Actual SITE Address Area/ (Market/Bank/ HO
Thana contact No
Residence/Other)
AC1 AC
Outdoor AC2 AC2 Type AC2 AC2 Status( If faulty , please mention faulty item) AC2 Outdoor timer
Brand Capacity status
Status Status
AVR SPD brand with SPD CO2 cylinder Expire date No of BTS grounding Battery TX Rack BTS Door
Status capacity status present or not of CO2 BTS Status GND GND GND
Mains
Rectifier Room Intruder Smoke High Fail Rectifier Low Water Low Others alarm
GND Bus-Bar Temperature Fault Voltage Alarm Fuel (If exist)
OK OK OK OK OK OK OK OK OK OK
NOK NOK OK OK OK OK OK OK OK N/A
NOK NOK OK OK OK OK OK OK OK N/A
NOK NOK ok OK OK Ok OK OK OK N/A
NOK NOK ok OK OK Ok OK OK OK N/A
NOK NOK ok OK OK Ok OK OK OK N/A
NOK NOK ok OK OK Ok OK OK OK N/A
NOK NOK ok OK OK Ok OK OK OK N/A
NOK NOK ok OK OK Ok OK OK OK N/A
NOK NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
NOK NOK ok OK OK Ok OK Ok OK N/A ok
OK OK ok OK OK Ok OK Ok OK N/A ok
OK OK ok OK OK Ok OK NA OK N/A ok
Nok OK ok OK OK Ok OK Ok NOK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok NOK NOK Ok OK Ok OK N/A ok
Nok OK ok N/A N/A Ok OK Ok N/A N/A ok
Nok NOK ok OK NOK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
OK OK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok NOK OK Ok NOK Ok OK N/A ok
NOK NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
OK OK ok OK OK Ok OK Ok OK N/A ok
NOK Missing ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Nok NOK ok OK NOK Ok OK Ok OK N/A ok
Nok NOK ok OK NOK Ok OK Ok OK N/A ok
Nok NOK ok OK OK Ok OK Ok OK N/A ok
Inf
Low fuel alarm problematic Done Present Inside Tap, Tie, Silicon gel, spray
open outside Tap, Tie, Silicon gel, spray
Present Inside Tap, Tie, Silicon gel, spray
Done Present Inside Tap, Tie, Silicon gel, spray
Done Present Inside Tap, Tie, Silicon gel, spray
Done Present Inside Tap, Tie, Silicon gel, spray
Done Present Inside Tap, Tie, Silicon gel, spray
Done Present Inside Tap, Tie, Silicon gel, spray
Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present ss Tap, Tie, Silicon gel, spray
NA Done Present SS Tap, Tie, Silicon gel, spray
NA Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present SS Tap, Tie, Silicon gel, spray
Humidity Not sensing, Low voltage
Not done Not Present Normal Tap, Tie, Silicon gel, spray
Water sensor faulty Not done Not Present Normal Tap, Tie, Silicon gel, spray
Humidity not sensing Not done Present ss Tap, Tie, Silicon gel, spray
Humidity & Temperature alarm po Not done Present ss Tap, Tie, Silicon gel, spray
Not done Present Inside Tap, Tie, Silicon gel, spray
Temperature alarm not sensing Not done Present ss Tap, Tie, Silicon gel, spray
NA Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present Normal iron box Tap, Tie, Silicon gel, spray
NA Done Not NA Tap, Tie, Silicon gel, spray
Smoke alarm port faulty from EMUNot done Not NA Tap, Tie, Silicon gel, spray
NA Done Present ss Tap, Tie, Silicon gel, spray
NA Done Present ss Blast, Tap, Tie, Silicon gel, spr
NA Done Present Inside Blast, Tap, Tie, Silicon gel, spr
NA Done Present Normal Holder, Tap, Tie, Silicon gel, s
NA Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present Inside Blast, Tap, Tie, Silicon gel, spr
NA Done Present Inside Blast, Tap, Tie, Silicon gel, spr
NA Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present Inside Tap, Tie, Silicon gel, spray
NA Done Present Inside Tap, Tie, Silicon gel, spray
Temperature alarm port faulty Not done Present ss Tap, Tie, Silicon gel, spray
Temperature Sensor faulty Not done Present ss Tap, Tie, Silicon gel, spray
Mains fail alarm was not work due
Done Present Inside Tap, Tie, Silicon gel, spray
Infra & Others
Snag List
Both AC faulty,
Battery backup zero, Only AC site but both AC faulty
Both AC faulty, FCU Can't room cooling properly. Temperature sensor faulty.
Only AC site & both AC are missing
nual bypass option (turn on AC) for when the controller is faulty. If this can be done remotely then this is preferable (ACP Off). 3High Temp
nual bypass option (turn on AC) for when the controller is faulty. If this can be done remotely then this is preferable (ACP Off). 3High Temp
nual bypass option (turn on AC) for when the controller is faulty. If this can be done remotely then this is preferable (ACP Off). 3High Temp
nual bypass option (turn on AC) for when the controller is faulty. If this can be done remotely then this is preferable (ACP Off). 3High Temp
ferable (ACP Off). 3High Temperature sensor faulty. 4. Humidity (both Low and High) sensor faulty. 5. Check that all lightning and aviation/
ferable (ACP Off). 3High Temperature sensor faulty. 4. Humidity (both Low and High) sensor faulty. 5. Check that all lightning and aviation/
ferable (ACP Off). 3High Temperature sensor faulty. 4. Humidity (both Low and High) sensor faulty. 5. Check that all lightning and aviation/
ferable (ACP Off). 3High Temperature sensor faulty. 4. Humidity (both Low and High) sensor faulty. 5. Check that all lightning and aviation/
hat all lightning and aviation/beacon light exists and working properly not ok (Aviation light not found & outdoor light faulty). 6. Rectifier
hat all lightning and aviation/beacon light exists and working properly not ok (Aviation light not found & outdoor light faulty). 6. Rectifier
hat all lightning and aviation/beacon light exists and working properly not ok (Aviation light not found & outdoor light faulty). 6. Rectifier
hat all lightning and aviation/beacon light exists and working properly not ok (Aviation light not found & outdoor light faulty). 6. Rectifier
tdoor light faulty). 6. Rectifier Grounding Cable missing. 7. CB at DCDB/TX Rack Grounding Cable missing. 8. Room wall is damped. 8. Fire e
tdoor light faulty). 6. Rectifier Grounding Cable missing. 7. CB at DCDB/TX Rack Grounding Cable missing. 8. Room wall is damped. 8. Fire e
tdoor light faulty). 6. Rectifier Grounding Cable missing. 7. CB at DCDB/TX Rack Grounding Cable missing. 8. Room wall is damped. 8. Fire e
tdoor light faulty). 6. Rectifier Grounding Cable missing. 7. CB at DCDB/TX Rack Grounding Cable missing. 8. Room wall is damped. 8. Fire e
Room wall is damped. 8. Fire extinguisher date expired. 9. GND Busbar missing.
Room wall is damped. 8. Fire extinguisher date expired. 9. GND Busbar missing.
Room wall is damped. 8. Fire extinguisher date expired. 9. GND Busbar missing.
Room wall is damped. 8. Fire extinguisher date expired. 9. GND Busbar missing.
Severity of
Snag
SL.No Snag Type
(Major/Min
Zamil MS or)
Site ID Zamil Zone Office PM Date
1 CTG_X0114 Feni Feni
17-Sep-18
2 CTG_X0114 Feni Feni
17-Sep-18
3 CTG_X0114 Feni Feni
17-Sep-18
4 CTG_X0114 Feni Feni
17-Sep-18
5 CTG_X0114 Feni Feni
17-Sep-18
6 CTG_X0114 Feni Feni
17-Sep-18
7 CTG_X0114 Feni Feni
17-Sep-18
8 CTG_X0114 Feni Feni
17-Sep-18
9 CTG_X0114 Feni Feni
17-Sep-18
10 CTG_X0325 Feni Feni
18-Sep-18
11 CTG_X0325 Feni Feni
18-Sep-18
12 CTG_X0325 Feni Feni
18-Sep-18
13 CTG_X0325 Feni Feni
18-Sep-18
14 CTG_X0325 Feni Feni
18-Sep-18
15 CTG_X0325 Feni Feni
18-Sep-18
16 CTG_X0325 Feni Feni
18-Sep-18
17 CTG_X0325 Feni Feni
18-Sep-18
18 CTG_X0737 Feni Feni
19-Sep-18
19 CTG_X0737 Feni Feni
19-Sep-18
20 CTG_X0737 Feni Feni
19-Sep-18
21 CTG_X0737 Feni Feni
19-Sep-18
22 CTG_X0737 Feni Feni
19-Sep-18
23 CTG_X0737 Feni Feni
19-Sep-18
24 CTG_X0620 Feni Feni
4-Oct-18
25 CTG_X0620 Feni Feni
4-Oct-18
26 CTG_X0620 Feni Feni
4-Oct-18
27 CTG_X0620 Feni Feni
4-Oct-18
28 CTG_X0620 Feni Feni
4-Oct-18
29 CTG_X0620 Feni Feni
4-Oct-18
30 CTG_X0620 Feni Feni
4-Oct-18
31 Feni Feni
CTG_X0487 13-Oct-18
32 Feni Feni
CTG_X0487 13-Oct-18
33 Feni Feni
CTG_X0487 13-Oct-18
34 Feni Feni
CTG_X0487 13-Oct-18
35 Feni Feni
CTG_X0487 13-Oct-18
36 Feni Feni
CTG_X0738 14-Oct-18
37 Feni Feni
CTG_X0738 14-Oct-18
38 Feni Feni
CTG_X0738 14-Oct-18
39 Feni Feni
CTG_X0738 14-Oct-18
40 Feni Feni
CTG_X0738 14-Oct-18
41 Feni Feni
CTG_X0246 27-Oct-18
42 Feni Feni
CTG_X0246 27-Oct-18
43 Feni Feni
CTG_X0246 27-Oct-18
44 Feni Feni
CTG_X0246 27-Oct-18
45 Feni Feni
CTG_X0246 27-Oct-18
46 Feni Feni
CTG_X0455 30-Oct-18
47 Feni Feni
CTG_X0455 30-Oct-18
48 Feni Feni
CTG_X0455 30-Oct-18
49 Feni Feni
CTG_X0455 30-Oct-18
50 Feni Feni
CTG_X0455 30-Oct-18
51 Feni Feni
CTG_X0161 31-Oct-18
52 Feni Feni
CTG_X0161 31-Oct-18
53 Feni Feni
CTG_X0161 31-Oct-18
54 Feni Feni
CTG_X0161 31-Oct-18
55 Feni Feni
CTG_X0161 31-Oct-18
56 Feni Feni
CTG_X0752 1-Nov-18
57 Feni Feni
CTG_X0752 1-Nov-18
58 Feni Feni
CTG_X0752 1-Nov-18
59 Feni Feni
CTG_X0752 1-Nov-18
60 Feni Feni
CTG_X0752 1-Nov-18
61 CTG_X0127 Feni Feni 3-Nov-18
Snag Details
ID light faulty No
OD light faulty No
Floor damped No
both AC faulty No
outdoorbusbar missing No
both AC faulty No
AC FAULTY No
id/od grounding missing No
VDT faulty No
SPD missing No
2 AC Completely damage No
AVR faulty No
ac faulty No
ac 2 pcs faulty No
fcu faulty No
AVR disconnect No
Measure and record Phase to ground voltage NOT OK GND Busbar & Cable misNo
Measure and record Neutral to ground voltage NOT OK GND Busbar & cable miNo
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU runn No
Ensuring tower/ pole galvanization/painting quality whether any member get rust
No
Check that all lightning and aviation/beacon light exists and working properly No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers ( No
Fire extinguisher date status (mention last filling date) NOT OK Fire Extinguish No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
LV Settings: LV, LLVD, BLVD, Charge current limit, no of string NOT OK LV, LLVD,No
Rectifier (indoor BTS)/ Battery charger fault (outdoor BTS) NOT OK Controller faNo
Fire extinguisher date status (mention last filling date) NOT OK Fire extinguish No
Outdoor light & emergency light not found NOT OK Outdoor light & emergencyNo
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
Check that all lightning and aviation/beacon light exists and working properl No
Room wall and roof is not damped NOT OK Room cage (Grill) rusted No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU controll
No
Check that all lightning and aviation/beacon light exists and working properly No
Class-C SPD Grounding NOT OK 1pcs SPD missing & GND missing No
BTS roof shed/tin is properly fixed and no chance of water leaking from anyw No
Fire extinguisher date status (mention last filling date) NOT OK Gas out of stockNo
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers ( No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and D No
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU controNo
Humidity (both Low and High) NOT OK Humidity port faulty from EMU box. No
Ensuring tower/ pole galvanization/painting quality whether any member get rust
No
Check the climbing facilities, platforms, catwalks and anti climbing devices for No
Check that all lightning and aviation/beacon light exists and working properly No
Fire extinguisher date status (mention last filling date) NOT OK Expire date: 01 No
FCU controller not found (running bypass mode) NOT OK FCU controller not f No
Clear site of rubbish, packaging materials NOT OK 1pcs OSN rack, 24pcs PBL (2VNo
DG room tin rusted and damaged. NOT OK DG room tin rusted and damaged. No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (CB No
AVR works in regulated mode NOT OK AVR running bypass mode due to coil fauNo
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU runni No
Ensuring tower/ pole galvanization/painting quality whether any member get rus
No
Check that all lightning and aviation/beacon light exists and working properly NNo
Fire extinguisher date status (mention last filling date) NOT OK Fire extinguish No
FCU inlet box rusted & damaged NOT OK FCU inlet box rusted & damaged No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers ( No
Inside MDB rating of SPD-60KA, Class B NOT OK Class B SPD not connected & caNo
Visually check to verify if No phase is twisted NOT OK All phase is twisted due No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and D No
Check that all lightning and aviation/beacon light exists and working properly No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers ( No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU controll
No
Check that all lightning and aviation/beacon light exists and working properly No
BTS, TX Rack & Rectifier GND cable not found NOT OK BTS, TX Rack & Rectifier No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
Fire extinguisher date status (mention last filling date) NOT OK Expired date : No
Appearance of commercial power from service pole to BTS NOT OK Energy metNo
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers ( No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
Manual bypass option (turn on FCU) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and D No
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU controll
No
Check that all lightning and aviation/beacon light exists and working properly No
Fire extinguisher date status (mention last filling date) NOT OK Gas out of stockNo
BTS, TX Rack, Battery Rack, AVR, Rectifier GND mis NOT OK BTS, TX Rack, BatterNo
Appearance of commercial power from service pole to BTS NOT OK Energy mete
No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
AVR works in regulated mode NOT OK AVR bypass mode due to breaker burnt No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
Check that all lightning and aviation/beacon light exists and working properly NNo
Access road condition NOT OK Site access road not found. Access different wayNo
AVR bypass mode due to Breaker burnt NOT OK AVR bypass mode due to BreakNo
Energy meter fixing not properly NOT OK Energy meter fixing not properly No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
Check that all lightning and aviation/beacon light exists and working properly NNo
Locking mechanism of Main Gate NOT OK Main gate hasbowl & angle broken No
BTS roof shed/tin is properly fixed and no chance of water leaking from anyw No
Fire extinguisher date status (mention last filling date) NOT OK Gas out of stockNo
BTS & Rectifier GND cable not found NOT OK BTS & Rectifier GND cable not fo No
MDB CB missing No
Tin broken No
Aviation Light not found, Emergency light not found & Outdoor light faulty No
DG Battery Down No
Appearance of commercial power from service pole to BTS NOT OK Energy mete
No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
AVR works in regulated mode NOT OK AVR disconnected due to MC faulty & buNo
Phase to phase voltage NOT OK Voltage measurement not possible due meter so
No
Measure and record phase to neutral Voltage NOT OK One phase missing foun No
Measure and record Neutral to ground voltage NOT OK Main GND missing No
Manual bypass option (turn on FCU) for when the controller is faulty. If this No
AC Controller has Auto, manual and bypass option to run the Air Cooler and No
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU controll
No
Emergency & outdoor light not found NOT OK Emergency & outdoor light not No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (CB No
Inside MDB rating of SPD-60KA, Class B NOT OK Not connected properly ( CableNo
AVR works in regulated mode NOT OK AVR parts missing, faulty & disconnecte No
Note Power Factor and energy meter SL No NOT OK pf: 97 SL No: Not seen No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
Fire extinguisher date status (mention last filling date) NOT OK Not found No
Energy meter not fixing in proper place NOT OK Energy meter not fixing in propNo
BTS, TX Rack & rectifier GND not found NOT OK BTS, TX Rack & rectifier GND n No
GND cable, Busbar & pit not found NOT OK GND cable, Busbar & pit not found No
GP share site. Site surrounding full of bush. NOT OK GP share site. Site surroundNo
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (CB No
Measure and record Neutral to ground voltage NOT OK Main GND missing No
FCU Controller has Auto, manual and bypass option to run. NOT OK FCU runni No
Rectifier only 2pcs Module running NOT OK Rectifier only 2pcs Module runningNo
BTS, Rectifier, TX rack & Battery GND not found NOT OK BTS, Rectifier, TX rac No
GND cable, busbar & pit missing No
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
AVR works in regulated mode NOT OK AVR parts missing and disconnected No
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this can No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
Check that all lightning and aviation/beacon light exists and working properly No
Room wall and roof is not damped NOT OK DG room & Bharanda wall damped No
Fire extinguisher date status (mention last filling date) NOT OK Fire extinguisheNo
Check for excessive or /faulty equipment and report to Banglalink NOT OK 1pcsNo
Appearance of commercial power from service pole to BTS NOT OK One phase N
mo
Power line from service pole to 100A TP CB to AVR to 63A Circuit Breakers (C No
AVR works in regulated mode NOT OK AVR parts missing & disconnected No
Phase to phase voltage NOT OK One phase missing found due to transformer faNo
Both AC ok, can cool room sufficiently by each and thermostat is inactive alwa No
Manual bypass option (turn on AC) for when the controller is faulty. If this c No
AC Controller has Auto, manual and bypass option to run the Air Cooler and DCNo
Fire extinguisher date status (mention last filling date) NOT OK Gas out of stockNo
Check for excessive or /faulty equipment and report to Banglalink NOT OK 1pcsNo
1. Both Ac missing
2. AVR All Parts missing and Disconnected
3. Fire extinguisher gas out of stock
4. All GND missing. GND Cable, Busbar and pit missing.
5. Main GND missing
No
6. 2pcs Battery busbar missing
7. Outdoor light Faulty.
8. FCP Battery missing
9. ACP Faulty.
10 AC Power cable hanging ( pole to Energy meter)
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A Avaible
Spare not
N/A N/A N/A N/A Pending Given N/A
Avaible