Sanitary plumbing and drainage
Plumbing Engineering Services Design Guide
Not all sanitary appliances willbe in
simultaneous use. The peak design flow
can be assessed by applying a
frequency of use K factor (see Table 6) to
the total sum of the dlacharge us, and
by using the following equation:
(Quw =k ¥S0U
Where:
,, = Wastewater tow rate (V5)
K = Frequency of use
SDU = Sum of aischarge units
Before the stack selection can be made,
any other continuous oF fixed flow must
be added to the Qww value, Tho
following equation explains further:
Og = Oy + + Oy
Where:
Qy4 = Total flowrate (Vs)
Qyq, = Wastewater flowrate (Vs)
= Continvous flowrate (us)
Q, = Pumped flowrate (Us)
‘Once the Qj, value has been obtalned, a
decision about the stack size, and
ventilation principle can be made by
referring to Tablo 7 and 8. Tho pipo sizes
relate t0 the pipe bores which have
{taditionally been used in the UK. The
theoretical minimum bore for 50, 75, 100
‘and 150 sizes is 44, 75, 96, and 146mm.
‘respectively. Both Table 4 and 8 aro
based on ‘swept entry’ equal branches,
‘which are requited inthe UK.
Table 5
Tepes
Wash ssn orb
Stover thou pug
Stowe wth uy
Sg inal win aie
Sia urinal (per B00)
Bam
Kchen Sk
Ostwasher Gaus
Washing machine (5k)
washing macnino (12g
WC win stestem |
Wo win 751 stm
We win ot ester
‘The Water Regulations & Byelaws inthe UK
io not alow the use of 7.50” 9 tre Wo
ftushing esterns on now insalsions, the
Inormaton i provided fr use m connection
nth exsing systems.
Table 6
‘age of epoinces K
intemitent uss, eg, dweing,
guesthouse, afco os.
Frequent use, 9 holel
restaurant school, spt o7.
Congested use, eg, tole
andor showers opentothe pubic | 1.0
Special use. e.g tboratory 12
Table 7 Maximum capacity of PRIMARY
ventilated alscharge stacks
iii sack & vet. Tivesisee
mn 26.
{00mm 52.
180mm 124
* No WO allowed on 75mm stacks
Table 8 Maximum capacity of
SECONDARY ventilated
Gischarge stacks
ia sek ee Tiesisee
‘Stack & vent | Vert
7mm" | 80mm 3a
100mm | Somm 73:
180mm | somm 183
[Ne WC allowed on 75mm stacks
comple 1
Determine ttl design fowate and stack
requromerts lr an -steroy Book of
Sparmona The eech tac wi serve one
Sparen per foer comensing 0
nvoom, en-sute shower tam an ly
‘tos wachon
DU per fat:
2weext7 = a4
2washbasinsx03= 06
bath = 13
1 shower = os
{itch siok = 13
washing machine = 0.6
1 dishwasher =| 2
‘Assume a primary ventiated stack is
adequate; therefore te bottom storey must
Connect separately o drain (se Figure 5).
For 10 storeys, 3DU:7.8 x 10 = 78
K=05, 800,,=05V78 = 4.421%
Q, & Q, = 2010, 50 Oy = 4.4208
From Table 7, a 100mm primary vented
‘stack has lit of 52,30 te size
adequate. Secondary ventiation is not
required.
Example 2
Determine total design flowrate and stack
requrements for an 11-storey Rote. The
Stack wil sorve two en-suite bathrooms on
‘each floor, thore will be ai conditioning
Unis on the rot with a peak discharge of
(.2U, and launcry equipment an the sth
floor witha peak discharge of 5s.
U per typical floor:
2WCsx 1.7 34
2wash basinex03= 06
2bathext 3 26
66
‘Asoume a primary ventilated stack is
adequate; therefore the bottom slorey must
Connect separately to drain (see Figure 8)
For 10 storeys, 30U;6.6 x 10 = 66
k=07, $00, =0.7 ¥66 =5.7I8,
4:57 +02+05=6.4N5
There are two options; a 150mm primary
ventilated stack, or a 100mm secondary
ventilated stack and 50mm secondary
vent. Practical considerations would
Gictate the best choice, for example a
proprietary fing such as the colar boss
(ee Figure 19) is only availabe in the
100mm size.
Self-sealing waste valves
‘Tho recent introduction to the plumbing
market of waste vaives to replace the:
water seal trap offers the installer an
‘opportunity to reconsider his system