You are on page 1of 6

POWER FLOW REPORT - CASO 2 BASE -

20141366F

P S A T 2.1.10

Author: Federico Milano, (c) 2002-2016


e-mail: federico.milano@ucd.ie
website: faraday1.ucd.ie/psat.html

File: C:\Users\Jesus Diego\Desktop\EXAMEN


FINAL\Caso2\Circuito2.mdl
Date: 14-Dec-2019 12:12:46

NETWORK STATISTICS

Buses: 6
Lines: 11
Generators: 2
Loads: 3

SOLUTION STATISTICS

Number of Iterations: 4
Maximum P mismatch [p.u.] 0
Maximum Q mismatch [p.u.] 0
Power rate [MVA] 100

POWER FLOW RESULTS


Bus V phase P gen
Q gen P load Q load
[p.u.] [rad] [p.u.]
[p.u.] [p.u.] [p.u.]

Bus1 1.07 0 2.7041


-0.14611 0 0
Bus2 1.05 -0.1727 0.5
0.68013 0 0
Bus3 1.0158 -0.24259 0
0 0 0
Bus4 1.0257 -0.18053 0
0 1 0.15
Bus5 1.0074 -0.23219 0
0 1 0.15
Bus6 1.0009 -0.2735 0
0 1 0.15

Maximum voltage at bus <Bus1>

LINE FLOWS

From Bus To Bus Line P Flow


Q Flow P Loss Q Loss
[p.u.]
[p.u.] [p.u.] [p.u.]
Bus2 Bus3 1 0.31608
0.05766 0.0049 -0.03951
Bus3 Bus6 2 0.3323
0.08013 0.0023 -0.00884
Bus1 Bus4 3 1.0041
0.05221 0.04428 0.13317
Bus2 Bus6 4 0.5598
0.06118 0.0204 0.00567
Bus2 Bus1 5 -0.78083
0.34693 0.06765 0.09035
Bus2 Bus5 6 0.23528
0.05483 0.00556 -0.02568
Bus1 Bus5 7 0.85151
0.05825 0.05126 0.12745
Bus6 Bus5 8 -0.13059
-0.00552 0.00176 -0.05521
Bus2 Bus4 9 0.16967
0.15952 0.00262 -0.0163
Bus5 Bus4 10 -0.12377
-0.02135 0.00309 -0.07649
Bus3 Bus5 11 -0.02113
0.01704 0.00027 -0.05059

Maximum apparent power limit


violation on line 3 [S = 1.00546 > S_max =
1]
Maximum apparent power limit
violation on line 5 [S = 0.854433 > S_max =
0.6]
LINE FLOWS

From Bus To Bus Line P Flow


Q Flow P Loss Q Loss
[p.u.]
[p.u.] [p.u.] [p.u.]

Bus3 Bus2 1 -0.31117


-0.09717 0.0049 -0.03951
Bus6 Bus3 2 -0.33
-0.08897 0.0023 -0.00884
Bus4 Bus1 3 -0.95982
0.08095 0.04428 0.13317
Bus6 Bus2 4 -0.53941
-0.05551 0.0204 0.00567
Bus1 Bus2 5 0.84848
-0.25658 0.06765 0.09035
Bus5 Bus2 6 -0.22973
-0.08051 0.00556 -0.02568
Bus5 Bus1 7 -0.80025
0.06919 0.05126 0.12745
Bus5 Bus6 8 0.13235
-0.04969 0.00176 -0.05521
Bus4 Bus2 9 -0.16704
-0.17582 0.00262 -0.0163
Bus4 Bus5 10 0.12686
-0.05514 0.00309 -0.07649
Bus5 Bus3 11 0.02139
-0.06764 0.00027 -0.05059

Maximum apparent power limit


violation on line 5 [S = 0.886426 > S_max =
0.6]

GLOBAL SUMMARY REPORT

TOTAL GENERATION

REAL POWER [p.u.] 3.2041


REACTIVE POWER [p.u.] 0.53402

TOTAL LOAD

REAL POWER [p.u.] 3


REACTIVE POWER [p.u.] 0.45

TOTAL LOSSES

REAL POWER [p.u.] 0.20409


REACTIVE POWER [p.u.] 0.08402

LIMIT VIOLATION STATISTICS


ALL VOLTAGES WITHIN LIMITS (1 BINDING).
ALL REACTIVE POWER WITHIN LIMITS.
ALL CURRENT FLOWS WITHIN LIMITS.
ALL REAL POWER FLOWS WITHIN LIMITS.
# OF APPARENT POWER FLOW LIMIT VIOLATIONS: 1