EXM2
100 to 250 kW
Highly Reliable and Efficient
UPS designed to provide
industry-leading performance
Vertiv™ Liebert® EXM2 | 100 to 250 kW
About Vertiv
Vertiv brings together hardware, software, analytics and ongoing services to ensure its customers’
vital applications run continuously, perform optimally and grow with their business needs. Vertiv
solves the most important challenges faced by today’s data centers, communication networks and
commercial and industrial facilities with a portfolio of power, cooling, and IT infrastructure solutions
and services that extends from the cloud to the edge of the network. Headquartered in Columbus,
Ohio, USA, Vertiv employs around 20,000 people and does business in more than 130 countries. For
more information, and for the latest news and content from Vertiv, visit Vertiv.com.
Vertiv.com
US AND CANADA LATIN AMERICA EUROPE, MIDDLE EAST AND ASIA PACIFIC
Manuf. and Assembly Locations 7 Manuf. and Assembly Locations 1 Manuf. and Assembly Locations 6
Service Centers 120+ Service Centers 20+ AFRICA Service Centers 60+
Service Field Engineers 850+ Technical Service Field Engineers 300+ Manuf. and Assembly Locations 5 Service Field Engineers 950+
Support/Response 120+ Customer Technical Support/Response 25+ Service Centers 70+ Technical Support/Response 90+
Experience Centers/Labs 4 Customer Experience Centers/Labs 2 Service Field Engineers 600+ Customer Experience Centers/Labs 5
Technical Support/Response 95+
Customer Experience Centers/Labs 6
Liebert® EXM2, The Next Generation Mid-size UPS for Mission-critical Applications
3
Vertiv™ Liebert® EXM2 | 100 to 250 kW
y Suitable to be installed
against the wall using
optional top fan kit
y Suitable to be installed
adjacent to the wall
1 Bypass Section
1 2
2 Power Section
3 Integrated Surge 2
Protection 6
6
4 Switch Assembly
3 3
5 Cable Termination
Section (Bottom as 4 4
standard)
6 Top cable
Termination panel 5
(Optional)
5
Liebert® EXM2 delivers an and electricity cost savings of Class 1 output performance under
outstanding Double conversion Liebert EXM2 can be attributed to: most stringent conditions:
efficiency of up to 97%, which y Network fault (voltage
y Latest generation IGBT
further increases up to 98.8% with variation, high/ low impedance
the Dynamic online mode, y Adoption of a three-level T-type
mains failures)
consequently reducing operating converter topology
costs and energy dissipation y DC controlled fan speed y Load fault (short circuit
(kW) to a minimum. This downstream of the UPS)
significantly minimizes the y Intelligent paralleling mode
consumption of the cooling system, y Type of load connected (PDU
y Advanced digital technology
providing an overall TCO reduction transformer)
and fast transfer
and rapid payback time.
The seamless activation of Liebert The unit discriminates between
Furthermore, the Liebert EXM2 can EXM2’s functioning modes ensures various interferences and responds
optimize efficiency at partial load the highest level of efficiency rapidly, meanwhile also ensures
thereby attaining additional cost without compromising power compatibility with downstream
savings through the intelligent quality and availability. The equipment (such as Transformers,
paralleling feature. The efficiency Dynamic online mode ensures STS, mechanical loads, etc).
Maximum Power Control (VFI) Maximum Energy Saving (VFD) Dynamic Online, High Efficiency &
Power Conditioning (VI)
Provides the highest level of power Detects when conditioning is not
conditioning and protects the load from required and allows the energy flow to Compensates the load THDi, PF, main
all electrical network disturbances. pass through the bypass line. sags and swells, ensuring fast transfer
output performance.
Dynamic online mode: No more availability tradeoff TYPICAL FUNCTIONING MODES OF A UPS
with efficiency SYSTEM
DOUBLE CONVERSION ECO MODE
MODE (VFI) (VFD)
Dynamic online mode is the latest within the IEC 62040 Class 1 Maximum Availability with Can’t ensure perfect power
Class 1 UPS quality
high efficiency mode of operation specification, thus offering the
offered by Vertiv, developed for same level of availability typically Highest level of Efficiency
up to 97%
Above 99.2% Efficiency
without sacrificing availability. In operating mode with the excellent Maximum Availability with
Class 1 UPS
fact, while in this mode, the inverter energy cost savings of a high
can instantaneously assume the load efficiency mode for a reduced total Up to 98.8% Efficiency
5
Vertiv™ Liebert® EXM2 | 100 to 250 kW
Innovative Internal Air Channel clear short circuit capacity of up to Scalable up to 1.5 MW
65 kA.
Designed in such a way that 6 units of intelligent paralleling
internal hot air drives directly Tolerates Higher Ambient helps to achieve maximum
towards heat sink without Temperatures capacity up to 1.5 MW. Comes
distressing the PCB's and other with Integrated Parallel and LBS
Internal components and circuitry
internal sensitive circuits, communication ports, and allow
of Liebert EXM2 are designed to
improving the service life of single touch to initiate inverter ON/
seamlessly operate up to 40 °C
components and UPS reliability. OFF for all parallel connected UPS
without any capacity impact and
system.
Conformal Coating further can sustain high ambient
temperature up to 50 °C with Symmetrical Power Factor
Applied as standard feature for all
auto-derating. Compatibility
PCBs in Liebert® EXM2. Its primary
purpose is to protect electronics Integrated Backfeed Protection Liebert EXM2 is fully adapted to
from environmental elements and meet diverse system requirements
Backfeed protection prevents any
corrosion. The coating acts as in terms of power capacity and
potential risk from electric shock
both a protective shield and redundancy allowing different
on the UPS mains and bypass
insulative material for a PCB. system designs.
input AC terminals in the event of a
Higher Short Circuit Handling failure of the rectifier and bypass y Output Power Factor up to 1
Capacity static switch SCR. The control
circuit includes output dry y No power derating from 0.5
During the short circuit, load will be lagging to 0.5 leading
contacts that activates an internal
transferred via bypass to clear
isolating device (optional) upon y Optimum space/power ratio
higher short circuit currents.
backfeed detection.
Fuse is considered optionally to
Intelligent Paralleling
15%
30%
Liebert® EXM2 Intelligent
Paralleling: three units at 30%
load each = 96.8% efficiency
User Interface and Advanced Diagnostic
7
Vertiv™ Liebert® EXM2 | 100 to 250 kW
VRLA LIB
VRLA LIB
LEAD LIB
ACID
Battery Management
Saves space Saves cooling cost
System
9
Vertiv™ Liebert® EXM2 | 100 to 250 kW
Vertiv's service program is First Time Fix Rate Fast Incident Response
designed to ensure that your Pro-active monitoring and data Vertiv LIFE Services allow for
critical power protection system is measuring ensure that when our immediate definition of the best
maintained in an optimum state of customer engineers are dispatched course of action, as a result of the
readiness at all times. on-site, they arrive prepared for regular communication between
first time resolution. your Liebert® EXM2 system and
The Vertiv™ LIFE™ Services remote our Vertiv LIFE Service centers.
diagnostic and preventive Proactive Analysis
monitoring service provides early Reporting
From Vertiv LIFE Service centers,
warning of UPS conditions and out
our experts proactively analyze the You will receive a comprehensive
of tolerances. This allows effective
data and trends of your equipment, report detailing the working order
proactive maintenance, fast
to recommend actions to ensure of your equipment and its
incident response and remote
their best performance. operational performance.
troubleshooting, giving customers
complete security and peace of
mind. With Vertiv LIFE Services you Minimized Total Cost of
will benefit from: Ownership of Your Equipment
The continuous monitoring of all
relevant parameters in turn
Uptime Assurance
maximizes unit performance,
Constant monitoring of UPS reduces on-site maintenance and
parameters, thus maximizing the extends the life of your equipment.
system’s availability.
Technical Specifications
Nominal Ratings (kVA/kW) 100 kVA 120 kVA 160 kVA 200 kVA 250 kVA
Input
Nominal input voltage (V) 380 / 400 / 415 (three-phase and sharing neutral with the bypass input)
Input voltage range without
228 to 478
battery discharge (V)*
Nominal input frequency (Hz) 50 / 60
Battery
Battery bus voltage (VDC) 360 to 528 , 2 Wire
Output
380 / 400 / 415
Nominal output voltage (V)
(three-phase and sharing neutral with the bypass input)
Nominal output frequency (Hz) 50 / 60
Inverter overload capacity <105 % for Continuous; <110% for 60min; <125 % 10 min; <150 % for 1 min; >150 % for 200ms
Efficiency
Double conversion mode Up to 97%
General
Noise at 1 m dBA 60 62
Altitude 1500 m no derating, 1500 to 3000 m derate power by 1 % per each 100 m increase
IP20
Protection level
IP21, IP31 optional
General and safety requirements for UPS IEC 62040-1
MKA4L0UKEXM2-R1-03/2021
UPS-EXM2-BR-V1-0321-EN