You are on page 1of 32

RT-PRC021-EN

Package
Gas / Electric Units

Convertible Models
YCC018-060

1½ – 5 Ton

Pub. No. 22-1295-05-0303 (EN)


General
Features

T-TOP™
WEATHERGUARD™
corrosion resistant screws
Powder Paint
WATER-SHED Base

High Efficiency
Climatuff® compressor
DuraTuff™ plate fin coil
Single Stage Gas Furnace
Easy Access

© 2003 American Standard Inc. All Rights Reserved 2 22-1295-05-0303 (EN)


Features
and Benefits Contents

Standard Equipment General Features 2


• High Efficiency
IMPACK performance is the highest in the
industry at 16 SEER. Features and Benefits 3
• Climatuff ® compressors
Protection against Standard Equipment 3
chemical, electrical,
and mechanical IMPACK Accessories 4
stresses are built in
for efficiency and a
longer life. The Selection Procedure 5
compressors are
backed by a 5-year Model Number Nomenclature 5
limited warranty, with
an optional warranty
for 5 more years.
(single phase residential use only)
Optional Equipment 6
• Powder Paint
Beautiful high gloss silver gray finish blends General Data 7
with any architectural style, New powder
paint covers surfaces uniformly increasing YCC018 7
protection from rust and corrosion.
• WEATHERGUARD™ YCC024 7
corrosion resistant screws
Holds it all together beautifully. Resists rust
YCC030 7
and corrosion. YCC036 7
• WATER-SHED Base
Superior water integrity is accomplished YCC042 9
with the WATER-SHED base pan having
elevated downflow openings and a YCC048 10
perimeter channel that prevents water
from draining into the ductwork.
YCC060 11
• T-TOP™
Exclusive one piece, solid unit top for Performance Data 12
improved water integrity and easy
component access. Cooling 12
• DuraTuff™ plate fin coil
Refrigeration coils are built with internally Temperature Rise 15
enhanced copper tubing for high efficiency
with less coil area.
Indoor Fan 16
Pressure Drop 19

Optional Equipment 19
Controls 20
Typical Wiring 21
Dimensions 24
• Single Stage Gas Furnace
The furnace features aluminized tubular Mechanical Specifications Options 31
heat exchangers that have demonstrated
their durability in torturous life cycle tests
and fire tests at either 20 or 25 MBTUH per
tube on natural gas or 24 MBTUH on
propane. The heat exchanger is backed by
a 10 year limited warranty with an optional
warranty available for the 11-15th years.
(residential use only)
(continued on page 4)

22-1295-05-0303 (EN) 3
Features and
Benefits

Standard Equipment
• Venting • Convertibility • Service
Induced draft venting reduces combustion IMPACK units are easily converted from All wiring is both numbered and color coded
problems associated with high winds and horizontal to down flow with the removal of thereby reducing training and servicing
combustion panels that have been im- one screw from each panel. Accordingly, costs related to circuit tracing and compo-
properly replaced. the need to stock both dedicated horizon- nents replacements.
• California NOx tal and dedicated down flow models has • Maintenance
The standard unit meets California NOx been eliminated. A plug on the outdoor fan motor allows the
requirements eliminating the inventory prob- • Installation top cover to be removed completely without
lems associated with unique models or kits. The ease of installation and application the hassle of cumbersome wires. The
• One for Us... flexibility exhibited through the design unique service orifice ring allows the indoor
Two for Customer reduce both field time and material. fan motor/blower to be removed as a unit.
Three-try direct spark ignition system • Structure • Corrosion
eliminates pilot related problems and The units are lighter weight through the use The drain pan is engineered material and
provides unsurpassed ignition reliability. of high technology components thereby eliminates the need for coatings and sealers
• Commonality reducing mounting structure requirements to prevent sweating and corrosion. The
The common cabinet among the TCC’s, and difficulty when manhandling. heavy gauge, zinc-coated steel cabinet has
WCX’s, and YCY’s minimizes both the • Handling a weather resistant enamel finish that
training of sales and service personnel and The three-way wooden skid allows for easy stays attractive and protects your invest-
replacement parts inventory. loading between the wheel wells on pickup ment for years.
• Easy Access trucks for transporting to job sites. • Low Ambient Control
Most electrical components can be diag- • Application Standard cooling operation to 55° F. as
nosed and replaced with the removal of one The low profile horizontal duct take-offs shipped, zero degree ambient cooling is
panel that is attached with two screws. eliminate the need for expensive transition accomplished with two kits. One for low
ducts in crawl space applications. cost installations when full tonnage is not
• Flexibility needed. The other kit maintains head
A single curb fits the entire IMPACK line • Duct Flanges pressure and full capacity at zero degrees.
from 1.5 tons through 5 tons thereby Only IMPACK has downflow duct flanges for
providing great installation flexibility on duct attachments that preserve the built-in • Quality and Reliability Testing
shopping malls, factories, schools, and water integrity. We perform a 100% coil leak test at the
other commercial buildings where a mix- factory. The evaporator and condenser coils
match of tonnages and utilities is desired. are leak tested at 200 psig and pressure
tested to 450 psig respectively. In addition
• Shipping the IMPACK designs were rigorously rain
Unit dimensions were carefully selected to tested at the factory to ensure water
provide an attractive aspect ratio and for integrity. Shipping tests are performed to
shipping and handling considerations. determine packaging requirements. Factory
• Good Neighbor shake and drop tests are used as part of the
Most units can be installed flush with the package design process to help assure that
residence or building thereby minimizing the unit will arrive at the job site in top
the ground space required. Blankets of condition. Additionally, all components are
insulation reduce blower noise and energy inspected at the point of final assembly.
losses to the outside environments. Substandard parts and components are
identified and rejected immediately. Every
• Rooftop Mounting unit receives a 100% run test before leaving
The cabinets are physically smaller than the production line to make sure it lives up
most competitive models. This means less to rigorous Trane requirements. We at Trane
intrusive installations on residential rooftops test our designs at our factory and not on
where aesthetics are critical. our customers!

IMPACK Accessories
• Standard Thermostats • Economizer
No special thermostats are needed with The downflow economizer fits inside the unit
IMPACK units. with only the rain hood and barometric relief
• Filter Frame Kit on the outside. Cabling is shipped with the
The IMPACK filter frames accept standard economizer. This cabling is easily routed to
filters and fit inside the unit. The frame kits the control box where it terminates in low
function in either horizontal or downflow duct voltage pigtails. The economizer features a
configurations. fully modulating low voltage motor eliminat-
ing the need for any high voltage wiring.
• UNI-CURB The economizer must be used with the filter
One universal curb fits all the IMPACK frame kit…no return air filter in the econo-
models. It ships knocked down. The curb mizer kit. A dry bulb sensor is shipped with
design incorporates the popular locking tabs the economizer. The downflow economizer
for quick and easy assembly. Full perimeter was not designed for use in horizontal
curbs are also available for all models.

4 22-1295-05-0303 (EN)
Features and
Benefits

IMPACK Accessories
applications. A horizontal only economizer • Propane Kits • Lifting Lug Kit
(which fits externally) is available. The BAYLPKT022A propane kit fits all of the Four reusable lugs in each kit allow units to
• Enthalpy Control Kit IMPACK single stage models. This kit has be easily lifted to rooftop installations. These
For those applications specifying an been constructed for greatest field flexibility lugs snap (no screws required) into slots in
economizer with enthalpy control, this and to minimize the number of parts that the unit drip lip channel.
control can be used in place of the dry bulb have to be discarded. • High Static Motor
sensor or, alternately, two enthalpy controls The BAYLPSS001 propane kit also includes Consists of a higher torque indoor fan
can be paired to provide differential 5 stainless steel burners. motor.
enthalpy control. • Low Ambient Kit • Start Kit
• 25% Fresh Air Kit An EDC provides low ambient cooling to 0° F. The kit mounts in the control box for those
The kit installs over the horizontal return air with some reduced capacity and protects installations specific conditions such as
opening with six screws for downflow require- the system against evaporator icing during excessive voltage drop due to long wires.
ments. It can be used on horizontal air flow other unusual cooling conditions. (This is a capacitor and start relay kit not a
applications by cutting a hole in the return air • Head Pressure Control Kit PTC device.) This kit can be a good
duct or in the unit filter access panel. This kit includes a solid state outdoor motor specification buster!
• Rectangular to Round Duct Kits control, junction box, and wiring. It provides • Coil Guard Kit
The adapter kit can be used in either full capacity down to 0° F. The guards are coated 1"X3" wire grills.
horizontal or downflow applications. These grills will protect the coil from normal
shipping and installation damage.

Selection Procedure
Model Number Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12
Y C C 0 3 6 F 1 M 0 A A
PRODUCT TYPE SERVICE DESIGN
YC = Packaged Gas/Electric MINOR DESIGN SEQUENCE
TC = Packaged Cooling
WC = Packaged Heat Pumps FACTORY INSTALLED OPTIONS
DC = Dual Fuel Heat Pumps EXAMPLES:
0 = No factory installed options
AIRFLOW CONFIGURATION B = Oversize Motor*
C = Convertible N = Filter Frame*
D = Downflow T = Fan Delay Relay*
H = Horizontal * Product Deviation Required
M = Manufactured Housing
P,X= 12 SEER AUXILIARY HEATING CAPACITY
Y = 13-14 SEER L = Low Heat
Z = 15-16 SEER M = Medium Heat
H = High Heat
NOMINAL NET COOLING 0 = No Heat
CAPACITY (MBH)
018 = 1 1/2 Tons ELECTRICAL CHARACTERISTICS
024 = 2 Tons 1 = 208-230/60/1
030 = 2 1/2 tons 3 = 208-230/60/3
036 = 3 Tons 4 = 460/60/3
042 = 3 1/2 Tons W= 575/3/60
048 = 4 Tons D = 380-415/3/50
060 = 5 Tons MAJOR DEVELOPMENT SEQUENCE
F = IMPACK
G = IMPACK Plus

22-1295-05-0303 (EN) 5
Optional
Equipment

OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [✓ ✓] indicates accessories included)
Indoor Thermostats — XT300C Prog. 7 Day, Auto/Manual 1 Htg/1 Clg .......................................................................................... TAYSTAT300C [ ]
XT302C Prog. 7 Day, Auto/Manual 2-Stage Htg/CIg w/Econ. .................................................................. TAYSTAT302C [ ]
Electronic 2 Htg/2 Clg (NonProg) ................................................................................................................... TAYSTAT375 [ ]
Outdoor Temp. Sensor (TAYSTAT300C,302C,375) ............................................................................... TAYSENS100A [ ]
Prog. Electronic 5/2 Day, Manual 1 Htg/1 Clg ................................................................................................ TAYSTAT340 [ ]
Electronic 1 Htg/1 Clg (NonProg) ................................................................................................................... TAYSTAT370 [ ]
Wallcover Plate (TAYSTAT370) ............................................................................................................. BAYCOVR100A [ ]
Heat/Cool (Horizontal) Manual 1 Htg/1Clg ......................................................................................................... AY28X092 [ ]
Heat/Cool (Vertical) Manual 1Htg/1Clg ......................................................................................................... BAYSTAT305 [ ]
Thermostat 1H/1C Sub-base Required (BAY28X184,187) ........................................................................... BAYSTAT182 [ ]
Thermostat 2H/2C Sub-base Required (BAY28X184,187) ........................................................................... BAYSTAT183 [ ]
Subbase Auto/Manual Changeover .......................................................................................................... BAYSTAT184 [ ]
Subbase Manual Changeover .................................................................................................................. BAYSTAT187 [ ]
Thermostat 1H/1C Manual Sub-base ........................................................................................................... BAYSTAT008 [ ]
Thermostat 2H/2C Auto Sub-base ................................................................................................................ BAYSTAT010 [ ]
Thermostat 1H/2C Manual Sub-base w/Econ. .............................................................................................. BAYSTAT012 [ ]
Locking Thermostat Cover (Thermostats) ............................................................................................................................................ BAY28X190 [ ]
Anti-short Cycle Timer (Mech. Stats Only) ......................................................................................................................................... BAYASCT001 [ ]
Roof Curb (Flat Roof) Universal 3 ................................................................................................................................................. BAYCURB030A [ ]
Roof Curb (Flat Roof) Universal 3 Acusti-Curb ............................................................................................................................. BAYCURB038A [ ]
Roof Curb Full Perimeter (YCC036F-H,042,048F-M) 3 Acusti-Curb ............................................................................................. BAYCURB033A [ ]
Roof Curb Full Perimeter (YCC048F-H - 060F) 3 Acusti-Curb ...................................................................................................... BAYCURB034A [ ]
Roof Curb Utility Extension Kit (BAYCURB030,038A) ....................................................................................................................... BAYUTIL030A [ ]
Roof Curb Utility Extension Kit (BAYCURB033A) .............................................................................................................................. BAYUTIL033A [ ]
Roof Curb Utility Extension Kit (BAYCURB034A) .............................................................................................................................. BAYUTIL034A [ ]
0-25% Manual Fresh Air Damper (YCC018-42F,048F-M) 1 ......................................................................................................... BAYDMPR040A [ ]
0-25% Manual Fresh Air Damper (YCC048F-H - 060F) 1 ............................................................................................................ BAYDMPR041A [ ]
0-25% Motorized Fresh Air Damper (YCC048F-H - 060F) 1 ........................................................................................................ BAYDMPR050A [ ]
12" Round Duct Adapter (2 per box) (YCC018-042F) ..................................................................................................................... BAYDUCT004A [ ]
14" Round Duct Adapter (1 per box) (YCC018-042F) ..................................................................................................................... BAYDUCT005A [ ]
0-100% Mod Economizer w/Baro. Relief (YCC018-042F,048F-M) 124 ..................................................................................... BAYECON054B [ ]
0-100% Mod. Economizer w/Baro. Relief (YCC048F-H - 060F) 124 ......................................................................................... BAYECON055B [ ]
0-100% Horizontal Economizer 12 .............................................................................................................................................. BAYECON073A [ ]
Enthalpy Control for Economizer (solid state). ................................................................................................................................ BAYENTH001A [ ]
Remote Potentiometer (BAYECON054,055B,073A) .......................................................................................................................... BAYSTAT023 [ ]
Filter Frame (YCC018 - 030F-L) (20 x 20 x 1) 1 ............................................................................................................................. BAYFLTR015A [ ]
Filter Frame (YCC030M,036G-L/M) (20 x 25 x 1) 1. ....................................................................................................................... BAYFLTR012A [ ]
Filter Frame (YCC036F-H,042,048F-M) (20 x 25 x 1) 1 ................................................................................................................. BAYFLTR013A [ ]
Filter Frame (YCC048F-H - 060F) (3-10 x 25 x 1) 1 ....................................................................................................................... BAYFLTR014A [ ]
Filter Frame (YCC030M,036G-L/M) (20 x 25 x 2) 1 ........................................................................................................................ BAYFLTR017A [ ]
Filter Frame (YCC036F-H,042,048F-M) (20 x 25 x 2) 1 ................................................................................................................. BAYFLTR018A [ ]
Filter Frame (YCC048F-H - 060F) (2-16 x 25 x 2) 1 ....................................................................................................................... BAYFLTR019A [ ]
Low Fire Kit (YCC018/024/030/036F-L) ............................................................................................................................................ BAYLOFR001 [ ]
Low Fire Kit (YCC024F-M) ................................................................................................................................................................ BAYLOFR002 [ ]
Low Fire Kit (YCC030/036F-M) ....................................................................................................................................................... BAYLOFR0003 [ ]
Low Fire Kit (YCC036F-H - 042,048F-M) .......................................................................................................................................... BAYLOFR004 [ ]
Low Fire Kit (YCC048-060F) ............................................................................................................................................................. BAYLOFR006 [ ]
High Static Motor (YCC030-042F) (230v/460v) (3/4 HP) ............................................................................................................... BAYHSMT043A [ ]
High Static Motor (YCC030-042F) (208v) (3/4 HP) ........................................................................................................................ BAYHSMT056A [ ]
High Static Motor (YCC048-060F) (230v/460v) (1 HP) .................................................................................................................. BAYHSMT044A [ ]
High Static Motor (YCC048-060F) (208v) (1 HP) ........................................................................................................................... BAYHSMT045A [ ]
LP Conversion Kit ............................................................................................................................................................................ BAYLPKT022A [ ]
LP Conversion Kit (with 5 stainless steel burners) ........................................................................................................................... BAYLPSS001A [ ]
Lifting Lug Kit ..................................................................................................................................................................................... BAYLlFT002A [ ]
Evaporator Defrost Control (Low Ambient Cooling) Kit 6. .............................................................................................................. BAYLOAM011A [ ]
Head Pressure Control (Low Ambient Cool) (208/240/460/575v) Kit 56 ...................................................................................... BAYLOAM323A [ ]
Low Ambient Condenser Motor (208/230v) 5 ............................................................................................................................... BAYMOTR307A [ ]
Low Ambient Condenser Motor (460v) 5 ...................................................................................................................................... BAYMOTR406A [ ]
Quick Start Kit (YCC---F1) .............................................................................................................................................................. BAYKSKT010A [ ]
Crankcase Heater (YCC---F)(230v) 6 ........................................................................................................................................... BAYCCHT003A [ ]
Condenser Coil Guard Kit (YCC018/024/030F-L) .......................................................................................................................... BAYGARD016A [ ]
Condenser Coil Guard Kit (YCC030M/036F-L/M/H) ....................................................................................................................... BAYGARD017A [ ]
Condenser Coil Guard Kit (YCC042/048F-M) ................................................................................................................................ BAYGARD020A [ ]
Condenser Coil Guard Kit (YCC048F-H,060F) .............................................................................................................................. BAYGARD021A [ ]
NOTES:
1 Must use filter frame when economizer/fresh air kit is used. 4 Downflow only.
2 Dry bulb control standard with economizer. 5 Use Low Ambient Condenser Motor With This Kit (except on YCC048-060F).
3 Ships knocked down. 6 Low Ambient cooling requires crankcase heater (BAYCCHT----A).

6 22-1295-05-0303 (EN)
General
Data

MODEL YCC018F1L0B YCC024F1L0B YCC030F1L0B YCC030F1M0AB YCC036F1L0B


RATED VOLTS/PH/HZ 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
RATINGS (COOLING) 1
BTUH 18000 23400 29200 29800 35200
Indoor Airflow (CFM) 600 800 1000 1000 1200
Power Input (KW) 1.86 2.55 3.17 3.27 4.02
EER/SEER (BTU/Watt-Hr.) 9.35 / 10.00 9.1 0/ 10.00 9.20 / 10.00 9.10 / 10.00 8.75 / 10.00
Noise Rating No. 1 8.0 8.0 8.0 8.0 8.0
A.G.A. RATINGS (HEATING) 2
(High) Input BTUH 48000 48000 48000 75000 50000
Capacity BTUH 57 37000 37000 37000 60000 40000
AFUE 78% 78% 78% 78% 78%
Temp. Rise °F. (Min./Max.) 35 - 65 35 - 65 35 - 65 35 - 65 15-45
(Low) Input BTUH 40000 40000 40000 60000 40000
Capacity BTUH 57 32000 32000 32000 48000 32000
AFUE 80% 80% 80% 80% 80%
Temp. Rise °F. (Min./Max.) 35 - 65 35 - 65 35 - 65 35 - 65 15-45
Type of Gas 3 NATURAL NATURAL NATURAL NATURAL NATURAL
POWER CONNS. — V/PH/HZ 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
Min. Brch. Cir. Ampacity 15.0 17.7 21.5 21.3 26.8
Br. Cir. Max. (Amps) 20 25 30 35 40
Prot. Rtg. Recmd. (Amps) 20 25 30 35 40
COMPRESSOR
No. Used 1 1 1 1 1
Volts/Ph/Hz 200-230/1/60 200-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
R.L. Amps — L.R. Amps 8 - 48 10.0 - 67 13.3 - 79 13.5 - 79 18.5 - 97
OUTDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 2 / 15 2 / 15 2 / 15 2 / 15 2 / 20
Face Area (Sq. Ft.) 4.5 4.5 5.43 5.43 6.34
Tube Size (in.) 3/8 COPPER 3/8 COPPER 3/8 COPPER 3/8 COPPER 3/8 COPPER
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 2 / 15 3 / 15 3 / 15 3 / 15 3 / 15
Face Area (Sq. Ft.) 3.25 3.25 3.25 3.96 3.96
Tube Size (in.) 3/8 COPPER 3/8 3/8 COPPER 3/8 COPPER 3/8
Refrigerant Control CAPILLARY CAPILLARY CAPILLARY CAPILLARY CAPILLARY
Drain Conn. Size (in.) 3/4" FEMALE NPT 3/4" FEMALE 3/4" FEMALE NPT 3/4" FEMALE NPT 3/4" FEMALE NPT
Duct Connections SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER PROPELLER PROPELLER
No. Used / Dia. (in.) 1 / 18 1 / 18 1 / 18 1 / 18 1 / 18
Type Drive / No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1 DIRECT / 1 DIRECT / 1
No. Motors — HP 1 - 1/5 1 - 1/5 1 - 1/5 1 - 1/5 1 - 1/5
Motor Speed R.P.M. 1080 1080 1080 1080 1080
Volts/PH/HZ 230/1/60 230/1/60 230/1/60 230/1/60 230/1/60
F.L. Amps — L.R. Amps 1.6 - 3.3 1.6 - 3.3 1.6 - 3.3 1.6 - 3.3 1.6 - 3.3
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia. x Width (in.) 9X9 9X9 9X9 10 X 9 10 X 9
No. Used 1 1 1 1 1
Drive / Speeds (No.) DIRECT / 2 DIRECT / 2 DIRECT / 2 DIRECT / 2 DIRECT / 2
No. Motors — HP 1 - 1/4 1 - 1/4 1 - 1/4 1 - 1/3 1 - 1/3
Motor Speed R.P.M. 1080 1080 1080 1080 1080
Volts/PH/HZ 200-230/1/60 200-230/1/60 200-230/1/60 200-230/1/60 200-230/1/60
F.L Amps 1.6/1.4 - 2.9 1.6/1.4 - 2.9 1.6/1.4 - 2.9 2.8/2.2 - 5.1 2.8/2.2 - 5.1
COMBUSTION FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Drive — Speeds (No.) DIRECT-1 DIRECT - 1 DIRECT -1 DIRECT- 1 DIRECT - 1
Motor HP — Speed (RPM) 1/35 - 3480 1/35 - 3480 1/35 - 3480 1/35 - 3480 1/35 - 3480
Volts/PH/HZ 240/1/60 208-240/1/60 240/1/60 240/1/60 240/1/60
F.L. Amps 0.6 0.6 0.6 0.6 0.6
FILTER — FURNISHED? NO NO NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY THROWAWAY THROWAWAY
Min Face Area-Lo (sq. ft.) 6 2.0 2.67 3.33 3.33 4.0
REFRIGERANT
Charge (lbs. of R-22) 4 3.8 LBS. 4 LBS. 4.4 LBS. 4.5 LBS. 5.3 LBS.
GAS PIPE SIZE (IN.) 1/2" 1/2" 1/2" 1/2" 1/2"
DIMENSIONS H X W X D H X W X D H X W X D H X W X D H X W X D
Crated (in.) 31-1/4 X 38 X 57 31-1/4 X 38 X 57 31-1/4 X 38 X 57 35-1/4 X 38 X 57 35-1/4 X 38 X 57
Uncrated SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
WEIGHT
Shipping (lbs.) / Net (lbs.) 341 / 301 350 / 310 398 / 358 398 / 356 426 / 386
*See unit nameplate for proper input adjustment
1 Rated in accordance with A.R.I. Standard 2 All models are UL Listed. Ratings 3 Convertible to LPG. 6 Filters must be installed in return air stream. 7 Unit is shipped on high input,
210/240. Noise tested in accordance with shown are for elevations up to 4 This value is approximate. For more Square footages listed are based on 300 f.p.m. unit is convertible to low input
A.R.I. Standard 270. A.R.I. standard rating 2000 ft. For higher elevations precise value, see Unit Nameplate. face velocity. If permanent filters are used size with a Low Fire accessory kit.
conditions are: 80 D.B. 67 W.B. entering reduce ratings at a rate of 4% per manufacturer's recommendation with a
air to indoor coil. 95 D.B. entering air to per 1000 ft. elevation. 5 Based on U.S. Government clean resistance of 0.05" W.C.
outdoor coil. Standard Tests.

22-1295-05-0303 (EN) 7
General
Data

MODEL YCC036F1M0B YCC036F1H0B YCC036F3L0B YCC036F3M0B


RATED VOLTS/PH/HZ 208-230/1/60 208-230/1/60 208-230/3/60 208-230/3/60
RATINGS (COOLING) 1
BTUH 35200 35200 35400 35400
Indoor Airflow (CFM) 1200 1200 1200 1200
Power Input (KW) 4.02 4.02 3.73 3.73
EER/SEER (BTU/Watt-Hr.) 8.75 / 10.00 8.75 / 10.00 9.50 / 10.00 9.50 / 10.00
Noise Rating No. 1 8.0 8.0 8.0 8.0
A.G.A. RATINGS (HEATING) 2
(High) Input BTUH 75000 100000 50000 75000
Capacity BTUH 57 60000 80000 40000 60000
AFUE 78% 78% 78% 78%
Temp. Rise °F. (Min./Max.) 30 - 60 45 - 75 15-45 30 - 65
(Low) Input BTUH 60000 80000 40000 60000
Capacity BTUH 57 48000 64000 32000 48000
AFUE 80% 80% 80% 80%
Temp. Rise °F. (Min./Max.) 30 -60 45 - 75 15-45 30 -65
Type of Gas 3 NATURAL NATURAL NATURAL NATURAL
POWER CONNS. — V/PH/HZ 208-230/1/60 208-230/1/60 208-230/3/60 208-230/3/60
Min. Brch. Cir. Ampacity 26.8 26.8 18 18
Br. Cir. Max. (Amps) 40 40 25 25
Prot. Rtg. Recmd. (Amps) 40 40 25 25
COMPRESSOR
No. Used 1 1 1 1
Volts/Ph/Hz 208-230/1/60 208-230/1/60 208-230/3/60 208-230/3/60
R.L. Amps — L.R. Amps 16.6 - 97 16.6 - 97 11 - 101.0 11 - 101.0
OUTDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 2 / 20 2 / 20 2 / 20 2 / 20
Face Area (Sq. Ft.) 6.34 6.34 6.34 6.34
Tube Size (in.) 3/8 COPPER 3/8 COPPER 3/8 COPPER 3/8 COPPER
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 3 / 15 3 / 15 3 / 15 3 / 15
Face Area (Sq. Ft.) 3.96 3.96 3.96 3.96
Tube Size (in.) 3/8 3/8 3/8 3/8
Refrigerant Control CAPILLARY CAPILLARY CAPILLARY CAPILLARY
Drain Conn. Size (in.) 3/4" FEMALE NPT 3/4" FEMALE NPT 3/4" FEMALE NPT 3/4" FEMALE NPT
Duct Connections SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER PROPELLER
No. Used / Dia. (in.) 1 / 18 1 / 18 1 / 18 1 / 18
Type Drive / No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1 DIRECT / 1
No. Motors — HP 1 - 1/5 1 - 1/5 1 - 1/5 1 - 1/5
Motor Speed R.P.M. 1080 1080 1080 1080
Volts/PH/HZ 230/1/60 230/1/60 230/1/60 230/1/60
F.L. Amps — L.R. Amps 1.6 - 3.3 1.6 - 3.3 1.6 - 3.3 1.6 - 3.3
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia. x Width (in.) 10 X 9 10 X 9 10 X 9 10 X 9
No. Used 1 1 1 1
Drive / Speeds (No.) DIRECT / 2 DIRECT / 2 DIRECT / 2 DIRECT / 2
No. Motors — HP 1 - 1/3 1 - 1/3 1 - 1/3 1 - 1/3
Motor Speed R.P.M. 1080 1080 1080 1080
Volts/PH/HZ 200-230/1/60 200-230/1/60 200-230/1/60 200-230/1/60
F.L Amps 2.8/2.2 - 5.1 2.8/2.2 - 5.1 2.8/2.2 - 5.1 2.8/2.2 - 5.1
COMBUSTION FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Drive — Speeds (No.) DIRECT - 1 DIRECT - 1 DIRECT - 1 DIRECT - 1
Motor HP — Speed (RPM) 1/35 - 3480 1/35 - 3480 1/35 - 3480 1/35 - 3480
Volts/PH/HZ 240/1/60 240/1/60 240/1/60 240/1/60
F.L. Amps 0.6 0.6 0.6 0.6
FILTER — FURNISHED? NO NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY THROWAWAY
Min Face Area-Lo (sq. ft.) 6 4.0 4.0 4.0 4.0
REFRIGERANT
Charge (lbs. of R-22) 4 5.3 LBS. 5.3 LBS. 5.7 LBS. 5.7 LBS.
GAS PIPE SIZE (IN.) 1/2" 1/2" 1/2" 1/2"
DIMENSIONS H X W X D H X W X D H X W X D H X W X D
Crated (in.) 35-1/4 X 38 X 57 35-1/4 X 38 X 64-5/8 35-1/4 X 38 X 57 35-1/4 X 38 X 57
Uncrated SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
WEIGHT
Shipping (lbs.) / Net (lbs.) 426 / 386 452 / 403 426 / 386 426 / 386
*See unit nameplate for proper input adjustment
1 Rated in accordance with A.R.I. Standard 2 All models are UL Listed. Ratings 3 Convertible to LPG. 6 Filters must be installed in return air stream. 7 Unit is shipped on high input,
210/240. Noise tested in accordance with shown are for elevations up to 4 This value is approximate. For more Square footages listed are based on 300 f.p.m. unit is convertible to low input
A.R.I. Standard 270. A.R.I. standard rating 2000 ft. For higher elevations precise value, see Unit Nameplate. face velocity. If permanent filters are used size with a Low Fire accessory kit.
conditions are: 80 D.B. 67 W.B. entering reduce ratings at a rate of 4% per manufacturer's recommendation with a
air to indoor coil. 95 D.B. entering air to per 1000 ft. elevation. 5 Based on U.S. Government clean resistance of 0.05" W.C.
outdoor coil. Standard Tests.

8 22-1295-05-0303 (EN)
General
Data

MODEL YCC036F3H0B YCC036F4H0A YCC042F1M0B YCC042F3M0B


RATED VOLTS/PH/HZ 208-230/3/60 460/3/60 208-230/1/60 208-230/3/60
RATINGS (COOLING) 1
BTUH 35400 35400 42000 42000
Indoor Airflow (CFM) 1200 1200 1400 1400
Power Input (KW) 3.73 3.73 4.79 4.79
EER/SEER (BTU/Watt-Hr.) 9.50 / 10.00 9.50 / 10.00 8.85 / 10.00 8.85 / 10.00
Noise Rating No. 1 8.0 8.0 8.0 8.0
A.G.A. RATINGS (HEATING) 2
(High) Input BTUH 100000 100000 100000 100000
Capacity BTUH 57 80000 80000 80000 80000
AFUE 78% 78% 78% 78%
Temp. Rise °F. (Min./Max.) 45 - 75 45 - 75 45 - 75 45 - 75
(Low) Input BTUH 80000 80000 80000 80000
Capacity BTUH 57 64000 64000 64000 64000
AFUE 80% 80% 80% 80%
Temp. Rise °F. (Min./Max.) 45 - 75 45 - 75 45 - 75 45 - 75
Type of Gas 3 NATURAL NATURAL NATURAL NATURAL
POWER CONNS. — V/PH/HZ 208-230/3/60 460/3/60 208-230/1/60 208-230/3/60
Min. Brch. Cir. Ampacity 18 8 31.3 22
Br. Cir. Max. (Amps) 25 15 50 35
Prot. Rtg. Recmd. (Amps) 25 15 50 35
COMPRESSOR
No. Used 1 1 1 1
Volts/Ph/Hz 208-230/3/60 460/3/60 208-230/1/60 208-230/3/60
R.L. Amps — L.R. Amps 11 - 101.0 4 - 51.0 20.6 - 105 14 -101.0
OUTDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 2 / 20 2 / 20 2 / 15 2 / 15
Face Area (Sq. Ft.) 6.34 6.34 8.62 8.62
Tube Size (in.) 3/8 COPPER 3/8 COPPER 3/8 3/8
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 3 / 15 3 / 15 3 / 15 3 / 15
Face Area (Sq. Ft.) 3.96 3.96 4.28 4.28
Tube Size (in.) 3/8 3/8 3/8 3/8
Refrigerant Control CAPILLARY CAPILLARY CAPILLARY CAPILLARY
Drain Conn. Size (in.) 3/4" FEMALE NPT 3/4" FEMALE NPT 3/4" FEMALE 3/4" FEMALE
Duct Connections SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER PROPELLER
No. Used / Dia. (in.) 1 / 18 1 / 18 1 / 18 1 / 18
Type Drive / No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1 DIRECT / 1
No. Motors — HP 1 - 1/5 1 - 1/2 1 - 1/5 1 - 1/5
Motor Speed R.P.M. 1080 1080 1080 1080
Volts/PH/HZ 230/1/60 460/1/60 230/1/60 230/1/60
F.L. Amps — L.R. Amps 1.6 - 3.3 1.7 - 3.8 1.6 - 3.3 1.6 - 3.3
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia. x Width (in.) 10 X 9 10 X 9 10 X 9 10 X 9
No. Used 1 1 1 1
Drive / Speeds (No.) DIRECT / 2 DIRECT / 2 DIRECT / 2 DIRECT / 2
No. Motors — HP 1 - 1/3 1 - 1/3 1 - 1/3 1 - 1/3
Motor Speed R.P.M. 1080 1080 1080 1080
Volts/PH/HZ 200-230/1/60 460/1/60 200-230/1/60 200-230/1/60
F.L Amps 2.8/2.2 - 5.1 1.1 - 2.6 2.8/2.2 - 5.1 2.8/2.2 - 5.1
COMBUSTION FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Drive — Speeds (No.) DIRECT - 1 DIRECT - 1 DIRECT- 1 DIRECT- 1
Motor HP — Speed (RPM) 1/35 - 3480 1/35 - 3480 1/35 - 3480 1/35 - 3480
Volts/PH/HZ 240/1/60 240/1/60 208-240/1/60 208-240/1/60
F.L. Amps 0.6 0.6 0.6 0.6
FILTER — FURNISHED? NO NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY THROWAWAY
Min Face Area-Lo (sq. ft.) 6 4.0 4.0 4.67 4.67
REFRIGERANT
Charge (lbs. of R-22) 4 5 LBS, 15 OZ 5 LBS, 15 OZ 6 LBS, 8OZ 6 LBS, 8OZ
GAS PIPE SIZE (IN.) 1/2" 1/2" 1/2" 1/2"
DIMENSIONS H X W X D H X W X D H X W X D H X W X D
Crated (in.) 35-1/4 X 38 X 64-5/8 35-1/4 X 38 X 64-5/8 35-1/4 X 38 X 64-5/8 35-1/4 X 38 X 64-5/8
Uncrated SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
WEIGHT
Shipping (lbs.) / Net (lbs.) 452 / 403 440 / 394 461 / 414 461 / 414
*See unit nameplate for proper input adjustment
1 Rated in accordance with A.R.I. Standard 2 All models are UL Listed. Ratings 3 Convertible to LPG. 6 Filters must be installed in return air stream. 7 Unit is shipped on high input,
210/240. Noise tested in accordance with shown are for elevations up to 4 This value is approximate. For more Square footages listed are based on 300 f.p.m. unit is convertible to low input
A.R.I. Standard 270. A.R.I. standard rating 2000 ft. For higher elevations precise value, see Unit Nameplate. face velocity. If permanent filters are used size with a Low Fire accessory kit.
conditions are: 80 D.B. 67 W.B. entering reduce ratings at a rate of 4% per manufacturer's recommendation with a
air to indoor coil. 95 D.B. entering air to per 1000 ft. elevation. 5 Based on U.S. Government clean resistance of 0.05" W.C.
outdoor coil. Standard Tests.

22-1295-05-0303 (EN) 9
General
Data

MODEL YCC048F1M0B YCC048F3M0B YCC048F1H0B YCC048F3H0B


RATED VOLTS/PH/HZ 208-230/1/60 208-230/3/60 208-230/1/60 208-230/3/60
RATINGS (COOLING) 1
BTUH 46500 46500 48000 48000
Indoor Airflow (CFM) 1600 1600 1600 1600
Power Input (KW) 5.23 5.23 5.19 5.05
EER/SEER (BTU/Watt-Hr.) 8.90 / 10.00 8.90 / 10.00 9.25 / 10.00 9.50 / 10.00
Noise Rating No. 1 8.2 8.2 8.4 8.4
A.G.A. RATINGS (HEATING) 2
(High) Input BTUH 100000 100000 125000 125000
Capacity BTUH 57 80000 80000 100000 100000
AFUE 78% 78% 78% 78%
Temp. Rise °F. (Min./Max.) 30 -60 30 - 60 45 - 75 45 - 75
(Low) Input BTUH 80000 80000 100000 100000
Capacity BTUH 57 64000 64000 80000 80000
AFUE 80% 80% 80% 80%
Temp. Rise °F. (Min./Max.) 30 - 60 30 - 60 45 - 75 45 - 75
Type of Gas 3 NATURAL NATURAL NATURAL NATURAL
POWER CONNS. — V/PH/HZ 208-230/1/60 208-230/3/60 208-230/1/60 208-230/3/60
Min. Brch. Cir. Ampacity 33.0 24.8 36.4 26.8
Br. Cir. Max. (Amps) 50 40 50 40
Prot. Rtg. Recmd. (Amps) 50 40 50 40
COMPRESSOR
No. Used 1 1 1 1
Volts/Ph/Hz 208-230/1/60 208-230/3/60 208-230/1/60 208-230/3/60
R.L. Amps — L.R. Amps 21.7 - 119 15.1 - 101.0 20.3 - 119.0 14.2 - 101
OUTDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 2 / 15 2 / 15 2 / 15 2 / 15
Face Area (Sq. Ft.) 8.62 8.62 9.2 9.2
Tube Size (in.) 3/8 3/8 3/8 3/8
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 3 / 15 3 / 15 3 / 15 3 / 15
Face Area (Sq. Ft.) 4.28 4.28 5.4 5.4
Tube Size (in.) 3/8 3/8 3/8 3/8
Refrigerant Control CAPILLARY CAPILLARY CAPILLARY CAPILLARY
Drain Conn. Size (in.) 3/4" FEMALE 3/4" FEMALE 3/4" FEMALE 3/4" FEMALE
Duct Connections SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER PROPELLER
No. Used / Dia. (in.) 1 / 18 1 / 18 1 / 22 1 / 22
Type Drive / No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1 DIRECT / 1
No. Motors — HP 1 - 1/5 1 - 1/5 1 - 1/2 1 - 1/2
Motor Speed R.P.M. 1080 1080 1080 1080
Volts/PH/HZ 200-230/1/60 200-230/1/60 200-230/1/60 200-230/1/60
F.L. Amps — L.R. Amps 1.6 - 3.3 1.6 - 3.3 3.3/3.9 - 8.5 3.3/3.9 - 8.5
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia. x Width (in.) 10 X 10 10 X 10 11 X 11 11 X 11
No. Used 1 1 1 1
Drive / Speeds (No.) DIRECT / 1 DIRECT / 1 DIRECT / 2 DIRECT / 2
No. Motors — HP 1 - 3/4 1 - 3/4 1 - 3/4 1 - 3/4
Motor Speed R.P.M. 1145 1145 1080 1080
Volts/PH/HZ 200-230/1/60 200-230/1/60 200-230/1/60 200-230/1/60
F.L Amps 4.3 - 11.2 4.3 - 11.2 5.0/4.3- 9.7 5.0/4.3- 9.7
COMBUSTION FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Drive — Speeds (No.) DIRECT - 1 DIRECT - 1 DIRECT - 1 DIRECT - 1
Motor HP — Speed (RPM) 1/35 - 3480 1/35 - 3480 1/35 - 3480 1/35 - 3480
Volts/PH/HZ 208-240/1/60 208-240/1/60 208-240/1/60 208-240/1/60
F.L. Amps 0.6 0.6 0.6 0.6
FILTER — FURNISHED? NO NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY THROWAWAY
Min Face Area-Lo (sq. ft.) 6 5.33 5.33 5.33 5.33
REFRIGERANT
Charge (lbs. of R-22) 4 6.42 LBS. 6.42 LBS. 8 LBS 8 LBS
GAS PIPE SIZE (IN.) 1/2" 1/2" 1/2" 1/2"
DIMENSIONS H X W X D H X W X D H X W X D H X W X D
Crated (in.) 35-1/4 X 38 X 64-5/8 35-1/4 X 38 X 64-5/8 39-3/8 X 47 X 66-1/4 39-3/8 X 47 X 66-1/4
Uncrated SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
WEIGHT
Shipping (lbs.) / Net (lbs.) 461 / 414 461 / 414 592 / 523 587 / 518
*See unit nameplate for proper input adjustment
1 Rated in accordance with A.R.I. Standard 2 All models are UL Listed. Ratings 3 Convertible to LPG. 6 Filters must be installed in return air stream. 7 Unit is shipped on high input,
210/240. Noise tested in accordance with shown are for elevations up to 4 This value is approximate. For more Square footages listed are based on 300 f.p.m. unit is convertible to low input
A.R.I. Standard 270. A.R.I. standard rating 2000 ft. For higher elevations precise value, see Unit Nameplate. face velocity. If permanent filters are used size with a Low Fire accessory kit.
conditions are: 80 D.B. 67 W.B. entering reduce ratings at a rate of 4% per manufacturer's recommendation with a
air to indoor coil. 95 D.B. entering air to per 1000 ft. elevation. 5 Based on U.S. Government clean resistance of 0.05" W.C.
outdoor coil. Standard Tests.

10 22-1295-05-0303 (EN)
General
Data

MODEL YCC048F4H0B YCC060F1M0B YCC060F3M0B YCC060F4M0B


RATED VOLTS/PH/HZ 460/3/60 208-230/1/60 208-230/3/60 460/3/60
RATINGS (COOLING) 1
BTUH 48000 60000 60000 60000
Indoor Airflow (CFM) 1600 2000 2000 2000
Power Input (KW) 5.05 6.52 6.32 6.32
EER/SEER (BTU/Watt-Hr.) 9.50 / 10.00 9.20 / 10.00 9.50 / 10.00 9.50 / 10.00
Noise Rating No. 1 8.4 8.4 8.4 8.4
A.G.A. RATINGS (HEATING) 2
(High) Input BTUH 125000 125000 125000 125000
Capacity BTUH 57 100000 100000 100000 100000
AFUE 78% 78% 78% 78%
Temp. Rise °F. (Min./Max.) 45 - 75 30 - 75 30 - 75 30 - 75
(Low) Input BTUH 100000 100000 100000 100000
Capacity BTUH 57 80000 80000 80000 80000
AFUE 80% 80% 80% 80%
Temp. Rise °F. (Min./Max.) 45 - 75 30 -75 30 -75 30 -75
Type of Gas 3 NATURAL NATURAL NATURAL NATURAL
POWER CONNS. — V/PH/HZ 460/3/60 208-230/1/60 208-230/3/60 460/3/60
Min. Brch. Cir. Ampacity 12.7 43.9 33.4 16.3
Br. Cir. Max. (Amps) 15 70 50 25
Prot. Rtg. Recmd. (Amps) 15 70 50 25
COMPRESSOR
No. Used 1 1 1 1
Volts/Ph/Hz 460/3/60 208-230/1/60 208-230/3/60 460/3/60
R.L. Amps — L.R. Amps 6.7 - 51 27.9 - 141.0 19.5 - 139 9.4 - 71
OUTDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 2 / 15 3 / 15 3 / 15 3 / 15
Face Area (Sq. Ft.) 9.2 9.2 9.2 9.2
Tube Size (in.) 3/8 3/8 3/8 3/8
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN PLATE FIN
Rows / F.P.I. 3 / 15 4 / 15 4 / 15 4 / 15
Face Area (Sq. Ft.) 5.4 5.4 5.4 5.4
Tube Size (in.) 3/8 3/8 3/8 3/8
Refrigerant Control CAPILLARY CAPILLARY CAPILLARY CAPILLARY
Drain Conn. Size (in.) 3/4" FEMALE 3/4" FEMALE 3/4" FEMALE 3/4" FEMALE
Duct Connections SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER PROPELLER
No. Used / Dia. (in.) 1 / 22 1 / 22 1 / 22 1 / 22
Type Drive / No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1 DIRECT / 1
No. Motors — HP 1 - 1/2 1 - 1/2 1 - 1/2 1 - 1/2
Motor Speed R.P.M. 1080 1080 1080 1080
Volts/PH/HZ 460/1/60 200-230/1/60 200-230/1/60 460/1/60
F.L. Amps — L.R. Amps 1.7 - 3.8 3.3/3.9 - 8.5 3.3/3.9 - 8.5 1.7 - 3.8
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia. x Width (in.) 11 X 11 11 X 11 11 X 11 11 X 11
No. Used 1 1 1 1
Drive / Speeds (No.) DIRECT / 2 DIRECT /2 DIRECT /2 DIRECT /2
No. Motors — HP 1 - 3/4 1 - 3/4 1 - 3/4 1 - 3/4
Motor Speed R.P.M. 1080
Volts/PH/HZ 460/1/60 200-230/1/60 200-230/1/60 460/1/60
F.L Amps 2.1 - 4.8 5.0/4.3 - 9.7 5.0/4.3 - 9.7 2.1 - 4.8
COMBUSTION FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Drive — Speeds (No.) DIRECT - 1 DIRECT - 1 DIRECT - 1 DIRECT - 1
Motor HP — Speed (RPM) 1/35 - 3480 1/35- 3480 1/35- 3480 1/35- 3480
Volts/PH/HZ 208-240/1/60 208-230/1/60 208-230/1/60 208-230/1/60
F.L. Amps 0.6 0.6 0.6 0.6
FILTER — FURNISHED? NO NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY THROWAWAY
Min Face Area-Lo (sq. ft.) 6 5.33 6.67 6.67 6.67
REFRIGERANT
Charge (lbs. of R-22) 4 8 LBS 11 LBS, 3 OZ 11 LBS, 3 OZ 11 LBS, 3 OZ
GAS PIPE SIZE (IN.) 1/2" 1/2" 1/2" 1/2"
DIMENSIONS H X W X D H X W X D H X W X D H X W X D
Crated (in.) 39-3/8 X 47 X 66-1/4 39-3/8 X 47 X 64-1/4 39-3/8 X 47 X 64-1/4 39-3/8 X 47 X 64-1/4
Uncrated SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING SEE OUTLINE DRAWING
WEIGHT
Shipping (lbs.) / Net (lbs.) 588 / 519 609 / 558 609 / 558 609 / 558
*See unit nameplate for proper input adjustment
1 Rated in accordance with A.R.I. Standard 2 All models are UL Listed. Ratings 3 Convertible to LPG. 6 Filters must be installed in return air stream. 7 Unit is shipped on high input,
210/240. Noise tested in accordance with shown are for elevations up to 4 This value is approximate. For more Square footages listed are based on 300 f.p.m. unit is convertible to low input
A.R.I. Standard 270. A.R.I. standard rating 2000 ft. For higher elevations precise value, see Unit Nameplate. face velocity. If permanent filters are used size with a Low Fire accessory kit.
conditions are: 80 D.B. 67 W.B. entering reduce ratings at a rate of 4% per manufacturer's recommendation with a
air to indoor coil. 95 D.B. entering air to per 1000 ft. elevation. 5 Based on U.S. Government clean resistance of 0.05" W.C.
outdoor coil. Standard Tests.

22-1295-05-0303 (EN) 11
Performance Data
Cooling

12 22-1295-05-0303 (EN)
Performance Data
Cooling

22-1295-05-0303 (EN) 13
Performance Data
Cooling

14 22-1295-05-0303 (EN)
Performance Data
Temperature Rise
22-1295-05-0303 (EN) 15
Performance Data
Indoor Fan

External Static Pressure

From Dwg. 21A730145 Rev. 0 From Dwg. 21A730239 Rev. 0

YCC030F–M

From Dwg. 21A670538 From Dwg. 21A730241 Rev. 2

16 22-1295-05-0303 (EN)
Performance Data
Indoor Fan

External Static Pressure

YCC036F–L, F–M, F1H

From Dwg. 21A730243 From Dwg. 21A730859 Rev. 1

YCC048F–M0B

From Dwg. 21A730901 Rev. 1 From Dwg. 21A661638 Rev. 1

22-1295-05-0303 (EN) 17
Performance Data
Indoor Fan

External Static Pressure

YCC036F–L

From Dwg. 21A730904 Rev. 0 From Dwg. 21A730912

YCC030F–M, YCC036F–M,H, YCC042F–M YCC048F–M YCC048F–H, YCC060F–M

From Dwg. 21A730915

From Dwg. 21A662530

From Dwg. 21A730923 Rev. 0

18 22-1295-05-0303 (EN)
Performance Data
Pressure Drop

Economizer Pressure Drop — (Return Air Restriction 0% Outdoor Air)

AIRFLOW BAYECON054B BAYECON055B BAYECON073A


(CFM) (in. H20) in. (H20) (in. H20)
600 .010 .010
800 .020 .015
1000 .050 .020
1200 .090 .040 .025
1400 .140 .050 .030
1600 .075 .035
1800 .100 .045
2000 .130 .055
2200 .150 .075
2400 .190 .100
From Dwg. 21A730983 Rev. 1

Optional Equipment
Horizontal Economizer and Rain Hood

From Dwg. 21C662056

22-1295-05-0303 (EN) 19
Optional
Equipment

Economizer and Rain Hood


(Downflow Applications)

ECONOMIZER APPLICATION A B C D E F G H
MODEL MODELS
BAYECON054B YCC018-048F-M 20 16-5/8 23-1/2 22-9/16 8-5/8 22-1/4 25-1/8 1-1/2
BAYECON055B YCC048F-H/060F 20 21 26 OMIT 12-1/8 26-1/8 32-1/8 1-3/4

25% Fresh Air Kit

Controls
Field Installed Control Options
Thermostats Economizer Controls of energy savings potential than the standard
Two stages heating/cooling or one stage The standard equipment offering is a fixed dry dry bulb control due to the additional wet bulb
heating/cooling thermostats are available in bulb changeover control. In addition to the sensing capability.
either manual or automatic changeover. standard offering, there are two other field
Differential Enthalpy
installed control accessories.
Programmable Electronic Replaces the standard dry bulb control with
Night Setback Thermostat Enthalpy Control two enthalpy sensors that compare total heat
Heating setback and cooling setup with 7-day, Replaces the dry bulb control with a solid content of the indoor air and outdoor air to
5-1-1 programming capability. Available in state dry bulb and wet bulb changeover determine the most efficient entering air
2 heating/cooling or 1 heating/cooling versions controller which has a fully adjustable set source. This control option offers the highest
with automatic changeover. point. Enthalpy control offers a higher level level of energy efficiency available.

20 22-1295-05-0303 (EN)
Typical
Wiring

YCC Field Wiring Diagram

NOTES:
1. FUSED DISCONNECT SIZE, POWER WIRING AND GROUNDING OF EQUIPMENT
MUST COMPLY WITH CODES.
2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT AND HEATER NAMEPLATE.
3. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM CONDUCTOR.
4. SEE UNIT DIAGRAM FOR ELECTRICAL CONNECTION DETAILS.
5. THE THERMOSTAT ON THE YCC UNIT MUST PROVIDE A “G” SIGNAL IN THE
COOLING MODE ONLY. DURING THE HEATING MODE THE FAN WILL BE
ENERGIZED BY THE SYSTEM.

From Dwg. 21D756979 Rev. 0

22-1295-05-0303 (EN) 21
Typical
Wiring

Wiring Diagram for YCC

(continued on next page)

22 22-1295-05-0303 (EN)
Typical
Wiring

Wiring Diagram for YCC

22-1295-05-0303 (EN) 23
Dimensions

BAYCURB030A,038A Roof Mounting Curb Outline YCC024-060 — Units

This member used on


YCC024-036F-L
YCC024-036F-M models only

AIR DUCT
MODEL NO. A B C D E
OPENINGS
YCC024-36F-L SUPPLY 21 11-1/4 - -
14-3/4
YCC024-36F-M RETURN - - 11-1/2 18-1/8
YCC036F-H SUPPLY 21 16-3/4 - -
6-1/4
YCC042-48F-M RETURN - - 21 21-1/8
YCC048F-H SUPPLY 21 19 - - C729942
3
YCC060F-M RETURN - - 21 22-1/8

Required Clearance for Unit Installation and Roof Penetration Hole Size Required

INSULATED DECK PANS


ARE INCLUDED WITH THE
D
BAYCURB038A ONLY.
A

CLEARANCE TO
COMBUSTIBLE MATERIAL
C
BOTTOM 0.0"
B
BACK 1.0"
LEFT SIDE 6.0"
RIGHT SIDE 6.0"
FRONT SIDE 12.0"
TOP 36.0"

SERVICE CLEARANCE & PENETRATION DIMENSIONS


MODEL NO. A B C D E F
YCC018-36F-L,F-M 42" 30" *6" 24" 36" 25"
YCC036F-H,042-48F-M 42" 30" *12" 30" 44" 25"
E
YCC048F-H,-60F 42" 30" *12" 36" 50" 25" F
* 18" WITH FRESH AIR ACCESSORY
* 30" WITH ECONOMIZER From Dwg. 21C662039

24 22-1295-05-0303 (EN)
Dimensions

BAYCURB033A Roof Mounting Curb Outline YCC036F-H/042/048F-M — Units


INSUL.
DECK

AIR DUCT
A B C
OPENINGS
SUPPLY
21 16-3/4 -
DUCT
RETURN
21 - 21-1/8
DUCT C662035

Required Clearance for Unit Installation and Roof Penetration Hole Size Required
INSUL.
DECK
D
A

C
B

SERVICE CLEARANCE DIMENSIONS


A B C D
44"
30" 30" *12" 30" 25"
*18" WITH 25% FRESH AIR ACCESSORY
30" WITH ECONOMIZER From Dwg. 21C662039

22-1295-05-0303 (EN) 25
Dimensions

BAYCURB034A Roof Mounting Curb Outline YCC048F-H/060F — Units


INSUL.
DECK

AIR DUCT
A B C
OPENINGS
SUPPLY
21 19 -
DUCT
RETURN
21 - 22-1/8
DUCT C662034

Required Clearance for Unit Installation and Roof Penetration Hole Size Required

D
A

C B

SERVICE CLEARANCE DIMENSIONS


A B C D
42" 30" *12" 36"
*18" WITH 25% FRESH AIR ACCESSORY
30" WITH ECONOMIZER From Dwg. 21C662038

26 22-1295-05-0303 (EN)
Dimensions

Field Fabricated (Side X Side) Ducts — YCC018-060F Units


Installed from Above Mounting Curb

This member
on YCC018-036F-L
models only.

P.V.C. Rubber Gasket Position on BAYCURB030AA for Unit Placement — YCC018-060F Units

This member
on YCC018-036F-L
NOTES: models only.
1. OVERLAP AND POSITION JOINTS IN P.V.C. RUBBER
GASKET.
2. AIR SEALS – APPLY P.V.C. RUBBER LAST TO INSURE
THERE IS ADEQUATE P.V.C. FOR THE WATER SEAL.
3. USE TYPICAL SEALING METHODS TO PREVENT AIR DUCT
LEAKAGE AT CURB-DUCT JOINT.

22-1295-05-0303 (EN) 27
Dimensions

YCC018-060 Outline — Rear


NOTE: ALL DRAWING DIMENSIONS ARE IN INCHES

From Dwg. 21D661690

CORNER WEIGHT (LBS) UNIT


MODEL A B C D E F G H J K L M N P
W1 W2 W3 W4 WEIGHT
YCC018F-L 68.3 61.7 84 92.9 307
YCC024F-L 69.4 60.0 85 99.5 314 55-1/4 36 25-3/16 18-9/16 11-1/16 6-9/16 6-13/16 17 21-5/16 25 17-1/2 10 3 4-7/16
YCC030F-L 70.5 61.4 87 99.8 319
YCC030F-M 84.06 68.08 92.1 113.7 358 20-3/4 25-13/16
YCC036F-L 78.3 68.3 95.6 109.7 352 55-1/4 36 29-3/16 18-9/16 11-1/16 6-9/16 6-13/16 17 17-1/2 10 3 4-7/16
19-3/4 24-13/16
YCC036F-M 86 67.6 93.2 115.13 364
YCC036F-H 90.3 73.8 101 123.7 399
YCC042F-M 103.8 88.7 98.6 122.6 412 62-3/4 36 29-3/16 18-9/16 11-1/16 6-9/16 11-1/8 17 19-3/4 28-1/4 17-1/2 10 3 8-3/4
YCC048F-M 104.6 84.6 102.2 126.4 418
YCC048F-H 123.8 104.6 132.5 157 518
65-5/16 45 33-3/8 21-1/16 15-1/16 4-15/16 9-1/8 21-15/16 25 29-7/32 20 14 3-1/2 8-5/16
YCC060F-M 135.4 109.8 137.3 169.3 552

28 22-1295-05-0303 (EN)
Dimensions

YCC018-060 Outline — Front


NOTE: ALL DRAWING DIMENSIONS ARE IN MM (INCHES)

CLEARANCE TO
COMBUSTIBLE MATERIAL
BOTTOM 0.0"
BACK 1.0" From Dwg. 21D661689
LEFT SIDE 6.0"
MODEL A B C D E F
RIGHT SIDE 6.0"
YCC018F-L
FRONT SIDE 12.0" KNOCKOUTS FOR 1/2" AND 1"
YCC024F-L 55-1/4 36 25-3/16 12-15/16 36-3/4
TOP 36.0" CONDUIT
YCC030F-L
YCC030F-M
RECOMMENDED SERVICE CLEARANCE KNOCKOUTS FOR 3/4" AND 1-1/4"
YCC036F-L 55-1/4 36 29-3/16 12-15/16 36-3/4
CONDUIT
BACK * 6.0" YCC036F-M
YCC036F-H
LEFT SIDE 30.0" KNOCKOUTS FOR 3/4" AND 1-1/4"
YCC042F-M 62-3/4 36 29-3/16 14-1/2 27-1/2
RIGHT SIDE 24.0" CONDUIT
YCC048F-M
FRONT SIDE 30.0" YCC048F-H KNOCKOUTS FOR 3/4" AND 1-1/2"
64-5/16 45 33-3/8 14-13/16 27-15/16
YCC060F-M CONDUIT
* 18" WITH FRESH AIR ACCESSORY
* 30" WITH ECONOMIZER NOTE: TABLE IN INCHES ONLY

22-1295-05-0303 (EN) 29
Dimensions

YCC018-060 Outline — Front with BAYCURB030A Curb


NOTE: ALL DIMENSIONS ARE IN INCHES

CABINET
MODEL BAYCURB "A" "B" "C" "D" "E" "F" "G" "H"
SIZE
"A" YCC018-30F-L 030A 14-1/8 16-5/8 36 34 25-3/16 13-3/4 — —
YCC030-36F-M
"B" 030A 14-1/8 16-5/8 36 34 29-3/16 13-3/4 — —
YCC036F-L
YCC036F-H 030A 14-1/8 16-5/8 36 34 29-3/16 13-3/4 8-1/8 —
"C" YCC042F-M
YCC048F-M 033A 14-13/16 16-5/8 36 34 29-3/16 13-3/4 — —

YCC048F-H 030A 14-1/8 21 45 34 33-3/8 13-3/4 10-1/8 9-7/8


"D"
YCC060F-M 034A 14-13/16 21 45 43 33-3/8 13-3/4 — —
From Dwg. 21D661772

30 22-1295-05-0303 (EN)
Mechanical
Specifications Options

General Condenser Coil — Outdoor coils shall be Downflow Accessories


All units shall be factory assembled, piped, internally enhanced 3/8-inch OD seamless (U.S. Domestic Models)
internally wired and fully charged with R-22. copper tubing mechanically bonded to Roof Curb — The roof curb shall be designed
All units shall be designed to operate at aluminum fins. Each coil shall be factory
to mate with the unit and provide support and
outdoor ambient temperatures as high as pressure and leak tested at 420 psig.
complete weather-tight installation when
115° F. Cooling capacities shall be rated in Indoor Air Fan — Direct-drive, forward- properly installed. Curb shall ship knocked
accordance with A.R.I. standards. The YCC-F curved, centrifugal type. Motor shall have down for field assembly, and include wood
heating/cooling unit design is U.L. listed, thermal overload protection. Permanently nailer strips.
specifically for outdoor applications using lubricated motor bearings. Motor/blower
propane or natural gas. All units shall be Downflow Economizer
assembly isolated from unit with rubber
designed for outdoor rooftop or ground level Modulating Economizer — This accessory
mounts.
installation. Exterior surfaces of all units shall shall be field installed and be composed of the
be phosphatized, zinc-coated steel with epoxy Condenser Fan — Direct-drive, draw thru following items: 0-100% fresh air damper,
resin primer and baked enamel finish. propeller type. Weather-proofed permanent damper drive motor fixed dry bulb enthalpy
Shipped for horizontal application, split capacitor fan motor shall have built-in
control, and low voltage polarized plug for
convertible to downflow. thermal overload and permanently lubricated
electrical connections. Solid state enthalpy or
motor bearings. differential enthalpy control is optional.
Casings
All panels shall be 20-gauge steel, gasketed Low Ambient — Standard refrigerant system Economizer operations shall be controlled by
and insulated. Foil-faced glass fiber insulation operation down to 55° F. Low ambient the preset position of the enthalpy control. A
shall be in the heat exchanger section. Foil- accessory required for operation in 0° F. barometric relief damper shall be standard
faced insulation shall be in the evaporator ambient condition. with the economizer and provide a pressure
section. Base pan and mounting rails shall be Heating System operated damper that shall be gravity closing
18 gauge. WEATHERGUARD™ exterior and prohibit entrance of outside air on
corrosion resistant screws shall be used for Gas-Fired Heating Section — Models shall equipment “off” cycle.
added resistance to rust and corrosion. provide completely assembled, wired and
Manual Fresh Air Hood
piped gas fired heating systems within unit.
Controls Manual outside air provides a fixed outside air
Design certified by U.L., specifically for
Refrigeration cycle controls shall include outdoor application. Threaded gas connection quantity from 0 to 25 percent. Includes hood
condenser fan, evaporator fan and compres- on the unit. and bird screen.
sor contactors. Compressors shall be Low Ambient Control
equipped with a combination internal winding Electronic Ignition System — Main burner is
lit each time thermostat calls for heat. Flame Control allows cycling of compressor under
thermostat/current overload. Internal high low ambient cooling conditions. Required for
pressure relief shall also be provided. sensor proves flame and keeps the main
burners on. Should a loss of flame occur, the cooling operation to 0° F.
Refrigeration System main valve closes and the spark recurs within Propane Gas Conversion Kit — For
Compressors — All units shall have hermeti- 0.8 second. When thermostat is satisfied, conversion from natural gas to LP gas.
cally sealed Climatuff® compressors. Com- main burner is extinguished.
pressors shall be equipped with over tempera- Forced Combustion Blower — Insures
ture, over current and high pressure protec- flame stability under varying wind conditions.
tion. Crankcase heaters shall be standard on Gives higher combustion efficiency and
all three phase models. location flexibility.
Evaporator Coil — Internally enhanced Heat Exchanger — Aluminized steel tubes.
3/8-inch OD seamless copper tubing mechani- Free floating design.
cally bonded to aluminum fins, factory
pressure and leak tested at 250 to 300 psig. Burners — 20-gauge aluminized steel. Multi-
port inshot.

22-1295-05-0303 (EN) 31
Literature Order Number RT-PRC021-EN P.I.
File Number PL-UN-RT-PRC021-EN 03/03
Supersedes YC-D-9
Stocking Location Webb/Mason-Houston

Trane
A business of
American Standard Companies Trane has a policy of continuous product and product data improvement and it reserves the right to change
www.trane.com design and specifications without notice.

You might also like