Observations and Recommendations on GTP, type test and Drawings of 33KV Current transformer (200-100/5-5-5A, 400-200/5-5A,) &
33kV Single phase Potential transformer
Name of Project: Assam Distribution System Enhancement and Loss Reduction Project.
AIIB Loan No.: L0315-A
Name of the Contractor: M/s Power Instrumentation (Guj) Ltd
Design / Drawing Title: Review of GTP, type test and Drawings of 33KV Current transformer (200-100/5-5-5A, 400-200/5-5A)
& 33kV Single phase Potential transformer submitted by M/S Power Instrumentation(Guj) Ltd
(Manufacturer- M/S Tushar Trans Equipment) for Tezpur Package.
Reference is made to APDCL Letter No: CPM (PIU)/APDCL/AIIB/ SMEC/PKG-11/GTP/SMEC/2021/07 Dated 28th June, 2022.
Observations/General Comments:
1. Please provide the diagrams in A3 format.
The above technical documents and drawings have been reviewed for each of following components as below:
Our comments are as follows-
1. 33KV Outdoor Live Tank Current Transformer (400-200/5-5A)
a) GTP
In SL No 28.1 the Output burden of Core I Shall be 15, as per Vol III Section I Cl 5.1, page 235 of 440.
b) Drawing (Drg No- 2TTPL0044, 2TTPL0044/A, 2TTPL0043/B, 2TTPL0043/C, 2TTPL0043/D)
In the Name Plate Rating for Core I shall be rectified as mentioned above in GTP.
c) Test Report
Please provide type test for the Specific Instrument transformer.
No specific Comment
b) Drawing (Drg No- 2TTPL0045, 2TTPL0045/A, 2TTPL0043/B, 2TTPL0043/C, 2TTPL0043/D)
In the Name plate PS class Shall be mentioned in Core III,as per Vol III Section I Cl 5.1, page 235 of 440.
c) Test Report
No Please provide type test for the Specific Instrument transformer.
In the Name plate PS class Shall be mentioned in Core III,as per Vol III Section I Cl 5.1, page 235 of 440.
c) Test Report
Please provide type test for the Specific Instrument transformer.
Project Management Consultant
c) Test Report
Please provide type test for the Specific Instrument transformer.
c) Test Report
Please provide type test for the Specific Instrument transformer.
Recommendations:
The Contractor shall comply with above requirement and accordingly resubmit the documents incorporating the above comments for
APDCL approval.