PANEL 1
20 M-CTO-5000-W CABINET TOP 1 45 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CBA-5000 CABINET BASE 1 46 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 7
22 M-CBL-5000 CABINET LEG 4 47 M-PWC-5000 POWER CONNECTOR 1
23 M-HP1-5000 CABINETHORIZONTAL PROFILE 1 2 48 M-CCK-5000 CONTACTOR CONNECTION KIT 2
24 M-HP2-5000 CABINET HORIZONTAL PROFILE 2 2 49 M-HLC-5000 CAPILLARY FOR SWITCH HIGH/LOW PRES 2
25 M-CTC-6000 CABINET TOP CORNER 4 50 M-REV-6000 RELIEF VALVE 1

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 5000 5000 CFM 02250193-958 400V/3Ph/50Hz WATER COOLED M-CMP-5000-460-3-60

RD 5000 5000 CFM 02250193-118 460V/3Ph/60Hz WATER COOLED M-CMP-5000-460-3-60

RD 5000 5000 CFM 02250194-170 575V/3Ph/60Hz WATER COOLED M-CMP-5000-575-3-60


83
4.23 ED/SPARE PARTS—RD6000 AIR COOLED
84

SECTION 4
02250196-600 R03
4.23 ED/SPARE PARTS—RD6000 AIR COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 2 28 M-CPS-6000 CABINET HANDLE 18
2 M-CON-6000 CONDENSER 1 29 M-STU-6000 CABINET STUD AND NUT 48
3 SEE REF. TABLE FAN MOTOR 6 30 M-FAS-6000 CABINET FASTENER 48
4 M-DRI-6000 DRIER-DEHYDRATOR 1 31 M-NUT-6000 CAGE NUT AND SCREW 64
5 M-EXC-6000 HEAT EXCHANGER 2 32 M-SCR-6000 SCREW TYPE 2 16
6 M-EXV-6000 EXPANSION VALVE 1 33 M-TRF-6000 TRANSFORMER 2
7 M-BYV-6000 BYPASS VALVE 1 34 M-PPR-6000 PHASE PROTECTION RELAY 1
8 M-SPR-6000 SEPARATOR 1 35 M-CNT-6000 CONTACTOR 1
9 M-RCV-6000 LIQUID RECEIVER 1 36 M-FCN-6000 FAN CONTACTOR 6
10 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 37 M-COP-6000 COMPRESSOR OVERLOAD PROTECTOR 1
11 M-FNS-0400 FAN ON/OFF SWITCH 3 38 M-FOP-60000 FAN OVERLOAD PROTECTOR 6
12 M-LPS-6000 LOW PRESSURE SWITCH 1 39 M-SNS-6000 SENSOR PROBE 6
13 M-MKP-6000 MIKROPROCESSOR 1 40 M-DBV-6000 DRAIN BALL VALVE 10
14 M-MNS-6000 MAIN SWITCH 1 41 M-EHH-6000 ELBOW FOR HEAT EXCHANGER HOSE 18
15 M-SLV-6000-24 SELENOID VALVE 1 42 M-TSC-6000 T CONNECTION FOR SWITCH CAPILLARY 2
16 M-MMV-6000 MEMBRANE VALVE 10 43 C-CLP-6000 DRYER CLAMP 1
17 M-MMM-6000 MEMBRANE 10 44 M-BPC-6000 BY-PASS CLAMP 1
18 M-CFR-6000 CABINET FRONT 1 45 M-CCP-6000 CONDUIT FOR CONTROL PANEL 23
19 M-CSI-6000 CABINET SIDE LEFT 1 46 M-CCB-6000 CONDUIT FOR CONTROL BOX 1
20 M-CSI-6000 CABINET SIDE RIGHT 1 47 M-KEP-6000 KIT FOR ELECTRICAL PANEL 1
21 M-CRE-6000 CABINET REAR 4 48 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
22 M-CTO-6000 CABINET TOP 2 49 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
23 M-CBA-6000 CABINET BASE 2 50 M-PWC-6000 POWER CONNECTOR 1
24 M-CBL-6000 CABINET LEG 4 51 M-CCK-6000 CONTACTOR CONNECTION KIT 3
25 M-HP1-6000 CABINET HORIZONTAL PROFILE 1 2 52 M-SCP-6000 CAPILLARY FOR SWITCH 3
26 M-HP2-6000 CABINET HORIZONTAL PROFILE 2 2 53 M-HLC-6000 CAPILLARY FOR SWITCH HIGH/LOW PRESS 2
27 M-CTC-6000 CABINET TOP CORNER 4 54 M-REV-6000 RELIEF VALVE 2

DECAL CAPACITY DRYER PART NUMBER POWER RATINGS COOLING COMPRESSOR FAN MOTOR

RD 6000 6000 CFM 02250193-929 400V/3PH/50HZ AIR COOLED M-CMP-3000-460-3-60 M-FMT-6000-460-3-60


RD 6000 6000 CFM 02250193-994 460V/3PH/60HZ AIR COOLED M-CMP-3000-460-3-60 M-FMT-6000-460-3-60
RD 6000 6000 CFM 02250194-148 575V/3PH/60HZ AIR COOLED M-CMP-3000-575-3-60 M-FMT-6000-575-3-60
85
4.24 ED/SPARE PARTS—RD6000 WATER COOLED
86

SECTION 4
02250196-628 R03
4.24 ED/SPARE PARTS—RD6000 WATER COOLED

SECTION 4
KEY PART NUMBER DESCRIPTION QTY KEY PART NUMBER DESCRIPTION QTY
1 SEE REF. TABLE COMPRESSOR 1 29 M-NUT-6000 CAGE NUTS 64
2 M-CON-6000-W CONDENSOR 1 30 M-SCR-6000 SCREWS 16
3 M-DRI-6000 DRIER-DEHYDRATOR 1 31 SEE REF. TABLE TRANSFORMER 1
4 M-EXC-6000 HEAT EXCHANGER 9 32 M-PPR-6000 PHASE PROTECTION RELAY 1
5 M-EXV-6000 EXPANSION VALVE 1 33 M-CNT-6000 CONTACTOR 1
6 M-BYV-6000 BY PASS VALVE 1 COMPRESSOR OVERLOAD
7 M-SPR-6000 SEPARATOR 1 34 M-COP-6000 PROTECTOR 1
8 M-RCV-6000 LIQUID RECEIVER 1 35 M-WFV-6000 WATER VALVE 1
9 M-HPS-6000 HIGH PRESSURE SECURITY SWITCH 1 36 M-SNS-6000 SENSOR PROBE 6
10 M-LPS-6000 LOW PRESSURE SWITCH 1 37 M-DBV-6000 DRAIN BALL VALVE 10
11 M-MKP-6000 MIKROPROCESSOR 1 ELBOW FOR HEAT EXCHANGER
12 M-MNS-6000 MAIN SWITCH 1 38 M-EHH-6000 HOSE 18
13 M-SLV-6000 SELENOID VALVE 2 T CONNECTION FOR SWITCH
14 M-MMV-6000 MEMBRANE VALVE 10 39 M-TSC-6000 CAPILLARY 2
15 M-MMM-6000 MEMBRANE 10 40 C-CLP-6000 CLAMP 2
16 M-CFR-6000 CABINET FRONT 1 41 M-BPC-6000 BY-PASS CLAMP 2
17 M-CSI-6000W CABINET LEFT-SIDE 1 42 M-CCP-6000 CONDUIT FOR CONTROL PANEL 23
18 M-CRS-6000 CABINET RIGHT-SIDE 1 43 M-CCB-6000 CONDUIT FOR CONTROL BOX 1
19 M-CRE-6000 CABINET REAR 4 44 M-KEP-6000 KIT FOR ELECTRICAL PANEL 1
20 M-CTO-6000 CABINET TOP 1 45 M-FHL-6000 LOW VOLTAGE FUSE HOLDER 2
21 M-CBA-6000 CABINET BASE 2 46 M-FHH-6000 HIGH VOLTAGE FUSE HOLDER 5
22 M-CBL-6000 CABINET LEG 4 47 M-PWC-6000 POWER CONNECTOR 1
23 M-HP1-6000 CABINET HORIZ. PROFILE 1 2 48 M-CCK-6000 CONTACTOR CONNECTION KIT 3
24 M-HP2-6000 CABINET HORIZ. PROFILE 2 2 CAPILLARY FOR SWITCH HIGH/LOW
49 M-HLC-6000 PRESSURE 2
25 M-CTC-6000 CABINET TOP CORNER 4
26 M-CHN-6000 CABINET HANDLE NEW 18 50 M-REV-6000 RELIEF VALVE 2
27 M-STU-6000 CABINET STUD AND NUT\ 48
28 M-FAS-6000 CABINET FASTENER 48

DRYER PART POWER


DECAL CAPACITY COOLING COMPRESSOR
NUMBER RATINGS

RD 6000 6000 CFM 02250193-559 400V/3Ph/50Hz WATER COOLED M-CMP-3000-460-3-60

RD 6000 6000 CFM 02250193-119 460V/3Ph/60Hz WATER COOLED M-CMP-3000-460-3-60

RD 6000 6000 CFM 02250194-171 575V/3Ph/60Hz WATER COOLED M-CMP-3000-575-3-60


87
4.25 ID—RD400
88

SECTION 4
02250195-264
4.25 ID—RD400

SECTION 4
DRYER WITHOUT PALLET SIZE
23.23” x 27.95” x 49.8”
RD 400
590mm x 710mm x 12651270mm
89
4.26 ID—RD500-850
90

SECTION 4
02250195-266
4.26 ID—RD500-850

SECTION 4
E (AIR
DRYER PART POWER F (WATER
DECAL A B C D CONNECTION COOLING G H
NUMBER RATINGS CONNECTION)
)
02250193-918 400V/3Ph/50Hz
02250193-850 230V/3Ph/60Hz 34.25” 15.55” 10.04” 14.76”
RD500 2” NPT-F
02250193-982 460V/3Ph/60Hz 870mm 395mm 255mm 375mm

02250193-137 575V/3Ph/60Hz
02250193-919 400V/3Ph/50Hz
02250193-851 230V/3Ph/60Hz 34.25” 15.55” 11.61” 14.17”
RD700 3” NPT-M AIR COOLED N/A N/A N/A
02250193-983 460V/3Ph/60Hz 870mm 395mm 295mm 360mm

02250193-138 575V/3Ph/60Hz
02250193-920 400V/3Ph/50Hz
02250193-852 230V/3Ph/60Hz 37.2” 17.52” 11.61” 14.17”
RD850 3” NPT-M
02250193-984 460V/3Ph/60Hz 945mm 445mm 295mm 360mm

02550193-139 575V/3Ph/60Hz
02250193-861 230V/3Ph/60Hz
02250193-947 400V/3Ph/50Hz 34.25” 15.55” 11.61” 14.17”
RD700 3” NPT-M
02250194-107 460V/3Ph/60Hz 870mm 395mm 295mm 360mm

02250194-161 575V/3Ph/60Hz 44.88” 50.78”


WATER COOLED 1” NPT-F 1140m 1290m
02250193-862 230V/3Ph/60Hz m m
02250193-948 400V/3Ph/50Hz 37.2” 17.52” 11.61” 14.17”
RD850 3” NPT-M
02250194-108 460V/3Ph/60Hz 945mm 445mm 295mm 360mm

02550194-162 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
RD 500 807 LB/336 kg 794 LB/360 kg
29.33”*33.27”*50” 34.25”*48.43”*59.45”
RD 700 847 LB/384 kg 835 LB/379 kg
745mm*845mm*1270mm 870mm*1230mm*1510mm
RD 850 952 LB/432 kg 941 LB/427 kg
91
4.27 ID—RD1000-1200
92

SECTION 4
02250195-267 R01
4.27 ID—RD1000-1200

SECTION 4
DRYER PART POWER A B (WATER
DECAL (1) COOLING C D
NUMBER RATINGS (DEPTH) CONNECTION)
02250193-921 400V/3Ph/50Hz
31.89”
RD1000 02250193-985 460V/3Ph/60Hz
810mm
02250194-140 575V/3Ph/60Hz
AIR COOLED N/A N/A N/A
02250193-922 400V/3Ph/50Hz
45.47”
RD1200 02250193-986 460V/3Ph/60Hz
1155mm
02250194-141 575V/3Ph/60Hz
02250193-949 400V/3Ph/50Hz
31.89”
RD1000 02250194-109 460V/3Ph/60Hz
810mm
02250194-163 575V/3Ph/60Hz 21.25” 29.13”
WATER COOLED 1” NPT-F
02250193-950 400V/3Ph/50Hz 540mm 740mm
45.47”
RD1200 02250194-110 460V/3Ph/60Hz
1155mm
02250194-164 575V/3Ph/60Hz

DRYER A (DEPTH) GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
31.89” 31.89” x 45.87” x 74.2” 34.64” x 48.82” x 76.38”
RD 1000 1113 LB/505 kg 1094 LB/496 kg
810mm 810mm*1165mm*1885mm 880mm x 1240mm x 1940mm
45.47” 45.87” x 45.87” x 74.2” 48.03” x 48.03” x 76.38”
RD 1200 1389 LB/630 kg 1367 LB620 kg
1155mm 1165mm x 1165mm x 1885mm 1220mm x 1220mm x 1940mm
93
4.28 ID—RD1600-2000
94

SECTION 4
02250195-268
4.28 ID—RD1600-2000

SECTION 4
A (WATER
DRYER PART POWER
DECAL (1) COOLING CONNECTION B C
NUMBER RATINGS
)
02250193-923 400V/3Ph/50Hz
RD1600 02250193-988 460V/3Ph/60Hz
02250194-142 575V/3Ph/60Hz
AIR COOLED N/A N/A N/A
02250193-924 400V/3Ph/50Hz
RD2000 02250193-989 460V/3Ph/60Hz
02250194-143 575V/3Ph/60Hz
02250193-951 400V/3Ph/50Hz
RD1600 02250194-113 460V/3Ph/60Hz
02250194-165 575V/3Ph/60Hz 21.25” 29.13”
WATER COOLED 1 1/4” NPT-F
02250193-953 400V/3Ph/50Hz 540mm 740mm
RD2000 02250194-114 460V/3Ph/60Hz
02250194-166 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
RD 1600 1819 LB/825 kg 1790 LB/812 kg 45.87” x 61.8” x 78.15” 48.81” x 64.17” x 79.53”
RD 2000 1865 LB/846 kg 1832 LB/831 kg 1165mm x 1570mm x 1985mm 1240mm x 1630mm x 2020mm
95
4.29 ID—RD2400
96

SECTION 4
02250195-269
4.29 ID—RD2400

SECTION 4
DRYER PART POWER A (WATER
DECAL (1) COOLING B C
NUMBER RATINGS CONNECTION)
02250193-925 400V/3Ph/50Hz
RD2400 02250193-990 460V/3Ph/60Hz AIR COOLED N/A N/A N/A
02250194-144 575V/3Ph/60Hz
02250193-954 400V/3Ph/50Hz
19.3” 25.2”
RD2400 02250194-115 460V/3Ph/60Hz WATER COOLED 1 1/4” NPT-F
490mm 640mm
02250194-167 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
48.23” x 78.74” x 78.15” 50.98” x 81.5” x 79.53”
RD 2400 2322 LB/1053 kg 2295 LB/1041 kg
1225mm x 2000mm x 1985mm 1295mm x 2070mm x 2020mm
97
4.30 ID—RD3000
98

SECTION 4
02250195-269
4.30 ID—RD3000

SECTION 4
DRYER PART POWER A (WATER
DECAL (1) COOLING B C
NUMBER RATINGS CONNECTION)
02250193-926 400V/3Ph/50Hz
RD3000 02250193-991 460V/3Ph/60Hz AIR COOLED N/A N/A N/A
02250194-145 575V/3Ph/60Hz
02250193-955 400V/3Ph/50Hz
19.3” 25.2”
RD3000 02250194-116 460V/3Ph/60Hz WATER COOLED 1 1/4” NPT-F
490mm 640mm
02250194-168 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
48.23” x 86.22” x 78.15” 50.98” x 92.52” x 79.53”
RD 3000 2778 LB/1260 kg 2752 LB/1248 kg
1225mm x 2190mm x 1985mm 1295mm x 2350mm x 2020mm
99
4.31 ID—RD3800
100

SECTION 4
02250195-270
4.31 ID—RD3800

SECTION 4
DRYER PART POWER A (WATER
DECAL (1) COOLING B C
NUMBER RATINGS CONNECTION)
02250193-927 400V/3Ph/50Hz
02250193-992 460V/3Ph/60Hz AIR COOLED N/A N/A N/A
02250194-146 575V/3Ph/60Hz
RD3800
02250193-956 400V/3Ph/50Hz
19.3” 25.2”
02250194-117 460V/3Ph/60Hz WATER COOLED 1 1/4” NPT-F
490mm 640mm
02250194-169 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
48.23” x 106.3” x 78.74” 50.98” x 113.78” x 79.53”
RD 3800 3053 LB/1385 kg 3023 LB/918 kg
1225mm x 2700mm x 2000m 1295mm x 2890mm x 2020mm
101
4.32 ID—RD5000
102

SECTION 4
02250195-271
4.32 ID—RD5000

SECTION 4
A (WATER
DRYER PART POWER
DECAL (1) COOLING CONNECTION B C D
NUMBER RATINGS
)
02250193-928 400V/3Ph/50Hz
RD5000 02250193-993 460V/3Ph/60Hz AIR COOLED N/A N/A N/A N/A
02250194-147 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
59.05” x 115.55” x 78.54” 66.93” x 123.42” x 82.67”
RD 5000 2820 LB/1279 kg 2420 LB/1098 kg
1500MM x 2935MM x 1955MM 1700mm x 3135mm x 2100mm
103
4.33 ID—RD6000
104

SECTION 4
02250195-272
4.33 ID—RD6000

SECTION 4
DRYER PART POWER A (WATER
DECAL COOLING B C
NUMBER RATINGS CONNECTION)
02250193-929 400V/3Ph/50Hz
02250193-994 460V/3Ph/60Hz AIR COOLED N/A N/A N/A
02250194-148 575V/3Ph/60Hz
RD6000
02250193-959 400V/3Ph/50Hz
24.4” 29.13”
02250194-119 460V/3Ph/60Hz WATER COOLED 1 1/4” NPT-F
620mm 740mm
02250194-171 575V/3Ph/60Hz

DRYER GROSS WEIGHT NET WEIGHT WITHOUT PALLET SIZE WITH PALLET SIZE
65.35” x 90.94” x 84.25” 70.47” x 96.06” x 88.58”
RD 6000 3150 LB/1429 kg 2750 LB/1248 kg
1660mm x 2310mm x 2140mm 1790mm x 2440mm x 2250mm
105
4.34 P&I—RD400
106

SECTION 4
02250195-291
4.34 P&I—RD400

SECTION 4
POS. DESCRIPTION

1 COMPRESSOR

2 REFRIGERANT CONDENSER

3 FAN MOTOR

4 FAN MOTOR SWITCH

5 EVAPORATOR

6 AIR-AIR EXCHANGER

7 PRESSURE REGULATOR

8 DEHYDRATOR

9 DEW POINT INDICATOR

10 BY-PASS VALVE

11 LIQUID RECEIVER

NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N


AND REVISION

MODEL REFRIGERANT TYPE LB

RD400 R134A 6.613


107
4.35 P&I—RD500-850
108

SECTION 4
02250195-293
4.35 P&I—RD500-850

SECTION 4
POS. DESCRIPTION

1 COMPRESSOR

2 REFRIGERANT CONDENSER

3 FAN MOTOR

4 FAN MOTOR SWITCH

5 EVAPORATOR

6 AIR-AIR EXCHANGER

7 PRESSURE REGULATOR

8 DEHYDRATOR

9 DEW POINT INDICATOR

10 BY-PASS VALVE

11 LIQUID RECEIVER

12 LIQUID SEPARATOR

NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND


REVISION

MODEL REFRIGERANT TYPE LB

RD500 8.818

RD700 R134A 9.369

RD850 11.023
109
4.36 P&I—RD700-850 WATER COOLED
110

SECTION 4
02250195-294
4.36 P&I—RD700-850 WATER COOLED

SECTION 4
POS. DESCRIPTION

1 COMPRESSOR

2 WATER CONDENSER

3 EVAPORATOR

4 AIR-AIR EXCHANGER

5 PRESSURE REGULATOR

6 DEHYDRATOR

7 DEW POINT INDICATOR

8 BY-PASS VALVE

9 LIQUID RECEIVER

10 LIQUID SEPARATOR

NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND


REVISION.

MODEL REFRIGERANT TYPE LB

RD700 9.369
R134A
RD850 11.023
111
4.37 P&I—RD1000-6000
112

SECTION 4
02250195-297
4.37 P&I—RD1000-6000

SECTION 4
POS. DESCRIPTION

1 COMPRESSOR

2 REFRIGERANT CONDENSER

3 FAN MOTOR

4 FAN MOTOR SWITCH

5 DEHYDRATOR

6 BY-PASS VALVE

7 LIQUID RECEIVER

8 LIQUID SEPARATOR

9 PRESSURE REGULATOR

10 ALUMINIUM BRAZED PLATE HEAT EXCHANGER

NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND


REVISION.

MODEL REFRIGERANT TYPE

RD1000

RD1200

RD1600

RD2000

RD2400 R134A

RD3000

RD3800

RD5000

RD6000
113
4.38 P&I—RD1000-6000 WATER COOLED
114

SECTION 4
02250195-298
4.38 P&I—RD1000-6000

SECTION 4
POS. DESCRIPTION

1 COMPRESSOR

2 WATER CONDENSER

3 DEHYDRATOR

4 BY-PASS VALVE

5 LIQUID RECEIVER

6 LIQUID SEPARATOR

7 PRESSURE REGULATOR

8 ALUMINIUM BRAZED PLATE HEAT EXCHANGER

NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N


AND REVISION.

MODEL REFRIGERANT TYPE

RD1000

RD1200

RD1600

RD2000

RD2400 R134A

RD3000

RD3800

RD5000

RD6000
115
4.39 WIRING DIAGRAM—RD400 (230-3-60-A)
116

SECTION 4
02250195-319-S1
4.39 WIRING DIAGRAM—RD400 (230-3-60-A)

SECTION 4
COMP DESCRIPTION

A01 Control circuit transformer


A30 Compressor chankaser heater
B01 Main terminal block
B15 Control circuit supply
EMR4 Phase protection relay
F1, F2, F3 A01 Primary protection
F13 Control circuit protection
K01 Compressor contactor (24V)
K10 Fan contactor (24V)
M01 Compressors
M10 Fan motor
P01-1 Thermal protection off-on compressor 1
P01-2 Thermal protection off-on compressor 2
P10 Over load protector
S01 Main switch
117
4.39 WIRING DIAGRAM—RD400 (230-3-60-A)
118

SECTION 4
02250195-319-S2
4.39 WIRING DIAGRAM—RD400 (230-3-60-A)

SECTION 4
COMP DESCRIPTION COMP DESCRIPTION

F10,F11 Control Circuit Protection PT6 Condenser Exit Temperature Sensor (Pt100)
S02 Remote Control Start Button B16 Computer Control
S03 Remote Control Stop Button HP Indicates High Pressure
P01-1 Thermal Protection Off-on Compressor 1 LP Indicates Low Pressure in the Circuit
P01-2 Thermal Protection Off-on Compressor 2
P02-1 Compressor Heat Thermal 1
P02-2 Compressor Heat Thermal 2
EMR4 Phase Protection Relay
S04 Obstruction For Manual On/off
S05 Remote Control Contact
S06 Service Contact
S11-1 Low Pressure Security Control 1
S11-2 High Pressure Security Control 2
K01-1 Compressor Motor Relay 1
K01-2 Compressor Motor Relay 2
A20 Electronic Timer Supply
A25 Compressor Heat Thermal 1 Supply
A26 Compressor Heat Thermal 2 Supply
P10 Thermal Protection Off-on Fan
A10 Remote Control Running Lamp (Green)
A11 Remote Control Standby Lamp (Red)
A41 Remote Control Alarm Contact
PT1 Inlet Air Temperature Sensor (Pt100)
PT2 Heat Exchanger Temperature Sensor (Pt100)
PT3 Low Pressure Line Sensor (Pt100)
PT4 High Pressure Line Sensor (Pt100)
119

PT5 Ambient Temperature Sensor (Pt100)


4.40 WIRING DIAGRAM—RD400 (460-3-60-A, 400-3-50-A)
120

SECTION 4
02250195-974-S1
4.40 WIRING DIAGRAM—RD400 (460-3-60-A, 400-3-50-A)

SECTION 4
COMP DESCRIPTION

A01 Control Circuit Transformer


A30 Compressor Chankaser Heaters
B01 Main Terminal Block
B15 Control Circuit Supply
EMR4 Phase Protection Relay
F1,F2,F3 Emr4 Poverload Protection
F4 A01 Primary Protection
F5 A40 Overload Protection
F13 Control Circuit Protection
K01 Compressor Contactor (24v)
M01 Compressor Motor
M10 Fan Motor
P01 Thermal Protection Off-on Compressor
P10 Fan Motor Over Load Protector
S01 Main Switch
121
4.40 WIRING DIAGRAM—RD400 (460-3-60-A, 400-3-50-A)
122

SECTION 4
02250195-974-S2
4.40 WIRING DIAGRAM—RD400 (460-3-60-A, 400-3-50-A)

SECTION 4
COMP DESCRIPTION COMP DESCRIPTION

F10,F11 Control Circuit Protection PT5 Ambient Temperature Sensor (Pt100)


P01 Thermal Protection Off-on Compressor PT6 Condenser Exit Temperature Sensor (Pt100)
P02 Compressor Heat Thermal Protector B16 Computer Control
P10 Thermal Protection Off-on Fan HP Indicated High Pressure
S30 Fan Heat Thermal Protector LP Indicated Low Pressure
EMR4 Phae Protection Relay TH Indicated High Temperature In The Circuit
S02 Remote Control Start Button
S03 Remote Control Stop Button
S04 Obstruction For Manual On/off
S05 Remote Control Contact
S06 Service Contact
S10 Fan Pressure Switch
S11-2 High Pressure Security Control 2
S11-1 Low Pressure Security Control 1
K01 Compressor Motor Relay
K10 Fan Motor Relay
A10 Remote Control Running Lamp (Green)
A11 Remote Control Stand-by Lamp (Red)
A20 Electronic Timer Supply
A41 Remote Control Alarm Contact
PT1 Inlet Air Temperature Sensor (Pt100)
PT2 Heat Exchanger Temperature Sensor (Pt100)
PT3 Low Pressure Line Sensor (Pt100)
PT4 High Pressure Line Sensor (Pt100)
123
4.41 WIRING DIAGRAM—RD500/700 (230-3-60-A)
124

SECTION 4
02250195-975-S1
4.41 WIRING DIAGRAM—RD500/700 (230-3-60-A)

SECTION 4
COMP DESCRIPTION

A01 Control Circuit Transformer


A30 Compressor Chankaser Heaters
B01 Main Terminal Block
B15 Control Circuit Supply
EMR4 Phase Protection Relay
F1,F2,F3 Emr4 Poverload Protection
F4 A01 Rimary Protection
F5 A30 Overload Protection
F13 Control Circuit Protection
K01-1 Compressor Contactor (24v)
K01-2 Compressor Contactor (24v)
K10 Fan Contactor (24v)
M01 Compressor Motor
M10-1 Fan Motor
M10-2 Fan Motor
P01 Thermal Protection Off-on Compressor
P10 Fan Motor Over Load Protector
S01 Main Switch
125
4.41 WIRING DIAGRAM—RD500/700 (230-3-60-A)
126

SECTION 4
02250195-975-S2
4.41 WIRING DIAGRAM—RD500/700 (230-3-60-A)

SECTION 4
COMP DESCRIPTION COMP DESCRIPTION

F10,F11 Control Circuit Protection PT3 Low Pressure Line Sensor (Pt100)
S02 Remote Control Start Button PT4 High Pressure Line Sensor (Pt100)
S03 Remote Control Stop Button PT5 Ambient Temperature Sensor (Pt100)
P01 Thermal Protection Off-on Compressor PT6 Condenser Exit Temperature Sensor (Pt100)
P02 Compressor Heat Thermal B16 Computer Control
P10-1 Thermal Protection Off-on Fan 1 HP Indicates High Pressure
P10-2 Thermal Protection Off-on Fan 2 LP Indicates Low Pressure
S30-1 Fan Heat Thermal 1 TH Indicates High Temperature In The Circuit
S30-2 Fan Heat Thermal 2
EMR4 Phase Protection Relay
S04 Remote Control Contact
S05 Obstruction For Manual On/0ff
S06 Service Contact
S10-1 Fan Pressure Switch 1
S10-2 Fan Pressure Switch 2
S11-1 Low Pressure Security Control 1
S11-2 High Pressure Security Control 2
K01 Compressor Motor Relay
K10-1 Ran Motor Relay 1
K10-2 Fan Motor Relay 2
A20 Electronic Timer Supply
A10 Remote Control Running Lamp (Green)
A11 Remote Control Stand-by Lamp (Red_
A41 Remote Control Alarm Contact
PT1 Inlet Air Temperature Sensor (Pt100)
PT2 Heat Exchanger Temperature Sensor (Pt100)
127
4.42 WIRING DIAGRAM—RD (500/700/850-1000-1200-1600-2000-2400-3000-3800-5000-6000)-460-3-60-A, 400-3-50-A
128

SECTION 4
02250195-314-S1
4.42 WIRING DIAGRAM—RD (500/700/850-1000-1200-1600-2000-2400-3000-3800-5000-6000)-460-3-60-A, 400-3-50-A

SECTION 4
COMP DESCRIPTION

A01 Control circuit transformer


A30 Compressor chankaser heater
B01 Main terminal block
B15 Control circuit supply
EMR4 Phase protection relay
F1, F2, F3 EMR4 Poverload Protection
F4 A01 Primary Protection
F5 A30 Overload Protection
F13 Control circuit protection
K01-1 Compressor contactor (24V)
K01-2 Compressor contactor (24V)
K10 Fan contactor (24V)
M01 Compressor
M10-1 Fan motor
M10-2 Fan motor
P01 Thermal protection off-on compressor
P10 Over load protector
S01 Main switch
129
4.42 WIRING DIAGRAM—RD (500/700/850-1000-1200-1600-2000-2400-3000-3800-5000-6000)-460-3-60-A, 400-3-50-A
130

SECTION 4
02250195-314-S2
4.42 WIRING DIAGRAM—RD (500/700/850-1000-1200-1600-2000-2400-3000-3800-5000-6000)-460-3-60-A, 400-3-50-A

SECTION 4
COMP DESCRIPTION COMP DESCRIPTION

F10,F11 Control Circuit Protection PT3 Low Pressure Line Sensor (Pt100)
S02 Remote Control Start Button PT4 High Pressure Line Sensor (Pt100)
S03 Remote Control Stop Button PT5 Ambient Temperature Sensor (Pt100)
P01 Thermal Protection Off-on Compressor PT6 Condenser Exit Temperature Sensor (Pt100)
P02 Compressor Heat Thermal B16 Computer Control
P10-1 Thermal Protection Off-on Fan 1 HP Indicates High Pressure
P10-2 Thermal Protection Off-on Fan 2 LP Indicates Low Pressure
S30-1 Fan Heat Thermal 1 TH Indicates High Temperature In The Circuit
S30-2 Fan Heat Thermal 2
EMR4 Phase Protection Relay
S04 Remote Control Contact
S05 Obstruction For Manual On/0ff
S06 Service Contact
S10-1 Fan Pressure Switch 1
S10-2 Fan Pressure Switch 2
S11-1 Low Pressure Security Control 1
S11-2 High Pressure Security Control 2
K01 Compressor Motor Relay
K10-1 Ran Motor Relay 1
K10-2 Fan Motor Relay 2
A20 Electronic Timer Supply
A10 Remote Control Running Lamp (Green)
A11 Remote Control Stand-by Lamp (Red_
A41 Remote Control Alarm Contact
PT1 Inlet Air Temperature Sensor (Pt100)
PT2 Heat Exchanger Temperature Sensor (Pt100)
131
4.43 WIRING DIAGRAM—RD700-850 (230-3-60-W)
132

SECTION 4
02250195-976-S1
4.43 WIRING DIAGRAM—RD700-850 (230-3-60-W)

SECTION 4
COMP DESCRIPTION

A01 Control circuit transformer


A30 Compressor chankaser heater
B01 Main terminal block
B15 Control circuit supply
EMR4 Phase protection relay
F1, F2, F3 EMR4 Poverload Protection
F4 A01 Primary Protection
F5 A30 Overload Protection
F13 Control circuit protection
K01 Compressor contactor (24V)
M01 Compressor
P01 Thermal protection off-on compressor
S01 Main switch
133
4.43 WIRING DIAGRAM—RD700-850 (230-3-60-W)
134

SECTION 4
02250195-976-S2
4.43 WIRING DIAGRAM—RD700-850 (230-3-60-W)

SECTION 4
COMP DESCRIPTION

F10,F11 Control Circuit Protection


S02 Remote Control Start Button
S03 Remote Control Stop Button
P01 Thermal Protection Off-on Compressor
P02 Compressor Heat Thermal
EMR4 Phase Protection Relay
S04 Remote Control Contact
S05 Obstruction For Manual On/off
S06 Service Contact
S10-1 Fan Pressure Switch 1
S10-2 Fan Pressure Switch 2
S11-1 Low Pressure Security Control 1
S11-2 High Pressure Security Control 2
K01 Compressor Motor Relay
A20 Electronic Timer Supply
A10 Remote Control Running Lamp (Green)
A11 Remote Control Stand-by Lamp (Red)
A41 Remote Control Alarm Contact
PT1 Inlet Air Temperature Sensor (Pt100)
PT2 Heat Exchanger Temperature Sensor (Pt100)
PT3 Low Pressure Line Sensor (Pt100)
PT4 High Pressure Line Sensor (Pt100)
PT5 Ambient Temperature Sensor (Pt100)
PT6 Condenser Exit Temperature Sensor (Pt100)
B16 Computer Control
135
4.44 WIRING DIAGRAM—RD (700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000) 460-3-60-W, 400-3-50-W
136

SECTION 4
02250195-976-S1
4.44 WIRING DIAGRAM—RD (700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000) 460-3-60-W, 400-3-50-W

SECTION 4
COMP DESCRIPTION

A01 Control circuit transformer


A30 Compressor chankaser heater
B01 Main terminal block
B15 Control circuit supply
EMR4 Phase protection relay
F1, F2, F3 A01 Primary protection
F13 Control circuit protection
K01 Compressor contactor (24V)
M01 Compressor
P01 Thermal protection off-on compressor
S01 Main switch
137
4.44 WIRING DIAGRAM—RD (700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000) 460-3-60-W, 400-3-50-W
138

SECTION 4
02250195-976-S2
4.44 WIRING DIAGRAM—RD (700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000) 460-3-60-W, 400-3-50-W

SECTION 4
COMP DESCRIPTION

F1,F2 A01 Primary protection


F10, F11 Control circuit protection
A01 Control circuit transformer
S02 Remote control start button
S03 Remote control stop button
P01 Thermal protection off-on compressor
P02 Compressor heat thermal
EMR4 Phase protection relay
S04 Remote control contact
S05 Obstruction for manual on/off
S06 Service contact
S10-1 Fan pressure switch 1
S10-2 Fan pressure switch 2
S11-1 Low pressure security control 1
S11-2 High pressure security control 2
K01 Compressor motor relay
A20 Electronic timer supply
A10 Remote control running lamp (Green)
A11 Remote control stand-by lamp (red)
A41 Remote control alarm contact
139
4.45 CONTROL CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000
140

SECTION 4
02250195-307
4.45 CONTROL CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000

SECTION 4
COMP DESCRIPTION COMP DESCRIPTION

F1,F2 Primary protection A20 Drain valve


F10,F11 Control circuit protection A41 Remote control alarm contact
A01 Control circuit transformer
S02 Remote control start button
S03 Remote control stop button
P01 Thermal protection off-on compressor
P02 Compressor heat thermal
P10-1 Thermal protection off-on fan 1
P10-2 Thermal protection off-on fan 2
P11-1 Fan heat thermal 1
P11-2 Fan heat thermal 2
EMR4 Phase protection relay
S04 Remote control contact
S05 Obstruction for manuall on/off
S06 Service contact
S10-1 Fan pressure switch 1
S10-2 Fan pressure switch 2
S11-1 Low pressure security control 1
S11-2 High pressure security control 2
K01 Compressor motor relay
K10-1 Fan motoro relay 1
K10-2 Fan motor relay 2
A10 Remote control running lamp (green)
A11 Remote control stand-by lamp (red)
141
4.46 POWER CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000
142

SECTION 4
02250195-307
4.46 CONTROL CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000

SECTION 4
COMP DESCRIPTION

A01 Control circuit transformer


A30-1/A30-2 Compressor chankaser heaters
B01 Main terminal block
EMR4 Phase protection relay
F1,F2 A01 primary protection
K01 Compressor contactor (24V)
K10-1 Fan contactor (24V)
K10-2 Fan contactor (24V)
K20 Water motor
M01-1/M01-2 Compressors (400V-440V)
M10-1 Fan motor (400V-440V)
M10-2 Fan motor (400V-440V)
P01 Thermal protection of
P10-1 Over load protector
P10-2 Over load protector
P20 Water motor protection
S01 Main switch
143
NOTES

144
NOTES