Cross Reference between

UPS Protocol <-> MODBUS Objects

Rev. 1.8
January 2019

Available
Modbus Referenced USHA
Description Notes (see CS121 CS141
address XIDs +
note1)
97 Output Voltage phase 1 only for (R)T 31/11 (other: ref.addr.140) ü 1V 1V -
98 Output Voltage phase 2 only for (R)T 31/11 ü 1V 1V -
99 Output Voltage phase 3 only for (R)T 31/11 ü 1V 1V -
100 Output Power [%], phase 1 xid408 ü 1% 1% 0.1%
101 Output Power [%], phase 2 xid414 ü 1% 1% 0.1%
102 Output Power [%], phase 3 xid420 ü 1% 1% 0.1%
103 Battery Capacity [%] xid206 ü 1% 1% 1%
104 Input Voltage [V], phase 1 xid309 mains rectifier ü 1V 1V 0.1V
105 Input Voltage [V], phase 2 xid315 ü 1V 1V 0.1V
106 Input Voltage [V], phase 3 xid321 ü 1V 1V 0.1V
107 Battery Temperature [C] xid209 ü 1% 1% 1%
108 Battery Autonomy Time [min] xid205 ü 1 min 1 min 1 min
109 Ups Status. Bit values, as follows: -
bit 0 power piped through xid3017.b6 Bypass is on ü
bit 1 shutdown ups - unused -
bit 2 inverter is on xid3017.b22 AND NOT xid3017.b24 ü
bit 3 ups on battery xid645.b19 Input bad ü
bit 4 alarm "low battery" xid3017.b14 ü
bit 5 alarm "overtemperature" xid645 (b18 OR b35 OR b36) any temperature alarm ü
bit 6 test in progress xid701 = 2 ü
bit 7 alarm "input bad" - unused. Use "On Battery" or Object 120 -
bit 8 alarm "overload" - unused. Use Object 122 -
bit 9 alarm "inverter error" xid645.b40 Inverter failure ü
bit 10 alarm "battery error" xid3017.b19 Battery Breaker is open (not a true err!) ü
bit 11 bypass is on (eco mode) xid3017.b25 ü
bit 12 inverter warning (eco mode) - unused -
bit 13 alarm "ups fail" - unused -
bit 14 snmp communication lost Comm lost on all parallel modules ü
bit 15 SiteManager/SiteMonitor - unused -
110 Battery Voltage [V] xid207 lowest value among all parallel modules ü 1V 1V 0.1V
111 Input frequency [Hz], phase 1 xid304 ü 1Hz 1Hz 0.1Hz
112 Input frequency [Hz], phase 2 xid310 ü 1Hz 1Hz 0.1Hz
113 Input frequency [Hz], phase 3 xid316 ü 1Hz 1Hz 0.1Hz
114 Powere Failures [counter] xid301 ü
115 Alarm "Battery Bad" - unused -
116 Alarm "On Battery" xid645.b18 copied from object 109.b3 ü
117 Alarm "Low Battery" xid3017.b14 copied from object 109.b4 ü
118 Alarm "Depleted Battery" - unused -
119 Alarm "Temperature Bad" xid617 ü
120 Alarm "Input Bad" xid618 ü
121 Alarm "Output Bad" xid619 ü
122 Alarm "Overload" xid620 ü
123 Alarm "On Bypass" xid3017.b6 copied from object 109.b0 ü
124 Alarm "Bypass Bad" xid621 ü
125 Alarm "Output Off as requested" xid622 ü
126 Alarm "Ups Off as requested" xid623 ü
127 Alarm "Charger Failed" xid624 ü
128 Alarm "Ups Output Off" - unused -
129 Alarm "System Off xid625 ü
130 Alarm "Fan Failure" xid626 ü
131 Alarm "Fuse Failure" xid627 no
132 Alarm "General Fault" 628+3017.b29 General Alarm is on, on any unit ü
133 Alarm "Diagnostic Test Failed" - unused -
134 Alarm "Alarm Communication Lost" 4 consecutive comm failues ü
135 Alarm "Awaiting Power" xid629 ü
136 Alarm "Shutdown Pending" xid630 ü
137 Alarm "Shutdown Imminent" xid631 ü
138 Alarm "Test In Progress" xid701 = 2 ü
139 Maintenance Bypass Breaker is open (not active) xid3017.b17 ü
140 Output Voltage phase 1 xid410 (since CS121 Rel.2.61 for Concept) ü 1V 1V 0.1V
141 Output Voltage phase 2 xid416 (since CS121 Rel.2.61 for Concept) ü 1V 1V 0.1V
142 Output Voltage phase 3 xid422 (since CS121 Rel.2.61 for Concept) ü 1V 1V 0.1V
143 Total Output Current, phase 1 [0.1A] xid406 (since CS121 Rel.3.21) ü 0.1A 0.1A 0.1A
144 Total Output Current, phase 2 [0.1A] xid412 (since CS121 Rel.3.21) ü 0.1A 0.1A 0.1A
145 Total Output Current, phase 3 [0.1A] xid418 (since CS121 Rel.3.21) ü 0.1A 0.1A 0.1A
146..151 UPS internals ü
146 UpsExtendedStatus, Low (b15..b0) xid3017, LSB ü
bit 0 Rectifier Mains Input OK
bit 1 Bypass Mains Input OK
bit 2 -
bit 3 -
bit 4 Rectifier is ON
bit 5 Inverter is ON
bit 6 Bypass is ON
bit 7 Aux mains input OK priority aux bad
bit 8 Booster is ON
bit 9 -
bit 10 -
bit 11 -
bit 12 Battery is charging
bit 13 Battery is discharging
bit 14 Battery is Low
bit 15 xvfi
147 UpsExtendedStatus, Hi (b31..b16) xid3017, MSB (ü)
bit 0 Output Breaker is Open
bit 1 Maintenance Bypass Breaker is Open
bit 2 Inverter Breaker K2 is Open
bit 3 Battery Breaker is Open no
bit 4 Rectifier Input Breaker is Open
bit 5 Bypass Input Breaker is Open
bit 6 Load is supplied
bit 7 UPS Output is Off
bit 8 Eco Mode is ON
bit 9 -
bit 10 -
bit 11 -
bit 12 New Alarm. Buzzer is ON parallel: buzzer is on, on any unit
bit 13 General Alarm. LED on Panel is ON at system level (considering parallel Redundancy)
bit 14 -
bit 15 -
148 UpsAlarms, b39..b24 xid645 (since SNMP Rel.3.21) (ü)
bit 0 Output Off xid 622
bit 1 UPS Shutdown xid 623
bit 2 Charger Failure xid 624
bit 3 System Off xid 625
bit 4 Fan Failure xid 626 at system level (considering parallel Redundancy)
bit 5 Fuse Failure xid 627 no
bit 6 General Fault xid 628 General Alarm on any UPS (parallel)
bit 7 -
bit 8 Awaiting Power xid 629
bit 9 Shutd. Pending xid 630
bit 10 Shutd.Imminent xid 631
bit 11 Ambient Temp. xid 632 no
bit 12 Inverter Temp. xid 633
bit 13 Bypass Temp. xid 634 no
bit 14 Battery Temp. xid 635 no
bit 15 -
149 UpsAlarms, b55..b40 xid645 (since SNMP Rel.3.21) (ü)
bit 0 Inverter Failure xid 636
bit 1 Emrgncy Pwr Off xid 637
bit 2 Batt. Grnding Err. xid 638 no
bit 3 Batt. Brkr Open xid 639 no
bit 4 Sync. Error xid 640
bit 5 Loss of redudancy xid 641
bit 6 Generator xid 3009
bit 7 -
bit 8 Battery Condition 0 (lsb) xid 201(0)
bit 9 Battery Condition 1 (msb) xid 201(1)
Battery Condition [1,0]:
0=Good; 1=Week; 2=Replace
bit 10 Battery Status 0 (lsb) xid 202(0)
bit 11 Battery Status 1 (msb) xid 202(1)
Battery Status [1,0]:
0=OK; 1=Low; 2=Depleted
bit 12 Output Source 0 (lsb) xid 40( 0)
bit 13 Output Source 1 xid 401(1)
bit 14 Output Source 2 (msb) xid 401(2)
Output Source [2,1,0]:
0=normal; 1=on battery; 2=on bypass
3=reducing; 4=boosting; 5=manual byp
6=service; 7=no source for fault
bit 15 -
150 UpsAlarms, b15..b0 xid645 (since SNMP Rel.3.21) (ü)
bit 0 -
bit 1 -
bit 2 -
bit 3 -
bit 4 -
bit 5 -
bit 6 -
bit 7 -
bit 8 -
bit 9 -
bit 10 -
bit 11 -
bit 12 -
bit 13 -
bit 14 -
bit 15 -
151 UpsAlarm, b23..b16 xid645 (since SNMP Rel.3.21) (ü)
bit 0 -
bit 1 -
bit 2 Temperature xid 617
bit 3 Input Bad xid 618
bit 4 Output Bad xid 619
bit 5 Overload xid 620
bit 6 Bypass Bad xid 621
bit 7 - (Should be 1)
bit 8 -
bit 9 -
bit 10 -
bit 11 -
bit 12 -
bit 13 -
bit 14 -
bit 15 -
152..159 SENSORMAN measurement values (since CS121 Rel.3.58) -
160 Output True Power [kW], phase 1 xid407 (since CS121 Rel.3.84) ü 1kW 1kW 0.1kW
161 Output True Power [kW], phase 2 xid413 (since CS121 Rel.3.84) ü 1kW 1kW 0.1kW
162 Output True Power [kW], phase 3 xid419 (since CS121 Rel.3.84) ü 1kW 1kW 0.1kW
163 AUX1 in/out - since CS121 Rel.4.42/(4.40+upstyp.ups) ü -
164 AUX2 in/out - since CS121 Rel.4.42/(4.40+upstyp.ups) ü -
165 AUX3 in/out - since CS121 Rel.4.42/(4.40+upstyp.ups) ü -
166 AUX4 in/out - since CS121 Rel.4.42/(4.40+upstyp.ups) ü -
167 Battery Current xid210--> 3026 since CS121 Rel.5.19 ü 1A 1A -
168 Output Frequency xid402 since CS121 Rel.5.19 ü 0.1Hz 0.1Hz -
169 UPS Modules Nr. 16 … 1 availability - ü - - -
170 UPS Modules Nr. 25 … 17 availability - ü - - -
171 Input AUX frequency [Hz], phase 1, see note(2) xid304 ü 1Hz 1Hz 0.1Hz
172 Input AUX frequency [Hz], phase 2, see note(2) xid310 ü 1Hz 1Hz 0.1Hz
173 Input AUX frequency [Hz], phase 3, see note(2) xid316 ü 1Hz 1Hz 0.1Hz
174 Input AUX Voltage [V], phase 1, see note(2) xid309 mains rectifier ü - ü -
175 Input AUX Voltage [V], phase 2, see note(2) xid315 ü - ü -
176 Input AUX Voltage [V], phase 3, see note(2) xid321 ü - ü -
177 Bypass frequency, see note(2) xid501 - ü -
178 Bypass voltage [V], phase 1, see note(2) xid503 - ü -
179 Bypass voltage [V], phase 2, see note(2) xid506 - ü -
180 Bypass voltage [V], phase 3, see note(2) xid509 - ü -
181 Alarm input AUX bad, see note(2) xid3017 b7 NO! b0 of the XID301 (Mains Input Rectifier ok) - ü -

Release history
0.1 September 2007 Draft Release, to be definitively checked§ and confirmed
0.2 2007-09-03 First official release
0.3 2009-09-03 Added objects 160…162
NOTE: The bits from Object148 (b0..b6) and Object 151 (b8..b14) are identical.
0.4 2010-01-12 Notes on objects 132, 147/b3, 148/b6,149/b3, 151/b14

0.5 2011-03-29 Clear note that following objects are not supported: 148/b5,11,13,14; 149/b2; 151/b13
- 2012-04-10 New objects 163...166, AUX in/out
1.0 2013-05-28 Mentioned that the list is valid for all UPSs produced by Newave since 2009
1.1 2013-12-18 Added USHA+ and measurement units
1.2 2014-08-19 Reg.151/b8..b15 are not defined anymore (previously assigned to redundant bits)
1.3 2015-03-10 AddedRegister 168, Output Frequency.
1.4 2015-06-12 Added register 167, Battery current. Available since CS121 Rev.5.19
1.5 2015-07-27 New Modbus Registers 169 and 170, which bitwise indicates which UPS module is connecetd, as follows:
1.5.1 2015-11-02 Object 167 get the value from XID210 --> XID3026
1.6 2017-01-19 Added addresses 171-174
1.7 2017-03-17 Removed word "unused" on address 115 because works on BACS
Fixed XID of address 109
Added address 181
1.8 2019-01-01 Minor corrections

Note1:
Support for all UPSs since 2009. Limited for PowerValue (R) T 31/11
PowerValue (R)T 31/11 supports Registers 97...138 through the CS121 Interface Card
To check if any unit is in Alarm (has the Alarm LED on), use Register 132
To check if any unit has a new alarm (has the buzzer on), use Register 147/b12
To check if the parallel system is in alarm, use Register 147/b13 (alarms from redundant units are ignored)
Note2:
Available only for systems with an auxiliary input.