Combustion Fan Power

24 vac on W Starts
Fan by Closing F1 F2
Relay.
Fenwal
Combustion
Fan Relay W (Heat) When Air Flow
L1 - L2 24 vac
120 vac Switch N/O Contact
Closes Ignition
Sequence Continues.

24 vac

W – BL
240 vac 120 vac 40-75 ohms
(D to F)
ACN1
F1 Energized
from Time
15-62 Secs
ACH1
F2
Windings in Series for 240v
All 120 and 24 Vac Combustion Fan Power
Referenced to Chassis Gnd
EXCEPT L1 to L2 (120vac)

Not
Used
W (Heat)
Lxi 400
24 vac
Remote Spa Pool
Wired to Separate
Ecommand Pool
Control for Remote
Temperature Control

Typical Sequence
Lxi Heater
1. Four Safeties are Closed
2. Call for Heat Sends W to Ignition Control
3. 15 Second Fan Pre-Purge
4. Air Flow Switch Closes
5. 40 Second Igniter Heat Up
6. 7 Second Trial for Ignition (Gas Valve)
7. Heat is On Until Call is Satisfied
8. W Removed from Ignition Control
9. Ignition Control Closes Gas Valve
10. 15 Second Fan Post Purge

All Four Inputs N/C (Closed) to Start Heater Sequencing