HIMONT Incorporated
SPHERIPOL TECHNOLOGY HIMONT PROPRIETARY
ruvrovenest #1, RELATED To SAFETY
CENTRAL PANEL FOR GAS MONITORS
HIMONT has installed in some of his operation facilities a
central panel for all gas detectors in order to improve the
general safety of the SPHERIPOL technology.
The general specification of the central panel is attached.
The estimated for the installation is 120,000 $us.HIMONT - PROPRIETARY
GENERAL CONC
Technical specification covering the installation of a
synoptic board, fitted with weathering monitoring station
for the gas-detector display at the SPHERIPOL production
Plants.
1. Purpose of the work
A. To make easier the environment control of possible
propylene release with regard to the actual
weathering condition is to shorten the time
required by the operator to undertake any step.
B The synoptic board could also have connection to a
computerized "intelligent system" to estimate the
amount and the probable source of the release,
thus suggesting the steps to undertake in order to
put the plant under the safiest conditions.
2. Technical description
A. Synoptic Board
The synoptic board, of the luminous, mosaic-type,
must show the planimetric and isometric drawing of
the plant with the planimetric and altimetric
location of the progressively numbered gas
detectors.
ALL of the readings of the "synoptic board" shall
be printed with abrasion resistant, indelible
colours.
The gas-detector location shall be marked with
identification name and installation level.
Each gas-detector shall be provided with the
following coloured signals:
~ normal operation : green
- pre-alarm orange
a alarm : red
such signals shall be realized with strong
intensity LEDS of the protruding type, located in
only one module.HIMONT - PROPRIETARY
The "detector anomaly" signal shall be different
from that of normal operation, that is:
- fixed green normal operation
= pulsating green : anomaly
The synoptic board placed on a self-supporting
frame, shall have the following sizes:
- width =: 2200
- length + 1500
- depth + 300
Honeywell standard, azure-coloured closet, under
the synoptic board’shall have the following size:
2200 X 1400 X 300.
Metereologic station
On the synoptic board a station shall be installed
with the following properties:
- wind direction
- wind velocity
- atmospheric moisture